Surepowr Series Sure 150

Similar documents
Surepowr Series 100 Installation Manual

SUREPOWR TM SERIES -SURE 49 FIELD INSTALLATION INSTRUCTIONS

SUREPOWR TM SERIES -SURE 24/25 FIELD INSTALLATION INSTRUCTIONS

Milwaukee's Electric Actuator Installation, Operation & Maintenance Manual

MOONEY FLOWGRID SLAM SHUT REGULATORS

Electric Actuator Installation, Operation & Maintenance Manual

Quarter Master Series 94 Actuator

Electric Actuator Installation, Operation & Maintenance Manual

VA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service

12 Series Linear Actuators. Operation & Maintenance Manual, Analog Positioner Installation

Your Global Flow Control Partner. Series 70 24V On/Off Electric Actuator Operation and Maintenance Manual

Installation Instructions

OPEN/CLOSE SERVICE ELECTRIC ACTUATORS OPERATION AND MAINTENANCE MANUAL COMMERCIAL AND INDUSTRIAL VALVES AND AUTOMATION

Series 10 Actuator. Installation, Operation and Maintenance Manual

Installation and Operating Manual

ANDCO Eagle Actuator Instruction Manual

Series 70 24V On/Off Electric Actuator Operation and Maintenance Manual

SERIES 73 ELECTRIC ACTUATOR OPERATION AND MAINTENANCE MANUAL. The High Performance Company

Installation & Operation Manual

Installation & Operation Manual

Installation & Operation Manual

Radius, LLC Electric quarter turn actuator EW series Installation, Maintenance and Operating Manual

Safe & Secure Series Electric Actuator with Internal Battery Back-up Installation, Operation & Maintenance Manual

AE Installation Operation & Maintenance Instructions

Quarter Master Chief Series 92 Actuator

Installation, Maintenance and Operation Manual

Installation, Operation and Maintenance Manual

Installation & Operation Manual

IMO-517 (7027) ISSUE 3/97 ERA12, 25, 50, 83, 125, 167, 208 AND 250 ELECTRIC ACTUATORS INSTALLATION, MAINTENANCE AND OPERATING INSTRUCTIONS

OIL FIELD ELECTRIC ACTUATOR INSTRUCTION MANUAL SPECIAL APPLICATIONS ACTUATORS Q 6.0.1

Installation & Operation Manual

12 Series Linear Electric Actuator Installation, Operation & Maintenance Manual

ECON ELECTRIC ACTUATOR Fig ELA60 Ex

K10 Intrinsically Safe Electro-Pneumatic Positioner Operating Manual

HQ Series ¼ Turn Electric Actuator

Installation & Operation Manual

NOAH ACTUATOR NA-SERIES MANUAL EMICO EUNHA MACHINERY INDUSTRIAL CO.,LTD.

LCR Series REVERSING ELECTRIC ACTUATORS. Installation, Maintenance and Operating Instructions

Installation & Operation Manual

Instruction Manual for Barber-Colman Series EA Electric High Torque Actuators

SPECIFICATIONS ATTENTION OPERATION DESCRIPTION

1.0 Features and Description

Current consumption Auxiliary switch. Angle of rotation 90 (internal electrical stops) Running time

HQ Series ¼ Turn Electric Actuator

ICI Indelac Controls, Inc. Installation, Operation & Maintenance Manual For Electric Spring Return Actuator

Valtek Position Pac GENERAL INFORMATION INSTALLATION INSTRUCTIONS OPERATION. Valtek Linear Actuators

Electric Modulating Actuator Installation, Operation & Maintenance Manual

Small Motorized Actuator

I-BFV.KIT Butterfly Valve Gear Operator Replacement

USER INSTRUCTIONS. Limitorque LY Series: LY 1001, LY 2001 and LY Installation Operation Maintenance. Experience In Motion

