User Guide. Model Insulation Tester / Megohmmeter. Introduction

Similar documents
Model Insulation Tester / Megohmmeter. User Manual

User Guide. Model Insulation Tester / Megohmmeter

User Guide. Model Insulation Tester / Megohmmeter

User's Manual. High Voltage Megohmmeter. Analog Insulation Tester plus AC Voltage and Continuity Tests. Model

Phase Sequence Tester

Model Battery Powered Milliohm Meter

User's Manual. Earth Ground Resistance Tester. Model Introduction

User's Guide. Model RPM10 Laser Photo / Contact Tachometer with IR Thermometer. Introduction

Model ST Instruction Manual. Digital Insulation Tester. reedinstruments. www. com

TES-1601 INSTRUCTION MANUAL AUTORANGING INSULATION TESTER SAFETY INFORMATION TES ELECTRICAL ELECTRONIC CORP. Warnings and Safety symbols:

User's Manual Digital High Voltage Insulation Tester Model

Panel Mount Digital Tachometer Model

User's Guide. EzFlex Thermo-Anemometer. Model EZ30 UNITS MAX MIN AVG VEL

User's Guide. Vane Anemometer. Model Measures Air Velocity & Temperature. Degrees C/F switchable

User's Guide. True RMS Multim eter. Extech 430

USER MANUAL. Insulation Tester + DMM. Model MG320

User's Manual. Model Hot Wire Thermo-Anemometer. Introduction

Digital/Analog Megohmmeter Model 1026 USER MANUAL

Digital/Analog Megohmmeter Model 1026

DIGITAL INSULATION TESTER RS-5500/5505 INSTRUCTION MANUAL

USER MANUAL. 10KV Digital High Voltage Insulation Tester. Model MG500. Additional User Manual Translations available at

User's Guide. CO 2 Meter. Model CO250

Dawson DDM190D. Digital Multimeter User s Manual

Mini Multimeter with Non-Contact Voltage Detector (NCV)

OPERATING INSTRUCTIONS

True RMS Autoranging Multimeter

KMP Insulation-Continuity Tester. Users Manual

Mini Multimeter with Non-Contact Voltage Detector (NCV)

Users Manual. MegOhmMeter

Autoranging Industrial Multimeter

Autoranging Multimeter

MM300. INSTRUCTION MANUAL Manual-Ranging Digital Multimeter

MY /2-DIGIT DIGITAL MULTIMETER Users Manual

99 Washington Street Melrose, MA Fax TestEquipmentDepot.com. Instruction Manual. Model 2831D 4 ½ Digit True RMS Digital Multimeter

RS-3 PRO RS-1007 PRO. CAT IV Analog Clamp meter Series. Users Manual. For detailed specifications and ordering info go to

USER MANUAL. 200A AC Mini Clamp Meter. Model MA130. Please visit for user manual translations

OPERATING INSTRUCTION

Instruction Manual. Model 307A Analog Insulation & Continuity Meter

Table of Contents Title Page No.

DT33B/C/D OPERATOR S MANUAL LIMITED WARRANTY AND LIMITATION OF LIABILITY

DIGITAL RCD(ELCB) TESTER

MAX. AC 600V HOLD V M H.V. LIVE CIRCUIT DIGITAL INSULATION TESTER DO NOT OPERATE IF LIT POWER DATA HOLD TEST ON / OFF 250V 500V 1000V OFF CAT.

Instruction Manual. 99 Washington Street Melrose, MA Fax TestEquipmentDepot.com. Model 308A Digital Insulation & Continuity Meter

Non-Contact Phase Rotation Tester

Tracer ORP PockeTester TM Code 1742

Test Equipment Depot Washington Street Melrose, MA TestEquipmentDepot.com INSTRUCTION MANUAL PSMR1

ANALOGUE INSULATION-CONTINUITY and VOLTAGE METER

Safety design conforming to the following provisions

362 Clamp Meter. Users Manual

DIGITAL INSULATION RESISTANCE TESTER (5KV, 1T )

OPERATING INSTRUCTIONS

INSTRUCTION MANUAL DM5B Fax: (503)

INSPECTOR LINE LOAD SIMULATOR INSTRUCTION MANUAL TASCO, INC.

