Installation Instructions for Series C F-Frame 310+ Electronic Circuit Breaker Types FDE, HFDE, FDCE

Similar documents
Installation Instructions for Series C F-Frame 310+ Electronic Circuit Breaker Types FDE, HFDE, FDCE

Installation Instructions for KPS and KPH Circuit Breakers and Molded Case Switches

Installation Instructions for TMQV Circuit Breakers and Molded Case Switches

Installation Instructions for JDB, JD, HJD, JDC, JW HJW, JWC Circuit Breakers and Molded Case Switches

Installation Instructions for R-Frame Circuit Breakers and Molded Case Switches

with Electronic Trip Units

O & M Manual for the EATON Generator Ready Loadcenter

A WARNING. Installation Instructions for KD, HKD, KDC, CKD, CHKD Circuit Breakers I.L. 29C092C

Installation Instructions for R-Frame G-Series (RG) 310+ Trip Unit

Removal/installation instructions for Series NRX (IZMX) drawout levering (racking) mechanism

Installation Instructions for Interlocking Trip Indicator with Remote Reset for Magnum Low Voltage Circuit Breakers

Modular Metering - Trip Unit for >1200A Mains DEH41187 Application Guide

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

Installation Instructions for NW, HNW, and NWC Circuit Breakers and N-frame Series C Molded Case Switches

Two-way cable interlock kit for Magnum fixed circuit breakers

www. ElectricalPartManuals. com Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers

Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version

Cutler-Hammer. Installation Instructions for the Digitrip OPTIM Pole Trip Unit Installation and Operation with L-Frame Series C Circuit Breakers

Two-way cable interlock kit for Magnum drawout circuit breakers

CM52 Network Protector with Arc Flash Reduction Module

Digitrip Retrofit System for General Electric AKR/AKRU-6D/7D-30S Series Breakers

Reprogramming guide. Power Defense ICCB. Instructional Leaflet IL EN WARNING WARNING. Instructions apply to:

Factory Authorized Mechanism Enhancement (FAME)

Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers

TVSS Installation for RLCM/CHGENLC, RLCU, and CHGEN ATSs

N-frame Circuit Breaker

CCP2-FLR1-21_ flange-rod operating mechanism

Q and M-Frame Circuit Breaker Instruction Leaflet for Installation and Operation for Thermal Magnetic Trip Units

Advanced Test Equipment Rentals ATEC (2832)

Cutler-Hammer. Installation Instructions for the ND OPTIM 550 PowerNet and/or Zone Interlock Accessories (ICK 550N, ZGK550N, ZGPK550N) I.L.

I.L. 29C121A WARNING 1. INTRODUCTION. Maximum Freq. Maximum Dielectric Voltage Current Withstand (V) (A) Voltage (V)

Instruction Booklet IB E. Contents

3-way multi-family drawout cable interlock kit - type 32 - RF

Instructions for using Functional Test Kit on Digitrip 520 and 1150 family of Power Circuit Breaker Trip Units and Series G and FD MCCB Trip Units

Digitrip Retrofit System for Allis-Chalmers LA-600 F Electrically Operated Fused Breakers

2.2. Molded Case Circuit Breakers. Contents. NG-Frame ( Amperes) Series G

Q and M-Frame Circuit Breakers Instruciton Leaflet for Alarm Switch and Auxiliary Switch Combinaiton

Installation and removal instructions for Series NRX RF fixed breaker three-way Type 32 cable interlock kit

! WARNING I.L D WARNING GENERAL INFORMATION

Cutler-Hammer I.L. 29C160G WARNING NOTICE 1-0 INTRODUCTION. General Information

COOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN

Digitrip Retrofit System for Siemens-Allis RLX-1600 Breakers

COOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S )

Digitrip Retrofit System for BBC LKD 8 Breakers

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN

I.L. 29C184A File WARNING

Table Line and Load Terminals. Terminal Body Material. Wire Type. Aluminum Copper Aluminum. English English English.

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

a WARNING Allen-Bradley Parts K-Frame Circuit Breaker Instruction Leaflet for Alarm Switch and Alarm /Auxiliary Switch Combination Bul.