FRACTIONAL HORSEPOWER MOTORS & ACCESSORIES

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

Installation & Operation Manual

OPERATION INSTRUCTONS MODEL SG 05.1 SG Quarter-Turn Actuators

Technical Specification. RCS Electric Actuators with a ProfiBus Field Control and Communication Module

McCANNA Actuation Systems B

ELECTRIC ACTUATOR HVAC/BAC ELECTRIC IOM. E024, EO25, E026, EO29 & E030 Installation Operation and Maintenance Instructions TABLE OF CONTENTS

MAx-305 & MAx-318 Series MAx-405 Through MAx-419 Series Two-Position Actuators

IOM FOR DYNATORQUE D-LOCK LOCKING DEVICE (DL TYPE)

MODULATING SERVICE ELECTRIC ACTUATORS OPERATION AND MAINTENANCE MANUAL COMMERCIAL AND INDUSTRIAL VALVES AND AUTOMATION

ROM Series. Keeping the World Flowing. Installation Manual. Valve Actuators

SERIES 70 TUNNEL DAMPER MODEL ELECTRIC ACTUATOR OPERATION AND MAINTENANCE MANUAL

Type SAM-01 to Type SAM-52 Electric Actuators. Type SAM-20, 30 mm rated travel, 6 kn thrust. Mounting and Operating Instructions EB 8330 EN

Quarter Master Series 94 Actuator

Direct-Coupled ControlSet Actuators (120/180/320 in-lbs.) Installation Guide 2-7/16"

CENTURA CE Series. Installation, Operation SR and Limit Maintenance Switch Method Instructions

RE Generation II Troubleshooting Guide Section I Preliminary Information and Evaluation

EX Series. Electric Actuators for Ball and Butterfly Valves

V Series 115 VAC AND 230 VAC STANDARD ELECTRIC ACTUATORS. Installation, Maintenance and Operating Instructions

VA-9070 Series Electric Rotary Actuators for Two-Position and Modulating Service

Products for Oil & Gas Production TEXSTEAM PUMPS

VALVCON. QX-Series ELECTRIC ACTUATORS. Installation, Maintenance and Operating Instructions

Hyponic. Quick-Start Guide. Manual

Current consumption Auxiliary switch. Angle of rotation 90 (internal electrical stops) Running time

RCS Actuators. Versatile Automation Solutions. RCS Actuators

Series 41 and 81 Modutrol IV Motors

EX Series. Electric Actuators for Ball and Butterfly Valves

SB 2000 PUSH TO SEARCH NEXT STAG E. Aerotech, Inc. FORM: QM 1320

Installation & Operation Manual

ROM Series. Established Leaders in Flow Control. Installation Manual. Valve Actuators

ELECTRIC ACTUATOR 94OE IOM. E024, EO25, E026, EO29 & E030 Installation Operation and Maintenance Instructions TABLE OF CONTENTS

Model 116 DPI Switch Installation and Operating Instructions

M9216 Series Electric Spring Return Actuators

Powers TM Controls EA 338 Electronic Actuator

SERIES 90/91 R PNEUMATIC ACTUATOR OPERATION AND MAINTENANCE MANUAL. The High Performance Company

XENON POWER SUPPLY 4000 Watt Gladiator IV

VALVCON V-Series ELECTRIC ACTUATORS 115 VAC AND 230 VAC With Iso/Readback Board Installed (Option U )

Operation & Instructions Manual SA 3 - SA 100 SAR 3 - SAR 100

A1500, A1500NF SPEED SWITCH SINGLE SET POINT - SELF CONTAINED. Introduction

Electric Actuator Instructions

V Series. 115 VAC AND 230 VAC STANDARD ELECTRIC ACTUATORS With Isolated Control/Position Feedback Board Installed (Option U )

Installation Instructions

SERIES 1000 ELECTRIC ACTUATORS

Installation & Operation Manual

Installation, Service and Parts List Series 56,800 for Class I & II, Division 2 Manual Adjust Brakes

Type Installation, Operation and Maintenance Instructions. Ordering Information. Contents CA20 -

MODEL NUMBER: MEDIUM DUTY ONBOARD AIR SYSTEM

1980 Rotating Cam Limit Switches. Ordering Guide & Technical Information

INSTALLATION & OPERATION MANUAL. Fan Powered Terminals VAV TERMINALS. Redefine your comfort zone.

