CP-8551 & CP Application. Features. Applicable Literature. Electronic to Pneumatic Transducers General Instructions

Similar documents
CP-9301 CP Application. Features. Applicable Literature. Electronic Actuator Drives General Instructions

AK Application. Features. Applicable Literature. Positive Positioner Pneumatic Relay General Instructions

TS , -850 Series TS , -850 Series TS-57031, TS

THC-2, THC-3, THCR-4, THCR-5. Enthalpy Control. General Instructions APPLICATION SPECIFICATIONS. ACCESSORIES None

CP-8301-xxx Series. Application. Features. Applicable Literature. 1 to 15 Vdc Input Electronic Actuator Drive General Instructions

AM-751, AM-752, AM-753, AM-754, AM-755. Applications. Applicable Literature

MA-5200 Series MA-5300 Series

AV-430. Application. Features. Applicable Literature. Valve Linkage for Pneumatic Actuators General Instructions

CP (Vdc) CP (Milliamp) CP (Slidewire)

453X Series. Application. Features. Two-Position Damper Actuator General Instructions

AV-401. Application. Features. Applicable Literature. Pneumatic Actuator Valve Linkage Kit General Instructions

MS Application. Features. Proportional Valve Actuator General Instructions

AV-497. Application. Features. Valve Linkage for MK-6811 and MK-6911 General Instructions

MP-5400 Series. Application. Features. Applicable Literature. Electronic Positive Positioning Hydraulic Actuator General Instructions

MF4E MF4E

MAx-305 & MAx-318 Series MAx-405 Through MAx-419 Series Two-Position Actuators

MF-22xx3. Application. Features. Floating Valve Actuator General Instructions

T500 Series. Applications. Features. Applicable Literature. Non-Digital, On/Off Thermostat General Instructions

SLC-811X Series. Single Loop Proportional Temperature Controller General Instructions APPLICATION SPECIFICATIONS

MP-5200 Series. Application. Features. Applicable Literature. Electronic Hydraulic Actuator General Instructions

TK-6024, TK-6124, TK-8024, TK-8124

2211 Series. Application. Features. One-Pipe Pneumatic Room Thermostats General Instructions SPECIFICATIONS

CP CP

MF Series MS Series

TS Series TS Series

MK-6600 Series, MK-6800 Series, and MK-6911

MS40-717X Series. Application. Features. DuraDrive Series Spring Return Proportional Actuators General Instructions

M9106-AGx-2N0x Series Electric Non-spring Return Actuators

AV-611. Application. Applicable Literature. Schneider Electric DuraDrive Globe Valve Linkage General Instructions

VB-9323 Series. Application. Features. Applicable Literature. 2-1/2" to 6" 125 Lb. Flanged Three-Way Diverting Valves General Instructions

MA40-704X Series MA41-707X Series MA41-715X Series

VB-8000 Series VB-9313 Series. Selection Guide. Applications. Applicable Literature. Selection Guide Contents. Valve and Actuator Selection Procedure

VA, VF, and VS Series Direct Mounted Globe Valve Assemblies. Application. Features

MC-351, 421, 431, MC-4311

TKS-5001, TKS , TKS-6001, TKS-7001

VB-9313 Series. Application. Features. Applicable Literature

MX4X-6XXX Series MX4X-7XXX Series. Selection Guide. Applications. DuraDrive Series Actuators and Accessories

Selection Guide. Vx-2x13-5xx-9-xx Series Vx-2x13-8xx-9-xx Series VB-2x xx Series. Schneider Electric Ball Valve Assemblies

TSMN-90xxx Series TSMN TSMN TSMN Electronic Room Temperature Sensor General Instructions

Powers TM Controls Three-way Electro-pneumatic (EP) Valve Model 2

EP-8000 Series Electro-Pneumatic Transducers

Type Type 1001 Transducers. I/P & E/P Transducers

OpenAir Electric Damper Actuator GDE/GLB Series Non-spring Return, 24 Vac Floating Control, Rotary

T-1001 TYPE 1001 I/P & E/P TRANSDUCERS

OpenAir Electric Damper Actuator GDE/GLB Series Non-spring Return Rotary 24 Vac 3-position Control

OpenAir Electric Damper Actuators GDE/GLB Series Non-spring Return Rotary 24 Vac - Modulating Control 0 to 10 Vdc

