Technical Information Control of the Active Power Feed-In at the Grid-Connection Point with the SMA CLUSTER CONTROLLER

Similar documents
Integrated Plant Control and Q on Demand 24/7 SUNNY TRIPOWER

Technical Information PV Inverters

Planning Guidelines SMA SMART HOME

SMA Export Control Solution

Hilton Hunkin Senior Application Engineer SMA Solar Technology South Africa

Planning Guidelines SMA SMART HOME The System Solution for more Independence

Technical Information SUNNY BOY / SUNNY TRIPOWER Temperature Derating

System Description SMA FLEXIBLE STORAGE SYSTEM in the United Kingdom

Technical Information Temperature Derating for Sunny Boy and Sunny Tripower

Planning Guidelines SMA SMART HOME The System Solution for Greater Independence

Multi-Function Interface MULTI-FUNCTION RELAY

Feed-in management with Solar-Log

Increased Self-Consumption with SUNNY ISLAND and SUNNY HOME MANAGER SMA FLEXIBLE STORAGE SYSTEM

Operating Manual SUNNY TRIPOWER 15000TL / 20000TL / 25000TL

Solar Inverters. No. 6, R. A. De Mel Mawatha, Colombo

Design of Off-Grid Systems with Sunny Island 4.4M / 6.0H / 8.0H Devices

PV Inverter SUNNY MINI CENTRAL 9000TL / 10000TL / 11000TL with Reactive Power Control

Technical Information Average Efficiency of the SMA Flexible Storage System

Technical information SUNNY BOY SMART ENERGY / SUNNY BOY STORAGE / SUNNY ISLAND

SMA FLEXIBLE STORAGE SYSTEM

Planning Guidelines SMA FLEXIBLE STORAGE SYSTEM WITH BATTERY-BACKUP FUNCTION

User Manual SMA FUEL SAVE CONTROLLER 2.0

1 EASY COMMISSIONING GUIDE FRONIUS PV-SYSTEM CONTROLLER

Total number of PV modules: 42 Energy usability factor: 99.9 % Number of PV inverters: 1

User Manual SMA FUEL SAVE CONTROLLER 2.0

AC THOR or AC ELWA -E

SMA FLEXIBLE STORAGE SYSTEMS. SMA Solar Technology AG

Operating Manual SUNNY BOY 3600 / 5000 SMART ENERGY BATTERY PACK SMART ENERGY

PRODUCT LIST ORDER:

One-Stop Service: Monitoring and Managing.

System description Off-Grid Systems with SUNNY ISLAND 4.4M / 6.0H / 8.0H

SUNNY TRIPOWER CORE1 60% UP TO. faster installation for commercial PV systems. Subline lorem ipsum dolor sit amet EN DE STANDS ON ITS OWN

:34 1/15 Hub-4 / grid parallel - manual

Sunny Tripower CORE1.

ASC SWITCHBOARD DATA SHEET

System description Multicluster Systems with Stand-Alone Grid or Increased Self-Consumption and Battery-Backup Function

500 / 630 / 720 / 760 / 800 / 850 / 900

Wind Power Inverter WINDY BOY 5000A/6000A

Service Manual for Installers SUNNY TRIPOWER 5000TL/6000TL/7000TL/8000TL/9000TL/ 10000TL/12000TL

Operating Manual SUNNY BOY STORAGE 2.5

SMA COMMERCIAL PRODUCTS SUNNY TRIPOWER CORE1. Stands on its own. Up to 60 % faster installation for commercial PV systems

System Description SMA FLEXIBLE STORAGE SYSTEM with BatteryBackup Function

Energy Produced by PV Array (AC):

System description SMA FLEXIBLE STORAGE SYSTEM

SUNNY BACKUP System. Solar Power Even in the Event of Grid Failure

DATA SHEET Automatic Sustainable Controller, ASC Plant Management

SP PRO ABB Managed AC Coupling

Increased requirements on external DC-breakers for transformerless PV inverters in Australia

Technical Data. Low Voltage Regulation System LVRSys. Flexible solution for power utilities. Voltage stabilization for industrial grids

Hub-4 / grid parallel - manual

ANCILLARY SERVICES WITH VRE (VARIABLE RENEWABLE ENERGY): FOCUS PV

Energy storage kits for residential and commercial customers. Ken Hobbs Technical Director, CCL Components Dean Kalek Technical Trainer, SMA Solar UK

