Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

Similar documents
MODEL 422 Submersible Pump Controller

KD LV Motor Protection Relay

Axpert-CSS AMTECH DRIVES Axpert-CSS Amtech

Types of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are:

2.1 Warnings & Agency Approvals Electrical Connections - Specifications Standard Wiring Configurations...2 4

User Manual. T6 Tachometer. Online: Telephone: P.O. Box St. Petersburg, Florida 33736

PBA Series Prelube Controls

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM

320 to 327 M Series Low and Medium Voltage Motor Protection Relays

ECU-02 Ver2.1 Automatic Engine Control Unit Operators Manual

Application Engineering

RVS-DN Digital Reduced Voltage Motor Starter

SECTION MOTOR CONTROL

Induction Power Supplies

825-P Modular Protection System for motors Specification Guide

MX431 Generator Automatic Voltage Regulator Operation Manual

SDS Enclosed Star-Delta Starter User Guide

INSTALLATION INSTRUCTIONS FOR SYMCOM'S MODEL 777-HVR-SP ELECTRONIC OVERLOAD RELAY

MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES M450

SE-3SCR-LM MANUAL MOTOR LOAD MANAGER

INSTALLATION INSTRUCTIONS FOR Owner's Copy FILTERED AND REGULATED POWER SUPPLY VOLTS DC INPUT: Hz.

RVS-DX Digital Reduced Voltage Motor Starter

Application Engineering

Installation and Construction Notes for EVSE4

MAGNETIC MOTOR STARTERS

5001TCP SPEED CONTROLLER

FM200 FLOW/NO-FLOW MONITOR INSTALLATION AND TECHNICAL MANUAL 120 VAC MODEL 6/1/2017

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase

RVS-AX Instruction Manual

ABB Softstarter Benefits Charnchanok Thongprad

5001TCP SPEED CONTROLLER

HGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology

BASIC ELECTRICAL MEASUREMENTS By David Navone

DEEP SEA ELECTRONICS PLC

DC Variable Speed Drive Panel

Electropneumatic Timing Relays Series 7000 Industrial

Open Chassis Star-Delta Starter User Guide

Using an SMC-50 Solid-State Smart Motor Controller for Pump Protection

VARNA Products 15 GPM (57 LPM) Prelube Kit for MTU 4000 Series Marine Engines

HP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control

MANUAL TROUBLESHOOTING. ECM Motor. ECM / ECM-DX Series. v100 Issue Date: 08/15/ Price Industries Limited. All rights reserved.

Series BFM Bulk Flow Monitor 1A FUSE RED LED RELAY. Part Number BFM-1 BFM-2 BFM-3 BFS-1

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

Model 930 Power Control System Instruction Manual

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL

SYMBOL LEGEND DANGER WARNING NOTE THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN

MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES MV600

Electronic Ballast EVG 2000-T

Phoenix Inverter

MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM

Product Manual. 42BYGH40(M)-160-4A NEMA 17 Bipolar 5.18:1. Planetary Gearbox Stepper

MAGPOWR Spyder-Plus-S1 Tension Control

Special Specification 6058 Battery Back-Up System for Signal Cabinets

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2

MCD 200 Series Soft Starters

VC-4820 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL

DENISON HYDRAULICS Jupiter 500 Driver Card Series S

Emotron DCM Control Unit

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E

Energy Division

TO COME. CEP7 Solid-State Overload Relay for Motor Control Centers and Enclosed Control

USERS MANUAL MCD REMOTE OPERATOR

AC Rectifiers for use with Armature Actuated Brakes. Product Overview. Full Wave. Half Wave. Combination Full and Half Wave. TOR-AC Full and Half Wave

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

INDEX Section Page Number Remarks

Deep Sea Electronics Plc

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs.

TECH XP600/1100 INSTALLATION AND OPERATION MANUAL

17429X.00 SERIES MODELS:

HGM7100N SERIES (HGM7110N/7120N) GENSET CONTROLLER USER MANUAL

Power Switching Principles

Motor Protection With The MonitorPro

Starting System DS-102 Series 200. Elmatik AS P.O.Box 309 NO-3471, Slemmestad T F

Phoenix DX Sensorless AC Vector Drive. 3 HP to 3500 HP

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW

Table of Contents. For latest version, visit:

Chapter 8. Understanding the rules detailed in the National Electrical Code is critical to the proper installation of motor control circuits.

