Storage, Bulk Transfer, and In-Plant Handling of Zeotropic Refrigerant Blends

Similar documents
Diesel-Driven Compressor Torque Pulse Measurement in a Transport Refrigeration Unit

Influence of Cylinder Bore Volume on Pressure Pulsations in a Hermetic Reciprocating Compressor

Experimental Investigation of Sound Pressure Levels Variation During Modulation of a Compressor in a Unit Case Study

Investigation of Torque-Fluctuation Reducer Made of Permanent-Magnets for Screw Compressors

Noise Reduction of Accumulators for R410A Rotary Compressors

A Two Stage-Double Acting Scroll Air Compressor

New Capacity Modulation Algorithm for Linear Compressor

Three Phase Hermetic Protector Application Process

Critical Solution Temperatures for Ten Different Non-CFC Refrigerants with Fourteen Different Lubricants

An Experimental Analysis on the Flow Rate in Scroll Compressors

Determination of the Performance, Leak Scenario, Flammability and Oil Return Characteristics of a Novel R22 Replacement

Development of Scroll Compressor for 16HP VRF System

Small Oil Free Piston Type Compressor For CO2

Transmission Error in Screw Compressor Rotors

Developments in Dry Running Seals for Reciprocating Compressors

CFD Analysis of Oil Discharge Rate in Rotary Compressor

The Performance Optimization of Rolling Piston Compressors Based on CFD Simulation

Development of High Performance 3D Scroll Compressor

Research of the Effectiveness of Use of New Mechanism in Reciprocating Compressors

Research And Development Of Variable-Speed Scroll Compressor

Comparing FEM Transfer Matrix Simulated Compressor Plenum Pressure Pulsations to Measured Pressure Pulsations and to CFD Results

A Large Modern High Speed Reciprocating Compressor

Reduction of Oil Discharge for Rolling Piston Compressor Using CO2 Refrigerant

Theoretical and Experimental Investigation of Compression Loads in Twin Screw Compressor

Elimination of Instability in Modulating Capacity Reciprocating Compressor

Important Parameters for Small, Twin-Screw Refrigeration Compressors

Numerical Simulation and Performance Analysis of Rotary Vane Compressors for Automobile Air Conditioner

A Low Friction Thrust Bearing for Reciprocating Compressors

Development of High Efficiency Swing Compressor for R32 Refrigerant

A Prototype Oil-Less Compressor for the International Space Station Refrigerated Centrifuge

Structural Analysis Of Reciprocating Compressor Manifold

Twin-Screw Compressor Performance and Suitable Lubricants with HFC-134a

Availability Analysis For Optimizing A Vehicle A/C System

Experimental Study Of The Oil Injection Screw Air Compressor

Development of a New Type Cylinder Head for Piston Compressors

Extending the Operation Range of Dry Screw Compressors by Cooling Their Rotors

Practical Stability Performance of Polyvinylether (PVE) With HFC Refrigerants

Scroll Expander for Carbon Dioxide Cycle

Compressor Noise Control

The Design Aspects of Metal- Polymer Bushings in Compressor Applications

A Study on the Starting Characteristics of a Reciprocating Compressor for a Household Refrigerator

Transient Thermal Analysis of Screw Compressors, Part III: Transient Thermal Analysis of a Screw Compressor to Determine Rotor-to-Rotor Clearances

Infinitely Variable Capacity Control

A Novel Automotive Two-Stage A/C Compressor

Noise Reduction in Bus A/C Systems with Screw Compressors Part II

Development of Highly Efficient Compressor Series Driven by IPM Motors

Comparison Between Different Arrangements of Bypass Valves in Scroll Compressors

Effects of Refrigerant Injection on the Scroll Compressor

Discharge Characteristics of an Oil Feeder Pump Using Nozzle Type Fluidic Diodes for a Horizontal Compressor Depending onthe Driving Speed

Oil Circulation Rate in Rotary Compressor: Its Measurement and Factors Affecting the Rate

Development of DC Inverter Scroll Compressor used for Marine Container Refrigeration Unit

Optimum Rotor Geometrical Parameters in Refrigeration Helical Twin Screw Compressors

Theoretical and Experimental Evaluation of the Friction Torque in Compressors with Straddle Bearings

Properties of Polyvinylether (PVE) as a Lubricant for Air Conditioning systems with HFC Refrigerants?Data Update?

