LARSEN & TOUBRO LIMITED TYPICAL SCHEME FOR PROTECTION OF SYNCHRONOUS MOTORS

Similar documents
A21M. Introduction: Functional Overview: Key Protection & Control Functions:

Unit Protection System for Pumped-Storage Power Stations

Synchronous motor control. 8/15/2007 Powerflow Technologies Inc 1

Motor Protection Fundamentals. Motor Protection - Agenda

Legal Name of the Customer (or, if an individual, individual's name): Name: Contact Person: Mailing Address: Physical Address: City: State: Zip Code:

RVS-DN Digital Reduced Voltage Motor Starter

Electrical Drives I. Week 11: Three phase Induction Motor Starting

Synchronous motor with fluid coupling drive arrangement for a preheater ID Fan. presenter Nathan Schachter CIMENTEC Engineering Ltd

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6

Protective Device Coordination ETAP Star

KD LV Motor Protection Relay

19 A.C. Motor Protection

CHAPTER 4 PROTECTION REQUIREMENTS

Application Note: Protection of Medium-Power Motors With SIPROTEC Compact 7SK80

AIR COOLED RECTIFIER SPECIFICATION S-50-A

34 th Hands-On Relay School

DG SYNCHRONIZING &AMF PANEL

Series Motor Protection

Chapter 3.1: Electrical System

CHAPTER 3 CAUSES AND EFFECTS OF ELECTRICAL FAULTS

T-Line Generator Control, Protection and Monitoring

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs.

RVS-DX Digital Reduced Voltage Motor Starter

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

320 to 327 M Series Low and Medium Voltage Motor Protection Relays

Module 2 CONTROL SYSTEM COMPONENTS. Lecture - 4 RELAYS

Bulletin 825 SMM Smart Motor Manager

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB

EE042: Practical Power System Protection for Engineers & Technicians

TRIPS AND FAULT FINDING

Application Note RESIDUAL BUS MAIN-TIE-MAIN AUTOMATIC TRANSFER SCHEME USING THREE GE 850 RELAYS

AC Motor Protection. Course No: E Credit: 3 PDH. Velimir Lackovic, Char. Eng.

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

NORTH CAROLINA INTERCONNECTION REQUEST APPLICATION FORM. Utility: Duke Energy Progress

Direct On Line (DOL) Motor Starter. Direct Online Motor Starter

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB

XM1 - Motor protection relay

Case Study on On EHV Circuit Breaker Flashover NTPC-SINGRAULI

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS

DEEP SEA ELECTRONICS PLC

Power Systems Trainer

SECTION MOTOR CONTROL

EFFECT OF CAPACITOR ON STARTING & RUNNING OF SINGLE PHASE INDUCTION MOTOR

Motor Protection Application Considerations

150 B180 N B D A 8L. Enclosure Type. Input Line Voltage Open Type V AC, 3-phase, 50 and 60 Hz V AC, 3-phase, 50 and 60 Hz

Standby Power Systems

Memshield - ACB Ratings & Specifications

SDC,Inc. SCR-Regenerative Ac Drive

DESIGN CONSIDERATIONS FOR APPLICATION OF SHUNT CAPACITORS IN HEAVY HATER PLANT (TUTICORIN)

Alternator protection, part 1: Understanding code requirements

SINAMICS SM150. 4/2 Overview. 4/2 Benefits. 4/2 Design. 4/6 Function. 4/8 Selection and ordering data. 4/8 Options

LA Motor Protection. A South African Company to be Proud of

Chapter 3.2: Electric Motors

Electrical Systems - Course 135 COMPOSITE ELECTRICAL PROTECTIVE SCHEMES: PART II

Jemena Electricity Networks (Vic) Ltd

QUOTATION BLADE 7 LX. Product code GEAL6S2BAA

NEW ZEALAND POST OFFICE NEGATIVE 50V D.C. TO POSITIVE 50V D.C. SUPPLY NOTES PR 2157 ISSUE 1 APRIL 1977

Starters. Overview. Siemens caters with following types of starters to agricultural and industrial sector.

