Fisher 2506 and 2516 Receiver Controllers

Similar documents
Fisher L3 Pneumatic Level Controller

Fisher 2100 Pneumatic and 2100E Electric Liquid Level Switches

L3 Pneumatic Level Controller

Fisher Pneumatic Controllers and Transmitters

Fisher 480 Series Yokeless Piston Actuators

Fisher 3660 and 3661 Positioners

Fisher 2625, 2625SST, and 2625NS Volume Boosters

Fisher VBL Volume Booster

Fisher 2506 and 2516 Receiver/Controllers

Fisher 546 Electro Pneumatic Transducer

2506 Series Multi-Trol Receiver/Controllers (Types 2506, 2516, 2516F)

Fisher 3710 and 3720 Positioners and 3722 Electro-Pneumatic Converter

Fisher 657 and 667 Diaphragm Actuators

Fisher 480 Series Yokeless Piston Actuators

Fisher VBL Volume Booster

Fisher 377 Trip Valve

Fisher 3024C Diaphragm Actuator

Fisher 377 Trip Valve

Fisher 3610J and 3620J Positioners and 3622 Electro-Pneumatic Converter

Fisher 3660 and 3661 Positioners

Fisher 656 Diaphragm Actuator

Fisher SS-263 Volume Booster

Fisher 1077 Manual Handwheel Rotary Actuator

Fisher Level Instruments

Fisher 685 Piston Actuator

Fisher 3024C Diaphragm Actuator

470 Series Piston Actuators

Type 310A-32A Pressure Reducing Regulator

Type 289RC Exhaust Booster

Fisher 2052 Diaphragm Rotary Actuator

Fisher 1B and 1BR Constant Pressure Pump Governor Actuators

Types 1808 and 1808A Pilot-Operated Relief Valves or Backpressure Regulators

Fisher A31A Cryogenic High Performance Butterfly Valve

Fisher 3710 and 3720 Positioners and 3722 Electro Pneumatic Converter

Type 3660 and 3661 Positioners

Fisher V250 Rotary Control Valve

Fisher 8532 High-Performance Butterfly Valve

Fisher i2p 100 Electro Pneumatic Transducer

Fisher 644 and 645 Differential Pressure Pump Governors

Fisher D4 Control Valve Assembly

Fisher WhisperFlo Aerodynamic Noise Attenuation Trim

Fisher 1052 Size 20 Diaphragm Rotary Actuator with F and G Mounting Adaptation

Fisher L2 Liquid Level Controller

Fisher 685SE and 685SR Piston Actuators

Fisher 4194A, B, and C Differential Pressure Controllers1 1

Fisher 8532 High-Performance Butterfly Valve

CML Electric Actuator for Baumann Series

Fisher 3710 and 3720 Positioners and 3722 Electro Pneumatic Converter

Fisher 9500 Butterfly Control Valve

Type 1051 and 1052 Diaphragm Rotary Actuators

Fisher V260 Ball Control Valve

Fisher 2052 Diaphragm Rotary Actuator

Fisher FIELDVUE DVC6000 Digital Valve Controller Dimensions

Fisher A31D Double-Flange High-Performance Butterfly Valve

M Series Manual Handwheel Gear Actuator

Type 1035/El-O-Matic Rack-and-Pinion Rotary Actuator

Y610A, Y611A, and Y612A Series Vacuum Service Equipment and Relief Valves

Baumann 24000S Stainless Steel Control Valve

Fisher CCV-N Fuel Gas Control Valve

Fisher RSS Lined Globe Valve

Fisher 461 Increased Outlet Angle Sweep-Flo Valve

Fisherr 1051 and 1052 Diaphragm Rotary Actuators

Fisherr 2052 Diaphragm Rotary Actuator

Fisher CAV4 Control Valve

Fisher SS-252B Continuous Catalytic Regeneration Valve

Fisher 1052 Size 70 Diaphragm Rotary Actuator

Monitoring Health of External Solenoid Valve (SOV) with FIELDVUE DVC6200 SIS Digital Valve Controllers