COOPER POWER SERIES. Pad-mounted Switchgear MN285019EN. Effective March 2017 Supersedes February 2007 (S )

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

Digitrip Retrofit System for Allis-Chalmers G-25 Breakers

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

Cutler-Hammer. Installation Instructions for Undervoltage Release Mechanism (Handle Reset) with LED for E 2 L and E 2 LM Mining Circuit Breakers

Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker

Effective November 2016 Supersedes September 1998 (S )

COOPER POWER SERIES. S.T.A.R. type LVR faulted circuit indicator installation instructions. Fault Indicators MN320005EN

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

WARNING. Instructions for Combination Bypass Isolation and Transfer Switches Amps I.L A FILE APPLICATION SAFETY PRACTICES

COOPER POWER SERIES. QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit A26 installation instructions

Cutler-Hammer I.B. ATS-RT03. Instructions for Cutler-Hammer Residential Automatic Transfer Switch

COOPER POWER SERIES. ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions. Fusing Equipment MN132017EN

COOPER POWER SERIES. Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions. Fusing Equipment MN132014EN

COOPER POWER SERIES. KA1169R Closing Coil Transfer-Switch Accessory Operation. Reclosers MN280069EN

O & M Manual for the EGSU Automatic Transfer Switch with RTC-100 Control and Integral Loadcenter-100 Amp

COOPER POWER SERIES. Dielectric grease application to recloser cable instructions. Reclosers MN280070EN

Installation Instructions for Type SM Safety Handle Mechanism for L-Frame Series C Circuit Breakers and Molded Case Switches

Magnum Breaker Remote Racking Device (MRR1000)

O & M Manual for the RLC1 Automatic Transfer Switch

Effective March 2015 Supersedes S August 2012

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

High-voltage primary bushings installation instructions

COOPER POWER SERIES. S.T.A.R. Hot line voltage indicator installation instructions. Fault Indicators MN320011EN. Indicator boot.

COOPER POWER SERIES. Testing a motor capacitor on a voltage regulator procedure instructions. Voltage Regulators MN225064EN

COOPER POWER SERIES. High-voltage primary bushings installation instructions. OEM Equipment MN800008EN

MAINFRAME HOT RUNNER TEMPERATURE CONTROL SYSTEMS. Instruction Manual

COOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN

DANGER. See Wiring Diagrams on page 7 for illustrations of both internal and connection wiring diagrams. WARNING

Cutler-Hammer I.B. ATS-RM05. Instructions for Cutler-Hammer Residential Automatic Transfer Switch

COOPER POWER SERIES. Electronic control battery testing, charging, and replacement instructions. Reclosers MN280074EN

Digitrip Retrofit System for the General Electric AKR 6D/7D-30/50 and AKRT 6D/7D-50 Series Breakers

Effective June 2016 New Issue

COOPER POWER SERIES. KA662R tank-lifting windlass assembly and installation instructions. Recloser Mountings MN280071EN

COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN

COOPER POWER SERIES. Edison Modular Fuse (EMF) Installation Instructions. Fusing Equipment MN132031EN

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

Installation Instructions for the 14" Walking Beam Interlock for L-Frame and MDL-Frame Series C Circuit Breakers and Molded Case Switches

38 kv Type VCPW-HD Simple Electrical Ground & Test Device (SEG&TD) lower terminal instruction booklet

COOPER POWER SERIES. KA716L7001 adjustable control valve kit for Types L, E, 4E, V4E, and V4L reclosers installation and adjustment instructions

Eaton Digitrip RMS and Digitrip OPTIM Trip Units with Types DSII and DSLII Low Voltage Power Circuit Breakers

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

Type DTU De-energized Tap Changer Application, Installation & Selection Guide. IL A Instruction Leaflet Page 1 September, 2003

Courtesy of CMA/Flodyne/Hydradyne Motion Control Hydraulic Pneumatic Electrical Mechanical (800) RG H ZG E C

