A Contactors. Technical Information. CA4 Miniature Contactors. Technical Information A94 CA4. Switching Motor Loads.

Similar documents
Technical Information

Technical Information

Technical Information

The contactor for large horsepower applications

Series CA5 Contactors

Technical Information

General + Definite Purpose Contactors

General + Definite Purpose Contactors

MAKING MODERN LIVING POSSIBLE. Technical brochure. Minicontactors CI 5-

Mini Contactors CI 4-

Contactor Types CI 61-98

CI-TI TM Contactors and Motor Starters Contactors CI 6-50

Approved Standards. Motor Contactor. Main contactor. Accessoires. 21 Motor Contactor J7KN

CI-TI Contactors and motor starters Types CI 61 - CI 98

AF series contactors (9 2650)

Model Number Legend. Motor Contactor J7KN. Motor Contactor J7KN 1

AF series contactors (9 2650)

RSC09 RSC16 RSC22 RSC38 RSC43 RSC63 RSC-AUX

System pro M compact Miniature Circuit Breaker SU200 M for branch circuit protection acc. to UL 489

Contactor TECHNICAL INFORMATION - FRAME 1

AF09... AF30 3-pole Contactors up to 20 HP / 480 VAC

MS25, MST25, MS20, MST20

Manual motor starter MS116

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC

C -5 to +55 (0.8 to 1.1Uc) Permissible o

Description. Positive safety relays

Manual Motor Protectors

General Informations 2 Technical data 3 Basic designs 4-8

Series CA6 Contactors

Approbationen IEC/EN ; UL 508; CSA-C22.2 No ; CE marking

Other Devices. Installation Contactors Z-SCH. Connection diagrams Z-SCH NO 3 NO / 1 NC. Permitted Installation Positions

CI-TI Contactors and Motor Starters Type CI 6-50

DATASHEET - DILMC9-10(24VDC) Technical data General. Contactor, 3p+1N/O, 4kW/400V/AC3. Catalog No Eaton Catalog No. XTCEC009B10TD.

TeSys contactors. Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current Ie. to be wired in series

Application Mini Contactors for Motors and Resistive Loads

AF09... AF38 4-pole Contactors AC / DC Operated - with Screw Terminals

Technical Information

Industrial Contactors CTX 3 3P 185A - 800A

and Refrigeration Institute). CNX Special Purpose Contactors

Contactors KNL A 68 KNL6, KNL9, KNL12, KNL16, KNL18, KNL22, KNL30. Dimensional drawing of KNL KNL6, KNL9, KNL12, KNL16, KNL18 KNL22, KNL30

Modular contactors and relays

Manual motor starter magnetic only MO325

Manual motor starter MS116

Approved Standards. Ordering Information. Mini Contactor Relays 4-pole J7KNA-AR. Model Number Legend. Main contactor. Accessories

ASL09..S 3-pole Contactors - Spring Terminals

Manual motor starter MS132

Approved Standards. Ordering Information. Mini Motor Contactor J7KNA. Model Number Legend. Main contactor. Accessories. Mini Motor Contactor J7KNA 1

Ktec Contactors and thermal overloads

AF40... AF96 3-pole contactors Technical data

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases

Data sheet. CI-TI TM Contactors and Motor Starters Circuit Breakers CTI B1427

UL & CSA Technical data A/AE9 A/AE/AF110, AL9 AL40 AC & DC operated

Industrial contactors CTX-1

3RT14 Contactors with 3 Main Contacts

MPW Series. MPW Catalog Number Sequence. Standard Features MPW U004

3 - Protection components Motor circuit-breakers

TAE pole Contactors

Motors Automation Energy Transmission & Distribution Coatings. Automation Contactors - CWM Line

General_technical_data Series

AE 9... AE 40 Contactors NE... Contactor Relays

Latch for Contactors 4-pole see page 36. Ratings Rated Aux. Contacts Type Coil voltage 2) AC2 Current Built-in Additional 24 24V= DC 5

