Standard Service / Installation / Operation Manual Type W & P Water / Glycol Heat Transfer Coils

Similar documents
Stratomizer. Standard Service/Installation/ Operation Manual. Please consult your local representative or the factory for warranty issues.

Daikin Steam Coils. Installation and Maintenance Manual IM 901. Types HI-F5, HI-F8, & E-F5. Group: Applied Air. Part Number: IM 901

INSTALLATION, OPERATION & MAINTENANCE INSTRATIONS

LED Pinspot 2. Snapshot. User Manual

INSTALLATION, START-UP AND SERVICE INSTRUCTIONS

LED Pinspot 2. Snapshot. User Manual

CUSTOMER S MANUAL. Coil models FV,FK,FH,FC,FD,FP,FS TV,TK,TC,TD

Refinery Supply Company, Inc.

Fluid Coil Installation, Operation and Maintenance

User Manual. Snapshot. Use on Dimmer. Outdoor Use. Sound Activated DMX 512. Master/Slave. 115/230V Power Switch. Replaceable Fuse.

PHANTOM (PH10 and PH12) COMMERCIAL AND INDUSTRIAL SERIES

ECONOMIZER FAN. Receiving and Inspection

Effective June 1, 2013 This guide supersedes all previous versions

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL RBK FRP FAN

Lincoln Hoist. Web Hoist Operating Manual. Lincoln Hoist

Levalarm Gold. Installation, Operation, & Maintenance Instructions R500.E253A 03/16/2016

VSI INDUSTRIAL BALL VALVES SERIES 7100 SERIES 8100 SERIES 7200 SERIES 8300 SERIES 7400 SERIES 8400 SERIES 8000 SERIES 8500

Snapshot. Use on Dimmer Outdoor Use Sound-Activated DMX Master/Slave 120 V/230 V Switchable Replaceable Fuse User-Serviceable.

Jet Fans. Instruction Manual READ AND SAVE THESE INSTRUCTIONS WARRANTY

MAINTENANCE MANUAL FOR THERMOSTATIC TEMPERATURE REGULATING VALVE TRAC STYLE P

Operators Manual. Recirculating Chiller /06/08

Model Repair Parts Sheet SPECIFICATIONS. Stake threads lightly after assembly. Note: Pump base is not available as a service item.

Snapshot LX5 USER MANUAL. OK on Dimmer Outdoor OK Sound Activated DMX512 Master/Slave 115V/230V Switch Replaceable Fuse User Serviceable Duty Cycle

PENBERTHY FROST PROOF EXTENSION INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

PO Box 645, Stockton, Missouri, FAX superiorgearbox.com W D0446-A 4/1/05 1

AIR/HYDRAULIC INJECTION GUN MODEL INSTRUCTIONS

DeZURIK " BAW AWWA BUTTERFLY VALVES WITH EPOXY-RETAINED SEAT

PHANTOM (PH10 and PH12) COMMERCIAL AND INDUSTRIAL SERIES

Bray/ VAAS Slurry Series Knife Gate Valve 760/762/765/766/767/768 Series Operation and Maintenance Manual

MODELS TSX AND TSX-S SINGLE DUCT ROUND AIR TERMINALS

MANUAL FLUID EXTRACTOR

MODELS SGX AND SSX SINGLE DUCT ROUND AIR TERMINALS

LED IMPORTANT SAFETY INSTRUCTIONS

FTIR PG28 PURGE GAS GENERATOR OPERATIONS & MAINTENANCE

CSA products for treated water. Water Combination air valve. Mod. FOX 3F RFP and Lynx 3F RFP

PT, PTS & PTP Series Pump/Reservoirs

Full View Flow Indicator

Model P-40 & Model P-25 POWER PUSHER

Industrial Turbo Meters, Sizes 2" through 6"

AIR CLEANERS. Model MX 6000 OWNER S MANUAL CAUTION. Read complete instructions before operating. Please file for future reference.