Quarter Master Chief Series 92 Actuator

Transcription:

RCS Acutators Surepowr Series Sure 50 Installation Manual Safety First In the maintenance and operation of mechanical equipment, safety is the basic factor which must be considered at all times. Through the use of the proper clothes, tools, and methods of handling, serious accidents causing injury to you or your fellow workers can be prevented. Throughout this manual are listed a number of safety precautions. Study them carefully and follow them; also insist that those working for you do the same. Remember, an accident is usually caused by someone s carelessness, neglect, or oversight. Installation CAUTION To prevent ignition of hazardous atmospheres, do not remove actuator cover unless power has been switched off or area is known to be non-hazardous. CAUTION Loaded spring inside actuator. Do not attempt to repair actuator below top gear plate, unless properly trained on specific repair methods for this actuator. Note: SurePowr actuators can be supplied for clockwise or counter-clockwise spring driven rotation (viewed from the top of the actuator). The spring drive rotation is noted on the actuator name tag and wiring diagram. Ensure that the actuator has been supplied with the proper spring drive operation for the application prior to installation on the driven device.. The actuator is shipped in the power off (fail) position. Ensure that the driven device is orientated to its fail position prior to installation of the actuator.. Care should be taken to maintain proper alignment between the actuator and the device shaft. The actuator should install on the shaft without binding. The mounting face should be centered on the bracket without binding or side load.. Mount the actuator to the device. Ensure the actuator is centered properly with the device shaft, and then tighten all bolts and nuts evenly.. Remove the cover bolts located around the actuator motor and control cover flange. 5. Terminate field wiring per the appropriate RCS wiring diagram supplied with the actuator. Use a minimum of #8 AWG stranded wire. Note: Ensure the driven device is properly positioned in its full fail position. If it is not, use the adjustable end of travel stop on the Sure 50 (see figure ) to properly adjust the fail end of travel stop. Only the fail end of travel may be adjusted. Electrically drive the actuator off of the stop and hold it in position with the motor brake. Loosen the lock nut to free the adjusting screw, then use a wrench to turn the screw. The total adjustment available is +/- 5. Release the brake and check the position of the driver device. Repeat the adjustment if necessary.