Application Mini Contactors for Motors and Resistive Loads

Emergency stop without emergency switching off/emergency stop function. Locking facility Lockable in the 0 (Off) position N/O 0 B 0

Controls. CONTACTORS CWB Line (up to 40A)

Micro Contactor MA Series

4 - Miniature controls

Contactors. Mini-contactors type LC1-SKGC for use in modular panels. Conforming to standards IEC/EN , IEC/EN , NF C , VDE 0660

Contact us. ABB France Electrification Products Division Low Voltage Products and Systems 3, rue Jean Perrin F Chassieu cedex / France

I r A short-circuit protective device: Observe the maximum permissible fuse of the contactor with direct device mounting.

FUJI Magnetic Contactors and Motor Starters

Manual motor starter MS132

Approvals UL 508; CSA-C22.2 No ; IEC/EN ; CE marking

Manual motor starter MS132

Circuit-Breakers M4 166 for motor protection. Auxiliary contacts 167 Signalling switch Auxiliary releases

Technical data for manual motor starters Type MS325

Motorized switch-disconnectors OTM 40 to 125 Amperes

Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN , VDE 0113 Part 1

Product range Overload relay ZB up to 150 A. Phase-failure sensitivity IEC/EN 60947, VDE 0660 Part 102

Technical Information

FMotor Circuit Controllers

B6, B7, BC6, BC7, TBC7 3- and 4-pole mini contactors VB6, VB7, VBC6, VBC7 3- and 4-pole mini reversing contactors Technical data

Bulletin 825 SMM Smart Motor Manager

NSL..S 4-pole / 8-pole Contactor Relays - Spring Terminals

AF40... AF96 3-pole contactors 30 to 60 hp at 480 V AC AC / DC operated with 1 N.O. + 1 N.C. auxiliary contacts

Installation Contactors RIC, RAC

Phone: Fax: Web: -

DATASHEET - ZB Delivery program. Overload relay, 50-65A, 1N/O+1N/C. Catalog No Eaton Catalog No. XTOB065DC1 EL-Nummer

Characteristics TeSys contactors 0 TeSys k contactors and reversing contactors

TeSys contactors 5. Characteristics 5. Mini-contactors TeSys LC1 SK and LP1 SK. Environment Rated insulation voltage (Ui) 5/30

Protection Equipment

3TM Vacuum Contactors

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features

NB1 Miniature Circuit Breaker

Bulletin 100-D IEC Contactors

Deliveryprogramme. Overloadrelay,24-40A,1N/O+1N/C. Articleno CatalogNo. XTOB040DC1. Auxiliarycontacts. Short-circuitprotection

AF / AF12Z pole Contactors AC / DC Operated - with Screw Terminals

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

VB6, VB7 3-pole mini reversing contactors with screw terminals 4 to 5.5 kw AC operated

KT4 Manual Motor Starter

Star Series Motor protection & control

Transcription:

