VB-9313 Series. Application. Features. Applicable Literature

Similar documents
VB-9313 Series. Application. Features. Applicable Literature

VB-9213 Series. Application. Features. Applicable Literature

VB-9323 Series. Application. Features. Applicable Literature. 2-1/2" to 6" 125 Lb. Flanged Three-Way Diverting Valves General Instructions

AV-430. Application. Features. Applicable Literature. Valve Linkage for Pneumatic Actuators General Instructions

AV-497. Application. Features. Valve Linkage for MK-6811 and MK-6911 General Instructions

AV-401. Application. Features. Applicable Literature. Pneumatic Actuator Valve Linkage Kit General Instructions

VB-8000 Series VB-9313 Series. Selection Guide. Applications. Applicable Literature. Selection Guide Contents. Valve and Actuator Selection Procedure

Erie VT/VS PopTop Series Two Position Spring Return Valves

VBB/VBS Series Ball Valve Assemblies

V5013B,C,F Three-Way Mixing and Diverting Valves

AM-751, AM-752, AM-753, AM-754, AM-755. Applications. Applicable Literature

TS , -850 Series TS , -850 Series TS-57031, TS

CP-8551 & CP Application. Features. Applicable Literature. Electronic to Pneumatic Transducers General Instructions

Selection Guide. Vx-7000 & Vx-9000 Series Mx4x-6xxx & Mx4x-7xxx Series. Globe Valve Assemblies. Actuator/Linkage Assemblies

MK-6600 Series, MK-6800 Series, and MK-6911

MS Application. Features. Proportional Valve Actuator General Instructions

CP-9301 CP Application. Features. Applicable Literature. Electronic Actuator Drives General Instructions

453X Series. Application. Features. Two-Position Damper Actuator General Instructions

Erie VM PopTop Series Modulating Valves

3-Way Linked Globe Valve Assemblies with Linear Series Actuators

VB-7000 Series 1/2 to 2 Globe Valves

599 Series Zone Valve Bodies:

AV-611. Application. Applicable Literature. Schneider Electric DuraDrive Globe Valve Linkage General Instructions

AK Application. Features. Applicable Literature. Positive Positioner Pneumatic Relay General Instructions

MF-22xx3. Application. Features. Floating Valve Actuator General Instructions

THC-2, THC-3, THCR-4, THCR-5. Enthalpy Control. General Instructions APPLICATION SPECIFICATIONS. ACCESSORIES None

VVP45 and VXP45 Series Two-port and Three-port Seat Valves ANSI Class 250 Short-stroke Valves

VZ*19* VZ219E, VZ319E, VZ419E VZ219C, VZ319C, VZ419C

T500 Series. Applications. Features. Applicable Literature. Non-Digital, On/Off Thermostat General Instructions

Electronic Globe Valve Guide Specifications

VG2000 Series Cast Iron Flanged Globe Valves

V5011N Two-Way Threaded Globe Valve

V5011N Two-Way Threaded Globe Valve

VGF Flanged Globe Valves

Selection Guide. Vx-2x13-5xx-9-xx Series Vx-2x13-8xx-9-xx Series VB-2x xx Series. Schneider Electric Ball Valve Assemblies

VA, VF, and VS Series Direct Mounted Globe Valve Assemblies. Application. Features

MAx-305 & MAx-318 Series MAx-405 Through MAx-419 Series Two-Position Actuators

SLC-811X Series. Single Loop Proportional Temperature Controller General Instructions APPLICATION SPECIFICATIONS

Components of Hydronic Systems

3. Installation and Commissioning 4. Maintenance 5. Spares

MX4X-6XXX-20X Series MX4X-7XXX-20X Series

MA-5200 Series MA-5300 Series

CP-8301-xxx Series. Application. Features. Applicable Literature. 1 to 15 Vdc Input Electronic Actuator Drive General Instructions

Features Globe Valve 2-Way & 3-Way Assembly Features:

ACTIVAL Three-Way Ball Valve with Threaded-End Connection

MP-5400 Series. Application. Features. Applicable Literature. Electronic Positive Positioning Hydraulic Actuator General Instructions

