VL Circuit Breaker DG 150A frame

Similar documents
VL Circuit Breaker FG 250A frame Breaker type Defined by the 3rd character of the catalog number K Global, Non-interchangeable

Table Line and Load Terminals. Terminal Body Material. Wire Type. Aluminum Copper Aluminum. English English English.

Interchangeable Built-in Fixed thermal Adjustable thermal Magnetic Fixed Adjustable Adjustable Electronic RMS 7 LS LSI

Table Types LD, HLD and LDC Thermal-Magnetic Circuit Breakers with Interchangeable Trip Units

Molded Case Circuit Breakers

Tmax Molded Case Circuit Breakers

L-Frame. With Standard Line and. Standard Terminals Only. Catalog Number. Price U.S. $ LDB2300 LDB2350 LDB2400 LDB2450 LDB2500 LDB2600

Tmax Molded Case Circuit Breakers

Speedfax Supplement to Product Catalog. Electrical, Commercial, and Industrial Power Distribution and Control Products

Courtesy of CMA/Flodyne/Hydradyne Motion Control Hydraulic Pneumatic Electrical Mechanical (800) RG H ZG E C

2.2. Molded Case Circuit Breakers. Contents. NG-Frame ( Amperes) Series G

VL Circuit Breakers. MG 800A Frame, VL Series. Selection/Dimensions. Revised 03/08/13. Dimensions, inches (mm) Interrupting Ratings

Product Line Overview. The Most Logically Designed Contact Assembly

S4 N 250 B W - 2 xxx. Isomax. Isomax Molded case circuit breakers S3 S8. MCCBs

Molded Case Circuit Breakers

L-Frame LD F. Circuit Breaker/ Frame Ampere Rating. Trip Unit Rating/ Plug Ampere Rating LD T5 7 W

VL Circuit Breaker Features & Benefits. powerful ideas RELIABLE SOLUTIONS

Industrial Generator Set Accessories. Standard Features. Line Circuit Breakers kw

The breakers offer thermal-magnetic trip protection according to Z and K characteristics.

Molded Case Circuit Breakers

Thermal-Magnetic For Mining Applications Class 600

SENTRON VL Series Product Specifications

Miniature Circuit Breakers

Molded Case Circuit Breakers

Bulletin 140U R-Frame Molded Case Circuit Breakers

Technical Information

S4 N 250 B W - 2 xxx. Isomax MCCBs. Isomax Molded case circuit breakers S1 S8

24.4. Miniature Circuit Breakers and Supplementary Protectors. For Immediate Delivery or Tech Support call KMParts.com at (866)

Protectors. 35mm DIN rail snap-on mounting. Wide range of accessories

Molded Case Circuit Breakers Reference Guide

APPENDIX E. Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection Device Specifications

Control Circuit Protection

Selection and Application Guide Supplement. WL UL Pole Circuit Breakers. usa.siemens.com/wlbreaker

Section 3: Molded Case Circuit Breakers

Series KTU7 UL489 Molded Case Circuit Breakers

25.4. Molded Case Circuit Breakers. For Immediate Delivery or Tech Support call KMParts.com at (866) Contents

Data Sheet Molded Case Circuit Breakers Molded Case Motor Circuit Protectors Molded Case Switches. Ex9 Series - M. na.noark-electric.

S200 UL 1077 Series S200. Supplementary protective devices. UL 1077 Series. Miniature. circuit breakers. S200 Supplementary protective devices

MCBs and accessories are certified under CSA C22.2 No. 235 per File LR Tripping characteristics

Series KTU7 UL489 Molded Case Circuit Breakers

Catalog LV 1 Add-On October sentron CIRCUIT-BREAKERS. 3VL Molded Case Circuit-Breakers approved according to UL 489 up to 1600 A

Data Sheet Molded Case Circuit Breakers Molded Case Motor Circuit Protectors Molded Case Switches Ex9 Series - M