Damper Actuator Installation

FAIRCHILD T5200 SERIES ELECTRO-PNEUMATIC TRANSDUCER Installation, Operation and Maintenance Instructions

OpenAir Electric Damper Actuators GDE/GLB Series Non-spring Return Rotary 24 Vac - Modulating Control 0 to 10 Vdc

TAC DuraDrive Product Guide Direct Coupled Actuators

System 350 P352AB Electronic Pressure Control Series

D-70, D-140, D-210, and D-280 Series Electric Non-Spring Return Actuators

Distributed By: M&M Control Service, Inc Product Product Code Technical Instructions Page #

NETSIAN TECHNOLOGY VALVE SCHEDULE

VE VVG Series Electronic Two-way Valves Normally Closed

Non-Spring Return EconoDrive Floating Actuator

P66 Series Electronic Fan Speed Controls

OpenAir Electronic Damper Actuators GLB Series Enhanced Non-spring Return Rotary

OpenAir Electric Damper Actuator GDE/GLB Series Non-spring Return, 24 Vac Floating Control, Rotary

D24-53 Series Electric Non-Spring Return Actuators 53 lb in Models (6 N m)

4 x 0-10Vdc Channels Fused 24V o/p terminals for actuator power Direct or buffered output signals

Application. Features

VB-9213 Series. Application. Features. Applicable Literature

The T5220 Series Electro-Pneumatic Transducer converts a DC current or voltage input signal to a directly proportional pneumatic output.

Auxiliary Equipment. Table of Contents. Auxiliary Equipment H-1. Product Product Code Technical Instructions Page #

VB-9313 Series. Application. Features. Applicable Literature

VA-7450 Series. Electric Valve Actuators

M9216 Series Electric Spring Return Actuators

DIN-A-MITE C. SCR Power Controller Delivers Up To 80 Amperes in a Compact Package. TOTAL CUSTOMER SATISFACTION 3 Year Warranty. Features and Benefits

Mid-West Instrument. Series 700 "Wet/Wet" Installation and Operating Instructions. Differential Pressure Transmitter

FAIRCHILD T5420 DIGITAL-PNEUMATIC TRANSDUCER Installation, Operation and Maintenance Instructions

Installation and Operation Instructions DLP Series

MF /MS Series

Flowrite EA 599 Series SKD Electronic Valve Actuator 24 Vac Proportional Control

OpenAir Electric Damper Actuators GDE/GLB Series Non-spring Return Rotary 24 Vac - Modulating Control 0 to 10 Vdc

Powers TM Controls SW 134 Pressure Electric Switch (Adjustable Differential)

MS41-634X Series. Features. SmartX Actuators Non-Spring Return Proportional General Instructions

Pattern Air Control Kit (PACK)

Actuator for Valves. heating systems air handling systems. The actuator can not be equipped with Self Testing Device STS.

DuraDrive MF /MS Series Non-spring Return Rotary Electronic Damper Actuators 24 Vac Three-position/Modulating

Minimum 27 in-lb torque

Erie VT/VS PopTop Series Two Position Spring Return Valves

SPECIFICATIONS ATTENTION OPERATION DESCRIPTION

MS Series MS Series MS Series

Mount directly to 1.05 jackshafts. (new ZG-120 bracket shown) EFB24-S N4, EFX24-S N4(H) EFB24-S, EFX24-S (p. 21)

M100F Incremental Motor Actuator R81F Interface Board

MA/F/S 4D-xxxx-xxx Two Position, Floating and Proportional Series SmartX Actuators Rotary Overshaft Actuators

Figure 1: WPR2 Dimensions and Hardware

DA-053 Series. Overview. Applications. Features & Benefits. Datasheet. 53lb-in (6 Nm), Non-Spring Return Damper Actuators

GE Measurement & Control

MAx1-720x Two Position Series MFx Floating Series MSx Proportional Series

FAIRCHILD T5220 SERIES ELECTRO-PNEUMATIC TRANSDUCER Installation, Operation and Maintenance Instructions

1329I Integrated Drive/Motor CE Filter Option Kit

Switching DC Power Supply

Type 2000 Transducer Product Instructions

SAX Electronic Valve Actuator

Versatile and Powerful

Laboratory Room Controller

Pressure Transmitter. Pressure transmitter with compact design Model EDC-K. Electronic. Applications. Special Features.