WINDGUARD BELT DRIVE (BD) INDUSTRIAL SERIES

Installation and Service Instructions for Self Adjust Brakes 81,000 Series

APCO ASR-400/450 SEWAGE AIR RELEASE VALVES

Air Curtain. Installation, Operating and Maintenance Instructions

WIND STOPPING 14 (WMI) AND WIND STOPPING 16 (WMH) INDUSTRIAL SERIES

40 V LITHIUM-ION BATTERY ATTACH YOUR RECEIPT HERE AB13786C 1. kobalttools.com ITEM # /

24-48 HP250II Butterfly Valve. Operation and Maintenance Manual. Job Name: Contractor: Date: Document #: 2448HP250OOOM Revision Date: 1/10/11

Self Cleaning Hood System Installation, Operation, and Maintenance Manual

Maintenance Information

KP-C Series. Close Coupled End Suction Centrifugal Pumps. Installation, Operation and Maintenance

GL Ludemann Y-Strainers

ENGINE COOLING SYSTEM

INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR INSTRUMENT ISOLATION VALVE

2" - 24" OS Series Butterfly Valves. Operation and Maintenance Manual. Job Name: Contractor: Date:

HAYWARD FLOW CONTROL TBH SERIES TRUE UNION BALL VALVE INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

INSTALLATION VARIABLE FREQUENCY DRIVE THREE PHASE ALX SERIES SPUN ALUMINUM EXHAUSTERS

WALKIE HIGH LIFT HYDRAULIC SYSTEM

Installation, Operation and Maintenance Manual

Installation and Service Instructions for Self Adjust Brakes 82,000 Series

Val-Matic 1-4 Combination Air Valve (Single Housing Type)

Warning. Document ref: A October 2015

COMPRESSED AIR LOADER MODEL: AL-1

INSTALLATION, OPERATION & MAINTENANCE MANUAL AXIAL UPBLAST FANS RTA, RWTA, RHTA, RB, RD, RTA SH

SEASONAL MAINTENANCE CHECKLISTS Johnson Controls

3-20 2FII & Groundhog Bonded Seat Butterfly Valve. Operation and Maintenance Manual. Job Name: Contractor: Date:

NSGV Direct Drive Pressure Blower (AF) Aluminum Housing & Wheel

Snapshot LX10 USER MANUAL. OK on Dimmer Outdoor OK Sound Activated DMX512 Master/Slave 115V/230V Switch Replaceable Fuse User Serviceable Duty Cycle

AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST

These instructions are applicable to the following models: ARI 1118 ARI 1148

ARION: 19 EIA-310E Standard Enclosure

These instructions are applicable to the following models: ARI 1108 ARI HP1108

APCO CRF-100A RUBBER FLAPPER SWING CHECK VALVES

Welker Sampler. Installation, Operation, & Maintenance Manual. Model GSS-4HP

DeZURIK 24" THRU 36" RESILIENT BUTTERFLY VALVES

This chapter describes how to perform periodic inspection and maintenance to ensure the long operating life of the chamber.

GT-200 GATE VALVES PN16, Screwed end

CARTRIDGE FILTER SYSTEMS OWNER S MANUAL

S Voltage Regulators GENERAL. PRODUCT INFORMATION Introduction. Contents. Acceptance and Initial Inspection. Handling and Storage.

DUST COLLECTOR (BOTTOM REMOVAL BAG & CAGE) INSTALLATION AND OPERATING INSTRUCTIONS

Installation, Operation, and Maintenance Manual

DIRECT-DRIVE PRESSURE WASHERS

Val-Matic 1-4 Combination Air Valve (Single Housing Type)

COMPACT BAGHOUSE COLLECTOR

Installation, Operation, and Maintenance Manual

ACHL Series Pump. Operation and Maintenance Manual Air Driven, Hand Operated High Pressure Liquid Pump

600PEW Portable. Owners Manual IMPORTANT DOCUMENT - DO NOT DISCARD. SprayMasterTech.com. Date Manufactured: / /