PRICING. Multi 9, Compact, Masterpact, Interpact, and Vigirex Circuit Protection Products. Class 600. October 2004

UTS400 SELECTION GUIDE CATALOG NUMBERING [PRODUCT SELECTION] UTS400 NT ATU 400A 3P LL LSIS UL MCCB

Molded Case Circuit Breakers

Q and M-Frame Circuit Breaker Instruction Leaflet for Installation and Operation for Thermal Magnetic Trip Units

US Brochure. Tmax XT Molded case circuit breakers Simply XTraordinary

Molded Case Circuit Breakers Amperes LSIA. LSIG Catalog Number 3-Pole Standard Interrupting Capacity 600V AC Rated V AC 13,950.

Amperes. F-Frame. Price U.S. $ Catalog Number. Price U.S. $ EDH2100 EDH2125 EDH2150 EDH2175 EDH2200 EDH2225

Manual motor protectors Type MS116 Type MS325 Type MS45X Type MS49X

Manual motor protectors Type MS116 Type MS325 Type MS45X Type MS49X

LOW VOLTAGE SWITCHGEAR

PowerPact B. Molded case circuit breakers and switches from A

MINIATURE CIRCUIT BREAKERS RCBO s & DIN RAIL MOUNTED FUSE HOLDERS

Page 2 DS LOW VOLTAGE POWER CIRCUIT BREAKERS Digitrip Trip Unit Inside Wiring Guide Outside Wiring Guide Shutter Drawout Unit Position Indicator Escut

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

Magnum IEC Low Voltage Air Circuit Breakers

Molded Case Circuit Breakers

Circuit-Breakers M4 166 for motor protection. Auxiliary contacts 167 Signalling switch Auxiliary releases

Molded Case Circuit Breakers

Molded Case Circuit Breakers

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers

C E R T I F I C A T E O F C O M P L I A N C E

DPX earth leakage DPX 3 -I earth leakage

Product index. 4 - Manual motor protectors. Manual motor protectors. Manual motor protectors Low Voltage Products & Systems 4.

2.3. Molded Case Circuit Breakers. Contents

PowerPact Circuit Breakers for Control Panel Disconnects Class 0611

DPX Thermal magnetic and trip-free switches DPX 3 -I 250

System pro M compact Miniature Circuit Br eakers Description Features

Low-Peak 600V Class RK1

PowerPact M-, P- and R-Frame, and Compact NS630b NS3200 Circuit Breakers

Critical Power Switchboards. Selection and Application Guide

DPX Magnetic only

UL 489/CSA C22.2 No. 5 Listed C60 Circuit Breakers 1.22 [31.1] 1.77 [45.1] 4.86 [123.4] Clearance 1.77 [45]

LPSRK30SP 30A 600V TD Dual Elem Class RK1 Low Peak Fuse

DMX 3 -I 2500 switch disconnectors

Series G Moulded Case. Circuit Breakers. Series G Moulded Case Circuit Breakers 1

Power Break II Switchboard

Type MP-T Type MP-HT Type MP-MT

UMBW-UL489 and UL1077 Listed

S200-C, 480Y/277 VAC Supplemental protectors UL 1077, CSA 22.2

MS General Information Extended Product Type: MS

A. Submit manufacturer's literature and technical data before starting work.

MS /27/2015. ABB contact for United States of America. General Information Extended Product Type: Categories

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases

PD-Series Ground Fault Circuit Protection

Certi cation Record INDUSTRIAL CONTROL EQUIPMENT Motor Controllers Magnetic

Cutler-Hammer Molded Case Circuit Breakers Amperes. January 2001 Vol. 1, Ref. No. [0477] G-Frame