A New Device to Measure Instantaneous Swept Volume of Reciprocating Machines/Compressors

Developing a Compact Automotive Scroll Compressor

Numerical Investigation of the Gas Leakage through the Piston-Cylinder Clearance of Reciprocating Compressors

The Characteristics of LGE Linear Oscillating Motor

Performance Improvement of a Reciprocating Air Microcompressor

Application of Manufacturing Simulation for Screw Compressor Rotors

CFD Simulation of a Scroll Compressor Oil Pumping System

A Motor Designer Looks at Positive Temperature Coefficient Resistors

The Effects of the Tribo-Conditions and Antiwear Additives on the Degradation of an Ester Oil and Analyses of Degradation Products

Verification of Flapper Suction-Va1ve Simulation Program

The Digital Simulation Of The Vibration Of Compressor And Pipe System

Design Parameters to Determine Tangential Vibration of Rotary Compressor

A Study On The Oil Supply System Of A Horizontal Rotary Compressor With Vane Utilized For Oil Feeding

Development of a Low Noise Rotary Compressor

Twin Screw Compressor Performance and Its Relationship with Rotor Cutter Blade Shape and Manufacturing Cost

Study of a Novel Compliant Suspension Mechanism in Low Side Type Scroll Compressor

The Reduction of the Noise/Vibration Generated by the Discharge Valve System in Hermetic Compressor for Refrigerator

Numerical and Experimental Research on Vibration Mechanism of Rotary Compressor

The Influence of Discharge Ports on Rotor Contact in Screw Compressors

Stepless Variable Capacity Control

Reducing the Fuel Consumption by Speed Control of the Air Conditioning Compressor

Transient Modeling of Vapor Compression Refrigeration Systems Using Measured Compressor COP

Experimental Investigation of Damping Coefficient for Compressor Reed Valves

Development of Rotary Compressor for Highefficiency CO2 Heat-pump Hot-Water Supply System

Polybasic Esters: A Novel Class of Synthetic Lubricants Designed for Use in HFC Compressors

Synthesis of Optimal Batch Distillation Sequences

Evaluation of methods to decrease the discharge temperature of R32 scroll compressor

Lubrication Analysis of Journal Bearings in R410A Rotary Compressor

On the Classification of Compressor,Pump or Engine Designs Using Generalized Linkages

Air Piping System Design for Reciprocating Compressors

Dr. Jim Henry, P.E. Professor of Engineering University of Tennessee at Chattanooga 615 McCallie Avenue Chattanooga, TN Dr.

Forces Analysis of Rotary Vane Compressor for Automobile Air Conditioning System

Reciprocating Air Microcompressor

Product Loss During Retail Motor Fuel Dispenser Inspection

Automotive Air Conditioning Manifold Gauge Sets

Opteon XP40. Thermodynamic Properties

Linear Compressor Without Position Controller

Models

On-Line Process Analyzers: Potential Uses and Applications

Development and Application of a Software Package for the Design of Twin Screw Compressors

Spool Seal Design and Testing for the Spool Compressor

Optimization of Suction Muffler Using Taguchi s DOE Method

Application of Trunk Piston Labyrinth Compressors in Refrigeration and Heat Pump Cycles

HCFCs Refrigeration Retrofit Guidelines

Waterous S100 Single Stage Pump

The Selection Of Screw Rotor Geometry With Compressor Speed As A Design Variable

Transcription:

Purdue University Purdue epubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 1996 Storage, Bulk Transfer, and InPlant Handling of Zeotropic Refrigerant Blends P. Pieczarka Elf Atochem North America J. Lavelle Elf Atochem North America Follow this and additional works at: http://docs.lib.purdue.edu/iracc Pieczarka, P. and Lavelle, J., "Storage, Bulk Transfer, and InPlant Handling of Zeotropic Refrigerant Blends" (1996). International Refrigeration and Air Conditioning Conference. Paper 39. http://docs.lib.purdue.edu/iracc/39 This document has been made available through Purdue epubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CDROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