Type NR oil switch installation and operation instructions

Freedom FlashGard Aftermarket Kit Installation Manual

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

COOPER POWER SERIES. RTE EL-BAY-O-NET FUSE Re-Fusing Instructions. Fusing Equipment MN132024EN

www. ElectricalPartManuals. com Digitrip Retrofit System for the Westinghouse DA-50 IL 33-DAC-2 WARNING

Transcription:

Instruction Leaflet IL03001E Effective April 011 Supersedes IL03001EH0 /08 Installation Instructions for Series C F-Frame 3+ Contents escription Page Introduction.............................. Installation............................... Manual Operation......................... 4 Inspection & Field Testing................... 4 Trip Unit Settings.......................... 5 Neutral Current Sensor Installation............ FE Zone Interlocking System...............

Instruction Leaflet IL03001E Effective April 011 Installation Instructions for Series C F-Frame 3+ WARNING O NOT ATTEMPT TO INSTALL, TEST, OR PERFORM MAINTENANCE ON EQUIPMENT WHILE IT IS ENERGIZE. EATH OR SEVERE INJURY AN/ OR SUBSTANTIAL PROPERTY AMAGE CAN RESULT FROM CONTACT WITH ENERGIZE EQUIPMENT. BEFORE INSPECTING THE CIRCUIT BREAKER IN AN ELECTRICAL SYSTEM, MAKE SURE THE CIRCUIT BREAKER IS SWITCHE TO THE OFF POSITION AN THAT THERE IS NO VOLTAGE PRESENT WHERE WORK IS TO BE PERFORME. ALWAYS FOLLOW GENERALLY ACCEPTE SAFETY PROCEURES. EATON IS NOT LIABLE FOR THE MISAPPLICATON OR MISINSTALLATION OF ITS PROUCTS. The user is cautioned to observe all recommendations, warnings and cautions relating to the safety of personnel and equipment, as well as all general and local health and safety laws, codes and procedures... The recommendations and information contained herein are based on Eaton experience and judgement, but should not be considered to be all-inclusive or covering every application or circumstance which may arise. If any questions arise, contact Eaton for further information or instructions. 1. Introduction The F-Frame electronic Circuit Breaker (Figure 1) is available in the 3-pole style with three rated currents (80A, 10A, 5A) and four electronic tripping options. For single-phase ground fault applications, both the supply and return must be routed through the Breaker...Throughout this document, the electronic circuit breaker will be referred to as a breaker...the circuit breaker is equipped with an electronic sensing and tripping mechanism which makes the inverse time delay release independently of ambient temperature. A thermal memory is incorporated which prevents power operation immediately after an overload trip.. Installation The installation procedure consists of inspecting and mounting the breaker, connecting and torquing the line and load terminations, and attaching terminal shield or barriers when supplied. To install the breaker, perform the following steps. THE BREAKERS ARE FACTORY SEALE. ACCESSORY INSTALLATION SHOUL BE ONE BEFORE THE BREAKER IS MOUNTE AN CONNECTE. Mounting hardware and unmounted terminations (where required) are supplied in separate packages. Make sure that the breaker is suitable for the installation by comparing nameplate data with system requirements. Inspect the breaker for completeness and check for damage before mounting. WARNING BEFORE MOUNTING THE BREAKER IN AN ELECTRICAL SYSTEM, MAKE SURE THERE IS NO VOLTAGE PRESENT WHERE WORK IS TO BE PERFORME. THE VOLTAGES IN ENERGIZE EQUIPMENT CAN CAUSE INJURY OR EATH. epending on the equipment configuration, the breaker can be mounted using different styles of hardware. The following steps describe how to mount the breaker using standard hardware. When special hardware is needed with the electrical operator, for example, the instruction leaflet describing the accessory also describes the special mounting arrangements. BEFORE MOUNTING THE BREAKER, CHECK TO SEE IF THE TERMINATION EVICES SHOUL BE INSTALLE FIRST. SEE TERMINATION INSTRUC- TIONS. To mount the breaker, perform the following steps: 1...For individual mounting panels, make sure the mounting panel is predrilled using bolt drilling plan (Figure ). For panel board mounting, only load end support mounting holes are required. For deadfront cover application, make sure panel cover is cut out to correct escutcheon dimensions (Figure 3). 1.35 (34,93) 1.35 (34,93) Line End 1.35 (34,93) 50 (19,05) Figure 1. F-Frame 3 + Electronic Circuit Breaker. The electronic options include with or without ground fault and a linear of I t response for the short delay time. The LS and LSG (catalog suffixes 33 and 35) have an I t response for the short delay time function. The LSI and LSIG (catalog suffixes 3 and 3) have a flat response for the short delay time function. The LSG and LSIG include the ground fault function. The LSI and LSIG configurations also have a zone interlock option which are specified with the 3ZG and 3ZG catalog suffixes. These breakers are designed to comply with Underwriters Laboratories, Inc. Standard UL-489 and Canadian Standards Association CSA-.. Load End Breaker Handle.85 (3,03) 14-.3 Tap Holes (M4 x.0) Figure. Breaker Mounting Bolt rilling Plan. 4.500 (11,43)