3-way 1/2-2 Globe Valves

TK-6024, TK-6124, TK-8024, TK-8124

FEATURES APPLICATION PRODUCT DATA

AV-608 Linkage Adapter Kit

MF4E MF4E

VG4000 Series. High-Capacity/High-Closeoff Electric Zone Valves

High Pressure 2-way 2 1/2-6 Globe Valves

Leakage rate. Valve body. U.S. Registered Trademark EN0B-0308GE51 R1002 Copyright 2002 Honeywell Inc. All rights reserved

Two-port and three-port small valves PN16, ANSI Class 250

V5832A/5833A,C SMALL LINEAR VALVES PN16 FOR MODULATING AND ON/OFF-CONTROL SPECIFICATIONS

3-Way Mixing and Sequencing Globe Valves, Flared (5/8 in. O.D.) with Electric, Hydraulic, and Pneumatic Actuators

2-WAY AND 3-WAY MOTORIZED VALVES FOR STEAM, VACUUM AND HOT WATER APPLICATIONS

Electro Controls. Valves / Linkages WattsIndustries.co.uk

MC-351, 421, 431, MC-4311

Flowrite VF 599 Series Two-Way Valves 2-1/2 to 6-inch Flanged Iron Body

Flowrite VF 599 Series Two-Way Valves 2-1/2 to 6-inch Flanged Iron Body

Booster Pump Control Valve

VBN2, VBN3 Control Ball Valves With Threaded Connections

MF Series MS Series

G765, 3-Way, Mixing Flanged Globe Valve

Flowrite 599 Series Three-Way Valves 1/2 to 2-inch Bronze Body

Flowrite 599 Series Three-Way Valves 1/2 to 2-inch Bronze Body

2-port and 3-port valves with T-bypass PN 16

CP (Vdc) CP (Milliamp) CP (Slidewire)

2211 Series. Application. Features. One-Pipe Pneumatic Room Thermostats General Instructions SPECIFICATIONS

Installation, Operation and Maintenance Instructions

Booster Pump Control Valve

Hydra Series Choke Valve **Patent Pending

Flowrite VF 599 Series Three-Way Valves 1/2 to 2-inch Bronze Body

LF24-SR US TF24-SR US TFX24 US LF24 US. B3 B Three-way Characterized Control Valve, Chrome Plated Brass Ball and Brass Stem

V5822A / 5823A,C SMALL LINEAR VALVES PN16 FOR MODULATING AND ON/OFF-CONTROL SPECIFICATIONS GENERAL

599 Series Zone Valve Bodies:

G7 (S) 3-way Mixing Flanged Globe Valve, Bronze or Stainless Steel Trim

Flowrite VF 599 Series Two-Way Valves 2-1/2 to 6-inch Flanged Iron Body

G765, 3-Way, Mixing Flanged Globe Valve

TS Series TS Series

Fisher CAV4 Control Valve

Flowrite 599 Series High Pressure Close-Off 2-Way Valves, 2-1/2 to 6-Inch, Flanged Iron Body, ANSI Classes 125 & 250

Specifications. Body Materials: Carbon steel, stainless steel, chrome-moly steel, other castable alloys

VG7000 Series Bronze Control Valves

08.20 VIC -300 MasterSeal Butterfly Valves

Fisher CAV4 Control Valve

V5013N Three-Way Threaded Globe Valve

V5013N Three-Way Threaded Globe Valve

3-port seat valves PN6 with flanged connection

TEMPERATURE REGULATORS W91/W94 Series

B2/B3 Series Characterized Control Valve, Non-Spring Return Actuator

CONTROL EQUIPMENT STAZ-16, STBZ-16

G3 (D) 3-way Globe Valve, Bronze Trim

3-port seat valves PN10 with flanged connection

D I S T R I B U T E D V A L V E S. NAVCO Series E Resilient Seat Butterfly Valve NAVCO

MP-5200 Series. Application. Features. Applicable Literature. Electronic Hydraulic Actuator General Instructions

Modulating Water Valves and Bulb Wells

3-port seat valves, external thread, PN16

Transcription:

V-9313 Series 2-1/2" and 3" Screwed NPT 2-1/2" to 6" 125 Lb. Flanged Three-Way Mixing s General Instructions pplication V-9313 series three-way mixing valves control hot or chilled water in heating or air conditioning systems. These valves must be piped with two inlets ( and ports) and one outlet ( port). They are used for twoposition or proportional control applications. assemblies require an actuator and a valve linkage that must be purchased separately. Danger: Do not use for combustible gas applications. The V-9313 series valve packings are not rated for combustible gas applications, and if used in these applications, gas leaks and explosions will result. Features Typical of V-9313-0-4-P 2-1/2" and 3" sizes 2-1/2" to 6". 250 psig pressure rating per NSI Standards (16.15 1985) for screwed cast bronze bodies. 125 psig pressure rating per NSI Standards (16.1 1993) for flanged cast iron bodies. Spring-loaded TFE packing. pplicable Literature Products Catalog, F-27384 Cross-Reference Guide, F-23638 Reference Manual, F-21683 pplication Manual, F-21335 Selection Guide, F-26094 Control Sizing, F-13755 Selection Chart for Water, F-11080 EN-205 Water System Guidelines, F-26080 Typical of V-9313-0-5-P 2-1/2" to 6" Printed in U.S.. 1/10 Copyright 2010 Schneider Electric ll Rights Reserved. F-24393-3

SPECIFICTIONS Specifications Table-1 Specifications/Models. ody Series V-9313-0-4-P ody Series V-9313-0-5-P Service Chilled or Hot Water Flow Characteristics (Figure-1) Mixing Sizes 2-1/2" and 3" 2-1/2" to 6" Type of End Fitting Screwed NPT 125 lb. Flanged ody ronze Iron Seat ronze Stem Stainless Steel Materials Plug rass Packing Spring-loaded TFE Disc None NSI Pressure Class (Figure-2) 250 (up to 400 psig below 150 F) 125 lb. Flanged (up to 200 psig below 150 F) llowable Control Media Temperature 40 to 300 F (4 to 149 C) llowable Differential Pressure for Water* 35 psi (241 kpa) Max. for Normal Life (refer to df Cavitation Limitations on Pressure Drop on page 6) Size C v Rating k vs Rating** Complete ody Part Number 2-1/2" 67 58 V-9313-0-4-12 Not vailable 74 64 Not vailable V-9313-0-5-12 3" 91 79 V-9313-0-4-13 Not vailable 101 87 V-9313-0-5-13 4" 170 147 V-9313-0-5-14 Not vailable 5" 290 251 V-9313-0-5-15 6" 390 337 V-9313-0-5-16 *Maximum recommended differential pressure in open position. Do not exceed recommended differential pressure (pressure drop) or integrity of parts may be affected. Exceeding maximum recommended differential pressure voids product warranty. **k vs = m 3 /h (ΔP = 100 kpa) C v = k vs x 1.156 Close-off Pressure Rating The close-off pressure rating is dependent on the size of the valve, valve linkage, and actuator. Consult the appropriate valve linkage general instruction sheet for the close-off ratings. Spring Return Position of ssembly For a valve assembly (valve, linkage, and actuator) to have a spring return position, the actuator must be of the spring return type. See Table-2 for spring return position of valve assemblies. 2 Copyright 2010 Schneider Electric ll Rights Reserved. F-24393-3