HGM501 Gen-set Controller USER MANUAL. Smartgen Technology

Application Description

OPERATING INSTRUCTIONS ECON-M

Low Frequency Inverter. User Manual

L. Photo. Figure 2: Types CA-16 Relay (rear view) Photo. Figure 1: Types CA-16 Relay (front view)

ADJUSTABLE FREQUENCY CRANE CONTROLS

SYMBOL LEGEND DANGER WARNING NOTE THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN

5220 AUTOMATIC MAINS FAILURE MODULE OPERATING MANUAL

Motor Controllers AC Semiconductor Motor Controller Type RSHP Flexy

User Manual 1KVA-5KVA INVERTER / CHARGER

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

Temperature Controllers

Phone: Fax: Web: -

Features and Benefits. Control Features

DEEP SEA ELECTRONICS PLC

Cat/DCG-6D1I/07-08/03/Ver 1 Page 2/10

TECH XP600/1100 INSTALLATION AND OPERATION MANUAL. Manufacturer of UL Listed Products.

POWERLINE 2000 Energy Management System TM

Generator Sets Controller 210. Operation Manual. Ver1.0

Transcription:

World Leader in Modular Torque Limiters Installation and Maintenance Instructions PTM-4 Load Monitor 1304 Twin Oaks Street Wichita Falls, Texas 76302 (940) 723-7800 Fax: (940) 723-7888 E-mail: sales@brunelcorp.com www.brunelcorp.com

Installation Instructions PTM-4 Load Monitor 1. INTRODUCTION 2 1.1 Method Of Operation 2 1.2 Set-up And Calibration 2 2. INSTALLATION AND WIRING 3 2.1 Typical Wiring Diagram 3 2.2 Analog Output Option Card Links 3 3. CONFIGURATION MODE 4 3.1 Amp Range 4 3.2 Full Scale Load 4 3.3 Single Or 3 Phase 4 4. CALIBRATION MODE 5 4.1 Auto-calibration 5 4.2 Manual Calibration 5 4.3 Calibration Constants Cloning 5 4.4 Start/stop 5 INDUSTRIAL CONTROL EQUIPMENT 8FA 2 5. SET-UP MODE 6 5.1 Start Delay 6 5.2 Trip Level 6 5.3 Trip Delay 6 5.4 Trip Hold 6 5.5 Trip Hysteresis 6 6. DIAGNOSTIC MODE 7 6.1 Peak Load 7 6.2 Voltage 7 6.3 Amps 7 6.4 Power 7 6.5 Quick Diagnostic Mode 7 6.6 Calculating The Power Factor 7 7. FREQUENTLY ASKED QUESTIONS 8 8. APPENDIX A 9 8.1 Calibrating For Known Torque Or Power Values 9 9. APPENDIX B 10 9.1 Using An External Current Transformer 10 10. SPECIFICATIONS 11 11. DIMENSIONS 11 12. MOUNTING BRACKET DIMENSIONS 12 1

1. INTRODUCTION 1.1 Method of Operation The PTM-4 Load Monitor measures the active electrical power (Watts or kilowatts) consumed by an AC motor. The motor active power is nearly linearly related to motor torque, which is not true for the more commonly monitored motor current. This effect is particularly noticeable below 50% of rated load, where the motor current changes very little. This fact makes it possible to use the motor active power as a very sensitive measure of motor torque, and is therefore a simple and effective method of overload or underload protection. Two trip relays are provided, which may be set for overload or underload trips and may be used to stop the motor and/or control warning devices. The relays may be set to hold (latch) on trip, in which case they may only be reset when the motor stops. Relay 1 is used for motor shutdown and is energized in the NC position for fail-safe operation in the case of power failure to the PTM-4. Relay 2 is normally de-energized in the NO position. There is also provision for an external remote trip inhibit/reset switch. Continuous logging of motor load is possible using the optional analog output card, which may be set for 4-20mA or 0-10V. The full-scale value of this output may be configured for any desired load value (up to 250%). A diagnostic mode is provided so that the values of motor power, current, voltage and peak load, may be displayed continuously, however a single press of the front panel keys ( quick diagnostic) will display these values momentarily, as shown on the front panel. When the motor stops (or in diagnostics mode) the peak load value last seen is displayed, as an aid to setting up and monitoring in general. The line voltage L1 is measured relative to a pseudoneutral voltage from an internal star resistor network connected to the L1, L2 and L3 terminals. The apparent power in L1 is the displayed Volts multiplied by the displayed Amps (single or three-phase). When using a three-phase motor, the displayed current and power should be multiplied by three to give the total power, and the displayed voltage should be multiplied by 3 to give the line to line voltage. When using a single-phase motor, the PTM-4 may be configured so that the voltage between the L1 and L2 terminals is internally multiplied by 2 in order to calculate voltage and power correctly. 1.2 Set-up and Calibration The set-up and operation of the PTM-4 is extremely straightforward and intuitive, however a full reading of this manual is recommended. When the PTM-4 is being set-up the three-digit display will alternate between a value and letters indicating the set-up parameter, which reduces the need to refer to this manual. An internal current transformer enables up to 8 Amp motors to be monitored, however there is no limit to the motor size if a standard external current transformer is used. Single or three phase motors may be used, up to 600VAC (line to line). The PTM--4 displays motor load expressed as a percentage of normal running load, which is set while the application is running under typical operating conditions, using the auto-ranging calibration feature. Trips are set relative to this 100% value: a trip level equal to or greater than 100% is automatically set as an overload, if less than 100% the trip is set as an underload. This normalized running load value of 100% may be manually adjusted up or down to achieve tripping at a specified power level (see Appendix A for information on how to do this). A start delay may be set to inhibit trips while the motor starts, because during this time high loads will be detected. 2