Switch adjustments for clockwise spring fail operation (viewed from the top of the actuator) a. Ensure actuator is de-energized and positioned in the clockwise (fail) position. Ensure the end of travel stop is properly adjusted. Rotate the screw clockwise to move the actuator output shaft in a counter-clockwise direction. Rotate the screw in a counter-clockwise direction to move the actuator output shaft in a clockwise direction. Loosen the setscrews on Cams and. Rotate both counter-clockwise until they clear the switch arms of Switches and. b. Rotate Cam clockwise until it comes in contact with Switch s arm and the switch breaks. A light click can be heard. Tighten the set-screws on Cam. c. Rotate Cam clockwise until it comes in contact with Switch s arm and the switch just breaks. A light click can be heard. d. Rotate Cam slightly further in the clockwise direction. This ensures that Switch will break just prior to the actuator reaching the full fail position. Tighten the setscrews on Cam.. If intermediate indication is needed, Cam can be set to any point within the range of travel. e. Energize the actuator. This will move the actuator to the opposite end of travel. Upon reaching the opposite end of travel, Cam should just engage the arm on Switch so that the switch just breaks. This action will stop the actuator. Check that the actuator has properly positioned the driven equipment. CAUTION Closely monitor the electrical stroke, as the travel limit switches are not yet properly adjusted. Ensure the actuator does not over-travel and damage the driven equipment. f. If actuator travel is insufficient, rotate Cam slightly clockwise until the cam just clears the arm of Switch. As soon as the cam clears the arm, the actuator will bump electrically towards the end of travel. Continue until the actuator reaches the full end of travel. If the actuator has over-traveled, rotate Cam slightly counter-clockwise, then move the actuator towards the fail position electrically. Stop and electrically reverse the direction of travel. Move the actuator until Cam operates Switch and the actuator stops. Repeat this procedure until the actuator is properly positioned. g. Rotate Cam until it comes in contact with Switch s arm and the switch just breaks. A light click can be heard. Rotate the cam slightly counter-clockwise. This ensures that Switch will break just prior to the actuator reaching the extreme opposite end of travel. If intermediate indication is needed, Cam can be set to any position within the range of travel. Tighten the setscrews on Cams and. Switch adjustments for counter-clockwise spring fail operation (viewed from the top of the actuator) a. Ensure the actuator is de-energized and positioned in the counter-clockwise (fail) position. Ensure the end of travel stop is properly adjusted. Rotate the screw counter-clockwise to move the actuator output shaft in a counter-clockwise direction. Rotate the screw in a clockwise direction to move the actuator output shaft in a clockwise direction. Loosen the setscrews on Cams and. Rotate both clockwise until they clear the switch arms of switches and. b. Rotate Cam counter-clockwise until it comes in contact with Switch s arm and the switch breaks. A light click can be heard. Tighten the setscrews on Cam. c. Rotate Cam counter-clockwise until it comes in contact with Switch s arm and the switch just breaks. A light click can be heard. d. Rotate Cam slightly further in the counterclockwise direction. This ensures that Switch will break just prior to the actuator reaching the full fail position. If intermediate indication is needed, Cam can be positioned at any point within the range of travel. Tighten the setscrews on Cam. e. Energize the actuator. This will move the actuator to the opposite end of travel. Upon reaching the opposite end of travel, Cam should just engage the arm on Switch so that the switch just breaks. This action will stop the actuator. Check that the actuator has properly positioned the driven equipment. f. If actuator travel is insufficient, rotate Cam slightly counter-clockwise until the cam just clears the arm of Switch. As soon as the cam Dresser

CAUTION Closely monitor the electrical stroke, as the travel limit switches are not yet properly adjusted. Ensure the actuator does not over-travel and damage driven equipment. g. Rotate Cam until it comes in contact with Switch s arm and the switch just breaks. A light click can be heard. Rotate the cam slightly further in the clockwise direction. This ensures that Switch will break just prior to the actuator reaching the extreme opposite end of travel. If intermediate indication is needed, Cam can be positioned at any point within the range of travel. Tighten the setscrews on Cams and. 6. Operate the actuator electrically several times to ensure proper operation and to verify that travel limits and stops are correctly set. 7. De-energize the actuator to verify proper spring drive operation. Ensure the driven device is properly positioned in the spring drive position. 8. If the actuator is supplied with an optional feedback potentiometer and/or position controller, verify proper calibration of input and output signals after making cam and stop bolt adjustments. 9. Replace the actuator cover and cover screws. 0. The actuator is now ready for electrical operation. RCS Surepowr Series Sure 50