MOdel No: MM19.V3 WARNING CAUTION 1. SAFETY INSTRUCTIONS

PRM-4. Phase Sequence and Motor Rotation Tester. Users Manual. For detailed specifications and ordering info go to

Calibrator Capabilities Function Range Resolution Measure V dc 28 V 1 mv Measure ma dc Source ma dc

INSTRUCTION MANUAL IDM97II DIGITAL MULTIMETER EN FR IT DE

Non-Contact Phase Rotation Tester

OPERATING INSTRUCTION

323/324/325 Clamp Meter

MEGOHMMETER. User Manual

Dawson DAN100. Analog Multimeter User s Manual

Digital Multimeter User's Manual

INSP-3 Wiring Inspection Tester

ATD-5570 Deluxe Automotive Meter with RPM and Temperature Functions Owner s Manual Features:

INSTRUCTION MANUAL CM69 TRMS AC EARTH LEAKAGE CLAMP METER. 1. SAFETY INFORMATION: Always read before proceeding. REMEMBER: SAFETY IS NO ACCIDENT

Users Manual. Phase Rotation Indicator

MegOhmMeter. Users Manual

Table of Contents. Title Page UT501/UT502 OPERATING MANUAL. Introduction. Unpacking the Meter. Safety Information. International Electrical Symbols

Megohmmeter Test Probe

Vol-Con XL (61-086) Voltage/Continuity Tester and Vol-Test (61-085) Voltage Tester Instruction Manual WARNING

BENCHTOP INSTRUMENT BENCH TYPE DIGITAL MULTIMETER DM-1140B OPERATION MANUAL V2.0

OPERATING INSTRUCTIONS

ASTROAI USER MANUAL DIGITAL MULTIMETER. NOTE: Fully read and understand this manual before using this instrument.

362 Clamp Meter. Users Manual

INSTRUCTION MANUAL IDM93N DIGITAL MULTIMETER EN FR IT DE

1.Safe testing IMPORTANT:

365 Detachable Jaw True-rms Clamp Meter

INSTRUCTION MANUAL IDM67 DIGITAL MULTIMETER

NEW 15KV HIGH VOLTAGE INSULATION RESISTANCE TESTER MODEL KM 7015 IN FEATURES : CAT IV 600V. Short Circuit Current 5mA.

i400s Calibration Information Introduction

Calibration Manual. Detachable Jaw True-rms Clamp Meter

373 Clamp Meter. Users Manual

Solar Power Light Meter

INSTRUCTION MANUAL ANALOGUE INSULATION TESTER KEW 3131M KYORITSU ELECTRICAL INSTRUMENTS WORKS,LTD., TOKYO JAPAN

Safety design conforming to the following provisions

Digital Insulation Resistance Testers. you can depend on

ATD-5540 Digital Automotive Engine Analyzer/Multimeter Owner s Manual

OPERATING INSTRUCTION

IAQ-CALC INDOOR AIR QUALITY METER MODEL 7515

Component Test Fixture

l The Battery Tester is designed for measuring the l AC four-terminal method to measure the internal

A.W. SPERRY INSTRUMENTS INC.

AMB V Insulation Resistance Tester. Users Manual. For detailed specifications and ordering info go to

USER GUIDE. Model RH10 Hygro Thermometer. Humidity and Temperature Meter

INSTRUCTION MANUAL CM95/ CM100 TRUE RMS FLEXIBLE CLAMP METER. 1. SAFETY INFORMATION: Always read before proceeding. REMEMBER: SAFETY IS NO ACCIDENT

For technical questions and replacement parts, please call

1662/1663/1664 FC. Electrical Installation Tester. Safety Information. Warnings

51 & 52 Series II. Users Manual. Thermometer. Test Equipment Depot Washington Street Melrose, MA TestEquipmentDepot.

INSTRUCTION MANUAL PORTABLE APPLIANCE TESTER

Transcription:

User Guide Model 380363 Insulation Tester / Megohmmeter Introduction Congratulations on your purchase of Extech s Insulation Tester/Megohmmeter. The Model 380363 provides three test ranges plus continuity and AC/DC voltage measurement. Manual datalogging stores up to 9 data sets. This professional meter, with proper care, will provide years of reliable service.