STORAGE, BULK TRANSFER, AND INPLANT HANDLING OF ZEOTROPIC REFRIGERANT BLENDS ABSTRACT Patrick Pieczarka, James Lavelle. Elf Atochem North America 2 Market St. Philadelphia, P A 1913 The refrigeration and air conditioning industries are moving from the use of single component and azeotropic refrigerants to zeotropic blends with varying temperature glides. This paper will discuss the potential impact on zeotropic blend composition from various OEM plant operations, such as bulk delivery, storage system design, inplant handling, and refrigeration equipment charging. We will examine delivery truck and bulk tank operations using a high glide HCF refrigerant, R47C, as an example. INTRODUCTION Original Equipment Manufacturers (OEMs) who build self contained air conditioning and refrigeration equipment usually charge their equipment with refrigerant while it is still on the production line. This charging operation is accomplished by use of a calibrated charging station which is fed liquid refrigerant from a bulk storage tank, often connected by long piping runs through the plant. Similarly, refrigerant repacking operations take refrigerant from bulk storage tanks and fill smaller packages for service use (e.g. 3 lb. cylinders or 2 lb. cans). With the phaseout of CFCs at the end of 1995, and future restrictions on the use of R22, the refrigeration and air conditioning industries have been evaluating the use of zeotropic refrigerant blends for use in new equipment. Traditional storage and bulk transfer operations could potentially affect the composition of zeotropic blends by allowing fractionation to occur. We will review basic bulk transfer operations, look at the composition of a high glide refrigerant blend during the process of tank truck loading, filling a bulk storage tank for the first time, and subsequent cycles of unloading the storage tank, and refilling by tank truck using vapor equalization. Recommendations will be given on avoiding fractionation during these operations. REFRIGERANT TRANSFER OPERATIONS AND STORAGE 1. Bulk Delivery by Tank Truck High pressure refrigerant delivery trailers usually resemble a small, cylindrical bulk storage tank on wheels. The pressure rating, safety device configuration, and testing schedule are all determined by Department of Transportation (DOT) regulations. 17

The procedure for bulk delivery by tank truck consists of the following steps: The trailer is loaded up to 9% liquid full, usually to a round number such as 4, lbs (for R12 deliveries). We used 35, lbs for R47C because of the lower liquid density. Unloading is performed by using a liquid pump, which is often permanently attached to the trailer in a compartment underneath. This pump pulls liquid from the bottom of the truck's tank and delivers it via the liquid hose to the storage tank (see Figure 1). The top of the tank and truck are connected by another hose to allow refrigerant vapor to move from one vessel to the other. This will avoid a buildup of pressure in the storage tank which would reduce or stop product flow through the liquid line. A sight glass is used in the liquid line to tell when no more liquid is being transferred. It is possible to have a small amount of liquid left in the truck at this point. Evaluation of the Delivery of Zeotropic Blends Using mathematical models we analyzed the composition ofr47c as it was loaded into a tank truck. We then investigated the shift in composition assuming this tank truck was unloaded into an empty, evacuated storage tank, such as would happen in a "first delivery." In this case there is no vapor equalization. Refrigerant will vaporize from the liquid phase to fill the vapor space above. This vapor will be at a different composition from the liquid, and therefore the liquid will change composition. For 47C, the vapor will contain extra R32 and R125, and less R134a. NOTE: This mathematical experiment will show the composition of R47C deviating out of specification. Recommendations will be made on how to avoid this for actual commercial deliveries. Individual plants should be reviewed on a case by case basis. Table 1: Experimental Parameters and Results for Initial Tank Fill with RA47C Temperature: 7 F Initial Liquid Composition 47C: 32/1251134a 23/25/52 weight% Tank Truck Storage Tank Volume Initial Truck Fill Liquid Composition: First Transfer to Tank Liquid Composition: 5, gallons 35, lbs 47C (85% liquid full) 22.93/24.95/52.12 33, lbs (1% liquid+ vapor) 6,565 gallons 33, lbs 47C (62% liquid full) 22.29/24.51/53.2 18