Wind power inverter WINDY BOY 5000-US/6000-US WINDY BOY 7000-US/8000-US. 1 Notes on this addendum. 1.1 Validity. 1.2 Target group

Transportation and Installation Requirements SUNNY CENTRAL 500CP XT/630CP XT/720CP XT/ 760CP XT/800CP XT/850CP XT/900CP XT/1000CP XT

PV SYSTEM WITH BATTERY STORAGE

Version: 1.0 Mat.-Nr.: DBUS-WB50-80US

Quick Installation Manual Alpha ESS Battery with SMA Flexible Storage System V1.0

Installation Guide SUNNY TRIPOWER 60

Your home and business energy independance. Energy Bundle CA5000TPV-3D

PV inverter SUNNY MINI CENTRAL 7000HV

Installation Manual SUNNY TRIPOWER 5000TL / 6000TL / 7000TL / 8000TL / 9000TL

Kythnos Island 20 Years Experience of System Technology for Renewable Energies

Installation Manual SMA SPEEDWIRE/WEBCONNECT DATA MODULE

Yield Reduction Due to Shading:

Installation Manual SMA SPEEDWIRE/WEBCONNECT DATA MODULE

Photovoltaics. MPI Hybrid Series

Fuzzy based STATCOM Controller for Grid connected wind Farms with Fixed Speed Induction Generators

ORDER:

SMA Utility Power System

Benefits of on-site real-time solar forecasting with CloudCAM

magellan solar export control solutions Magellan Power Solar Gate

SMA INTEGRATED STORAGE SYSTEM

14 October 09 Vas Kandiah AOQ SSMBB

Power Conditioning of Microgrids and Co-Generation Systems

High speed, closed loop frequency control using PMU measurements for power grids

WINDY BOY. Grid Connection of Small Wind Turbine Systems

PV Master OPERATION MANUAL

PV Development and Grid Access Study for a Club Resort in Indonesia

Sunny Tripower. Can do everything that we can

Solutions for Profitable PV Power Plants

Technical Data. Windy Boy 6000US. Windy Boy 5000US. Windy Boy 7000US

220Volt 10Watt LED FLOODLIGHT R Volt 20Watt LED FLOODLIGHT R Volt 30Watt LED FLOODLIGHT R

CLA-VAL e-drive-34. User Manual. Motorised Pilots. CLA-VAL Europe LIN072UE - 04/16

Installation - Quick Reference Guide Off-Grid Systems

SUNNY TRIPOWER 12000TL-US / 15000TL-US / 20000TL-US / 24000TL-US / 30000TL-US

Technical Information SUNNY TRIPOWER 60 / SUNNY HIGHPOWER PEAK1

SP PRO KACO Managed AC Coupling

* Protected from tools and particles greater than 2.5 millimeters * Protected form low pressure water jets from any direction

Accessories for Stand-alone inverter SUNNY ISLAND GENMAN

Generator Interconnection System Impact Study For

Grid Interconnection and Grid Integration Features of PV Inverters

Sunny Island Generator - White Paper

Yield Reduction Due to Shading:

[RENEX] [İstanbul, Ekim 2011]

TN004 Australian & New Zealand Export Power Control Functionality

Hardware Testing of Photovoltaic Inverter Loss of Mains Protection Performance

Advanced controls of PV for microgrid applications

Facilitated Discussion on the Future of the Power Grid

Description of the Operating Parameters SUNNY TRIPOWER 60 SUNNY HIGHPOWER PEAK1

PV Solar Proposal. Harmon Electric. Presented by: Robert Wittmann, Energy Consultant (480)

Transcription:

Technical Information Control of the Active Power Feed-In at the Grid-Connection Point with the SMA CLUSTER CONTROLLER To control the generated power of a PV system that is directly fed into the grid, the SMA Cluster Controller* has proved its value as a central controlling unit in many large-scale PV power plants. However, what is the situation when there are other loads in a PV system and the active power feed-in is to be controlled directly at the grid-connection point? The Cluster Controller can also offer potential solution approaches for this application case. From firmware version 1.02.12.R, the Cluster Controller can integrate an external measurement source for the active power feed-in at the grid-connection point and thus create the prerequisite for control of the active power feed-in at the grid-connection point. This document describes the solution approach of such a closed-loop control in greater detail. In addition to explanations of the required system components (inverter and control and measurement equipment), it provides valuable information on configuration of the PV system. This document does not replace the valid user manuals and installation manuals of the products used. * In this document, the SMA Cluster Controller is referred to as Cluster Controller. Wirkleistung_NAP_CC-TI-en-13 Version 1.3 ENGLISH