In this manual helpful tips are indicated with this color. 2. INSTALLATION AND WIRING CAUTION! Hazardous voltages exist! Make sure all supplies are isolated. Before attempting to reset any internal links remove the unit from the wiring cabinet or enclosure. 2.1 Typical Wiring Diagram TYPICAL WIRING DIAGRAM PTM-4 A remote inhibit/reset switch is wired as shown, this inhibit function may be required to prevent underload trips on motor stop. The remote reset contact prevents reset when the motor is running. Note that when the factory installed analog output option is set for 4-20mA use the A+ terminal for the switch return, when set for 0-10V use the A- terminal. 2.2 Analog Output Options This must be specified at the time of ordering for 4-20mA or 0-10V. 3 PH MAIN 600V 60Hz Max. CIRCUIT BREAKER OR FUSED DISCONNECT External CT required if over 8 amps locked Rotor * L1 L2 L3 T1 T2 T3 MOTOR A1 C1 A2 *Note: Current Input to PTM-4 Must be taken from phase not used by CPT (Control Power Transformer) Starter Contactor Coil EXTERNAL POWER SOURCE 85-265V AC CPT 120V AC Nominal CT+ CT- L1 L2 L3 WARNING DANGEROUS VOLTAGES DISCONNECT FROM MAIN SERVICE BEFORE PERFORMING ANY WORK. INSTALLATION MUST BE PERFORMED BY QUALIFIED PERSONNEL 1 2 RS V A P/Reset A- A+ C R1 R2 N L Remote Trip Reset Double Pole Double Throw monentary pushbotton A- Analog Output Load A+ meter RS A+ for 4-20mA out A- for 1-10V out A1 Warning Light C1 A2 Remote Trip Inhibit RS A+ for 4-20mA out A- for 1-10V out C1 For single phase applications L1 and L2 should be used, with L2 connected to N. If a neutral line is available in a three-phase application, you can simplify the wiring and improve accuracy by connecting L2 to N and not wiring L3 (in this case you should configure the unit for single-phase operation). The polarity of CT+ and CT- is not critical and may be reversed. 3

3. CONFIGURATION MODE Power up the unit, and then press and hold down the down arrow and the check to enter configuration mode. Configuration mode must be used before turning on the motor to set the current range, the full-scale analog output, and whether you are using single or threephase wiring. To exit configuration mode (or Calibration or Set Modes), hold the check down. The unit will exit any mode automatically if the buttons are not touched for a period of 25 seconds. 3.1 Amp Range Press the check to scroll to the Amp range. Set this to 1, 2, 4 or 8A to match the expected motor current (in one line for a 3-phase system). Set so that the full load motor current is between 65% to 130% of the selected range. Press up arrow to increase the value, or down arrow to decrease it. It is recommended that the range be actually changed at this stage (even if it is returned to the original value) so that the last calibration is cancelled. Then you will get a zero load reading prior to calibration, which will not give spurious relay trips. 3.2 Full Scale Load Press the check to scroll to the 0-10V or 4-20mA analogue output full-scale load setting. Set the load value you want to give 10V or 20mA output. Normally this value will be 150% to 250%. 3.3 Single or 3 Phase Press the check to scroll to three-phase or single-phase selection. It is important to set this correctly in order to calculate Power and Voltage properly. Set ON or OFF using up arrow or down arrow. If neutral is connected to the L2 terminal then set for 3-phase OFF. 4