Safety 1. Circuits under test must be de-energized and isolated before connections are made (except for voltage measurements). 2. Circuit connections must not be touched during a test. Use extreme caution when working near bare conductors and bus bars. Accidental contact with conductors could result in electrical shock. 3. Use caution when working near voltages above 60VDC or 30VACrms. 4. After insulation tests, capacitors must be discharged. 5. Test leads (including alligator clips) must be in good working order, clean and without broken or cracked insulation. 6. When servicing, use only specified replacement parts. International Safety Symbols Caution, refer to this manual before using this meter Dangerous Voltages Meter is protected throughout by double or reinforced insulation Specifications General specifications Display Sampling rate Test ranges AC/DC Voltage range Resistance range Lo Resistance range Over range indicator Zero adjust Memory Low battery indicator Power source Power consumption Fuse protection Operating conditions Dimensions Weight Safety ratings Category Rating 3-3/4 digit (4000 count) LCD 1 reading per second Resistance: 4MΩ, 40MΩ, 400MΩ, 4000MΩ, 10GΩ Test Voltages: 250V, 500V, 1000V 999V 9999Ω 40Ω OL displayed when measurement exceeds range Automatic Nine (9) data records BT symbol displayed when battery voltage is low Six (6) 1.5 AA batteries 20 to 95mA (depending upon function) 0.5A / 600V fast blow fuse 32 to 122 o F (0 to 50 o C); 80% RH 9.3 x 4.6 x 2.1 (235 x 116 x 54mm) 1.15 lbs (520g) Pollution degree 2; indoor use; CE marked; Meets IEC 61010-1 and IEC 61557 standards CAT III-1000V 2

Range Specifications MEGOHMMETER RANGES Range Test Voltages Resolution Accuracy 4MΩ 40MΩ 400MΩ 4000MΩ 10GΩ 250V (+30% ~ -0%) 500V (+30% ~ -0%) 1000V (+30% ~ -0%) 0.001MΩ 0.01MΩ 0.1MΩ 1MΩ 00.01GΩ 3%+5 (<1000M) 5%+5 (>1000M) (% reading + digits at 23 o C ± 5 o C < 80% RH) Analog Bar Graph 0 to 10GΩ Nominal Current 1mA Circuit Protection Test inhibited if input 30V AC or DC AC VOLTAGE (40Hz-500Hz) Range Res. Accuracy Input impedance Overload Protection 999VAC 1V ±2% + 2d 9MΩ 1000Vrms DC VOLTAGE Range Res. Accuracy Input impedance Overload Protection 999VDC 1V ±1% + 2d 9MΩ 1000Vrms RESISTANCE & CONTINUITY Range Res. Accuracy Max. open circuit Volt Overload Protect. Resistance: 999.9Ω 0.1Ω ±1% + 3d 3V 1000Vrms Continuity 100Ω ± 80Ω) LOW RESISTANCE Ω Range Res. Accuracy Max. open circuit Volt Overload Protection 40Ω 0.01Ω ±2% + 2d 6V >30V AC/DC 3

Meter Description 10 1. LCD Display 2. LOCK button 3. MEMORY control button 4. UP arrow key 5. TEST button 6. Rotary switch 7. DOWN arrow key 8. READ memory button 9. ZERO adjust button 10. Input terminals The tilt stand and battery compartment are located at the rear of the instrument 1 2 3 4 5 6 9 8 7 Warning Ensure that the circuit under test does not include components that can be damaged by 1000VDC; such devices include power factor correction capacitors, low voltage mineral insulated cables, electronic light dimmers, and ballasts/starters for fluorescent lamps. Operation Connecting Test Leads For all measurements connect the red test lead to the VΩ input terminal and the black test lead to the COM input terminal. Test Lead Check 1. Set the rotary switch to the Ω range. 2. Touch the test lead tips together. 3. Resistance should read less than 0.5Ω and the audio tone should sound. 4. With the leads not touching, the display should read OL indicating over-range. 5. Readings displayed other than the readings described above are evidence of a problem and the test leads must be replaced before using the meter. Failure to do so could result in damage to equipment and electrical shock. If replacing the test leads does not solve the problem, return the instrument for repair. 4