Table-2 Required Compatible ctuators/linkages. ctuator Series Required Linkage 2-1/2" to 4" s *Stem Up = Flow port to port. Stem Down = Flow port to port. 5" & 6" s Spring Return Position* M-318, M-418, M-419 V-395 Stem Up or Down MC-351, MC-431, MC-4311, MC5-4311 V-396 or V-352 V-352 MF-63103, MF-63123 V-672 None MK-6801, MK-6811, MK-6821 V-495 MK-8801, MK-8811, MK-8821 V-496 Stem Up MK-8901, MK-8911, MK-8921 V-496 MM-400, MMR-400 V-630 or None MM-500, MMR-500 V-630-30 Stem Up or Down MP-361, MP-461-600, MP-465, MP5-4651 Stem Down V-395 MP-371, MP-471-600, MP-475, MP5-4751 Stem Up MP-381, MP-382, MP-481-600, MP-485, MP-486, MP-4851, MP5-4851 V-396 or V-352 V-352 MP-9713, MP-9750 V-357 (4" only) V-357 None MP-9810 V-358 Flow Characteristics Three-way mixing valves are designed so that the flow from either of the inlet ports to the outlet is approximately linear, which means the total flow from the outlet is almost constant over the stroke of the valve stem. See Figure-1 for typical flow characteristics of V-9313 series valve bodies. 100% Rated Flow 90% 80% 70% 60% 50% 40% 30% 20% 10% 0% "" Port "" Port 0% Stem In 20% 40% Stroke 60% 80% Stem Out 100% Figure-1 Typical Flow Characteristics. Rangeability Rangeability is the ratio of rated flow to the minimum controllable flow through a valve. For mixing valves, control begins as soon as plug displacement allows flow. Thus, three-way valve rangeability normally exceeds 500:1, which is the reciprocal of 0.2% nominal leakage. F-24393-3 Copyright 2010 Schneider Electric ll Rights Reserved. 3

Temperature/Pressure Ratings See Figure-2 for temperature and pressure ratings. Consult the appropriate valve linkage general instruction sheet for the effect of valve body ambient temperatures on specific actuators. Ratings conform with published values and disclaimer. V-9313-0-4-P (Screwed Cast ronze ody) Standards: NSI 16.15 1985 Materials: STM 584-93b: UNS C83450, UNS C83600, or UNS C84400 V-9313-0-5-P (Flanged Cast Iron ody) Standards: NSI 16.1 1993 Materials: STM 126-93 Class 165 psig (1138 kpa) 321 psig (2218 kpa) 300 (149) Temperature F ( C) 250 (121) 200 (93) 150 (65) 100 (38) 50 (10) Maximum Fluid Temperature 300 F (149 C) Minimum Fluid Temperature 40 F (4 C) Maximum Fluid Temperature 281 F (138 C) V-9313-0-5-P V-9313-0-4-P 50 (345) 100 (689) 150 (1034) 200 (1379) 250 (1724) 300 (2068) Pressure psig (kpa) 350 (2458) 400 (2758) Figure-2 Temperature and Pressure Ratings for V-9313 Series odies. 4 Copyright 2010 Schneider Electric ll Rights Reserved. F-24393-3

VLVE SIZING ND SELECTION Water ody Part Number C v Rating Two-position Two-position control valves are normally selected line size to keep pressure drop at a minimum. If it is desirable to reduce the valve below line size, then 10% of available pressure (that is, the pump pressure differential available between supply and return mains with design flow at the valve location) is normally used to select the valve. Proportional to ypass Flow Proportional mixing valves used to bypass flow (Figure-6) are piped on the outlet side of the load to throttle the water flow through the load and therefore control heat output of the load. These valves are usually selected to take a pressure drop equal to at least 50% of the available pressure. s available pressure is often difficult to calculate, the normal procedure is to select the valve using a pressure drop at least equal to the drop in the coil or other load being controlled (except where small booster pumps are used) with a minimum recommended pressure drop of 5 psi (34 kpa). When the design temperature drop is less than 60 F (33 C) for conventional heating systems, higher pressure drops across the valve are needed for good results (Table-3). Table-3 Conventional Heating System. Design Temperature Load Drop F ( C) 60 (33) or More 50% 1 x Load Drop 40 (22) 66% 2 x Load Drop 20 (11) 75% 3 x Load Drop *Recommended minimum pressure drop = 5 psi (34 kpa). Secondary Circuits with Small ooster Pumps: 50% of available pressure difference (equal to the drop through load, or 50% of booster pump head). Proportional to lend Water Flows Proportional valves used to blend two water flows (Figure-7 and Figure-8) control the heat output by varying the water temperature to the load at constant flow. These valves do not require high pressure drops for good control results. They can be sized for a pressure drop of 20% of the available pressure or equal to 25% of the pressure drop through the load at full flow. Water Table See Table-4 for water capacity of V-9313 series valves. C v Equation Recommended Pressure Drop* (% of vailable Pressure) Table-4 Water Capacity in Gallons Per Minute for V-9313 Series. Differential Pressure (ΔP in psi) Where: C v = Coefficient of flow GPM = U.S. gallons per minute (60 F, 15.6 C) ΔP = Differential pressure in psi (pressure drop) Multiplier on Load Drop 1 2 3 4 5 6 7 8 9 10 15 20 25 30 35 V-9313-0-4-12 67 67 95 116 134 150 164 177 190 201 212 259 300 335 367 396 V-9313-0-5-12 74 74 105 128 148 165 181 196 209 222 234 287 331 370 405 438 V-9313-0-4-13 91 91 129 158 182 203 223 241 257 273 288 352 407 455 498 538 V-9313-0-5-13 101 101 143 175 202 226 247 267 286 303 319 391 452 505 553 598 V-9313-0-5-14 170 170 240 294 340 380 416 450 481 510 538 658 760 850 931 1006 V-9313-0-5-15 290 290 410 502 580 648 710 767 820 870 917 1123 1297 1450 1588 1716 V-9313-0-5-16 390 390 552 675 780 872 955 1032 1103 1170 1233 1510 1744 1950 2136 2307 C v = GPM ΔP ΔP= GPM 2 ( ) GPM = C v ΔP C v F-24393-3 Copyright 2010 Schneider Electric ll Rights Reserved. 5