Wastewater Combination Air Valve. Operation, Maintenance and Installation Manual

INSTALLATION, OPERATION AND MAINTENANCE MANUAL WALL EXHAUST FANS BELT & DIRECT DRIVE XB, HV, HVA, ADD, DDS, DDP

Separator Systems Operations & Maintenance Manual

582 Series. Instruction Manual. Two-Door Wafer Check Valve N-582 (R-08/2016)

Installation, Operation and Maintenance Manual

General Safety Information. Document KSFB and KSFD DANGER CAUTION WARNING! DBC DB3. Horizontal

READ AND SAVE THESE INSTRUCTIONS. Air Boss MP600M Vertical Air Flow Mist Precipitator Industrial Applications. TRION

Owner s Manual SMT PORTABLE SERIES IMPORTANT DOCUMENT - DO NOT DISCARD 600PE 1100PE 1100HC. SprayMasterTech.com. Date Manufactured: / / 600PE 1100PE

SOLAIRE 3200 SERVICE MANUAL

Caring for your Steel Windows & Doors

INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR Engine Mounted Radiators with Extended. Shafts

KEYSTONE SERIES 320 BUTTERFLY VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

MANUAL INSTALLATION. Active Chilled Beam Linear. ACBL Series. v101 Issue Date: 04/10/ Price Industries Limited. All rights reserved.

Waukesha Cherry-Burrell Valves

Transcription:

Standard Service / Installation / Operation Manual Type W & P Water / Glycol Heat Transfer Coils Please consult your local representative or the factory for warranty issues. July 2017 DRS Marlo Coil Customer Service 6060 Highway PP High Ridge, Missouri 63049 Phone: 636.428.6017 Fax: 636.677.1203

TABLE OF CONTENTS 1.0 EQUIPMENT DESCRIPTION... 1 2.0 RECEIVING INSTRUCTIONS... 1 2.1 INSPECTION... 1 2.2 UNPACKING... 1 3.0 HANDLING... 1 4.0 STORAGE... 2 5.0 INSTALLATION... 2 5.1 COIL START-UP/OPERATION... 2 6.0 MAINTENANCE... 3 6.1 PERIODIC VENTING... 3 6.2 INSPECTION... 3 6.3 CLEANING... 3 7.0 REPAIR... 3 8.0 REMOVAL FROM SERVICE... 4 9.0 TROUBLESHOOTING... 4 2017 LEONARDO DRS i

Thank you for purchasing a DRS Marlo Coil water/glycol heat transfer coil. If you have any questions regarding the installation or operation of the product, please contact your local DRS Marlo Coil Sales Representative or DRS Marlo Coil. WARNING READ ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING. FOLLOW THE PROCEDURES FOR SAFE AND PROPER INSTALLATION, MAINTENANCE, AND OPERATION. IMPROPER INSTALLATION, MAINTENANCE, OR OPERATION MAY RESULT IN A VOIDED WARRANTY. 1.0 EQUIPMENT DESCRIPTION The DRS Marlo Coil water/glycol heat transfer coil is a fluid to air heat transfer device intended to be used in commercial, institutional, industrial, marine, or process use. The product is custom designed to be used only in the application for which it was originally designed. DRS Marlo Coil must be contacted for advice before any changes from the original intended application of the product are made, including the supply utilities, the air volume, or the environment. 2.0 RECEIVING INSTRUCTIONS 2.1 INSPECTION All coils are carefully inspected and packaged for shipment at the factory. Despite these precautions, rough handling enroute may cause damage. Coils should be inspected upon receipt. Loose bolts and/or screws must be retightened. Any shortages, damage, or breakage should be indicated on the carrier's freight bill and signed by the driver or the carrier's representative. If damage is noted after delivery, it should be reported to the carrier and a claim filed at once. For additional assistance, contact the sales representative from whom you purchased the coil, or the factory. 2.2 UNPACKING All coils are packaged to prevent damage. Care should be taken when unpacking to avoid damage to the finned surface area. Gloves should be worn to avoid hand and finger injuries, as finned coils do have sharp edges. 3.0 HANDLING The instructions contained in this section must be followed to avoid injury to personnel or damage to the coil. Do not lift or handle the coil by the face area, headers, tubes, or connections. Wear gloves when handling coils and be careful around fins and other edges of metal. Rigging and lifting methods may include slings at both ends of the coil, which encompass both coil channels. Lifting devices deemed suitable by the user may be attached at each end of the top coil channel. All slings, devices, and apparatus should be of a rating suitable for the loads they will be subjected to, and ensure that no deformation of the coil casing occurs. DRS Marlo Coil assumes no responsibility for lifting apparatus, devices, and methods used by others for rigging and lifting. 2017 LEONARDO DRS 1