Typical Wiring Diagrams Units should be connected using the wiring diagram supplied with the actuator. Spring Drive CW on Loss of Power Spring Drive CCW on Loss of Power FIELD WIRING L CW STOP CCW L - NEUTRAL SP- POSITION SNAP ACTION SWITCH (SEE TE ) YELLOW BROWN ACTUATOR WIRING TB 5 6 POSITION CONTROL BOARD SW. SW. J E E J C M THERMAL OVERLOAD AUTOMATIC RESET BLUE YELLOW FIELD WIRING CW L STOP CCW L - NEUTRAL SP- POSITION SNAP ACTION SWITCH (SEE TE ) ACTUATOR WIRING TB POSITION CONTROL BOARD YELLOW SW. BROWN 5 SW. 6 J E E J C M THERMAL OVERLOAD AUTOMATIC RESET BLUE YELLOW 9 7 8 SW. J5 +t? HEATER 9 7 8 SW. J5 +t? HEATER MOTOR-DRIVE BOTH CCW & CW INTERMEDIATE STOP CAPABILITY SPRING-DRIVE CW ON LOSS OF POWER 0 TB 5 6 SW. AUX 5 BRIDGE RECTIFIER MOTOR BRAKE AUX E E MOTOR-DRIVE BOTH CCW & CW INTERMEDIATE STOP CAPABILITY SPRING-DRIVE CCW ON LOSS OF POWER 0 TB 5 6 SW. AUX 5 BRIDGE RECTIFIER MOTOR BRAKE AUX E E Figure Power to TB terminal and TB terminal will motordrive and brake-hold actuator in full CCW position. Power to TB terminals and will brake-hold actuator in its current position. Power to TB terminal and TB terminal will motordrive and spring-hold actuator in full CW position. Loss of power will spring-drive and spring-hold actuator in full CW position. Figure Power to TB terminal and TB terminal will motordrive and brake-hold actuator in full CW position. Power to TB terminals and will brake-hold actuator in its current position. Power to TB terminal and TB terminal will motordrive and spring-hold actuator in full CCW position. Loss of power will spring-drive and spring-hold actuator in full CCW position. IMPORTANT Direction of rotation is based on viewing actuator from top. IMPORTANT To operate multiple actuators in parallel from a single source requires isolating relays in the field wiring. Dresser

Dimensional Information 5.78 Ø.56 Ø. x /" NPT Conduit Entry Ports 5.7 Clearance for Cover Removal 7.8 5.0 7.6 to NPT Ports Lifting Lug /8-6 U Thread,.6 deep x Lifting Lug /8-6 U-B Thread,.88 deep CCW Travel Stop CW Travel Stop Figure.5" Conduit Entry /8-6 U x.65 Deep Typ. places located on a.756 D.B.C. CCW Spring Return.0 Dia. x.8 DP..0 0.5 x 0.76 [8mm x 7mm] Key Typ. places Conduit Entry.00 Dia. Bore Depth.50" CW Spring Return.75" Notes. Direction of rotation is based on viewing actuator from top.. Actuator shown in power fail position.. Two keys are recommended for driving device.. Actuator suitable for mounting in any orientation. Standard Features Four SPDT Limit Switches PTC Heater Motor Brake Position Indicator Adjustable Travel Stop in fail position Figure 5 RCS Surepowr Series Sure 50 5

