MX431 Generator Automatic Voltage Regulator Operation Manual

Similar documents
ADVR-12. Hybrid Universal Analog Digital Voltage Regulator Operation Manual

AVR Hybrid Universal Analog Digital Voltage Regulator Operation Manual

EA07. Generator Automatic Voltage Regulator Operation Manual

PM500. Voltage Regulator User Manual. A Regal Brand. Scan here for other languages.

PM300E Voltage Regulator Instruction Manual

PI734G - Winding 312. Technical Data Sheet APPROVED DOCUMENT

PI736F - Winding 312. Technical Data Sheet

EA16. Generator Automatic Voltage Regulator Operation Manual

PM300 VOLTAGE REGULATOR INSTRUCTION MANUAL

PM734E - Winding 28. Technical Data Sheet APPROVED DOCUMENT

INSTRUCTION MANUAL FOR. VOLTAGE REGULATOR Model: APR Part Number:

James Hamilton Electrical Pty Ltd (Inc in Qld) A.C.N trading as. Power Drive Systems. Generator Control Specialists

MAGNAMAX DVR DIGITAL VOLTAGE REGULATOR

INSTRUCTION MANUAL FOR VOLTAGE REGULATOR APR P/N

INSTALLATION AND SET-UP MANUAL FOR THE NEW: AVR-07. A CONTROLPAK AVR Automatic Voltage Regulator for three-phase and single-phase alternators

IVT-1260 & IVT Generator Auxiliary Excitation Booster Operation Manual. (Patent Pending)

UCI274E - Winding 06 APPROVED DOCUMENT. Technical Data Sheet

UCI224E - Winding 06. Technical Data Sheet APPROVED DOCUMENT

UCI224C - Winding 06. Technical Data Sheet APPROVED DOCUMENT

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER

FAULT FINDING MANUAL. For Stamford AC Generators

UCI224E - Winding 311 Single Phase. Technical Data Sheet APPROVED DOCUMENT

HCI 534E/544E - Technical Data Sheet

HCI 434E/444E - Technical Data Sheet

UCI224F - Winding 311 Single Phase. Technical Data Sheet APPROVED DOCUMENT

UCI274H - Technical Data Sheet Winding 06

EG3000. Generator Electronic Governor Controller Operation Manual

HCI434E/444E - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet

HCI534F/544F - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet

UCI224F - Winding 25. Technical Data Sheet APPROVED DOCUMENT

UCI224F - Winding 14. Technical Data Sheet APPROVED DOCUMENT

UCI274C - Technical Data Sheet Winding 06

UCDI224F - Technical Data Sheet

PI044G - Winding 06 APPROVED DOCUMENT. Technical Data Sheet

HCI 534C/544C - Technical Data Sheet

UCI224C - Technical Data Sheet

HCI434C/444C - Winding 17 APPROVED DOCUMENT. Technical Data Sheet

PI144J - Winding 05 APPROVED DOCUMENT. Technical Data Sheet

UCDI274J - Technical Data Sheet

UCI274H - Technical Data Sheet

HCI 434E/444E - Technical Data Sheet

HCI 534F/544F - Technical Data Sheet

HCI 434D/444D - Technical Data Sheet

UCI274E - Winding 14 APPROVED DOCUMENT. Technical Data Sheet

EA06. Generator Automatic Voltage Regulator Operation Manual

Model ER-340XRi / ER-680XRi / ER-1220XRi DC drive product manual HG iss 9 1

UCI224F - Technical Data Sheet

HCI 534E/544E - Technical Data Sheet

UCI274D - Technical Data Sheet

HCI 534E/544E - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

HCI 534C/544C - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

UCDI274K - Technical Data Sheet

5001TCP SPEED CONTROLLER

UCI274D - Technical Data Sheet

UCI274G - Technical Data Sheet

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

HCI 434F/444F - Technical Data Sheet

UCDI274K - Technical Data Sheet

UCI224G - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

MODEL 422 Submersible Pump Controller

UCDI224E - Technical Data Sheet

UCI224E - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

UCI224C - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

UCI224D - Winding 311 APPROVED DOCUMENT. Technical Data Sheet. Generator Solutions AS