4.0 STORAGE In the event that the coil will not be put into service immediately, certain precautions should be taken. The coil should be stored indoors in a clean, dry location that is level and sturdy. Coil connections must be capped. When placing coils into storage after being in service, coils must be completely drained. On Type W and P coils, all plugs must be removed to assure complete drainage. Type W coils should be blown out utilizing compressed air, blown through the header connection. Type P coils are provided with drain plugs on the supply connection and on each auxiliary header. If it is necessary to store the coil outdoors, the coil should be stored off the ground and wrapped fully with a tarpaulin or plastic. Periodically inspect the coil to be sure the finned surface area is free of accumulated dirt or dust, and to be sure no damage has occurred. 5.0 INSTALLATION Install the coil with the casing level. The coil should be supported at a minimum with supports at each end. Longer coils may require intermediate supports to prevent casing from bowing. Coils may also be supported by suitable ductwork by bolting or welding the entire casing perimeter to the duct on both sides. The entering side of the coil face should be safed-off (baffled) to ensure that all air flows through the coil core. All duct and safe-off connections should be sealed to prevent air leakage. Failure to do so will result in loss of performance. Do not exceed the maximum design temperature, pressure or flow rate. Coils should always be installed so the supply connection is at the bottom and on the leaving air side. Failure to do so will result in loss of performance. Threaded piping hook-ups should always be made using two pipe wrenches. Use one wrench to prevent movement of the coil connection, and the other to tighten the joint. All piping must be fully supported at sites other than the coil. If the coil will be subject to severe expansion and contraction, flexible connections are recommended. A typical piping arrangement is shown in Appendix A. Refer to Appendix A Typical Water/Glycol Coil Piping, page 5. Once the coil is piped, it should be filled with the working fluid. The coil vent is located on top of the return connection and should be loosened during the filling process. Once the flow from the vent becomes completely liquid, re-tighten the vent plug. Flow liquid through the coil for several minutes and periodically vent the coil to ensure all air has been removed. Once the coil is in operation check the piping connections for leaks. Re-tighten connections as necessary. Refer to Water Coil Start Up Check List, page 5. 5.1 COIL START-UP/OPERATION Open all valves in return lines. With fan OFF, slowly open supply valves allowing partial flow in graduated steps for 1-3 minutes until full flow is achieved. If the coil is subject to air vs. fluid delta temperature greater than 75 F, allow the coil to heat soak for 15 to 30 minutes before energizing the fan. This reduces the risk of damage to the coil due to thermal shock. 2017 LEONARDO DRS 2