ComfortPoint Programmable Lon, VAV/Unitary Controllers

Transcription:

CP-8551 & CP-8552 Electronic to Pneumatic Transducers General Instructions Application The CP-8551 and CP-8552 transducers receive a variable electronic input signal and produce a 3 to 15 psig (21 to 103 kpa) pneumatic output signal to position pneumatic damper and valve actuators in HVAC systems. Features Durable enclosure with easily accessible wiring terminations Panel or DIN rail mounting for quick, snap-on installation Two-wire loop powered or three-wire voltage input High accuracy with low hysteresis Long-term driftless operation with high repeatability Low air consumption and large air flow capacity Control input protection from short circuit or reverse polarity Applicable Literature Environmental Controls Reference anual, F-21683 EN-123 Air Quality Requirements for Pneumatic HVAC Control Systems Engineering Information, F-22516 Pneumatic Products Catalog, F-27383 Printed in U.S.A. 4/10 Copyright 2010 Schneider Electric All Rights Reserved. F-26159-6

SPECIFICATIONS Transducer Inputs Input Signal: CP-8551, 4 to 20 ma. CP-8552, 4 to 20 ma, 6 to 9 V, and 0 to 10 V. Input Impedance: CP-8551, 550 ¾ maximum, 400 ¾ minimum. CP-8552, 550 ¾ maximum, 400 ¾ minimum, 4 to 20 ma input; >10,000 ¾ voltage input. Power Input Requirements: 4 to 20 ma Input, None. 0 to 10 and 6 to 9 V Input, Requires 20 to 30 Vac, 3.9 VA (CP-8552), 50/60 Hz, or 24 to 30 Vdc power supply, 1.6 watts maximum. Input Range Selection: CP-8551, None. CP-8552, Jumper selectable. Air Supply Required: 20 psig (138 kpa) nominal, 30 psig (207 kpa) maximum. Clean, dry, oil free air required (refer to EN-123, F-22516). Air Consumption for Sizing Air Compressor: aximum 0.012 scfm (5.66 ml/s) @ 20 psig (138 kpa) supply. Air Capacity for Sizing Air ains: inimum 550 scim (150.24 ml/s). Air Connections: ale barbed fittings for flexible 1/4" O.D. pneumatic tubing. Wiring Connections: Screw terminals for use with 16 to 22 AWG wire. Transducer Outputs Output Signal: 3 to 15 psig (21 to 103 kpa) nominal, Direct Acting. aximum Pneumatic Output: 1 to 18 psig (7 to 124 kpa). Output Air Capacity & Pressure: 515 scim (141 ml/s) maximum with a 20 psig (138 kpa) supply. Operating Characteristics: Linearity, ±1% of span @ 75 F (24 C). Hysteresis, 0.75% of span @ 75 F (24 C). Adjustments: CP-8551, None. CP-8552, 4 to 20 ma Range None. 0 to 10 and 6 to 9 V Range Adjustable start point and span potentiometers. Environment Ambient Temperature Limits: Shipping and Storage, -40 to 160 F (-40 to 71 C). Operating, 32 to 140 F (0 to 60 C). Humidity: 5 to 95% R.H., non-condensing. Locations: NEA Type 1. Agency Listings: UL 873: Underwriters Laboratories (File #E9429 Category Temperature-Indicating and Regulating Equipment). CSA: Certified for use in Canada by Underwriters Laboratories. Canadian Standards C22.2 No. 24-93. European Community: EC Directive (89/336/EEC). Low Voltage Directive (72/23/EEC). Accessories AL-3X2 Pressure gauge. K-335 In-line air filter. B-371 Branch tee. -127 90 drop ear elbow. -636 4 in. T and B wire tie. P-610 35 mm DIN rail (1-3/8 W x 36 L x 3/10 H in). Note: Order the AL-3X2 Pressure Gauge, the B-371 Branch Tee, and the -127 90 Drop Ear Elbow separately and field assemble to provide optional pressure indication for the CP-8551 and CP-8552 transducers. 2 Copyright 2010 Schneider Electric All Rights Reserved. F-261596-6