UCI274D - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

INDEX Section Page Number Remarks

PI144D - Technical Data Sheet

PI144J - Technical Data Sheet

EG1069X. Generator Electronic Governor Controller Operation Manual

5001TCP SPEED CONTROLLER

PI044D - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet

PI144G - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet

PI044H - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet

PI044F - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet

PI044E - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet

PI144E - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet

PI144F - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet

ESD5500E Series Speed Control Unit

UCDI274J - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

Model 340i / 680i / 1220i DC drive product manual HG iss 8 1

Instruction Manual. Installation Operation Maintenance. KCR 760 Voltage Regulator

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM

ENGINE GOVERNING SYSTEMS

PI144D - Winding 17. Technical Data Sheet APPROVED DOCUMENT

PI144K - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

PI044F - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

PI044D - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

PI144J - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

ENGEN -100/ENGEN -200 ENGINE GENERATOR CONTROLLER

BCI164C - Technical Data Sheet Winding 06

ESC2301. Universal Electronic Governor Controller Operation Manual

INSTRUCTION MANUAL FOR

ALTERNATOR DE-EXCITATION WITH K1 AND K2 ON ANALOGUE

Low Voltage Alternators - 4 pole LSA 44.3

HCI634J - Winding 311 and 312 APPROVED DOCUMENT. Technical Data Sheet

R250 A.V.R. Installation and maintenance R250 0V E+ E- VOLT STAB FREQ. & L.A.M. CONFIG. 50Hz. 47.5Hz. 57Hz LAM 1 13% 2 25% OFF LAM OFF 9

A CONTROLPAK AVR Automatic Voltage Regulator for three-phase and single-phase alternators

HCM534D - Winding 14 APPROVED DOCUMENT. Technical Data Sheet

HCI634V - Technical Data Sheet

SECTION MOTOR CONTROL

Transcription:

Generator Automatic Voltage Regulator Operation Manual Self Excited Automatic Voltage Regulator 1

1. SPECIFICATION Sensing Input Voltage Frequency 190 ~ 264 VAC Max, 1 phase, 2 wire 50 / 60 Hz, selectable Power Input (PMG) Voltage 170 ~ 220 VAC Max, 3 phase 3 wire Current 3A / Phase Frequency 100 ~ 120 Hz, nominal Output Voltage Max. 120 VDC Current Continuous 2.7A Intermittent 6A for 10 sec Resistance Min. 15 ohm Voltage Regulation < ± 1% ( with 4% engine governing ) Voltage Build-up Residual voltage at AVR terminal > 5 VAC Thermal Drift 0.05% per C change in AVR ambient External Volt Adjustment ± 10% with 1K ohm 1 watt trimmer Unit Power Dissipation Max. 12 watt Under Frequency Protection (Factory Setting) Set point 95% Hz Slope 170% down to 30 Hz Soft Start Ramp Time 3 sec. Analogue Input Max. Input Sensitivity Input Resistance Droop Input Burden Max. sensitivity Max. input ± 5 VDC 1V for 5% generator volt 1K ohm 10 ohm 0.07 A for 5% droop (PF=0) 0.33 A Over Voltage Detector Input Set point 300V. Time delay 1 Sec (fixed) CB trip coil volt 10 ~ 30 VDC / 0.5 Amp CB trip coil resistance 20 ~ 60 ohms Over Excitation Protection Set point 90 VDC Time delay 10 sec (fixed) Typical System Response AVR response 10 ms Filed current to 90% 80 ms Machine Volt to 97% 300 ms Environmental 100Hz ~ 2K Hz 3.3g Relative Humidity 0 ~ 70 C 95% (see note 6) Operating temperature -40 to +70 C Storage temperature -40 to +85 C Current Limit Input 10 ohms burden Sensitivity range 0.5 ~ 1A Weight 394g ± 2% 2. GENERAL DESCRIPTION EA341 is a two phase sensed Automatic Voltage Regulator and forms part of the excitation system for a brush-less generator. Excitation power is derived from a three-phase permanent magnet generator (PMG), to isolate the AVR control circuits terminals. Sustained generator short circuit current is another feature of the PMG system. from the effects of nonlinear loads and to reduce radio frequency interference on the generator 2