6.0 MAINTENANCE 6.1 PERIODIC VENTING WARNING PRIOR TO PERFORMING ANY MAINTENANCE, THE COIL SHOULD BE CHECKED TO BE SURE IT IS OUT OF SERVICE. GLOVES, PROTECTIVE CLOTHING, AND EYE PROTECTION SHOULD BE WORN AT ALL TIMES WHEN CLEANING THE COIL TO PREVENT CUTS TO THE HANDS AND FINGERS. Periodically vent the coil to remove accumulated air. 6.2 INSPECTION The coil should be visually checked periodically to assure that finned surfaces are free of dirt, debris, and other airborne deposits. The coil (and system) should also be checked periodically for any signs of leakage or malfunction. 6.3 CLEANING 1. External cleaning of the coils may be accomplished by employing either of the following methods: Large debris may be removed by hand. Dirt or dust may be removed by brushing or vacuuming the face of the coil on the air entering side. A solution of warm water and soap, or detergent, may be used to remove severe dirt build-up. A soft bristle brush should be used to avoid damaging the finned surface area. Gently scrub dirt build-up from the air entering side of the coil face, the surrounding areas, and the air leaving side of the coil, as required. Rinse the area with clean water, being careful to avoid getting water into other equipment, especially electrical devices, filters, etc. Low pressure steam may also be used to clean the coil. Cover any equipment, wiring, etc. that may be affected by the steam spray. Using a wand, spray the steam through the coil face in the direction opposite the airflow until all dirt is removed. 2. After cleaning, inspect the coil and repeat cleaning as necessary. When the area has been completely cleaned, dried, and inspected, re-install any filters, access panels, etc. that may have been removed for cleaning. Any disconnected electrical power may be reconnected at this time. 7.0 REPAIR If it is believed that the coil is in need of repair, the DRS Marlo Coil sales representative from whom the coil was purchased, or the factory, should be called. Unauthorized repair of the coil may result in a voiding of the warranty. 2017 LEONARDO DRS 3

8.0 REMOVAL FROM SERVICE If the coil is removed from installation, follow the storage instructions in section 4.0. 9.0 TROUBLESHOOTING Once a coil has been properly installed, it should provide the required cooling/heating conditions. Situations may arise which preclude normal functioning of the coil. The following chart should be consulted for troubleshooting. Problem Situation SOLUTION Liquid Leakage Coil Piping Connection Loose/Leaking Re-tighten connection. If unsuccessful, undo connection apply thread sealant and reassemble. Damaged Coil During Shipment Contact factory. Air Leakage At Coil Face Connection Air Pressure Drop Too High Liquid Pressure Drop Too High Leaving Air Temperature Too Low/High Excessive Expansion/Contraction During Operation Corrosion of Coil Materials and/or Joints Coil Freeze-Up Bypass Around Coil Face Incorrect Measurement Technique or Improperly Balanced Restricted Airflow Entering or Leaving Ductwork Coil Fins Are Dirty Improper Measurement Technique or System Improperly Balanced Restrictions In Piping Improper Measurement Technique or System Improperly Balanced Coil Fins Are Dirty Contact factory. Contact factory. Contact factory. Re-connect ductwork and/or safe-offs using proper sealing techniques. Follow manufacturer s directions for devices being used. Consult SMACNA manual on testing, adjusting, and balancing. Allow adequate duct lengths for transitions to coil face. Clean coil core per maintenance instructions. Follow proper techniques for devices being used. Consult SMACNA manual on testing, adjusting, and balancing. Change piping so same line sizes are used as coil supply and return connections. Changes to line sizes should be made further upstream/down-stream of coil. Make sure proper techniques and devices are being used. Make sure manufacturers directions for devices are being followed. Consult SMACNA manual on testing, adjusting, and balancing. Clean coil core per maintenance instructions. 2017 LEONARDO DRS 4

Air Entrainment in Liquid System Check water/glycol for a foamy appearance. If present, repair system leaks and/or install an air separator to remove air from liquid. Water Coil Start Up Check List Job Name: DRS Marlo Coil Model Number: Serial Number: Date: By: Tag: Check Overall Appearance of Coil Coil Installation Level Coil Supported at Each End or Around Full Face Perimeter on Both Sides Coil Installed with Supply Connection at Bottom and on Leaving Air Side Duct Connection Sealed to Prevent Leakage Piping Supported at Locations Other than Coil Piping Connections Tight and Leak Free Air Purged from Coil Coil Vented Periodically to Ensure All Air Is Removed (Performed after coil has been in operation for several minutes) APPENDIX A 2017 LEONARDO DRS 5