Series L9 UL-489 Miniature Circuit Breakers

Selection Information Molded Case Circuit Breakers


Product index. 4 - Manual motor protectors. Phone: Fax: Web: -

Data Sheet DIN Rail Miniature Circuit Breakers Ex9 Series - B1NQ

Motor Circuit Breakers C4

S200 UL 489 Series. Miniature circuit breakers S200. Features. Description

S200 UL 489 Series. Miniature Circuit Breakers. Description. Features

3.1. Power Breakers, Contactors and Fuses. Contents. Series NRX Low Voltage Power Circuit Breakers. Power Circuit Breakers

BULLETIN 140U. Molded Case Circuit Breakers SELECTION GUIDE

Preliminary AC1615S. ABB Molded Case Circuit Breakers

Cutler-Hammer. January 2001

Transcription:

VL Circuit Breaker DG 150A frame Breaker type Defined by the 3rd character of the catalog number G Global (UL, CSA, IEC, CE, CCC), interchangeable K Global, non-interchangeable W Global, 100% rated, non-interchangeable, electronic only Trip unit type Defined by the 5th character of the catalog number B Thermal-magnetic, model 525 N LI, electronic, model 545 P LSI, electronic, model 545 X LIG, electronic, model 545 U LSIG, electronic, model 545 D LSI, electronic with LCD, model 576 E LSIG, electronic with LCD, model 576 R LI, electronic, Model 555 T LSI, electronic, Model 555 W LIG, electronic, Model 555 V LSIG, electronic, Model 555 A LSI, electronic with LCD, Model 586 G LSIG, electronic with LCD, Model 586 K LSI + GF alarm, electronic with LCD, Model 586 For DC applications, use thermal magnetic trip unit only. For reverse-feed applications, select non-interchangeable trip breakers only. Due to the location of the magnetic tripping solenoid, the left accessory pocket of electronic breakers is not available for accessories. HACR rated. Interrupting ratings Interrupting Class Breaker Type b RMS symmetrical amperes (ka) UL 489 IEC 60947-2 UL or IEC Volts AC Volts AC Volts DC a 240 480 600Y/347 240 I cu /I cs 415 I cu /I cs 690 I cu /I cs 250 500 600 N NDGB 65 35 18 65 / 65 40 / 40 12 / 6 30 18 H HDGB 100 65 18 100 / 75 70 / 70 12 / 6 30 18 42 L LDGB 200 100 18 200 / 150 100 / 75 12 / 6 30 18 UL / CSA / NOM 40ºC 50/60Hz IEC 40ºC 50/60Hz a For DC applications and wiring diagrams, see p. 5 of VL Information Guide. b Special version, Type HDGD. See Speedfax catalog for more information. Trip Unit Model 525 Thermal magnetic trip units, model 525 I n Trip unit rating I i Nominal instantaneous trip (amps) adjustable range (amps) 50 450 480 510 540 570 600 60 450 480 510 540 570 600 70 450 500 550 600 650 700 80 450 520 590 660 730 800 90 500 600 700 800 900 1000 100 500 600 700 800 900 1000 110 550 660 770 880 990 1100 125 625 750 875 1000 1125 1250 150 800 960 1120 1280 1440 1600 Trip Unit Model 545 960 I i 1120 AMPS 1280 1440 800 1600 Electronic trip units, Model 545 with LI (Trip unit type N) or LIG (Trip unit type X) Trip Functions I n = 150A 40º C TM ~ TRIP UNIT/DISPARADOR 525 Trip unit model 525 Type / Tipo CDT3 60 30 30 30 30 32 35 40 45 50 60 100 40 40 45 50 60 63 70 80 90 100 150 60 60 63 70 80 90 100 110 125 150 rating (amps) t r Long time delay switch settings (seconds) Pt @ 6 x I r 60, 100, 150 2.5 4 6 8 10 14 17 20 25 30 rating (amps) I i Nominal instantaneous trip switch settings (amps) 60 75 90 120 180 240 300 360 480 600 660 100 125 150 200 300 400 500 600 800 1000 1100 150 187 225 300 450 600 750 900 1200 1500 1650 Fixed settings (LIG only) rating (amps) I g Ground fault pickup (amps) t g Ground fault delay 60 48.07 sec 100 80.07 sec 150 120.07 sec Trip unit model 545 9