C4 Miniature Contactors Contactors C4 Rated Insulation Voltage U i to IEC 947-1 [V] 500V UL/CS [V] 600V Rated Impulse Voltage U imp [kv] 8 Rated Voltage U e Main Contacts C 50/60Hz [V] 230, 240, 400, 415, 500 DC [V] 24, 48, 110, 220, 440 Operating Frequency for C Loads [Hz] 50/60Hz Switching Motor Loads Standard IEC Ratings C-2, C-3, C-4 230V [] 12 DOL & Reversing 240V [] 12 50Hz/60 C 400V [] 9 415V [] 9 500V [] 7 230V [kw] 1.7 240V [kw] 1.8 400V [kw] 2.5 415V [kw] 2.6 500V [kw] 2.3 UL/CS 115V [] 13.8 DOL & Reversing 1 230V [] 10 60Hz/60 C 115V [HP] 0.75 230V [HP] 1.5 200V [] 11 230V [] 9.6 460 V [] 7.6 3 575 V [] 6.1 200 V [HP] 3 230 V [HP] 3 460 V [HP] 5 575 V [HP] 5 Maximum Operating Rate C2 [ops/hr] 300 t 9 for C3; 20 for C2/4 C3 [ops/hr] 600 Starting time t = 0.25s C4 [ops/hr] 300 C4 (200,000 Op. Cycles) 230V [] 3.9 50Hz 240V [] 3.9 400V [] 3.3 415V [] 3.3 230V [kw] 0.92 240V [kw] 0.96 400V [kw] 1.5 415V [kw] 1.6 Max. Operating Rate [ops/hour] 250 Wye-Delta (Star Delta) 230V [] 21 50 Hz 240V [] 21 400V [] 16 415V [] 16 500V [] 12 230V [kw] 5.8 240V [kw] 6.3 400V [kw] 7.9 415V [kw] 8.2 500V [kw] 7.7 C-1 Load, 3 Switching e I [] 20 mbient Temperature 40 C 230V [kw] 8 240V [kw] 8.3 400V [kw] 14 415V [kw] 14 500V [kw] 17 mbient Temperature 60 C e I [] 16 230V [kw] 6.4 240V [kw] 6.7 400V [kw] 11 415V [kw] 12 500V [kw] 14 Continuous Current (UL/CS) General Purpose Rating (40 C) Open [] 12 Enclosed [] 12 Lighting Loads Elec.Dischrg.Lamps-C-5a, Open [] 18 single compensated Enclosed [] 18 Max. capacitance at 10k [µf] 750 prospective short circuit 20k [µf] 400 current available at the 50k [µf] ~ contactor. Incandescent Lamps - C-5b, Electrical endurance ~100,000 operations [] 9.3 94 Discount Schedule -1

Contactors C4 Miniature Contactors Electrical Data Switching power transformers C-6a Inrush = n Rated transformer currrent 230V [] 5.4 240V [] 5.4 400V [] 4.1 415V [] 4.1 500V [] ~ 230 VC [kv] 2.2 240 VC [kv] 2.2 400 VC [kv] 2.8 415 VC [kv] 2.9 500 VC [kv] 2.7 DC Ratings DC-1 Rating at 60 C [kw] x 1 Pole 24VDC [] 9 48VDC [] 6 110VDC [] 1 220VDC [] 0.3 440VDC [] 0.1 2 Pole in Series 24VDC [] 9 48VDC [] 8 110VDC [] 6 220VDC [] 1.2 440VDC [] 0.3 3 Pole in Series 24VDC [] 9 48VDC [] 9 110VDC [] 9 220VDC [] 4 440VDC [] 0.6 Short Time Current Withstand Ratings cw l 60 C 1 s [] 110 4 s [] 85 10 s [] 60 15 s [] 50 60 s [] 30 240 s [] 20 900 s [] 20 Off Time Between Operations [Min.] 3 Resistance and Watt Loss e l C3 Resistance per power pole [mω] 5.5 Watt Loss - 3 power poles [W] 1.3 Coil and 3 power poles C [W] 2.7 DC [W] 3.8 Coil Data Voltage Range C: 50Hz, 60Hz, 50/60 Hz Pickup `[x U s ] 0.85 1.1 Dropout [x U s ] 0.3 0.65 DC Pickup [x U s ] 0.85 1.1 Dropout [x U s ] 0.1 0.25 Coil Consumption C: 50Hz, 60Hz, 50/60 Hz Pickup [V/W] 22/20 Hold-in [V/W] 4/1.4 DC Pickup [W] 2.5 Hold-in [W] 2.5 Operating Times C: 50Hz, 60Hz, 50/60 Hz Pickup [ms] 15 40 Dropout [ms] 15 25 with RC Suppressor Dropout [ms] 15 25 DC Pickup [ms] 18 40 Dropout [ms] 6 12 with Integ. Suppression Dropout [ms] 8 12 with Diode Suppression Dropout [ms] 35 50 C4 Discount Schedule -1 95