Insulation Resistance Measurements (Megohmmeter Tests) Warning: Do not perform Insulation Resistance measurements if AC Voltage is present on the device under test. 1. Connect the red test lead to the VΩ input terminal; black lead to the COM terminal. 2. Set the function switch to the desired MΩ test voltage position. 3. Connect the tips of the test leads to the equipment under test. If there is a voltage present, it will be displayed. A repetitive beep and the flashing high voltage symbol will be displayed if the voltage is over 30V. 4. The display will show ---- until the TEST button is pushed. Press and hold the TEST button. The upper right display shows the test voltage applied. The main display shows the resistance. If the display reads OL, the measurement is beyond the range of the instrument. 5. Keep the test leads connected to the equipment under test and release the TEST button. The circuit will discharge through the meter. Keep the test leads connected until the circuit is completely discharged and the upper right display shows 0 volts. Test Lock Function For hands-free operation, use the TEST LOCK feature. 1. With the test leads connected to the equipment under test, press the LOCK key to enter the LOCK mode. The LOCK icon will appear on the display. 2. Press the TEST key to start the test. A beeper will sound every 2 seconds to indicate that the meter is in Lock mode. 3. Press LOCK or TEST to disable the Lock function and end the test. Notes on IR (Megohmeter) testing: 1. The maximum measurement range for the 380363 is 10GΩ. Frequently, insulation resistance will exceed this value and the meter will show the overload display symbol OL, indicating that the insulation under test is good. 2. If the device being tested is highly capacitive, the display will indicate an increasing resistance value over time. Allow the reading to stabilize before ending a test. Manual Data Store and Read Mode To Clear Memory 1. Turn the meter off. 2. Press and hold down the MEM key, and turn the meter on. 3. The display will show MEM0 in the upper left hand corner - indicating that the memory has been erased. Entering data into memory 1. Press the MEM key to enter the displayed data into memory (a beep will sound). 2. The display will show MEM and the memory address number in the upper left hand corner. Total memory size is 9 sets. 3. When memory is full, the meter will sound two quick beeps. Reading memory data 1. Press the READ key to enter Read Mode. The display will show the READ icon and the memory address number in the upper left hand corner. 2. Use the and arrow keys to scroll through the stored readings. 3. Press the READ key again to exit this mode. 5

AC/DC Voltage Measurement 1. Set the Rotary switch to the ~ V position. 2. Connect the red test lead to the VΩ terminal and the black test lead to the COM terminal. 3. Connect the test leads to the circuit under test. 4. Read the voltage value on the LCD. The meter shows DC voltage in the upper right and AC voltage on the main display. Resistance Measurement and Audible Continuity Test WARNING Do not run this test unless ACV = 0. Do not use this mode to check diodes. 1. Set the Rotary switch to the Ω position. 2. Connect the red test lead to the VΩ terminal and the black lead to the COM terminal. 3. Connect the tips of the test leads to the circuit under test. 4. Read the resistance value on the display. When the resistance of a circuit is less than approx. 100Ω ± 80Ω, the audible tone will sound. LOΩ Low Resistance Measurement 1. Set the Rotary switch to the LoΩ position. 2. Connect the red test lead to the VΩ terminal and the black lead to the COM terminal. 3. Touch the test leads together and press the key to zero the display. 4. Connect the probes to the ciruit under test. If there is a voltage present, it will be displayed. A repetitive beep and the flashing high voltage symbol will be displayed if the voltage is over 30V. Remove the voltage before proceeding to the next step. 5. Press and hold the TEST key until a stable reading is displayed. 6. Release the TEST key. The upper right hand display will hold the reading until a new test is started or a different function is selected. 7. Swap the red and black probes to reverse the polarity of the test current. The reading should remain the same. This test is useful to detect corroded connections which can cause different readings in both polarities. 6