The AVR senses the voltage in the main generator winding and controls the power fed to the exciter stator and hence the main rotor to maintain the generator output voltage within the specified limits, compensating for load, speed, temperature and power factor of the generator. Soft start circuitry is included to provide a smooth controlled build up of generator output voltage. A frequency measuring circuit continually monitors the shaft speed of the generator and provides under-speed protection of the excitation system by reducing the generator output voltage proportionally with speed below a pre-settable threshold. A further enhancement of this feature is an adjustable VOLT per Hertz slope to improve engine recovery time on turbo charged engines. Soft start circuitry is included to provide a smooth controlled build up of generator output voltage. Uncontrolled excitation is limited to a safe period by internal shutdown of the AVR output device. This condition remains latched until the generator has stopped. Provision is made for the connection of a remote voltage trimmer, allowing the user fine control of the generator s output. An analogue input is provided allowing connection to a controller or other external devices with compatible output. The AVR has the facility for droop CT connection, to allow parallel running with other similarly equipped generators. NOTE : 1. Derate linearly from 3.7A at 50 C to 2.7A at 70 C. 2. The stated voltage regulation may not be maintained in the presence of certain transmitted radio signals. Any change in regulation will fall within the limits in Criteria B of S.EN.61000-6-2 : 2001. 3. After 10 minutes. 4. Applies to Mod status E onwards. Generator de-rate may apply. Check with factory. Factory set, semi-sealed, jumper selectable. 5. Any device connected to the analogue input must be fully looting (galvanically isolated from ground), with an insulation strength of 500Vac. 6. Non condensing. 3. SUMMARY OF AVR CONTROLS CONTROL FUNCTION DIRECTION VOLT To adjust generator output voltage Clockwise increases output voltage STABILITY To prevent voltage hunting Clockwise increase the damping effect UFRO To set the UFRO knee point Clockwise reduces the knee point frequency DROOP To set the generator droop to 5% at 0pf Clockwise increases the droop TRIM To optimize analogue input sensitivity Clockwise increases the gain or sensitivity EXC To set the over excitation cut off level Clockwise increase the cut off level DIP To set the frequency related voltage dip Clockwise increases the voltage dip 4. ADJUSTMENT OF AVR CONTROLS 4.1 Voltage Adjustment The generator output voltage is set at the factory, but can be altered by careful adjustment of the VOLT control on the AVR board, or by the external hand trimmer if fitted. Terminals 1 and 2 on the AVR will be fitted with a shorting link if no hand trimmer is required. WARNING Do not increase the voltage above the rated generator voltage. If in doubt, refer to the rating plate mounted on the generator case. Do not ground any of the hand trimmer terminals, as these could be above earth potential. Failure to observe this could cause equipment damage. 3