Starting of Induction Motors

PSNH INTERCONNECTION REQUEST

Softstarters. Softstarters Type SSM Medium voltage ,800V 1

CIS-IEEE 2017 Conference Renewable Energy Session Renewable Energy s Impact of Power Systems

RVS-AX Instruction Manual

RM B. Features. Drive Model Number Scheme. A RM6 Product Series

Guidelines for connection of generators:

Diesel Generator Set S3.8 Series Engine

Single Phase Induction Motor. Dr. Sanjay Jain Department Of EE/EX

130 KW / 165 KVA POWERED by

Experiences in a Motor Protection Retrofit

Submittal Data Information

Fusesaver specification form

Synchronous Motor Drives

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear

Question Number: 1. (a)

Unit-II Synchronous Motor

Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 25 kw to 10 MVA or less)

Motor Protection. Voltage Unbalance & Single-Phasing

Dynamic Study of Bonaire Island Power System: Model Validation and Project Experience

This generator set has been designed to meet ISO 8528 regulation. This generator set is manufactured in facilities certified to ISO 9001.

A problem with the motor windings. A phase loss on mains terminals L1, L2, or L3 during run mode. Parameter 2-3 Current Imbalance Delay.

American Traction Systems. DC Bus Capacitorss. Total. Dual Chopper Module. Dual. Inverter. 750kW. 750kW Generator Module. Module

MP-4000 Motor Protection

DKG-705 AUTOMATIC MAINS FAILURE AND REMOTE START UNIT WITH PARALLEL TO MAINS AND DUAL GENSET PARALLEL FEATURES

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Maryland Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kw to 10 MW or less)

This generator set has been designed to meet ISO 8528 regulation. This generator set is manufactured in facilities certified to ISO 9001.

Technical Explanation for Inverters

This generator set has been designed to meet ISO 8528 regulation. This generator set is manufactured in facilities certified to ISO 9001.

SECTION V SWITCHBOARD I 4 Engine/Gen Control Cubicles II 1 Synchronizing System III 1 Ground Detection Network IV 1 600V Feeder Section V 2

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM

This generator set has been designed to meet ISO 8528 regulation. Enclosed product is tested according to EU noise legislation 2000/14/EC

Mono Pumps PSS Eco 1-60

GENERATOR & SINGLE-FUNCTION PROTECTION

CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM

AGN Alternator Ratings and Overload

Features IN THIS CHAPTER

Application Note CTAN #127

Diesel generator set QSK78 series engine 2750kVA kVA 50 Hz

MAGNETIC MOTOR STARTERS

Grid Stability Analysis for High Penetration Solar Photovoltaics

Transcription:

LARSEN & TOUBRO LIMITED TYPICAL SCHEME FOR PROTECTION OF SYNCHRONOUS MOTORS R.Seshadri Larsen & Toubro Limited Mysore works

1.0 GENERAL DETAILS 1.1 Synchronous Motors: Synchronous motors come in large sizes like 1 MW and above. Protection of a synchronous motor is different from a normal induction motor protection since a synchronous motor has DC rotor in addition to stator. This document gives details of a protection scheme for large size synchronous motors. 2.0 Relays to be used for protection of Synchronous motor, typical size ( 1750 kw) L&T recommends following relays : a) Comprehensive Motor Protection Relay type MM30W b) Stator differential relay type MD32-G c) Rotor Earth fault relay type UBO/CR d) DC under voltage relay for rotor side, Type UBC-80 e) DC under current relay for rotor side, Type UBC/A/37 One each of above relays are required to offer a complete protection to the synchronous motor. The SLD for the protection is enclosed. Section 3 gives details of individual protections offered by the above relays. 3.0 Protections offered by Motor Protection Relay MM30W MM30W is completely microprocessor based and uses state of the art technology. It provides totally 12 protections. It receives inputs from three phase CTs, one bus PT and gives trip contact as outputs. Following are the protections offered by MM30W: 3.1 Thermal overload This protection will save the motor from any over load conditions from 105% to 600%. If at any time, the motor draws more current than its rated current, thermal over load protection will first give alarm and then eventually trip after a time delay which is defined by the over load trip time characteristics of the motor. Relay has facility to match closely its trip time characteristics with the over load characteristics of the motor. 2

-2-3

3.2 Locked rotor protection : -3- MM30W offers protection against a locked rotor condition both while starting as well as while running. The LR trip time delay while running can be set by the user. When starting the trip time delay is automatically made as twice that of the starting time. This will save the motor from frequent momentaer over loads ( like crusher moros etc.) 3.3 Repeat Starts Protection: Large machines can be damaged when the operator tries to start them again and again without knowing the cause of trip. It should be noted that every time a start impulse is given, the motor experiences a high current impulse, which progressively increases heating in the stator. This protection saves the motor from damage due to frequent starts. If the number of starts have exceeded a set value within a set time, the start command is inhibited by the relay. 3.4 Negative sequence protection : The motor can get over heated whenever there is unbalance current flowing in the stator. Even a small unbalance in voltage, of the order of 2%, can cause a temperature rise by 10% for the same load. This will not be detected by the thermal overload element since the motor current is still at rated current. This protection monitors the unbalance level and trips the motor if unbalance level exceeds say 30%. 3.5 Over current Protection : This is a protection against external short circuits in the feeder. 3.6 Earth Fault Portection : This is a protection against E/F which can happen frequently in an industry. E/F pick up levels can be set to as low as 10% levels there will not be any spurious tripping since the E/F element in MM30W has a third harmonic filter. 3.7 Under current protection : This is a protection against motor running without load. This saves the motor from conditions of sudden load throw off - like gear box detachment etc...4