Using the LOCK Function to measure resistance The Lock function can be used to make several resistance measurements in succession without the need to push and hold the TEST key for each measurement. 1. Press the LOCK key to enter the LOCK mode, and then press the TEST key. 2. Zero out the test lead resistance. 3. Connect the probes to the test locations in succession. 4. Press the LOCK key to disable the lock function. Note: The meter cannot indicate if the circuit is live in this mode. Ensure that the circuit is deenergized before connecting the test leads or the fuse may blow. Auto Power Off To conserve battery life, the meter will automatically turn off after 15 minutes of non-use. To turn the meter back on, turn the rotary switch to OFF, then to the desired function. Analog Bar Graph The analog bar graph displays resistance on a logarithmic scale and voltage on a linear scale. The value always tracks the main display. Maintenance Battery Replacement When the low battery symbol appears (BT) on the LCD the six 1.5V AA batteries must be replaced. 1. Turn the meter off and remove the test leads 2. Remove the four (4) Phillips head screws on the rear of the meter 3. Remove the meter s rear cover 4. Replace the batteries observing polarity 5. Affix the rear cover and secure the rear screws Fuse Replacement If the meter turns ON but does not measure correctly, check the internal fuse. 1. Turn the meter off and remove the test leads 2. Remove the four (4) Phillips head screws on the rear of the meter 3. Remove the meter s rear cover 4. Check and replace the fuse if necessary (0.5A / 600V fast blow) 5. Affix the rear cover and secure the rear screws Cleaning Periodically wipe the case with a dry cloth. Do not use solvents or abrasives to clean this instrument. 7

Applications Measuring Power Tools and Small Appliances This section applies to any device under test that uses a line cord. For double insulated power tools, the meter s leads should be connected to the device s housing (chuck, blade, etc.) and to the lines of the power cord. Refer to the diagram. Testing AC Motors Disconnect the motor from the line by disconnecting the wires from the motor terminals or opening the mains switch. If the mains switch is opened, and the motor also has a motor-starter, then the starter must be held in the ON position. With the mains switch opened, the measured resistance will include the resistance of the motor wire and all other components between the motor and the main switch. If a weakness is indicated, the motor and other components should be checked individually. If the motor is disconnected at the motor terminals, connect one meter lead to the grounded motor housing and the other lead to one of the motor leads. Refer to diagram at below. Motor Starter Mains Switch Line GND Notes: 1. The STARTER must be in the ON position during the 8

Testing DC Motors 1. Disconnect the motor from the line. 2. To test the brush rigging, field coils and armature, connect one meter lead to the grounded motor housing and the other lead to the brush on the commutator. 3. If the resistance measurement indicates a weakness, raise the brushes off of the commutator and separately test the armature, field coils and brush rigging (one at a time). Leave one lead connected to the grounded motor housing while testing the motor components. This also applies to DC Generators. Testing Cables 1. Disconnect the cable under test from the line. 2. Disconnect the opposite end of the cable to avoid errors as a result of leakage from other equipment. 3. Check each conductor to ground and/or lead sheath by connecting one meter lead to ground and/or lead sheath and the other meter lead to each of the conductors in turn. 4. Check insulation resistance between conductors by connecting meter leads to conductors in pairs. Refer to diagram. In the diagram, note that the 3-conductor cable has two wires shorted to the ground shield. This two-wire/shield connection is then connected to one side of the meter. The remaining conductor is connected to the other side of the meter. 9

Repair and Calibration Extech offers repair and calibration services for the products we sell. Extech also provides NIST certification for most products. Call the Customer Service Department for information on calibration services available for this product. Extech recommends that annual calibrations be performed to verify meter performance and accuracy. Support line (781) 890-7440 Technical support: Extension 200; E-mail: support@extech.com Repair & Returns: Extension 210; E-mail: repair@extech.com Product specifications subject to change without notice For the latest version of this User s Guide, Software updates, and other up-to-the-minute product information, visit our website: www.extech.com Warranty EXTECH INSTRUMENTS CORPORATION warrants this instrument to be free of defects in parts and workmanship for one year from date of shipment (a six month limited warranty applies on sensors and cables). If it should become necessary to return the instrument for service during or beyond the warranty period, contact the Customer Service Department at (781) 890-7440 ext. 210 for authorization or visit our website at www.extech.com (click on Contact Extech and go to Service Department to request an RA number). A Return Authorization (RA) number must be issued before any product is returned to Extech. The sender is responsible for shipping charges, freight, insurance and proper packaging to prevent damage in transit. This warranty does not apply to defects resulting from action of the user such as misuse, improper wiring, operation outside of specification, improper maintenance or repair, or unauthorized modification. Extech specifically disclaims any implied warranties or merchantability or fitness for a specific purpose and will not be liable for any direct, indirect, incidental or consequential damages. Extech's total liability is limited to repair or replacement of the product. The warranty set forth above is inclusive and no other warranty, whether written or oral, is expressed or implied. Copyright 2005 Extech Instruments Corporation. All rights reserved including the right of reproduction in whole or in part in any form. 10