TYPICAL APPLICATIONS (wiring diagram) CP-8551 +4 to 20 ma Current Input Signal + B 3 to 15 psig (21 to 103 kpa to controlled device (direct acting) Signal Common Figure-1 CP-8551 Typical Wiring. CP-8552 24 Vac/dc Power Common Signal Common Voltage Input Signal 1 24H CO +IV1 1 2 3 B 3 to 15 psig (21 to 103 kpa to controlled device (direct acting) 1 When multiple CP-8552s or other devices are powered by a common source, uniform wiring polarity must be maintained between all 24H and CO terminals. Check to ensure that the controller s CO terminal is not connected to any other ground reference. Figure-2 CP-8552 Typical Wiring for Voltage Input. CP-8552 Signal Common CO 1 2 B 3 to 15 psig (21 to 103 kpa to controlled device (direct acting) +4 to 20 ma Current Input Signal +IV1 3 Figure-3 CP-8552 Typical Wiring for Current Input. INSTALLATION Inspection Requirements Inspect the package for damage. If damaged, notify the appropriate carrier immediately. If undamaged, open the package and inspect the device for obvious damage. Return damaged products. Wiring diagrams. Tools (not provided): Screwdriver for mounting screws. Drill and drill bit for mounting screws. Appropriate accessories. Two (2) # 6 mounting screws (not provided). -636 4 in. T and B wire tie (not provided). Training: Installer must be a qualified, experienced technician. F-26159-6 Copyright 2010 Schneider Electric All Rights Reserved. 3

Precautions General Warning: Disconnect the power supply (line power) before installation to prevent possible electrical shock and equipment damage. ake all connections in accordance with the wiring diagram and in accordance with national and local electrical codes. Use copper conductors only. Do not exceed the ratings of the device(s). Supply Air Caution: Particles in the air supply larger than 0.03 microns (4 mpa) may adversely affect the reliability and life of the transducer. If air supply is questionable, install a K-335 in line air filter between the main air supply and the main air port of the device. A refrigerated air dryer, particulate filter, and coalescing filter should provide a quality air supply (refer to EN-123, F-22516). Compressor oil must be non-paraffin mineral base or naphtha base. Synthetic base oils will destroy pneumatic controls and void the warranty. Location ounting Caution: NEA Type 1 devices are intended for indoor use primarily to provide a degree of protection against contact with the enclosed equipment. Do not locate unit in areas subject to incidental contact, vibration, severe mechanical shock, excessive moisture, or corrosive fumes. Refer to Figure-5 for mounting dimensions. Caution: The CP-8551 and CP-8552 transducers must be mounted within 5 of the upright position. (Refer to "UP" arrow on printed circuit board.) 1. Remove transducer cover by grasping both sides of cover and pulling gently. 2. Select the mounting location. 3. Rail mount transducer on a vertical surface by snapping to a 35 mm DIN mounting rail (not provided) or wall mount with two screws (not provided). ultiple units can be mounted side by side on a DIN mounting rail. 4. Pull wires through bottom of enclosure and make necessary connections. 5. Position wires to clear the wiring access hole in the cover. 6. Use a small plastic wire tie to secure the wires to the strain relief tab provided on the mounting base to the left of the wiring terminations (Figure-4 ). 7. Replace cover and make pneumatic connections. Wiring Use 16 to 22 AWG wire for Class II wiring terminals. Use flexible 1/4" O.D. tubing for main and branch male pneumatic connections. 4 Copyright 2010 Schneider Electric All Rights Reserved. F-261596-6

Jumper Selection (CP-8552 Only) Note: The CP-8552 is factory calibrated for the 4 to 20 ma and 0 to 10 V ranges. Switching to the 6 to 9 V range requires recalibration of the start point and span potentiometers. The CP-8552 has three jumper selectable input ranges. Refer to Figure-4 for jumper block detail. ake proper jumper selection as follows: 1. Choose input range. 2. Consult Table-1 for jumper position. 3. Place jumper over square posts on appropriate lettered block (Figure-4 ). 4. Calibrate by performing appropriate CHECKOUT procedure. Table-1 CP-8552 Jumper Selection. x = Insert jumper at position shown in chart. Range A B C 4 to 20 ma X 6 to 9 V X 0 to 10 V a X a CP-8552 factory supplied at 0 to 10 V input. Transducer Start Zero point adjust potentiometer Span adjust potentiometer Wiring terminations 1 2 3 Jumper block Square post A B C Jumper Figure-4 CP-8552 Internal View. F-26159-6 Copyright 2010 Schneider Electric All Rights Reserved. 5