Fisher 685 Piston Actuator

Fisher 2625, 2625SST, and 2625NS Volume Boosters

Fisher 4194HA, HB, and HC Differential Pressure Indicating Controllers

Zero Point Calibration HART Communicating Fisher FIELDVUE DVC6200 Digital Valve Controllers

Baumann Mikroseal Control Valve

Fisher FIELDVUE DVC6200 Digital Valve Controller / Magnet Assembly Dimensions

Fisher A31D Double-Flange High-Performance Butterfly Valve

Fisher 4195KA, KB, KC, and KS Gauge Pressure Controllers

Fisher CV500 Rotary Globe Control Valve

Fisher POSI-SEAL A31A Cryogenic High Performance Butterfly Valve

Baumann Sanitary Angle Control Valve

Fisher 249 Caged Displacer Sensors

Baumann Sanitary Angle Control Valve

Type D2 FloPro Control Valve

type 630r relief Valve

WARNING. Mounting Instructions D103998X012 June DVC6200/DVC2000 Digital Valve Controller Linear Actuator Side Mount

Fisher D and DA Control Valves

Fisher 4194S Differential Pressure Controllers

4195KA, KB, KC, and KS Controllers. Instruction Manual Form 5207 April 2007

Fisher D2T FloPro Control Valve

Fisher 4194HS Differential Pressure Indicating Controllers

Fisher 2625 and 2625NS Volume Boosters

3582 Series Pneumatic and Type 3582i Electro-Pneumatic Valve Positioners

Fisher Whisper Trim III Cages

Features. Product Bulletin 51.6:8590 August Valve D104017X012

Baumann Sanitary Control Valve

Fisher RSS Lined Globe Valve

490 Series Actuators. 490 Series. Contents. Introduction

Fisher D4 Control Valve Assembly

Type HSR Pressure Reducing Regulator for Residential, Commercial, or Industrial Applications

Fisher Multi-Port Flow Selector Valve

Types 1808 and 1808A Pilot-Operated Relief Valves or Backpressure Regulators

Baumann Little Scotty Bronze Control Valve

Transcription:

2506/2516 Receiver Controllers Product Bulletin Fisher 2506 and 2516 Receiver Controllers The 2506 receiver controller takes the input from a pneumatic transmitter, matches it against the adjustable set point, and provides a proportional pneumatic output to a control valve actuator. The 2506 receiver controller may be used in conjunction with a remote receiving indicator or recorder also using the output from the transmitter. The 2516 receiver controller has both proportional band and reset control. The reset adjustment efficiently brings the set point back to its original position. Features Easy Maintenance Simple design of the receiver controller allows fast, easy maintenance and minimal spare parts inventory. Easy Adjustment Proportional band and reset adjustment is accomplished quickly and without special tools. The control set point is manually adjustable in the case or through remote air loading (figures 2 and 3). Application Versatility Reset may be added to a receiver controller originally furnished without it. Mounting Versatility 2506 and 2516 receiver controllers may be attached to the casing or yoke of a control valve actuator, or placed anywhere between the transmitter and valve. Stable Control A pressure balanced relay provides intermittent bleed and gives accurate, stable control. The addition of reset action on the 2516 unit offers drift compensation, yet provides smooth, stable control. Easy Reversibility 2506 and 2516 receiver controllers may be changed from direct to reverse action, or vice versa, by simply repositioning the reversing switch. W4687 W4688 FISHER 2506 RECEIVER CONTROLLER FISHER 2516 RECEIVER CONTROLLER www.fisher.com