3.8 Prolonged start protection : -4- When the motor is starting, some times it may take a longer time than specified, to start. This happens in high inertia motors. This may also be due to some maintanence problems. If this happens frequently, then motor can get damaged. MM30W monitors the starting current and starting time if the current does not reduce to a preset level at the end of the starting time, it will initiate the trip, thus savung the motor from further damage. 3.9 Single phasing protection : Single phasing is condition where a large amount of negative sequence will be present, of the order of 53% and above MM30W has inverse time characteristics for trip for negative sequence. It will trip on negative sequence, with shorter time delay, in shorter timehence, whenver there is single phasing. 3.10 Phase reversal Protection: Motors can run in reverse direction when there is phase reversal. Phase reversal is 100% negative sequence condition. MM30W will protect the motor feeder by tripping on negative sequence whenever there is a phase reversal.while starting 3.11 Under Voltage / Over voltage Protection : This protects the motor from stator side under / Over voltages. 3.12 Under / Over frequency protection : This protects the motor from stator side under / Over frequencies. 3.13 Low PF protection : Synchronous motors can easily go into a low PF condition since their rotor excitation is externally controlled. MM30W monitors the PF level of the motor and gives an alarm contact under low PF conditions. 3.14 Auxiliary supply failure protection: If the auxiliary supply to relay is absent, then there is no protection MM30W has a facility where by it will generate a contact whenever its auxiliary supply fails. This contact can be used for alarm / trip. 3.15 Protection against unathorised change in settings : MM30 generates an alarm contact whenever it is taken into programme mode. Consequently it is difficult to change the settings without raising an alarm...5

4.0 Differential protection : -5- Relay MD32-G offers a comprehensive differential protection for the synchronous motor. In large machines, it is advaisable to monitor the internal short circuits with a separate relay which will trip instantaneously. MD32 G provides this protection. With a dual slope trip characteristics, MD32G offers a very high through fault stability and avoids spurious trippings under fluctuating loads and external faults. 5.0 Rotor side protections : Rotor of a synchronous machine is a DC winding- hence it needs DC relays. 5.1 Relay UBO-CR protects the rotor from any earth faults. 5.2 Relay UBC-80 provides protection against under voltage for rotor. 5.3 Relay UBC/A/37 provides protection against under excitaion to rotor. All these protections take care of the motor from any loss of field condition also. 6.0 Out of step protection : The normal method is to use a separate relay for out of step protection. L&T has a separate relay IM30-GOS for this application. This is basically caculating the out of step condition by evaluating the position and magnitude of the impedance vector ( from the stator side measurement of current and voltage). While this may be good for a generator, it may not be effective for a motor. MM30W provides a more direct monitoring for an impending out of step condition. Out of step occurs due to sudden over load ( exceeding peak torque rating )on the machine or fall in the applied voltage to stator. Under these conditions motor draws excessive current - it produces a non uniform or pulsating torque - and goes into stalling mode. This current drawn during out of step is of a low PF. 6

-6- b) MM30W monitors all above conditions independently and on line. - it has current measurement and a LR setting to save motor from momentary over loads - it has U/V element - to save motor from Under voltage conditions - it has PF element to monitor quality of current and recognise out of step condition. Only thing is motor PF is low during starting - hence PF element should be inhibited during starting. This can be automatically done by ITR/TTR contact. 7. PC Communication software : Many of the relays ( except the DC relays) proposed above have RS485 port through which they can communicate all data with a central PC system. MSCOM communication software is available this will help in continuous polling of the relays from a remote point and log all the relevant feeder data. 8. Control & Relay Panel for Synchronous Motor Protection ; Since there are a total of 5 relays ( MM30W, MD32G, UBO/CR, UBC/80, UBC/A/37), it is advisable to mount all these rel;ays on a small panel with all associated control accessories duly wired together. L&T can offer a total solution for synchronous motor protection in the form of a pre wired C&R panel. ---oooooo@&@oooooo---