1 Differences between Open-Loop and Closed-Loop Control SMA Solar Technology AG 1 Differences between Open-Loop and Closed-Loop Control Open-Loop Control In the control of a PV system, external setpoints (e.g. for power limitation) are transferred directly to the inverters. This feature is used, for example, in large PV systems with direct active power feed-in. The Cluster Controller assumes the role of a central communication unit in this case. It can process all kinds of signal setpoints and pass these on to the inverters. An external company (e.g. a direct marketer or electric utility company) thus has direct access to the PV system and can, for example, directly limit the inverter's nominal PV system power. Limitation of the inverter's generated active power has a direct affect on the grid-connection point as no loads exist in the system (see Figure 1). Figure 1: Example of a decentralized large-scale PV power plant with Cluster Controller and implementation of grid operator setpoints via open-loop control Re Position A B C D E F G H I K L M Explanation Module temperature sensor Inverter and PV modules Outside temperature sensor Irradiation sensor Cluster Controller Sunny Portal Router Ripple control receiver or remote terminal unit Grid station Control room Grid control room Utility grid 2 Wirkleistung_NAP_CC-TI-en-13 Technical Information

SMA Solar Technology AG 1 Differences between Open-Loop and Closed-Loop Control Closed-Loop Control In the case of systems with self-consumption (see Figure 2), the proportion of grid feed-in depends on the current consumption which can also fluctuate over time. A typical requirement for these systems is that the active power feed-in at the grid-connection point is to be limited to a predefined maximum value, for example. A central closed-loop control is required for this, which uses the setpoint, the actual measurement value at the grid-connection point, and the currently generated active power to automatically calculate a required power limitation (output value) of the inverters. Figure 2: Example of a decentralized large-scale PV power plant with Cluster Controller and implementation of grid operator setpoints via closed-loop control Position A B C D E F G H I K L M N O Explanation Module temperature sensor Inverter and PV modules Outside temperature sensor Irradiation sensor Cluster Controller Industrial load Sunny Portal Router Ripple control receiver or remote terminal unit Energy meter Control room Grid control room Grid station Utility grid Technical Information Wirkleistung_NAP_CC-TI-en-13 3

2 Required System Components for Active Power Control SMA Solar Technology AG Possible Application Cases for Active Power Control: PV systems with self-consumption and the requirement to limit the active power feed-in at the grid-connection point to 0 watts (Zero Export) Such applications can be required in very weak utility grids. PV systems with self-consumption and restricted maximum active power feed-in at the grid-connection point PV systems with self-consumption, additional producers (e.g. PV arrays) and the requirement to limit the active power feed-in at the grid-connection point With such applications, the PV proportion can make a significant contribution to closed-loop control without the necessity for communication with the other producers in the PV system. 2 Required System Components for Active Power Control Central communication unit for system configuration, measured value processing, and closed-loop control SMA Cluster Controller from firmware version 1.02.12.R: Device type "CLCON-10" for maximum of 75 SMA Speedwire devices Device type "CLCON-S-10" for maximum of 25 SMA Speedwire devices Required authorizations for using the Cluster Controller You carry out configuration of the active power control via the user interface of the Cluster Controller in the Installer user group. To configure the SMA inverters, you also require your personal SMA Grid Guard code (application form is available at www.sma-solar.com) Measuring device for active power feed-in at the grid-connection point For PV systems with total current < 63 A via three line conductors: SMA Energy Meter (device type: EMETER-10) For PV systems with total current > 63 A: SMA Energy Meter (device type: EMETER-10) from firmware version 1.02.04.R and three current transformers for 5 A secondary current (e.g. ABB CM-CT series) Supported SMA Inverters: SMA Inverters Sunny Tripower: STP 50-40 / STP 50-US-40 STP 20000TL-30 / STP 25000TL-30 STP 15000TLEE-10 / STP 20000TLEE-10 STP 15000TL-10 / STP 17000TL-10 STP 5000TL-20 / STP 6000TL-20 / STP 7000TL-20 / STP 8000TL-20/ STP 9000TL-20 / STP 10000TL-20/ STP 12000TL-20 STP 12000TL-US-10 / STP 15000TL-US-10 / STP 20000TL-US-10 / STP 24000TL-US-10 STP 30000TL-US-10 Sunny Boy: SB 3000TL-21 / SB 3600TL-21 / SB 4000TL-21 / SB 5000TL-21 / SB 6000TL-21 SB 2500TLST-21 / SB 3000TLST-21 From inverter firmware version 1.01.19.R 2.81.07.R 2.63.03.R 2.62.04.R 2.53.02.R 2.80.00.R 2.81.00.R 2.80.02.R 2.80.22.R Visualization Sunny Portal for visualizations in preconfigured diagrams and creation of individual pages 4 Wirkleistung_NAP_CC-TI-en-13 Technical Information