C4 Miniature Contactors Contactors C4 Mechanical Data Service Life Mechanical C [Mil.] 10 DC [Mil.] 20 Electrical C-3 (400V) [Mil.] 0.7 Shipping Weights C - C4 [kg] 0.16 [Lbs] 0.35 C - CU4 [kg] 0.35 [Lbs] 0.77 DC - C4 [kg] 0.16 [Lbs] 0.35 DC - CU4 [kg] 0.35 [Lbs] 0.77 Terminations - Power Terminal Type Combination Screw Head: Cross, Slotted, Posidrive Environmental and General Specifications mbient Temperature Storage -55...+80 C (-67...176 F) Operation -25...+60 C (-13...140 F) Conditioned 15% current reduction after C-1 at >60 C -25...+70 C (-13...158 F) ltitude at installed site 2000 meters above sea level per IEC 947-4 Resistance to Corrosion / Humidity Damp-alternating climate: cyclic to IEC 68-2, 56 cycles. Dry heat: IEC 68-2, +100 C (212 F), relative humidity <50%, 7 days. Damp tropical: IEC 68-2, +40 C (104 F), relative humidity <92%, 56 days. Shock Resistance IEC 68-2: Half sinusoidal shock 11ms, 30g (in all three directions) Vibration Resistance IEC 68-2: Static >2g, in normal position no malfunction <5g Operating Position Standards pprovals Refer to Dimension Pages IEC947-1/4, EN 60947; UL 508; CS 22.2, No. 14, SEV1025 CE, UL, CS, SEV, SUV, Lloyd s Registry of Shipping, Bureau Veritas, Maritime Register of Shipping, Elektrizitats-Inspektorat Finland 1 Wire [mm 2 ] 0.75...2.5 2 Wires [mm 2 ] 0.75...2.5 1 Wire [mm 2 ] 0.75...2.5 2 Wires [mm 2 ] 0.75...2.5 1 Wire [WG] 18...14 2 Wires [WG] 18...14 Torque Requirement [Nm] 1...1.5 [Lb-in] 7...15 Terminations - Control Terminal Type Combination Screw Head: Cross, Slotted, Pozidrive Coils 1 or 2 [mm 2 ] 0.75...2.5 Wires [WG] 18...14 Control Modules 1 or 2 [mm 2 ] 0.75...2.5 Wires [WG] 18...14 Torque Requirement [Nm] 1...1.5 [Lb-in] 7...15 Degree of Protection - contactor IP 2LX per IEC 529 and DIN 40 050 (with wires installed) Protection gainst ccidental Contact Safe from touch by fingers and back-of-hand per VDE 0106; Part 100 96 Discount Schedule -1