Cavitation Limitations on Pressure Drop valve selected with too high a pressure drop can cause erosion of discs and/or wire drawing of the seat. In addition, cavitation can cause noise, damage to the valve trim (and possibly the body), and choke the flow through the valve. Do not exceed the maximum differential pressure (pressure drop) for the valve selected. The following formula can be used on higher temperature water systems, where cavitation could be a problem, to estimate the maximum allowable pressure drop across the valve: Pm = 0.5 (P 1 Pv) Where: Pm = Maximum allowable pressure drop P 1 = bsolute inlet pressure (psia) Pv = bsolute vapor pressure (refer to Table-5) N O T E dd 14.7 psi to gauge supply pressure to obtain absolute pressure value. For example, if a valve is controlling 200 F water at an inlet pressure of 18 psig, the maximum pressure drop allowable would be: Pm = 0.5 [(18 + 14.7) 11.53] = 10.6 psi (Vapor pressure of 200 F water is 11.53 psi.) If the pressure drop for this valve is less than 10.6 psi, cavitation should not be a problem. Systems where cavitation is shown to be a problem can sometimes be redesigned to provide lower inlet velocities. s having harder seat materials should be furnished if inlet velocities cannot be lowered. Table-5 Vapor Pressure of Water Table. Water Temp. ( F) Vapor Pressure (psig) Water Temp. ( F) Vapor Pressure (psig) Water Temp. ( F) Vapor Pressure (psig) Water Temp. ( F) Vapor Pressure (psig) 40 0.12 90 0.70 140 2.89 190 9.34 50 0.18 100 0.95 150 3.72 200 11.53 60 0.26 110 1.28 160 4.74 210 14.12 70 0.36 120 1.69 170 5.99 220 17.19 80 0.51 130 2.22 180 7.51 230 20.78 dditional Sizing Information For additional valve sizing information, see: C-28 Control Sizing, F-13755 Selection Chart Water, F-11080 Sizing Slide Rule, TOOL-150 6 Copyright 2010 Schneider Electric ll Rights Reserved. F-24393-3