Installation Instructions for Series C F-Frame 3+ Instruction Leaflet IL03001E Effective April 011 Line End.90.313 (3,81) (58,5) Load End R50 (,35).594 (15,09) 3.40 (8,4).00 (50,98).80 (0,3) Breaker Handle Figure 3. Breaker Escutcheon imensions. 3.40 (8,4) ø.188 (4,8) Hole for access to Push-to-Trip 3.4 (9,5). If the breaker includes factory installed internal accessories, make sure accessory wiring can be reached when the breaker is mounted. 3. Position the breaker on the mounting surface. 4. Install mounting screws, washers and nuts. Tighten screws firmly, but do not exceed 8 pound-inches (3.1 N.m.) If an optional terminal end cover is to be installed with the breaker (usually line end only), it must be positioned before the cable is connected to terminals. CAUTION WHEN ALUMINUM CONUCTORS ARE USE, THE APPLICATION OF A SUITABLE JOINT COMPOUN IS RECOMMENE TO REUCE THE POSSIBILITY OF TERMINAL OVERHEATING. TERMINAL OVERHEATING CAN CAUSE NUISANCE TRIPPING AN AMAGE TO THE BREAKER. Table 1. Terminal Types. Terminal Catalog No. Terminal Body Material Screw Head Type 3TA5F * Aluminum 3/1 Socket Hex 3TA5FM * Aluminum 5mm Socket Hex 3TA5FK * Aluminum 5/1 Socket Hex AWG Wire Range Metric Wire Range Wire Type Torque Value lb. in. (N-m) #4-40 5-95 Cu/Al (13.) #4-40 5-95 Cu/Al (13.) #-300 1-150 Cu/Al 5 (31) 3TA0F * Aluminum Slotted #14-1/0.5-50 Cu/Al See Table. 3TA50FB * Aluminum Slotted #14-#4.5-1 Cu/Al See Table 3T0FB * Steel Slotted #14-1/0.5-50 Cu/Al See Table 3T150FB * Stainless Steel Slotted #4-4/0 5-95 Cu only NNote: Terminal wire connectors are UL listed for standard wire size as defined in UL 48A & UL 48B.. * Package of 3.. Individual terminal identified as TA5F1. Table. Terminal Torque Values of Slotted Head. See Table Metric Wire Range. Torque Value (N-m) AWG Wire Range Torque Value Lb in..5-3.9 #14-35 4.5 #8 40 1-5 5.0 #-4 45 35-95 5.5 #3-4/0 50 Table 3. Bolted Connections (Keeper Nut or End Cap). Termination Catalog No. Screw Head Type) Nut Thread Size Torque Value Lb in. (N-m) KPR1A/KPR1AM User Supplied -3/M5 35-(4.0) KPEKxxx Slotted -3/M5 35-(4.0) After mounting the breaker, line and load terminals and accessory leads should be connected (see accessory schematic diagram on side of breaker). IF TERMINAL SHIEL OR INTERPHASE BARRIERS ARE TO BE INSTALLE ON THE BREAKER, INSTALL THEM AFTER THE TERMINALS ARE CON- NECTE. If required, install terminal shield on breaker cover with mounting screws provided. If required, install an interphase barrier by sliding barrier into dovetail grooves between terminals. After the breaker is installed, check all mounting hardware and terminal connecting hardware for correct torque loading. Torque values for line/load terminals are provided in Tables 1, and 3. 3