Trip Unit Model 545 (continued) Electronic trip units, Model 545 with LSI (Trip unit type P) or LSIG (Trip unit type U) Trip Functions 60 30 30 30 30 32 35 40 45 50 60 100 40 40 45 50 60 63 70 80 90 100 150 60 60 63 70 80 90 100 110 125 150 rating (amps) I sd Short time pick-up switch settings (amps) x I r 60, 100, 150 1.5 2 2.5 3 4 5 6 7 8 10 rating (amps) t sd Short time delay switch settings (seconds) @ 8xl r 60, 100, 150 0 0.1, I 2 t OFF 0.2, I 2 t OFF 0.3, I 2 t OFF 0.4, I 2 t OFF 0.5, I 2 t OFF 0.1, I 2 t ON 0.2, I 2 t ON 0.3, I 2 t ON 0.4, I 2 t ON Fixed settings rating (amps) t r Long time delay I i Nominal instantaneous trip I g Ground fault pick-up (LSIG only) t g Ground fault delay (LSIG only) 60 660A 48A.07 sec. 100 10 sec. (I 2 t @ 6 x I r ) 1100A 80A.07 sec 150 1650A 120A.07 sec Trip Unit Model 555 Switch 4 Electronic trip units, Model 555 with LI (Trip unit type R) or LIG (Trip unit type W) Trip Functions Switch 4 (LIG Only) 60 30 30 30 30 32 35 40 45 50 60 100 40 45 50 55 60 63 70 80 90 100 150 60 63 70 75 80 90 100 110 125 150 rating (amps) t r Long time delay switch settings (seconds) I 2 t @ 6 x I r 60, 100, 150 2.5 4 6 8 10 14 17 20 25 30 rating (amps) I i - Nominal instantaneous trip switch settings (amps) 60 75 90 120 180 240 300 360 480 600 660 100 125 150 200 300 400 500 600 800 1000 1100 150 187 225 300 450 600 750 900 1200 1500 1650 rating (amps) I g - Ground fault pick-up switch settings (amps) 60 48 24 24 24 36 36 36 60 60 60 100 80 40 40 40 60 60 60 100 100 100 150 120 60 60 60 90 90 90 150 150 150 rating (amps) t g Ground fault delay switch settings (seconds) 60, 100, 150 0.07 0.10 0.20 0.30 0.10 0.20 0.30 0.10 0.20 0.30 10