Contactors C4 Miniature Contactors uxiliary Contacts Built-in uxilary Contacts uxiliary Contact Blocks Current Switching C-1 Ith at 40 C [] 10 16 at 60 C [] 6 12 C-15, switching electromagnetic loads at: [V] 230 240 400 415 500 230 240 400 415 500 [] 2 2 1 1 0.6 6 5 2.5 2 1.25 DC-13, switching DC electromagnets at: [V] 24 48 110 220 440 24 48 110 220 440 [] 2 0.6 0.45 0.1 0.04 5 0.6 0.45 0.25 0.04 Short-Circuit Protection - gg Fuse Type 2 Coordination [] 10 16 Load carrying capacity per UL/CS Rated Voltage C [V] 600 max. 600 max. Continuous Rating 40 C [] 10 general purpose 10 general purpose Switching Capacity C Heavy pilot duty (600) Heavy pilot duty (600) Rated Voltage DC [V] 600 max. 600 max. Switching Capacity DC Standard pilot duty (Q600) Standard pilot duty (Q600) Terminals Terminal Type C4 Maximum Wire Size per IEC 947-1 Flexible with Wire- 1 Conductor [mm 2 ] 0.75 2.5 0.75 2.5 End Ferrule 2 Conductor [mm 2 ] 0.75 2.5 0.75 2.5 Solid/Stranded- 1 Conductor [mm 2 ] 0.75 2.5 0.75 2.5 Conductor 2 Conductor [mm 2 ] 0.75 2.5 0.75 2.5 Recommended Tightening Torque [Nm] 1 1.5 1 1.5 Max. Wire Size per UL/CS [WG] 18 14 18 14 Recommended Tightening Torque [lb-in] 7 15 7 15 CRZE4/CRZY4 Electronic Timers Permissible voltage CRZE4 (C or DC) 110V (-23%) - 250V (+10%) CRZY4 (C only) 110V (-23%) - 120V (+10%) 220V (-20%) - 250V (+10%) Voltage drop 5V max Load current for reliable operation 10m min Load current 20 C 600m 40 C 440m 55 C 320m Leakage current at 220V CRZE4 5m CRZY4 Y 17m, D 6m Reset time 200ms Voltage failure duration having no influence on timing sequence CRZE4 15ms CRZY4 20ms Repeat accuracy ±5% Time interval for start commands CRZE4 1.4 x set time CRZY4 2 x set time mbient temperature Storage -40 C to +80 C Operation -20 C to +55 C Discount Schedule -1 97