Instruction Leaflet IL03001E Effective April 011 Installation Instructions for Series C F-Frame 3+ 3. Manual Operation Manual operation of the breaker is controlled by the handle and the PUSH-TO-TRIP button. The breaker has three indicated handle positions, two of which are displayed on the cover with raised lettering to indicate ON and OFF...The sliding handle barrier has color-coded indicators; red = ON, green = OFF, and white = TRIPPE...The international symbol for ON and OFF, I/O is also displayed (see Figure 4). 4. Inspection & Field Testing Although Series C molded case breakers are designed to provide years of almost maintenance-free operation, breakers in service should be inspected periodically...the following procedure describes how to inspect and test a breaker in service. WARNING O NOT ATTEMPT TO INSTALL, TEST OR PERFORM MAINTENANCE ON EQUIPMENT WHILE IT IS ENERGIZE. EATH OR SEVERE INJURY CAN RESULT FROM CONTACT WITH ENERGIZE EQUIPMENT. BEFORE INSPECTING THE CIRCUIT BREAKER IN AN ELECTRICAL SYSTEM, MAKE SURE THE CIRCUIT BREAKER IS SWITCHE TO THE OFF POSITION AN THAT THERE IS NO VOLTAGE PRESENT WHERE WORK IS TO BE PERFORME. SPECIAL ATTENTION SHOUL BE PAI TO REVERSE FEE APPLICATIONS TO ENSURE NO VOLTAGE IS PRESENT. CAUTION VERIFY THE CLEANING AGENTS OR SOLVENTS USE TO CLEAN THE BREAKER ARE SUITABLE FOR THE JOB. SOME COMMERCIAL CLEANING AGENTS WILL AMAGE THE NAME PLATES OR MOLE PARTS. Figure 4. Breaker Manual Controls. Circuit Breaker Reset After tripping, the breaker is reset by moving the breaker handle to the extreme OFF position. IN THE EVENT OF AN OVERLOA TRIP, WAIT TWO MINUTES BEFORE SWITCHING TO ON. THE WAIT WILL CLEAR A ESIGNE THERMAL ELAY. Inspection Procedure 1...Remove dust, dirt, soot, grease and/or moisture from the surface of the breaker with a lint-free dry cloth, brush or vacuum cleaner... o not blow debris into the breaker...if contamination is found, look for the source and eliminate the problem.. Switch the breaker to ON and OFF several times to verify that the mechanical linkages are free and do not bind. If mechanical linages are not free, replace the breaker. 3. Press the TRIP-TO-PUSH button to mechanically trip the breaker... Trip, reset and switch the breaker ON several times. If the mechanism does not rest each time the breaker is tripped, replace the breaker. 4. Check the base, cover and operating handle for cracks, chipping and discoloration. The breaker should be replaced if cracks or severe discoloration is found. 5. Check terminals and connectors for looseness or signs of overheating...overheating will show as discoloration, melting or blistering of conductor insulation, or as pitting or melting of conductor surfaces due to arcing...if there is no evidence of overheating or looseness, do not disturb or tighten the connections. If there is evidence of overheating, terminations should be cleaned or replaced. Before reenergizing the breaker, all terminations and cables should be refurbished to original installation conditions.. Check the breaker mounting hardware. Tighten, if necessary....check the area where the breaker is installed for any safety hazards, including personal safety and fire hazards. Exposure to certain types of chemical can cause deterioration of electrical connections. 4