SMA Solar Technology AG 3 Configuration and Commissioning of Active Power Control 3 Configuration and Commissioning of Active Power Control Due to the numerous configuration options for the Cluster Controller, only the most important steps for configuration and commissioning of active power control at the grid-connection point are described below. Note that all settings are made via the integrated web server of the Cluster Controller. Additional configuration options are described in the user manual of the Cluster Controller. 3.1 Standardization to the Total System Power All specifications for active power limitation of the system (setpoint) are given as a percentage of the total system power. By default, the Cluster Controller always determines the total of the nominal AC power of all the inverters in the system as a value for the total system power. However, this value can also be changed manually if, for example, the peak power of the PV modules in watts is to be taken as the total system power, or if additional producers exist in the system. If this is the case, the value of the total system power can be adjusted manually. To do this, you must select the entry User-defined in the Total system power drop-down list ( ) and then enter the required value in the input field ( ). Configuration is carried out under Cluster Controller > Grid management services > General settings. Figure 3: Manual adjustment of the total system power value (example) 3.2 Selecting the Operating Mode Closed-Loop Control By default, the operating mode open-loop control is selected in the Cluster Controller. For closed-loop control, however, you must select operating mode closed-loop control ( ). Note here that all setpoints for active power limitation are automatically adopted for closed-loop control. Configuration is carried out under Cluster Controller > Grid management services > General settings. Figure 4: Select operating mode closed-loop control Technical Information Wirkleistung_NAP_CC-TI-en-13 5

3 Configuration and Commissioning of Active Power Control SMA Solar Technology AG 3.3 Selecting Measurement Source for System Active Power at the Grid-Connection Point To record the actual value, that is, the measured system active power at the grid-connection point, you must select the measurement source used ( ). The Cluster Controller can receive and process the actual value in three ways: via the SMA Energy Meter (recommended) If there are multiple SMA Energy Meters in the PV system, you must ensure that the SMA Energy Meter intended for active power measurement at the grid-connection point is used by the Cluster Controller as a measurement source for closed-loop control (see user manual of the SMA Cluster Controller). via actual value setpoint through, for example, a SCADA system via Modbus TCP via signal setpoint of a three-phase active power measuring device with a current output for 4 to 20 ma The parameter Sum of inverter performance is required only for test purposes. Configuration is carried out under Cluster Controller > Settings > Grid connection. Figure 5: Select measurement source for the actual value (example) 3.4 Selecting Signal Source for Setpoint The setpoint for limitation of the active power feed-in at the grid-connection point is specified as a % of the total system power. Note that the setpoint, in the case of closed-loop control, always refers to the grid-connection point and not to the inverter. For the setpoint, you must select at least one signal source ( ). If your grid operator requires that the PV system feeds in 0 watts, you must select Manual specification as signal source and enter the value 0 in the input field Active power ( ). Configuration is carried out under Cluster Controller > Grid management services > Active power. Figure 6: Select signal source and enter active power (example) 6 Wirkleistung_NAP_CC-TI-en-13 Technical Information