INSTLLTION Inspection Requirements Mounting Inspect the package for damage. If damaged, notify the appropriate carrier immediately. If undamaged, open the package and inspect the device for obvious damage. Return damaged products. Tools (not provided): Pipe wrenches Training: Installer must be a qualified, experienced technician ppropriate accessories Caution: Install the valve with the flow in the direction of the flow arrows ( and ports are inlets and port is the outlet). Do not exceed the ratings of the device. void locations where excessive moisture, corrosive fumes, or vibration are present. 1. The valve should be mounted in a weather-protected area in a location that is within the ambient limits of the actuator. When selecting a location, allow sufficient room for valve linkage, actuator, and other accessories and for service of the product. 2. The preferred mounting position for the valve is with the valve stem vertical above the valve body. void mounting the valve so that the valve stem is below horizontal. 3. The valves must be piped with two inlets ( and ports) and one outlet ( port). Screwed odies The V-9313-0-4-P series screwed valve bodies conform to merican Standard Taper Pipe Threads (NPT). 1. pply pipe dope sparingly to all but the last two threads of a properly threaded, reamed, and cleaned pipe. Make sure that pipe chips, scale, etc. do not get into the pipe since this material may lodge in the valve seat and prevent proper closing and opening of the valve. 2. Start the joint by hand screwing the pipe into the valve. If the thread engagement feels right, turn the pipe by hand as far as it will go. 3. Use a pipe wrench to fully tighten the valve to the pipe. Do not over tighten or strip threads. See Table-6 and Figure-3 for the normal engagement length of the threads. Figure-4 shows a means of tightening the pipe so that the valve is not twisted or crushed. Table-6 Normal Thread Engagement etween Male Pipe Thread and ody. Size Inches (NPT) Normal Engagement Size Inches (NPT) Normal Engagement 2-1/2" 15/16" 3" 1" Right Wrong Pipe threads too long. Pipe jims seat. Figure-3 Normal Thread Engagement. F-24393-3 Copyright 2010 Schneider Electric ll Rights Reserved. 7

ssembly Tighten pipe using this pipe wrench. Use pipe wrench to prevent valve from turning. Figure-4 Installation of Screwed End s. Flanged odies The V-9313-0-5-P series flanged valve bodies conform to merican Standard 125 Lb. Cast Iron Pipe Flanges. The companion flanges (not provided) should be the same specification as the valve. The 125 lb. flanges have plain flat faces and should not be bolted to a raised faced flange. 1. ll parts should be clean to assure the best results. 2. The pipe with the companion flanges installed should be properly supported and aligned. e sure the companion flange is flush with the face of the valve body flange and lined up squarely. 3. Use a gasket material (not provided) that is recommended for the medium being handled. Caution: Do not apply pipe dope to the valve flange, gasket, or companion flange. 4. See Figure-5 for flange and flange bolt details. Figure-5 also shows the proper way a flanged valve should be mounted. ody Gasket Companion Flange Figure-5 Installation of Flanged End s. 8 Copyright 2010 Schneider Electric ll Rights Reserved. F-24393-3

TYPICL PIPING ll piping must comply with local codes and ordinances. Refer to Figure-6 through Figure-8 for typical piping. Coil ypass ypass Return Coil Return Supply Stem down flow through coil. Stem up flow through coil bypass. Supply Stem up flow through coil. Stem down flow through coil bypass. Figure-6 Typical Piping for Control of Heating or Cooling Coil. System Pump Supply ypass Return oiler Figure-7 Typical oiler Hot Water Reset. Coil alancing Cock Secondary Pump From Other Zones To Other Zones Return alancing Cock Supply Figure-8 Typical Primary-Secondary Piping. F-24393-3 Copyright 2010 Schneider Electric ll Rights Reserved. 9