If a replacement AVR has been fitted or re-setting of the VOLT adjustment is required, proceed as follows : 1. Before running generator, turn the VOLT control fully anti-clockwise. 2. Turn remote VOLT trimmer (if fitted) to midway position. 3. Turn STABILITY control to midway position. 4. Connect a suitable voltmeter (0~300V ac) across line to neutral of the generator. 5. Start generator set, and run on no load at nominal frequency e.g. 50~53Hz or 60~63Hz. 6. If the red Light Emitting Diode (LED) is illuminated, refer to the Under Frequency Roll Off (UFRO) adjustment. 7. Carefully turn VOLT control clockwise until rated voltage is reached. 8. If instability is present at rated voltage, refer to stability adjustment, then re-adjust voltage if necessary. 9. Voltage adjustment is now completed. 4.2 Stability Adjustment The AVR includes stability or damping circuit to provide good steady state and transient performance of the generator. A jumper link selector is provided to optimize the response of the stability circuit to various size generators. The link should be positioned as shown in the diagram according to the kw rating of the generator. The correct setting of the Stability adjustment can be found by running the generator at no load and slowly turning the stability control anti-clockwise until the generator voltage starts to become unstable. The optimum or critically damped position is slightly clockwise from this point (i.e. where the machine VOLT are stable but close to the unstable region). The UFRO adjustment is preset and sealed and only requires the selection of 50 or 60Hz and 4 pole or 6 pole, using the jumper link as shown in the diagram. For optimum setting, the LED should illuminate as the frequency falls just below nominal, i.e. 47Hz on a 50Hz system or 57Hz on a 60Hz system. 4.4 DROOP Adjustment Generators intended for parallel operation are fitted with a quadrature droop C.T. which provides a power factor dependent signal for the AVR. The C.T. is connected to S1, S2 on the AVR, (see generator wiring diagram for details). The DROOP adjustment is normally preset in the works to give 5% voltage droop at full load zero power factors. Clockwise increases the amount of C.T. signal injected into the AVR and increases the droop with lagging power factor (cos Ø). With the control fully anti-clockwise there is no droop. 4.5 Trim Adjustment An analogue input (A1 A2) is provided to connect to the controller or other devices. It is designed to accept dc signals up to ±5 VOLT. The dc signal applied to this input adds to the AVR sensing circuit. A1 is connected to the AVR 0 VOLT. Positive on A2 increases excitation. Negative on A2 decreases excitation. The TRIM control allows the user to adjust the sensitivity of the input. With TRIM fully anti-clockwise the externally applied signal has no effect. Clockwise it has maximum effect. Normal setting is fully clockwise when used with a controller. WARNING Any devices connected to this input must be fully floating and galvanically isolated from ground, with an insulation capability of 500V ac. Failure to observe this could result in equipment damage. 4.3 Under Frequency Roll Off (UFRO) Adjustment The AVR incorporates an under-speed protection circuit which gives a VOLT / Hz characteristic when the generator speed falls below a presentable threshold known as the knee point. The red Light Emitting Diode (LED) gives indication that the UFRO circuit is operating. 4

4.6 Er Excitation (EXC) Adjustment This adjustment is set and sealed in the works and should not be tampered with. An over excitation condition is indicated by the illumination of the red LED which also indicates under-speed running and over-volt. The generator must be stopped to reset an over-excitation trip. 4.7 DIP Adjustment This feature is mostly used when the generator is coupled to turbo charged engines with limited block load acceptance. The feature works by increasing the V/Hz slope to give greater voltage roll off in proportion to speed. With the DIP control fully anti-clockwise, the generator voltage will follow the normal V/Hz line as the speed falls below nominal. Turning the DIP control clockwise provides greater voltage roll off aiding engine recovery. 5. FITTING AND OPERATING (Refer to generator wiring diagram for connection details) TRIM High Temperature DROOP VOLT DIP EXC. TRIP C-A < 90KW C-B 90-550KW B-A > 550KW UFRO LED STABILITY C B A Figure 1 Outline Drawing UNIT : mm ATTENTION 1. AVR can be mounted directly on the engine, genset, switchgear, control panel, or any position that will not affects operation. For dimension reference, please see Figure 1. 2. All voltage readings are to be taken with an average-reading voltmeter Meggers and high-potential test equipment must not be used. Use of such equipment could damage the AVR. 5

k1-k2 linked for normal operation. K2 K1 P2 P3 P4 XX X 3 2 2 1 High Temperature TRIM DROOP VOLT A1 A2 S1 S2 1 2 3 4 5 6 7 8 SENSING SELECTION DIP FREQUENCY SELECTION EXC. TRIP UFRO 3 2 1 STABILITY SELECTION C B A INDICATOR LED Exciter 3-1 4P/60HZ 3-2 4P/50HZ 2-1 6P/50HZ NO LINK 6P/50HZ 3Ø Bridge Generator C-B 90KW~550KW B-A OVER 550KW Figure 2 Disposition Drawing PMG 勵勵勵 Exciter 3Ø 整整整 Bridge 主主主主主 Generator G ~ C.T 220V R S T 外外外整 1KΩ For 1K external 歐歐 adjusted P2 P3 P4 XX X 2 1 2 3 S1 S2 Figure 3 Wiring Drawing Note : When the system voltage over 220VAC, a transformer is necessary at sensing input terminal is recommend. Use only original supplied spare protection fuse for fuse replacement. Please accept our sincere apology if any modification in performance, specification or appearance is made without prior notice. 6