Trip Unit Model 555 (continued) Switch 4 Electronic trip unit, Model 555 with LSI (Trip unit type T) Trip Functions Switch 4 60 30 35 40 50 60 30 35 40 50 60 100 40 50 60 80 100 40 50 60 80 100 150 70 80 100 125 150 70 80 100 125 150 rating (amps) t r Long time delay switch settings (seconds) I 2 t @ 6 x I r 60, 100, 150 4 4 4 4 4 14 14 14 14 14 rating (amps) I sd Short time pick-up switch settings (amps) x I r 60, 100, 150 1.5 2 2.5 3 4 5 6 7 8 10 rating (amps) t sd Short time delay switch settings (seconds) 60, 100, 150 0 0.1, I 2 t OFF 0.2, I 2 t OFF 0.3, I 2 t OFF 0.4, I 2 t OFF 0.5, I 2 t OFF 0.1, I 2 t ON 0.2, I 2 t ON 0.3, I 2 t ON 0.4, I 2 t ON rating (amps) I i Nominal instantaneous trip switch settings (amps) 60 75 90 120 180 240 300 360 480 600 660 100 125 150 200 300 400 500 600 800 1000 1100 150 187 225 300 450 600 750 900 1200 1500 1650 Electronic trip unit, Model 555 with LSIG (Trip unit type V) Trip Functions Switch 4 60 30 35 40 50 60 30 35 40 50 60 100 40 50 60 80 100 40 50 60 80 100 150 70 80 100 125 150 70 80 100 125 150 rating (amps) t r Long time delay switch settings (seconds) I 2 t @ 6 x I r 60, 100, 150 4 4 4 4 4 14 14 14 14 14 rating (amps) I sd Short time pick-up switch settings (amps) x l r 60, 100, 150 1.5 2 2.5 3 4 5 6 7 8 10 rating (amps) I i Nominal instantaneous trip switch settings (amps) x l n 60, 100, 150 5 5 5 5 5 11 11 11 11 11 rating (amps) t sd Short time delay switch settings (seconds) 60, 100, 150 0 0.1, I 2 t OFF 0.2, I 2 t OFF 0.3, I 2 t OFF 0.4, I 2 t OFF 0.5, I 2 t OFF 0.1, I 2 t ON 0.2, I 2 t ON 0.3, I 2 t ON 0.4, I 2 t ON rating (amps) I g Ground fault pick-up switch settings (amps) 60 48 24 24 24 36 36 36 60 60 60 100 80 40 40 40 60 60 60 100 100 100 150 120 60 60 60 90 90 90 150 150 150 rating (amps) t g Ground fault delay switch settings (seconds) 60, 100, 150 0.07 0.10 0.20 0.30 0.10 0.20 0.30 0.10 0.20 0.30 11

Trip Unit Model 576 and 586 X3 440JM ESC Electronic trip units with LCD Model 576 (Trip unit type D and E) or Model 586 (Trip unit type A, G and K) I n Trip unit rating (amps) Trip unit model 576 Trip unit model 586 I r Continuous amps range a t r Long time delay settings (I 2 t @ 6 x I r ) I sd Short time pick-up range t sd Short time delay settings Ii Nominal instantaneous trip range ab 75-660A 60 30-60 2.5, 4, 6, 8, 10, 14, 0.1, 0.2, 0.3, 0.4, 0.5 sec. 100 40-100 1.25-10 x I 17, 20, 25, 30 sec. r 125-1100A or I 2 t @ 8 x I 150 60-150 r 188-1650A rating (amps) I g Ground fault pick-up range ac 60 24-60A 100 40-100A 150 60-150A t g Ground fault delay Pre-alarm indication 0.1, 0.2, 0.3, 0.4, 0.5 sec. 80-100% I2t @.5 x I n x I r (Amps) a Current settings are adjustable in 1-amp increments. b Model 586, can turn function OFF. Instantaneous trip override function will be enabled to ensure self protection of circuit breaker. c Model 586, trip unit type K = alarm only. Motor circuit protectors Amp I i Nominal instantaneous trip rating adjustable range (amps) 150 450-900 a 150 750-1500 b 150 1250-2500 c a Settings adjustable in increments of 90 amps. b Settings adjustable in increments of 150 amps. c Settings adjustable in increments of 250 amps. Molded case switch Amp rating Self-protective instantaneous override Short-circuit current rating 480 V AC a 150 2500A 65 ka a Max. available current when protected by an appropriate overcurrent protective device. 600 V DC circuit breakers Amp rating Short-circuit rating 600 V DC 50, 60 70, 80, 90, 100, 110, 42 ka 125, 150 12