Installation Instructions for Series C F-Frame 3+ Instruction Leaflet IL03001E Effective April 011 C 3 1 A I r E F G H B Test Port 1 15 5 0 4 8 4 3 1 Ii I S (xi r) SHORT. 8 1.0 M N O L P K Q J R t S/t G (ms) SHORT/GN 4 5 4 t L(s) TEST/ LONG ALARM.. 4. 3 STATUS. IG(x In) GN Settings t * G Inst. 300 Inst. J K L t M N O S (ms) 300 P Q R LSIG 8a 8 3 1 E F C G H B A I r Test Port 1 15 5 0 4 8 4 4 3 1 t L(s) IS(xIr) TEST/ LONG SHORT ALARM.. 8 1.0. 4. 3 Inst. 300 STATUS. IG(x In) t G (ms) GN GN 4 5 C A I r E TEST/ ALARM STATUS F G H 3 1 LSG B Test Port 1 15 5 0 4 8 4 4 3 t L(s) LONG 1 I S (xir) SHORT Inst. 300 ts(ms) SHORT LSI 9 4 5 C 3 1 A I r E TEST/ ALARM STATUS F G H B Test Port 1 15 5 0 4 8 4 4 3 t L(s) LONG 1 I S (xir) SHORT 4 5 5. Trip Unit Settings 1...Test Port - A test port is built into each trip unit to allow use of a functional test kit. The test kit performs a test of the Long elay, Short delay Ground Fault functions.. Test LE - To be used with a no trip functional test. This LE is a dual function light. As previously stated, the LE is used as a no trip indicator when using the test port. In normal modes, this LE indicates a high load alarm. It will light If the continuous current is 85% of the I r Setting and must be present for a 38 second duration. 3. l r - Continuous current setting - In accordance with standards requirements, the trip unit initiates a trip of the circuit breaker within hours for an overload of 135% and will trip as a function of l²t for higher currents. Continuous current values for each lettered setting are indicated by the chart displayed on the right side of the trip unit label. 4. t L - The number of seconds required to trip @ x I r., i.e. l r -50 A, t L - sec load current - 1500 A (X). The breaker will trip in seconds. 5. I S - Setting in multiples of l r. For short circuit conditions that exceed the short delay pick-up setting, the trip unit initiates a trip after a predetermined delay.. The l G - (xln) switch is the ground fault pick-up switch. It is used on the LSIG & LSG styles to set the ground fault pick-up as a percentage of I (frame current). For example, a 50 A frame with an I (xin G ) setting of 0.4 will provide a ground fault pick-up at 90 A....For the LSI style, the short delay time is a flat response determined by the ts switch settings of INST, the LE is used as a no trip indicator when using the ms, or 300 ms. For the LS styles, the short delay time is an I²t function. 8. For the LSIG style, the short delay is a flat response determined by the t sd /t g switch settings of INST, ms or 300 ms. This switch is a dual switch that also determines the ground fault time settings of INST, ms or 300 ms. For example, if the t sd /t g switch is set at position J, then both short delay time and ground fault time are at INST flat. As another example, set the t sd /t g switch at position L; the short delay flat time is INST and the ground fault flat time is at 300 ms. The LSIG label (see above 8a) should be used in conjunction with the t sd /t g switch to set any one of nine possible combinations of short delay and ground fault flat times. The LSIG label should be applied to the left side Breaker Frame Nameplate. 9. For the LSG style, the short delay time is an I²t function while the ground fault flat time is set by the t switch.. Status LE - A green status light indicates the operational status of the trip unit. If the load current exceeds approximately 0% of the maximum current rating (In) the breaker, the status light will blink on and off once each second. LS Figure 5. Trip Unit Settings. 5

Instruction Leaflet IL03001E Effective April 011 Installation Instructions for Series C F-Frame 3+. Neutral Current Sensor Installation Ground fault trip units are supplied from the factory with pigtail lead connections for a neutral current sensor (white and grey wires). A neutral current sensor is available, but must be ordered separately. Ground Fault Trip Units detect ground fault currents through Residual Sensing. They are not designed to use source ground or zero sequence ground fault sensing methods. If the system neutral is grounded, but no phase to neutral loads are used, the neutral current sensor is not necessary. In that case, the white and grey leads on the trip unit should be cut off before installation. If the system neutral is grounded and phase to neutral loads are used, then the neutral current sensor (see Figure ) must be used. It should be connected to the breaker according to the diagram in Figure. It has the same turns ratio as the phase current sensors in the trip unit sensors in the trip unit. THE POLARITY OF THE SENSOR CONNECTIONS IS CRITICAL. ALWAYS OBSERVE THE POLARITY MARKINGS ON THE INSTALLATION RAW- INGS. THE POLARITY MARKINGS ARE IENTIFIE AS WHITE OTS ON THE TRANSFORMERS. TO INSURE CORRECT GROUN FAULT EQUIPMENT PERFORMANCE, CONUCT FIEL TESTS TO COMPLY WITH NATIONAL ELECTRIC COE REQUIREMENTS UNER ARTICLE 30-95 (C). + - Figure. Neutral Sensor imensions. Source N L C R White + Neutral Sensor Grey Load Figure. Neutral Sensor iagram.