Product Bulletin 2506/2516 Receiver Controllers Specifications Available Configurations For additional information, refer to table 2 2506: A receiver controller that is set for either proportional or snap action (S) control or is set for either direct or reverse (R) action 2516: A 2506 that also provides proportional plus reset control 2516F: A 2516 that also provides anti reset windup control Input Signal 0.2 to 1.0 bar (3 to 15 psig) or 0.4 to 2.0 bar (6 to 30 psig) Output Signal (1) See table 1 Output Action Direct Action: An increasing fluid, interface level, or density increases output pressure or, Reverse Action: An increasing fluid, interface level, or density decreases output pressure Remote Set Point Signal From a control device, provide a remote set point signal that is 0.2 to 1.0 bar (3 to 15 psig) or 0.4 to 2.0 bar (6 to 30 psig) that matches the receiver controller input signal range Supply Pressure (2) Normal Operating Pressure: See table 1.. Maximum Pressure to Prevent Internal Part Rupture (1) : 3.4 bar (50 psig) Steady State Air Consumption See figure 1 Proportional Band, Reset, and Anti Reset Windup See table 2 Performance Hysteresis: 0.6 percent of output pressure change at 100 percent of proportional band, or differential gap Standard Supply and Output Pressure Gauge Indications See table 1 Standard Tubing Connections 1/4 NPT internal Operative Ambient Temperature Limits (2) Standard: -40 and 71 C (-40 and 160 F) High Temperature: -18 and 104 C (0 and 220 F) Hazardous Area Classification 2506/2516 receiver controllers comply with the requirements of ATEX Group II Category 2 Gas and Dust Meets Customs Union technical regulation TP TC 012/2011 for Groups II/III Category 2 equipment II Gb c T*X III Db c T*X Construction Materials Case and Cover: Die cast aluminum Flapper: K93600 nickel alloy Bellows: Bronze (standard) or stainless steel (optional) Nozzle: C36000 (Brass) Proportional Band Valve Body, Seat, and Plug: Brass Gaskets: Chloroprene (standard) or silicone (high temperature) Relay Body: Aluminum/brass Relay Valve Plug and Seats: Brass Relay Diaphragm: Nitrile (standard) or polyacrylate (high temperature) Reset Valve Body, if Used: Die case zinc Reset Valve Plug and Seat Ring, if Used: 18 8 stainless steel Approximate Weight 4.53 kg (10 pounds) Dimensions Refer to figure 5 Options Reverse action; Instrument pressure gauge; stainless steel bellows; Gauge markings in bar, kg/cm 2, kpa, or Psig/kPa; and High temperature gasket and relay materials NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 - Process Instrument Terminology. 1. Either direct or reverse acting. 2. The pressure/temperature limits in this document and any other applicable standard or code limitation should not be exceeded. 2