Terminal Connectors Wire range Cables per connectors Wire size Torque Ib-in. (Nm) Catalog number #8 1/0 1 (Cu only) #6 3/0 1 (Cu / Al) #6 3/0 1 (Cu only) #8 #6 #1/0 #6 #1 1/0 3/0 #6 #1 1/0 3/0 35 (3.95) 70 (7.91) 50 (5.85) 120 (13.56) 50 (5.65) 120 (13.56) 3TW1DG20 a 3TA1DG30 ab 3TC1DG30 ad Compression connector kits #14 2/0 1 (Cu / Al) 3CLD20 a #14 2/0 1 (Cu / Al) 2CLD20 c Distribution connector kits #14 #2 3 (Cu / Al) #14 #8 #6 #2 35 (3.95) 60 (6.78) 3TA3DG02 a #14 #4 6 (Cu / Al) #14 #4 35 (3.95) 3TA6DG04 a a Packaged as 3 connectors. b Standard connectors when an L suffix is used on an assembled breaker catalog number. c Packaged as 2 connectors. d Required for 100% rated DG breakers. Requires 90 C cable sized at 75 C ampacity. Internal accessories Auxiliary and alarm switch kits Auxiliary / Alarm switches only (requires a base) Description Mounting pocket Catalog number Description Catalog number 1 Alarm switch 1 A/B a bases AMBL2 and AMBL3 Left, 1 NO (normally open contact) ASWPA rightb ASKL1 2 Aux. switches 1A + 1B base AMBL1 2 Aux. + 1 Alarm switch 1A + 1B, 1A/B bases a AMBL2 and AMBL3 Left, right Left, right b ASKL2 ASKL3 a Includes 1A and 1B contact for alarm purposes, only one of which may be installed at any time. b Kit includes 2 bases - one for mounting switches in left pocket and another for mounting in right pocket. Auxiliary and alarm switch mounting base only Description Mounting pocket Catalog number For 2 Aux + 1 Alarm Left AMBL2 For 2 Aux + 1 Alarm Right AMBL3 For 3 Aux Left, right AMBL1 Shunt trip Control voltage Catalog number 48 60 VAC STRLM60 110 127 VAC STRLN120 208 277 VAC STRLS277 380 600 VAC STRLV600 24 VDC STRLB24DC 48 60 VDC STRLC60DC 110 127 VDC STRLD125DC 220 250 VDC STRLE250DC Shunt trips or UVR s may be mounted in the Right Pocket only. Internal accessory locations Left accessory pocket Right accessory pocket Up to 3 auxiliary switches Shunt trip or UVR or up to 3 auxiliary switches Up to 2 auxiliary switches + 1 alarm switch Maximum of 6 switches total. Maximum of 2 alarm switches, 1 Left + 1 Right Pocket. Shunt trip or UVR or up to 2 auxiliary switches + 1 alarm switch 1 NC (normally closed contact) ASWPB (A) Normally open contacts are open when the breaker contacts are open. (B) Normally closed contacts are closed when the breaker contacts are open. Undervoltage release Control voltage Catalog number 110 127 VAC UVRLN120 220 250 VAC UVRLR240 208 VAC UVRLP208 277 VAC UVRLS277 380 425 VAC UVRLT415 440 480 VAC UVRLU480 12 VDC UVRLA12DC 24 VDC UVRLB24DC 48 VDC UVRLC48DC 60 VDC UVRLG60DC 110 127 VDC UVRLD125DC 220 250 VDC UVRLE250DC 13

Dimensions.60 [15.5] 1.375 [35] 1.375 [35].09 [2.5] (150A).16 [1.3] (250A) 4.19 [106.5] 3.56 [90.5] 3.20 [81.5].75 [19] 6.88 [174.5] 3.49 [88.5].51 [13] 2.98 [75.5] 5.87 [149] 2.28 [58] 4.74 [120.5] Y ø.21 [ø5] 2.06 [52.5] 2.50 [63.5] 1.25 [31.5] 4.12 [104.5] (3P) 1.25 [32].62 [16] NFT00772a Y Y X X (complete breaker).69 [17.5] (3P) X 2.55 [65] 5.17 [131.5].76 [19.5].75 [19].16 [4].69 [17.5] (3P) 2X ø.22 [ø5.5] (3P) Shipping weight, lbs. (kg) Frame Trip unit Complete Poles only Thermal-mag Electronic breaker 2,3 3.35 (1.52) 1.35 (.62) 1.60 (.72) 5.9 (2.7) Permissible mounting positions 90 90 30 30 14