Installation Instructions for Series C F-Frame 3+ Instruction Leaflet IL03001E Effective April 011. FE Zone Interlocking System Zone selective interlocking is provided for the short delay and the ground fault delay tripping functions for improved system protection. The FE Trip Unit zone selective interlocking feature is compatible with OPTIM and igitrip Trip Units, Models 5 and higher. It will also be compatible with Series G LG Trip Units when available, as well as with other FE breakers. The zone selective interlocking feature is a means of communications over a pair of wires between two or more compatible trip units. Zone Selective interlocking will localize the effects of an interruption and provide positive coordination between circuit breakers as a response to different fault conditions and locations. Three wires exit the beaker with the following color code and function: White with Black Stripe = Zone Out White with Red Stripe = Zone In Black = Common An example of a Zone Interlock system would be a 5A FE breaker used as the upstream breaker and an 80A FE breaker as the downstream breaker. The Zout wire (white/black stripe) of the 80A breaker would be connected to the Zin wire (white/red stripe) of the 5A breaker. Both common wires (black) must be connected. More breakers could be added in a similar fashion to form a zone of protection. For faults outside the zone of protection the trip unit on the circuit breaker nearest the fault sends an interlocking signal (Zout) to the trip unit of the upstream circuit breaker (Zin). This interlocking signal restrains immediate tripping of the upstream circuit breaker until its programmed coordination time is reached. This, zone selective interlocking applied correctly can reduce damage due to circuit or ground fault conditions. A table of the settings of two breakers versus the outcomes [both trip, ownstream (n) trips], of the breakers is indicated in Table 4 for the conditions mentioned in the table heading. Table 4. Settings of Two Breakers Versus the Outcomes. Upstream ownstream INST ms 300 ms INST Both 43 ms n 43 ms n 43 ms ms Both 5 ms n 5 ms n 5 ms 300 ms Both 43 ms n 43 ms n 43 ms NNote: A single FE breaker with the Zone Interlocking feature enabled will not trip at the programmed time settings, unless Self Interlocked. To be Self Interlocked, the Zout wire is connected to the Zin wire.

Instruction Leaflet IL03001E Effective April 011 Installation Instructions for Series C F-Frame 3+ The instructions for installation, testing, maintenance, or repair herein are provided for the use of the product in general commercial applications and may not be appropriate for use in nuclear applications. Additional instructions may be available upon specific request to replace, amend, or supplement these instructions to qualify them for use with the product in safety-related applications in a nuclear facility. The information, recommendations, descriptions, and safety notations in this document are based on Eaton s experience and judgment with respect to Retrofitting of Power Breakers. This instructional literature is published solely for information purposes and should not be considered all-inclusive. If further information is required, you should consult an authorized Eaton sales representative. The sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between the parties. This literature is not intended to and does not enlarge or add to any such contract. The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and Eaton. NO WARRANTIES, EXPRESSE OR IMPLIE, INCLUING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OR WARRANTIES ARISING FROM COURSE OF EALING OR USAGE OF TRAE, ARE MAE REGARING THE INFORMATION, RECOMMENATIONS, AN ESCRIPTIONS CONTAINE HEREIN. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and description contained herein. Eaton Corporation Electrical Group 00 Cherrington Parkway Moon Township, PA 158 United States 8-ETN-CARE (8-38-3) Eaton.com 011 Eaton Corporation All Rights Reserved Printed in USA Publication No. IL03001E / TBG000539 Part No. IL03001EH0 April 011