SMA Solar Technology AG 3 Configuration and Commissioning of Active Power Control 3.5 Configuring the Inverter for Closed-Loop Control In addition to the settings options that relate to the Cluster Controller, you must also adjust the following inverter settings for closed-loop control: Configure the inverter for higher-level closed-loop control Configure behavior of inverters at output value "0%" Configure control speed of inverters Configure the inverter for higher-level closed-loop control In order for the inverters to be able to receive output values from the Cluster Controller in the course of closed-loop control, you must configure the inverters appropriately. To do this, you must select the inverter parameter Operating mode Active power in the system view and then the entry Act. power lim. via PV system ctrl in the drop-down list ( ). Configuration is carried out under "Name of your system" > Settings > Equipment & device control system (Solar Inverters) > Configuration of feed-in management. Figure 7: Configure the inverter for higher-level closed-loop control Configure behavior of inverters at output value "0%" In closed-loop control, the inverters receive the setpoints for power reduction continually as a calculated output value. If the output value "0%" (= complete power reduction), there are two variants via which the inverter can reduce its power to the required 0 watts: Opening the grid relay Blocking only active power feed-in with closed grid relay as before With operating mode closed-loop control, to achieve dynamic regulation of the active power feed-in, only the active power feed-in should be blocked and the grid relay should remain closed. To do this, you must select the inverter parameter Grid disconnection at 0% specification and the entry No in the drop-down list ( ). Note that with a 0-watt closed-loop control in the PV system, there is always a base load (self-consumption) of approx. 25 W x number of inverters in the PV system. This results in minor control deviations. Configuration is carried out under "Name of your system" > Settings > Equipment & device control system (Solar Inverters) > Configuration of feed-in management. Figure 8: Configure behavior of inverters at output value "0%" Configure control speed of inverters For appropriate control speed in the range of 3 to 10 seconds, you must enter the value 200 for the inverter parameter Active power gradient ( ). Configuration is carried out under "Name of your system" > Settings > Equipment & device control system (Solar Inverters) > Inverters. Figure 9: Configure control speed of inverters Technical Information Wirkleistung_NAP_CC-TI-en-13 7

3 Configuration and Commissioning of Active Power Control SMA Solar Technology AG 3.6 Configuring Behavior of Inverters in the Event of No Setpoint or a Failure in Communication (Fallback) Fallback is an operating mode in the Cluster Controller used for grid management services. It controls the feed-in behavior of the inverters in the event of a communication failure. The inverters must fulfill the system requirements (see Section 2, page 4). There are two types of fallback: Fallback in the event of missing or invalid external setpoint Fallback in the event of failure of Speedwire communication between Cluster Controller and SMA inverters You can activate and configure both types independently of each other. Make the following settings in each case: Activate/deactivate fallback ( ) Enter a time period after which, a lack of data transmission from the higher-level component is to be recognized as an error ( ) Enter active power limitation of the inverters in the event of recognized error ( ) SMA recommends that you coordinate activation and configuration of the fallback with the grid operator. Configure fallback in the event of missing or invalid external setpoint Note that, with exclusively manual specification of the active power limitation (signal source Manual specification), fallback configuration is not possible. Configuration is carried out under Cluster Controller > Grid management services > Active power > Fallback settings. Figure 10: Configure fallback for missing or invalid external setpoint (example) Configure fallback in the event of failure of Speedwire communication between Cluster Controller and SMA inverters Configuration is carried out under "Name of your system" > Settings > Equipment & device control system (Solar Inverters) > Act. power lim. via PV system ctrl. Figure 11: Configure fallback in the event of failure of Speedwire communication between Cluster Controller and inverters (example) 3.7 Visualization and Measured Values The Sunny Portal is available for visualization of active power control at the grid-connection point. In Sunny Portal you can quite easily configure your own pages with corresponding diagrams (see user manual "SUNNY PORTAL / SMA CLUSTER CONTROLLER - Creating a Page for the Visualization of the Active Power Feed-in at the Grid-Connection Point" at www.sma-solar.com). In the future, SMA will make additional preconfigured pages available as part of the Sunny Portal updates. In addition, you can use the Modbus interface of the Cluster Controller to visualize measured values using a higher-level communication unit (e.g. a SCADA system) (see the technical description "SMA CLUSTER CONTROLLER Modbus Interface" at www.sma-solar.com). 8 Wirkleistung_NAP_CC-TI-en-13 Technical Information

SMA Solar Technology AG 4 FAQs 4 FAQs Does a reduction in the active power feed-in to 0 watts really mean "0"? Since this is closed-loop control, the active power feed-in at the grid-connection point is always controlled dependent on the consumption or the switching on or off of loads. As a result, oscillations occur in the range of three to ten seconds. This transient response can be influenced by the inverter parameter Active power gradient (see Section 3.5, "Configure control speed of inverters"). Note also that with a 0-watt closed-loop control in the PV system, there is always a base load (self-consumption) of approx. 25 W x number of inverters in the PV system. This results in minor control deviations. How is the actual value of the active power feed-in via the three line conductors measured? With closed-loop control, the cumulative power value over all three line conductors is taken. Can additional producers in the system also be taken into account? Yes - in this case, however, only the total system power can be influenced by the closed-loop control setpoints. Technical Information Wirkleistung_NAP_CC-TI-en-13 9