Operation Power On: The electric motor drives the gear train, which in turn winds the spring and turns the device. An internal limit switch de-energizes the motor and energizes the brake, which holds the return spring and device in position. Power Off: When the current is interrupted by either a control signal or a power failure, the return spring drives the device to its original position. Note: It is recommended that the actuator be driven electrically in both directions for normal operation to prolong cycle life. Maintenance Gear train is permanently lubricated at the factory for the average life of the actuator. No further attention is required. Thermal Overload The internal thermal overload switch de-energizes the motor and prevents overheating of the motor windings due to excessive operation, stalling or high ambient temperatures. De-energizing the motor due to thermal overload will result in actuator spring-driving to the power loss position. Duty Cycle The maximum duty-cycle to be expected without interruption by thermal cut-off at an ambient temperature of 65C (50 F) is 5% ( OFF times for every ON time). Storage The Surepowr actuator must be stored in a clean, dry, temperature controlled building which is protected from the weather. Precautions shall be taken to prevent condensation inside or outside the actuator. If there is insufficient external temperature and humidity control, the internal heaters must be energized to protect the unit against condensation from extreme temperature variations. The actuators shall be stored off the floor on suitable pallets and must be covered with an unsealed dust protector allowing side and bottom ventilation. Conduit entries must be sealed with the shipping plugs provided or other suitable means. The control cover is to be installed. Isolation Relays CAUTION To prevent ignition of hazardous atmospheres, do not remove actuator cover unless power has been switched off or area is known to be non-hazardous. To operate multiple actuators in parallel from a single signal requires isolating relays in the field wiring. Consult Factory. Troubleshooting (New Unit) Note: Most actuator problems occur due to incorrect cam/ travel limit switch setting, or the incorrect setting of an external travel stop on the device that the actuator is operating. Problem : Actuator is receiving electric power but the motor does not respond. Instructions: a. Check actuator nameplate to insure correct model, voltage type and spring return direction.b. Check ll wiring against the wiring diagram provided with the actuator. c. Actuator with clockwise fail position: Using a volt meter, check that power is available between TB terminal and TB terminal. Then check the voltage between TB terminal (common) and the two legs of the motor and capacitor. The meter should indicate a value equal to or greater than the supply voltage indicated on the actuator nametag. Actuator with counter-clockwise fail position: Using a volt meter, check that power is available between TB terminal and TB terminal. Then check the voltage between TB terminal (common) and the two legs of the motor and capacitor. The meter should indicate a value equal to or greater than the supply voltage indicated on the actuator nametag. If power is not present at the motor or capacitor leads: Cam adjustments are required Switch malfunction Improper wiring Problem : Actuator is receiving electric power but the motor only hums. Instructions: a. Perform steps a through c listed above. b. Check that the bridge rectifier does not have power when power is applied to the motor. c. Check to insure the brake is completely disengaged when power is applied to the motor. 6 Dresser

Problem : Actuator runs but operation is erratic. Instructions: a. Perform steps a through c listed above. b. Check ambient temperature. Standard Surepowr actuators have a maximum ambient operating temperature rating of 65 C. c. Check duty cycle (frequency of operation). See above for details. d. Ensure that actuator is not continuously stalled. Problem : Motor runs continuously in spring return direction after actuator output shaft Instructions: a. Adjust spring return side travel cam/switch so that the cam trips the switch before the shaft stops motion. Problem 5: Motor runs continuously but output shaft does not turn. Instructions: 5a. Ensure that motor leads are connected correctly. Note: Standard Surepowr actuators are manufactured with thermal overload protectors in series with the motor common. Should any of the above problems cause the protector to open, it will automatically reset when the motor temperature is lowered to a safe level. Locating and Ordering Parts For ease and accuracy in identifying and ordering spare or replacement parts, submit the following information from unit nameplate.. Serial Number. Model Number. Voltage RCS Surepowr Series Sure 50 7

About Dresser products Dresser is a designer, manufacturer and distributor of natural gas measurement, pressure control and pipeline integrity products, service and repair. Dresser products are highly engineered, technically superior and are designed to help global customers meet and exceed requirements for mission-critical natural gas projects. Leading Dresser product lines include: Dresser Meters & Instruments, Becker Control Valves, Mooney & RedQ Regulators, Pipeline Solutions, FloSystems Prefabricated Sets and Blackhawk Products. About Dresser, Inc. Dresser, Inc. is a leader in providing highly engineered infrastructure products for the global energy industry. The company has leading positions in a broad portfolio of products, including valves, actuators, meters, switches, regulators, piping products, natural gas-fueled engines, retail fuel dispensers and associated retail point-of-sale systems, and air and gas handling equipment. Leading brand names within the Dresser portfolio include Dresser Wayne retail fueling systems, Waukesha natural gas-fired engines, Masoneilan control valves, Consolidated pressure relief valves, and Roots blowers. It has manufacturing and customer service facilities located strategically worldwide and a sales presence in more than 00 countries. Dresser, Inc. RCS Acutators 60 Port Northwest Dr. Houston, TX 770-65 Tel: (8) 590-06 Fax: (8) 89-879 00 Dresser, Inc. All rights reserved. www.dresser.com/rcsactuators IM_Sure 50.0