2506/2516 Receiver Controllers Product Bulletin Table 1. Supply Pressure Data OUTPUT SIGNAL STANDARD SUPPLY AND OUTPUT NORMAL OPERATING SUPPLY PRESSURE (2) PRESSURE GAUGE INDICATIONS (1) Bar Psig 0.2 to 1.0 bar (3 to 15 psig) 0 to 30 psig 1.5 20 0.4 to 2.0 bar (6 to 30 psig) 0 to 60 psig 2.4 35 1. Consult your Emerson sales office or Local Business Partner about gauges in other units. 2. Control and stability may be impaired if this pressure is exceeded. Table 2. Additional Information Proportional control (2506) Snap action control (2506) Control Mode (1) Full Output Change Obtainable Over Output Of: Output Signal Proportional plus reset control (2516) Proportional plus reset with anti reset windup (2516F) Proportional Band: Adjustable from 0 to 100% of transmitter signal. Snap Action: Control output is at 0 or 100% of input supply pressure. Switching depends on position of sensor and is adjustable. Proportional Band: Adjustable from 0 to 200% of transmitter signal. Recommended setting is from 20 to 200%. Reset: Adjustable from 0.01 to 74 minute per repeat with standard reset valve setting. Proportional Band: Adjustable from 0 to 200% of transmitter signal. Recommended setting is from 20 to 200%. Reset: Adjustable from 0.01 to 74 minute per repeat with standard reset valve setting. Anti Reset Windup: Provides relief when output pressure falls or when output pressure rises depending on valve adjustment. 0.2 to 1.0 bar (3 to 15 psig) or 0.4 to 2.0 bar (6 to 30 psig) 0 to 1.4 bar (0 to 20 psig) or 0 to 2.4 bar (0 to 35 psig) 0.2 to 1.0 bar (3 to 15 psig) or 0.4 to 2.0 bar (6 to 30 psig) 1. Proportional control is continuously active between 0 and 100 percent of the transmitter signal span. Differential gap provides snap action between 0 and 100 percent of the transmitter signal. Do not use reset controllers in snap action. Figure 1. Steady State Air Consumption 2 SUPPLY AIR FLOW, SCFH BAND SETTING OF 5 BAND SETTING OF 0 OR 10 2 SUPPLY AIR FLOW, SCFH BAND SETTING OF 5 BAND SETTING OF 0 OR 10 OUTPUT, PSIG 1 0.2 TO 1.0 BAR (3 TO 15 PSIG) OUTPUT SIGNAL RANGE OUTPUT, PSIG 1 0.4 TO 2.0 BAR (6 TO 30 PSIG) OUTPUT SIGNAL RANGE Notes 1 To convert psig to bar, multiply by 0.06895. 2 Scfh standard cubic feet per hour (60 F and 14.7 psia). To convert to normal M 3 /hr normal cubic meteres per hour (0 C and 1.01325 bar, absolute ), multiply by 0.0268 A7242 3

Product Bulletin 2506/2516 Receiver Controllers Figure 2. Fisher 2506 Receiver Controller Schematic TRANSMITTER INPUT REVERSING SWITCH BELLOWS VENT OR REMOTE SETPOINT CONNECTION BELLOWS SENSING BELLOWS RESTRICTION RELAY UPPER CHAMBER NOZZLE BEAM/FLAPPER ASSEMBLY VENT SUPPLY PRESSURE RELAY LOADING PRESSURE TRANSMITTER INPUT OUTPUT PRESSURE RELAY DIAPHRAGM ASSEMBLY SUPPLY RELAY BLEED PRESSURE PRESSURE RELAY LOWER CHAMBER RELAY VALVE INNER OUTPUT PRESSURE TO CONTROL VALVE VALVE ASSEMBLY BD2388 F B2383 Principle of Operation 2506 Receiver Controller The principle of operation for the direct acting 2506 receiver controller is illustrated in figure 2. Supply pressure enters the inlet side of the relay and input pressure from the transmitter enters the reversing switch. Output pressure from the receiver controller is delivered to the diaphragm of the control valve actuator. As long as the transmitter input pressure and process level remain constant, the bellows beam remains motionless. This allows the supply pressure to bleed through the nozzle as fast as it enters the relay through the fixed restriction. If there is an increase in pressure from the transmitter, pressure increases in the sensing bellows assembly, tending to push the beam toward the nozzle. This action builds up pressure in the relay's upper chamber as air continues to pass through the fixed restriction. The buildup of pressure in the upper chamber pushes the relay diaphragm assembly downward, opening the relay supply valve. Supply pressure then flows into the relay's lower chamber until the relay diaphragm assembly is pushed back to its original position and the relay valve is closed again. The increased pressure in the lower chamber is transmitted to the diaphragm of the control valve actuator. At this same time, pressure in the proportional bellows assembly is being increased through the 3 way proportional valve assembly, which causes the beam to move away from the nozzle, thus stopping the pressure buildup in the relay's upper chamber. The receiver controller is again in equilibrium with an increased input from the transmitter and an increased output to the diaphragm of the control valve actuator. If a decrease in transmitter input pressure occurs, the reverse of the above cycle takes place, with a decrease in output pressure. 4