4. CALIBRATION MODE The unit may be auto-calibrated for a load reading of 100% when the motor is running at normal load. This may be changed manually to set a different reading if required, for example to correspond with a known motor power (see Appendix A). Start the motor with a normal load. 4.1 Auto-Calibration Hold up arrow and down arrow and the check down to enter calibration mode. The Load value will adjust itself automatically to 100%. If the Amp Range has been changed then the load reading will be zero and trips will not operate, therefore it is unnecessary to short out relay contacts to get the motor started. 4.2 Manual Calibration After auto-calibration has set the load to 100%, and before 20 seconds have elapsed, the load value may be adjusted to a different value with up arrow or down arrow. This method is useful if it is required to set trips at given power levels (see Appendix A). 4.3 Calibration Constants Cloning This method may be used to clone units so that they all have identical load calibrations. To do this, enter calibration mode with the motor stopped, i.e. zero current. If the unit has been previously calibrated, the display will indicate the value of the first calibration constant (range 0-8) which may be noted for cloning other units to match this one. Otherwise a default value will be displayed which may be adjusted to the correct cloning value. Hold up arrow and down arrow and the check with the motor stopped. Adjust to the cloning value. Press the check to scroll to the second calibration constant (range 0-250), and adjust to the cloning value. 4.4 Start/Stop When the motor is started, and the load value is greater than 5%, and during the start delay, the unit will display the load value alternating with: When the motor is stopped, the unit will display the peak load seen during the last run, alternating with: 5

5. SET-UP MODE Hold up arrow and down arrow down to enter set-up mode. 5.1 Start Delay Press the check to scroll to the start delay. The value will auto-range to whole seconds if the value is greater than 9.9 seconds. The start delay will inhibit trips for the delay interval. This will need to be adjusted experimentally for optimal protection, if it is too short then trips may operate during motor acceleration. Hold up arrow or down arrow down to rapidly change the value. 5.2 Trip Level The trip values are in two repeated blocks of items (for each relay). Only trip1 is illustrated here. Press the check to scroll to trip level 1. A trip level equal to or greater than 100% is automatically set as an overload, if less than 100% the trip is set as an underload. Hold up arrow or down arrow down to rapidly change the value. 5.3 Trip Delay Press the check to scroll to trip delay 1. For an overload for example, this is the total time spent above the trip level before the trip will operate. The trip delay is set to the minimum value necessary to avoid nuisance trips, which may be caused by normal load disturbances, or the trip delay may be used to detect sustained overloads or underloads. 5.4 Trip Hold Press the check to scroll to trip hold (or latch) 1. When set to ON the relay will hold its tripped state when the load is changed or the motor is stopped. A held, or latched, relay may only be reset by holding down the check or closing an external contact when the motor is stopped. Press the check to scroll to trip level 2 etc. 5.5 Trip Hysteresis There is a fixed trip hysteresis of 5% to prevent relay chatter around the trip level. This means that if you set a trip level of 110%, the trip will be on at or above 110%, but will be off at less than 105%. Similarly for a trip level of 90% (underload) it will be on at 90% or less and off above 95%. 6

6. DIAGNOSTIC MODE 6.1 Peak Load Hold up arrow and the check down to enter diagnostic mode. The initial display will be the peak load detected since start. 6.2 Voltage When in diagnostic mode, pressing up arrow will display the L1 voltage. The display will indicate the voltage from L1 to the pseudo-neutral or N (multiply by 3 to give the line to line voltage for three-phase). 6.3 Amps When in diagnostic mode, pressing down arrow will display the motor current. The current is given for L1, so for 3 phase multiply by 3 for the total motor current. 6.4 Power When in diagnostic mode, pressing the check will display the power. The display is auto ranging and will be in Watts, or kw if greater than 999Watts. The power is given for L1, so for 3 phase multiply by 3 for the total motor power. 6.5 Quick Diagnostic Mode Diagnostic mode is normally used when setting up the unit to check that the correct current range has been selected. However please note that when in Diagnostic mode, Set Mode, or Configuration modes the trips are not effective, because the load value is not available. If you want to quickly see the values for peak load, voltage, current or power when running normally, simply press the buttons as you would in diagnostic mode, but do not hold them down. In this mode the indicator will not be displayed alternating with the value, and the value will only be displayed for one second before reverting to load. Also note that in quick diagnostic mode the values for voltage and current will lag changes by several tens of seconds, however there is no lag for power or peak load values. 6.6 Calculating the Power Factor The Power Factor (PF) indicates how efficiently the motor is matched to the load. Most motors should operate with PF in the range 0.4 to 0.8 if properly loaded. PF is defined as the ratio of the active power to the apparent power (PF is often defined, as the cosine of the phase angle between the voltage and the current, but this is only true for undistorted sine waves). PF = Power / (Volts x Amps) 7