CHECKOUT 1. Make sure the valve stem operates freely before installing the valve linkage and the actuator. 2. If the stem does not operate freely, it may indicate that the valve was twisted or crushed during installation or that the stem was bent by rough handling. These conditions may require that the valve be replaced. 3. fter the piping is under pressure, check the valve body and the connections for leaks. 4. fter the valve linkage and the actuator are installed, check their operation. a. Drive the actuator and run the valve to the stem down position. Make sure the linkage and valve stem move freely. t the stem down position, the valve should shut off the port. b. Drive the actuator and valve to the stem up position. gain, the valve stem and linkage should operate smoothly. t the stem up position, the valve should shut off the port. MINTENNCE Regular maintenance of the total system is recommended to assure sustained performance. See Table-7 for maintenance kit part numbers. Table-7 Maintenance Kits for V-9313 s. ody Part Number Replacement Packing ssembly Repair Kit* V-9313-0-4-12 RY-931-12 V-9313-0-4-13 RY-931-13 V-9313-0-5-12 RY-931-12 V-9313-0-5-13 Y-651-1 RY-931-13 V-9313-0-5-14 RY-931-14 V-9313-0-5-15 RY-931-15 V-9313-0-5-16 RY-931-16 *Kit includes replacement packing and stem & plug assembly. Water System Maintenance ll heating and cooling systems are susceptible to valve and system problems caused by improper water treatment and system storage procedures. These guidelines are provided to help avoid valve and water system problems resulting from improperly treated water or storage procedures in cooling and hot water systems, and to obtain maximum life from Schneider Electric valves. Durability of valve stems and packings is dependent on maintaining non-damaging water conditions. Inadequate water treatment or filtration, not in accordance with chemical supplier/shre handbook recommendations, can result in corrosion, scale, and abrasive particle formation. Scale and particulates can result in stem and packing scratches and can adversely affect packing life and other parts of the hydronic system. To maintain non-damaging conditions, follow these guidelines: Clean the system prior to start up. Use a nitrite or molybdate-based treatment program. Use filtration equipment where needed. Properly store off-line systems and monitor water treatment results using corrosion test coupons. Follow the advice of a water treatment professional. Consult EN-205 for further details. 10 Copyright 2010 Schneider Electric ll Rights Reserved. F-24393-3

DIMENSIONL DT Part Number Size Table-8 Dimensions for V-9313 Series s (Figure-9 and Figure-10). C V-9313-0-4-12 2-1/2" 8-1/2 (216) 4-5/8 (118) 4-1/4 (108) Dimensions in Inches (mm) D (Stem Down) E (Stroke) V-9313-0-5-12 2-1/2" 8-1/2 (216) 5-3/8 (137) 3-1/2 (89) 7/8 (22) 7 (178) V-9313-0-5-13 3" 9-1/2 (241) 6-3/8 (162) 3-3/4 (95) 1-5/8 (41) 7-1/2 (191) F 3-7/8 (98) V-9313-0-4-13 3" 9-1/2 (241) 5 (127) 4-3/4 (121) 4-5/8 (118) V-9313-0-5-14 4" 11-1/2 (292) 8-1/2 (216) 4-1/2 (114) 9 (229) V-9313-0-5-15 5" 13 (330) 8-3/4 (222) 5 (127) 10-1/8 (257) 1-3/4 (45) V-9313-0-5-16 6" 14 (356) 9-3/4 (248) 5-7/8 (149) 11 (279) E 1/2" - 20 Threads 1-1/4" - 16 Threads D C Flow Flow Flow F Figure-9 Typical of V-9313-0-4-P, 2-1/2" and 3" odies. E 1/2" - 20 Threads D 1-1/4" - 16 Threads C Flow Flow Flow F Figure-10 Typical of V-9313-0-5-P, 2-1/2" to 6" odies. F-24393-3 Copyright 2010 Schneider Electric ll Rights Reserved. 11

Table-9 Flange Detail for merican Standard 125 lb. Cast Iron Pipe Flanges. (Figure-11). Flanges Drilling olting Nominal Flange Flange Diameter Pipe Size Diameter Thickness of olt Circle C 2-1/2" 7" 11/16" 5-1/2" 3" 7-1/2" 3/4" 6" 4" 9" 7-1/2" 15/16" 5" 10" 8-1/2" Diameter of olt Holes D 3/4" Number of olts 4 Diameter of olts 5/8" Length of Machine olts E 2-1/2" 8 7/8" 3/4" 6" 11" 1" 9-1/2" 3-1/4" 3" E D C Figure-11 Flange Dimensions. On October 1st, 2009, TC became the uildings business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric, however there remains references to TC as a corporate brand in the body copy. s each document is updated, the body copy will be changed to reflect appropriate corporate brand changes. Copyright 2010, Schneider Electric ll brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice. F-24393-3 Schneider Electric 1354 Clifford venue P.O. ox 2940 Loves Park, IL 61132-2940 www.schneider-electric.com/buildings