2506/2516 Receiver Controllers Product Bulletin Figure 3. Fisher 2516 Receiver Controller Schematic REMOTE SETPOINT BELLOWS TRANSMITTER INPUT REVERSING SWITCH BELLOWS VENT OR REMOTE SETPOINT CONNECTION BELLOWS BEAM/ FLAPPER ASSEMBLY BELLOWS RELIEF VALVE SPRING RELIEF VALVE DIAPHRAGM ADJUSTING SCREW ORIFICE SENSING BELLOWS NOZZLE RESET BELLOWS RESTRICTION RELAY DIAPHRAGM ASSEMBLY RELAY UPPER CHAMBER BEAM/ FLAPPER ASSEMBLY RELAY LOWER CHAMBER RESET VALVE RESET VALVE SUPPLY OUTPUT PRESSURE TO CONTROL VALVE VALVE OUTPUT PRESSURE VALVE 2516 RECEIVER/CONTROLLER 2516F RECEIVER/CONTROLLER 38B6019 A 38A2972 A BD2389 E B2384 1 SUPPLY PRESSURE RELAY LOADING PRESSURE TRANSMITTER INPUT OUTPUT PRESSURE RELAY BLEED PRESSURE PRESSURE RESET PRESSURE 2516 Receiver Controller The principle of operation for the 2516 receiver controller is the same as the 2506 receiver controller, but includes a reset adjustment. Refer to figure 3. Note from the principle of operation of the 2506 receiver controller that an increase in pressure from the transmitter increases the pressure in the sensing bellows, moves the beam toward the nozzle, increases the pressure to the control valve, and at the same time increases the pressure through the proportional valve to the proportional bellows, thus stopping the pressure buildup to the control valve. With the 2516 receiver controller, the pressure in the line leading to the proportional bellows slowly passes through the reset valve and builds up the pressure in the reset bellows. Pressure buildup in the reset bellows pushes the beam toward the nozzle, again increasing the pressure throughout the system to the control valve actuator and proportional bellows. Increased pressure to the control valve actuator increases pressure through the reset valve to the reset bellows and starts another increase in the pressure throughout the system and to the control valve. This pressure buildup in the system continues until the pressure from the transmitter is decreased and the system is brought back to the set point. If a change in the system causes a decrease in outlet pressure, the reverse of the above cycle takes place. The above pressure changes are simultaneous and are described above as a step by step sequence for explanation purposes only. The reset adjustment dial on the 2516 receiver controller is calibrated in minutes per repeat. This is the time in minutes required for the reset action to produce a quantity correction which is equal to the correction produced by proportional control action. In other words, this is the time in minutes required for 5

Product Bulletin 2506/2516 Receiver Controllers the controller to increase its output pressure by an amount equal to previous proportional increase caused by a change in control conditions. 2516F Receiver Controller During a prolonged difference between set point and the controlled variable, such as encountered with intermittent control applications (e.g., batch temperature control or wide open monitors on pressure control), reset ramps the controller output to either zero or full supply pressure; this condition is reset windup. When the controlled variable crosses the set point, there will be a delay before the controller output responds to the change in controlled variable. Anti reset windup minimizes this delay and permits returning the controlled variable to set point more quickly with minimal overshoot. The 2516 receiver controller also has an anti reset windup relief valve (2516F). Refer to figure 3. This valve provides differential pressure relief to prevent proportional pressure from exceeding reset pressure by more than a set value. The valve consists of two pressure chambers separated by a spring loaded diaphragm. Reset pressure registers on the spring side of the diaphragm and proportional pressure registers on the other side. As long as controlled pressure changes are slow enough for normal proportional and reset action, the relief valve spring will keep the relief valve diaphragm from opening. However, a large or rapid increase in controller pressure will cause the relay to increase loading pressure to the control device. The increase in controller pressure also causes the pressure to increase in the proportional system and on the proportional side of the relief valve diaphragm. If this increase is greater than the relief valve spring setting, the relief diaphragm moves off the orifice in the differential relief valve. This allows the pressure on the proportional side of the diaphragm to bleed into the reset system. This action provides quick relief of excessive proportional pressure and reduces the time required by the system to return to the control point. A user can reverse the differential relief action to relieve on decreasing output pressure. 6