Controller Output Scaling In order to properly control the actuator, the output of the controller must be scaled appropriately. Table-2 below illustrates the correct output which corresponds to the electronic input of the transducer. Table-2 Electronic/Pneumatic Transducer Conversion Chart. Electronic Input Output (PSI) 4-20 ma 6-9 Volts* 0-10 Volts* 3 4.00 6.00 0.00 4 5.33 6.25 0.83 5 6.67 6.50 1.67 6 8.00 6.75 2.50 7 9.33 7.00 3.33 8 10.67 7.25 4.17 9 12.00 7.50 5.00 10 13.33 7.75 5.83 11 14.67 8.00 6.67 12 16.00 8.25 7.50 13 17.33 8.50 8.33 14 18.67 8.75 9.17 15 20.00 9.00 10.00 * Applies only to CP-8552. CHECKOUT 4 to 20 ma Range (CP-8551 and CP-8552) Note: The CP-8551 and CP-8552 4 to 20 ma span and start point potentiometers are not field adjustable. To check transducer operation: 1. Check for foreign material such as dirt or oil in the air supply. Also check for clogged filters. Supply air contamination by dirt or oil is the most likely cause of malfunction. 2. Verify that the unit is mounted upright and wired correctly. 3. Verify that 20 psig (138 kpa) main air is present. 4. Verify with a digital multimeter that a 4 to 20 madc signal is present and of correct polarity. 5. Adjust the input signal to 4 ma. Branch pressure should be 3 psig ± 1.0 (21 kpa). 6. Adjust the input signal to 20 ma. Branch pressure (direct acting) should be 15 psig ± 1.0 (103 kpa). 7. Unit is functional if correct pressures are indicated. Replace an inoperative transducer with a functional unit. 6 Copyright 2010 Schneider Electric All Rights Reserved. F-261596-6

0 to 10 or 6 to 9 V Range (CP-8552 only) AINTENANCE FIELD REPAIR To check transducer operation: 1. Check for foreign material such as dirt or oil in the air supply. Also check for clogged filters. Supply air contamination by dirt or oil is the most likely cause of malfunction. 2. Verify that the unit is mounted upright and wired correctly. 3. Verify that 24 Vac power is available and 20 psig (138 kpa) main air is present. 4. Verify with a digital voltmeter that an input signal between 0 to 10 or 6 to 9 V is present and of correct polarity. 5. Use a digital voltmeter to verify the presence of the correct power supply voltage between terminals 1 and 2. 6. Adjust the input signal to bottom of range (0 or 6 V). 7. Branch pressure should be 3 psig (21 kpa). If not, adjust start point potentiometer (Figure-4 ) to obtain a 3 psig (21 kpa) output. 8. Adjust input to top of range (9 or 10 V). 9. Branch pressure should be 15 psig (103 kpa). If not, adjust SPAN potentiometer (Figure-4 ) to obtain a 15 psig (103 kpa) output. 10. Recheck steps 6 through 9. 11. Unit is functional if correct pressures are indicated. Replace an inoperative transducer with a functional unit. Regular maintenance of the total system is recommended to assure sustained optimum performance. Field repair is not recommended. Replace an inoperative transducer with a functional unit. DIENSIONAL DATA 4-5/8 (118) 4 (102) 2-3/4 (70) 4-1/4 (108) 1-21/32 (42) 9/16 (14) 1-3/32 (28) 5/16 (8) 2-1/4 (57) 2-13/16 (71) 1/2 (13) 2-5/32 (55) Front View Side View Dimensions shown are in inches (mm). Figure-5 CP-8551 and CP-8552 Dimensions. F-26159-6 Copyright 2010 Schneider Electric All Rights Reserved. 7

On October 1st, 2009, TAC became the Buildings business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric, however there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate corporate brand changes. Copyright 2010, Schneider Electric All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice. F-26159-6 Schneider Electric 1354 Clifford Avenue P.O. Box 2940 Loves Park, IL 61132-2940 www.schneider-electric.com/buildings