C4 Miniature Contactors Contactors C4 Determining Contact Life To determine the contactor s estimated electrical life, follow these guidelines: 1. Identify the appropriate Utilization Category from Table. 2. On the following pages, choose the graph for the Utilization Category selected. Table IEC Special Utilization Categories (Number of operations under load) ➊ 3. Locate the Rated Operational Current (l e ) along the bottom of the chart and follow the graph lines up to the intersection of the appropriate contactor s life-load curve. 4. Read the estimated contact life along the vertical axis. Conditions for testing Conditions for testing making and electrical life breaking capacity Category Typical pplications Rated Current Make Break Make Break I/Ie U/Ue cos Ic/Ie Ur/Ue cos I/Ie U/Ue cos Ic/Ie Ur/Ue cos C-1 Non-inductive or slightly ll values 1 1 0.95 1 1 0.95 1.5 1.05 0.8 1.5 1.05 0.8 inductive loads, resistance furnaces C-2 Slip-ring motors: ll values 2 1.05 0.65 2 1.05 0.65 4 1.05 0.65 4 1.05 0.65 Starting, plugging C-3 Squirrel-cage motors: Ie 17mp 6 1 0.65 1 0.17 0.65 10 1.1 0.65 8 1.1 0.65 Starting, switching off 17mp < Ie 100mp 6 1 0.35 1 0.17 0.35 10 1.1 0.35 8 1.1 0.35 motors during running Ie > 100mp 6 1 0.35 1 0.17 0.35 8➌ 1.1 0.35 6➍ 1.1 0.35 C-4 Squirrel-cage motors: Ie 17mp 6 1 0.65 6 1 0.65 12 1.1 0.65 10 1.1 0.65 Starting, plugging, inching ➒ 17mp < Ie 100mp 6 1 0.35 6 1 0.35 12 1.1 0.35 10 1.1 0.35 Ie > 100mp 6 1 0.35 6 1 0.35 10➎ 1.1 0.35 8➌ 1.1 0.35 C-5a Switching of electric discharge 2 1.05 0.45 2 1.05 0.45 3 1.05 0.45 3 1.05 0.45 lamp control C-5b Switching of incandescent lamps 1 1.05 1 1.05 1.5 1.05 1.5 1.05 C-13 Control of solid state loads 2 1 0.65 1 1 0.65 10 1.1 0.65 1.1 1.1 0.65 with transformer isolation C-15 Electromagnets for contactors, 10 1 0.3 1 1 0.3 10 1.1 0.3 10 1.1 0.3 valves, solenoid actuators Make Break Make Break I/Ie U/Ue L/R ➏ Ic/Ie Ur/Ue L/R➏ I/Ie U/Ue L/R➏ Ic/Ie Ur/Ue L/R➏ [ms] [ms] [ms] [ms] DC-1 Non-inductive or slightly ll values 1 1 1 1 1 1 1.5➑ 1.1➑ 1➑ 1.5➑ 1.1➑ 1➑ inductive loads, resistance furnaces DC-2 Shunt-motors: ll values 2.5 1 2 1 0.1 7.5 4 1.1 2.5 4 1.1 2.5 Starting, switching off motors during running DC-3 Shunt-motors: ll values 2.5 1 2 2.5 1 2 4 1.1 2.5 4 1.1 2.5 Starting, plugging, inching DC-4 Series-motors: ll values 2.5 1 7.5 1 0.3 10 4 1.1 15 4 1.1 15 Starting, switching off motors during running DC-5 Series-motors: ll values 2.5 1 7.5 2.5 1 7.5 4 1.1 15 4 1.1 15 Starting, plugging, inching DC-15 Electromagnets for contactors, 1 1 6 x P➐ 1 1 6 x P➐ 1.1 1.1 6 x P➐ 1.1 1.1 6 x P➐ valves, solenoid actuators ➊ Utilization categories and test conditions for C & DC. For contactors according to IEC 158-1, starters according to IEC 292-1... 4 and control switches according to IEC 337-1 and IEC 337-1. ➌ With a minimum value of 1000 for I or Ic. ➍ With a minimum value of 800 for Ic. ➎ With a minimum value of 1200 for I. ➏ T0.95 for DC-15: Time in milliseconds for reaching 95% of steady-state current Ie x T0.95 is 300% of the time constant T = L/R of the circuit. ➐ P = Ue x Ie rated power [W]. The value "6 x P" has been derived from an empiric relationship which covers most magnetic loads for DC up to an upper limit of P = 50W. ➑ Only according to VDE. ➒ Plugging is understood as stopping or reversing the motor rapidly by reversing the motor primary connections while the motor is running. Inching [or jogging] is understood as energizing a motor once or repeatedly for short periods to obtain small movements of the driven mechanism. Legend Ue Rated operational voltage U Voltage before make Ur Recovery voltage Ie Rated operational current I Making current Ic Breaking current L Inductance of test circuit R Resistance of test circuit 98 Discount Schedule -1

Contactors C4 Miniature Contactors LIfe Load Curves Life-Load Curves C-1, C-2, C3, C-4 C3 90%/C-4 10% 10 C7-9 C-1, C-2, C-3, C-4, C-3 & 4 mixed; Ue = 380...460 VC C-1, C-2, C-3 C-4, C3 & 4 C4 Contact Life (Millions of Operations) 1 0.1 0.01 1 10 100 Rated operational current Ie C-1, C-2, C-3, C-4, C-3 & 4 mixed [] Contact Life for Mixed Utilization Categories C-3 and C-4 In many applications, the utilization category cannot be defined as either purely C-3 or C-4. In those applications, the electrical life of the contactor can be estimated with the following equation: L mixed = L ac3 / [1+P ac4 x (L ac3 /L ac4-1)], where: L mixed L ac3 L ac4 P ac4 pproximate contact life in operations for a mixed C-3/C-4 utilization category application. pproximate contact life in operations for a pure C-3 utilization category (from the C-3 life-load curve). pproximate contact life in operations for a pure C-4 utilization category (from the C-4 life-load curve). Percentage of C-4 operations NOTE: The life-load curves shown here are based on Sprecher+Schuh tests according to the requirements defined in IEC 947-4-1. Since contact life in any given application is dependent on environmental conditions and duty cycle, actual application contact life may vary from that indicated by the curves shown here. Discount Schedule -1 99