2506/2516 Receiver Controllers Installation Figure 4 illustrates the installation of a 2506 or 2516 receiver controller on a Fisher 2500 transmitter. In this case, the receiver controller input connection and the supply pressure connection are made at the factory. To complete the installation, a 1/4 inch line is run from the connection marked on the back of the receiver controller case (figure 5) to the connection on the diaphragm case of the actuator. Figure 6 illustrates the mounting of the 2506 or 2516 receiver controller on the yoke of an actuator. In this case, the diaphragm connection is made at the factory. The supply pressure line should be connected to the 1/4 NPT INPUT connection of the regulator, if used, mounted on the yoke of the actuator. Also, a 1/4 inch line is run from the INSTRUMENT connection on the back of the receiver controller case (figure 5) to the OUTPUT connection of the transmitter. Figure 5 illustrates the dimensions for the 2506 and 2516 receiver controller. Ordering Information When ordering, specify: Application Product Bulletin 1. Description of the service, such as throttling or on off 2. Pressure range, composition, and temperature of the process fluid 3. Ambient temperature Construction Refer to the specifications. Carefully review each specification, indicating your choice whenever a selection is to be made. 7

Product Bulletin 2506/2516 Receiver Controllers Figure 4. Receiver Controller Mounted on a Fisher 2500 Controller/Transmitter SUPPLY 2500 CONTROLLER/ TRANSMITTER 2506/2516 RECEIVER/ CONTROLLER FROM DIAPHRAGM CONNECTION TO ACTUATOR CONTROL VALVE WITH DIAPHRAGM ACTUATOR DF5357 A A6041 8

2506/2516 Receiver Controllers Product Bulletin Figure 5. Dimensions 154 (6.06) INSTRUMENT CONNECTION REGULATOR MOUNTING AREA SUPPLY CONNECTION OF REGULATOR 61 (2.38) YOKE MOUNTING PIPE STAND MOUNTING 86 (3.38) 83 (3.25) 171 (6.75) 240 (9.44) OPTIONAL GAUGES SUPPLIED ONLY WHEN SPECIFIED 226 (8.88) MOUNTING HOLES (2 PLACES) 5/16 18 UNC BELLOWS VENT OR REMOTE SET POINT CONNECTION OUTPUT CONNECTION (MARKED DIAPHRAGM) SUPPLY CONNECTION 57 (2.25) 108 (4.25) 45 (1.75) TAPPED VENT (OPTIONAL) INSTRUMENT CONNECTION CASE VENT 117 (4.62) VALUE SHOWN ADDED TO 0.5 CASING DIAMETER WILL RESULT IN ENVELOPE DIMENSION 114 (4.50) 191 (7.50) AD4913 J 38B3960 A B2032 2 CASING MOUNTED YOKE MOUNTED WALL MOUNTED 9

Product Bulletin 2506/2516 Receiver Controllers Figure 6. Receiver Controller Mounted on the Actuator Yoke INDICATOR 2500 TRANSMITTER SUPPLY SUPPLY PANEL LOADER CENTRALIZED CONTROL BOARD SUPPLY 2506/2516 REMOTE RECEIVER/ CONTROLLER CONTROL VALVE WITH DIAPHRAGM ACTUATOR DF5379 A6042 10

2506/2516 Receiver Controllers Product Bulletin 11

Product Bulletin 2506/2516 Receiver Controllers Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user. Fisher is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners. The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice. Emerson Automation Solutions Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Cernay 68700 France Dubai, United Arab Emirates Singapore 128461 Singapore www.fisher.com 121986, 2017 Fisher Controls International LLC. All rights reserved.