Results of the Initial Fill Study Table 1 and Figure 2 show the resulting liquid compositions from filling of a tank truck and delivering that load to an empty storage tank. Since tank trucks are filled almost all the way with liquid there is little fractionation of the blend to fill the vapor space. In this example, the blend delivered to the tank fractionated in two ways: when the liquid level in the truck was reduced, more product had to boil to fill the vapor space, and the liquid delivered to the storage tank had to vaporize to fill the tank's vapor space. There are several strategies which will avoid this composition shift during first deliveries, including breaking the tank vacuum with R47C (flashed liquid), then using vapor equalization during delivery, as we will demonstrate in the next section. 2. Use of Product from the Storage Tank and Refilling by Tank Truck Analysis of Composition Shift Figure 3 shows the shift in composition of R47C liquid as product is removed from the storage tank, such as would occur during normal plant operations. The drop in liquid level in the tank means that more product vaporization must occur to fill the vapor space. In any storage container fractionation will alter the liquid composition close to when the container runs empty. In most OEM plants the tank is refilled before running empty. Bulk deliveries will occur using VAPOR EQUALIZATION. Figure 4 shows the tank truck liquid composition and the storage tank liquid composition during transfer of 33, lbs of R47C from a truck to a tank. By using vapor equalization there is no need to vaporize liquid 47C from the truck in order to fill the volume left behind in the truck. The liquid product entering the storage tank remains at essentially the same composition (original specification) throughout the transfer process. Leakage Leakage of zeotropic blends from the vapor space can cause additional composition shift. The vapor which escapes the storage system will contain a higher proportion of R32 and R125 compared to R134a. Therefore, the liquid which must vaporize to replace the leaked product will remove more of the higher pressure refrigerants from the liquid. Overall the refrigerant blend will shift in composition towards more R 134a. Recommendations Add vapor to tank for first delivery. Always use vapor equalization for bulk deliveries. Review the laboratory analysis for blend composition on each bulk delivery to ensure product is on spec. If possible, check the composition of the storage tank and at the charging stations frequently to confirm proper blend compositions. Review any blend adjustments with your supplier. Leak check storage facilities often and repair any leaks promptly. 19

3. InPlant Transfer and Charging Stations Transfer pumps, feed lines, and charging stations are designed to operate best when filled with liquid refrigerant (no refrigerant vapor present). Vapor can cause inefficient pump operation, reduced flow of product, and incorrect charge size delivered to the system being charged. These problems associated with vapor refrigerant in the lines and pumps will outweigh any problems associated with the fractionation which would occur. To avoid any flashing of refrigerant in the handling lines and transfer pumps, we recommend the following: Use pumps specifically designed for pumping liquid refrigerant under pressure Insulate piping to reduce flashing near hot locations Locate the charging stations as close to the tank as possible (minimize length of piping) Charging stations should have receivers which will hold liquid refrigerant for the charging piston, and the receivers should be maintained liquid full to reduce chance of fractionation. CONCLUSIONS 1. Emptying of bulk delivery and storage tanks will cause fractionation of zeotropic refrigerant blends. The extent of composition change should be evaluated for the specific blend/container combination to establish minimum inventory levels. 2. Vapor equalization on bulk deliveries will eliminate fractionation of the liquid refrigerant being delivered. Repeated bulk deliveries should not cause a progressive change in the composition of a zeotropic blend. 3. Product compositions can be adjusted to maintain proper blend compositions within the storage tank. Frequent monitoring of tank and charging station compositions is recommended. 4. No changes to inplant delivery or charging systems is needed when using zeotropic blends. It is important to avoid vaporization of refrigerant at any point downstream of the storage tank for smooth production line operation, not just to avoid fractionation. llo

Figure 1: Bulk Delivery Diagram @ ( i == ;? Figure 2: Initial Fill Compositions R47C in Truck and Tank 2.,~7C As Formulated: ~ 1.~ t: : : :: : : ::: :: 23 l o.: F : : :: 32 I 125 I l34a :: : % I 25 % I 52 % E ~.5 T o 1 T. 1i 1~5 +::::::::::::::::::::::::::::::::::::::::::: :::::: Q) a.. ~2 +1++i.!... 32 c 125 Component 134a Liquid wt% Truck Liquid wt% Tank Ill

"C Figure 3: Composition of R47C Liquid As Storage Tank is Emptied s 2...,~~'""'"""'~.!!! ~~ ~ ~~~~~~~~~~~~~~~=~ ~ E 1 " 5 f C? = ::::; ::: ~ ::: ::_::::.4""7.,_C:;_A~s~F""'o=~'u.la::o:t::ced,: ~ 1 f 321125/134a I ~.5 f _ 23% I 25% I 52 % E... f ~ ~~"'=~~""!!!~ f "C.! 2 (1:1 '3... E 1.5 It 1 < U) E.5.; Cl) (,)... ;.5 ~ 1 i5 ~ 1.5 Figure 4: Composition During Delivery _ ~Tank Truck Truck and Tank, Vapor Equalization ~ ~ ~ Tank i 5 1 15 2 25 Pounds Transferred (1 ) ' CAs ormulated: 32 I 125 I 134a 23 % I 25 % I 52 % v _,1 v 3 35 ::::. 134a 25 32 112