7. FREQUENTLY ASKED QUESTIONS Q Why does the display read zero or an unlikely value when the motor is running? A Check that you have used L1 for the current sensing, you must use the same phase as that connected to the L1 terminal. Check that you are using the correct current range. If you have just changed current ranges then you will read zero load when you start the motor; you must enter calibration mode and set the normal running load. Remember that this feature enables you to calibrate without any trips happening. Check that you have selected single or 3-phase depending on your wiring arrangement (single-phase selection multiplies the voltage between L1-L2 by 2). Check that you have correctly followed the calibration or cloning procedures. Q Why does the underload trip activate when I stop the motor? A In applications where the motor current decays very slowly upon stopping, an underload may be detected before a stop is detected (< 5% load). Increase the underload trip delay to avoid this nuisance tripping. If this method is not acceptable, it is possible to inhibit tripping by applying an external remote inhibit on motor switch-off using a spare NC switch on the control contactor, see the wiring diagram. Q Why is it not possible to get high enough readings to set overload trips (load>100)? A Check that the current range is set correctly, and re-run auto-calibrate. If all seems correct and you still cannot achieve high enough readings, try using the diagnostics mode. This will enable you to check the actual voltage and current values. Q Why does the trip LED stay lit after the motor is tripped and how do I turn it off? A The trip LED indicates a fault condition and if the Trip Hold function is turned ON for the trip, the relay stays held in the trip position. To reset the PTM-4 and the relay, make sure the motor is stopped, and then hold down the check or the external reset button if installed. Q Why is the peak load always higher than expected? A Try increasing the start delay, there will be a surge in load during motor start. There may also be load spikes that are shorter than the trip delay. Q Why is the remote reset not working? A You must use the A+ terminal when the analog output is 4-20mA, or the A- terminal when the analog output is 0-10V. 8

8. APPENDIX A 8.1 Calibrating for known Torque or Power values Firstly you will need data on motor power versus torque for your application. This could be experimental data using the PTM-4 as a power meter. Alternatively it may be derived from the motor manufacture s data (rated power and efficiency) and the type of mechanical system. Then a graph may be drawn as follows. If only one data point is available (from the data sheet rated power and efficiency for example) then simply draw a straight line to the origin. Now say the normal running power is found to be 250W, then you would normally calibrate so that 250W reads as 100% load. If you want to set a trip level at say 32.5ft-lb, which is 580W from the graph, then this level is: 100 x 580/250 = 232% If you find that the calculated trip level is greater than 250% then you will need to manually calibrate the running load to less than 100%. For the example above you might find that the normal running power is 200W, then you could manually calibrate this down to say 70%, giving a trip level of: 70 x 580/200 = 203% Watts (L1) Torque v Power 700 600 500 400 300 200 100 0 0 10 20 30 40 ft-lb Alternatively you may wish to have a trip level of exactly 200%, then for a normal running power of 200W as in the last example, you would manually calibrate for a load of: 200 x 200/580 = 69% Clearly these methods may be used if you simply wish to set trips based on motor power, and are not considering torque directly. 9

9. APPENDIX B 9.1 Using an External Current Transformer For less than 8A applications, the PTM-4 can be wired directly. For greater than 8A applications, choose a standard 5A secondary current transformer with a primary rated for the application. The CT range is reduced by looping cable through the CT hole, e.g. for a 60A (R CT ) rated transformer and two turns (N CT = 2) through the CT hole, the nominal current that can be monitored is 60/2 = 30A. Normally the unit would be set for the 4A range, but whatever the range chosen the actual motor current is given by: A = R CT /N CT _ reading/5 and the Power by: Power = R CT /N CT _ reading/5 A guide is to make R CT /N CT = FLC where FLC is the motor Full Load Current from the manufacturer s data sheet. For lightly loaded motors it may be necessary to increase the number of turns (N CT ) through the CT in order to achieve acceptable readings and sensitivity. CAUTION! When current is flowing through the primary of the current transformer, always have the unit connected properly, or short out the secondary terminals. If the secondary terminals are left open circuit, dangerous voltages can be developed and there is risk of electric shock! 10

10. SPECIFICATION PTM-4 LOAD MONITOR - SPECIFICATIONS Power Supply 85-264VAC 50-60Hz, 5VA max. Motor Voltage Ranges Programmable: 3 600VAC or 1 345VAC (L1 to the L2 or L3 terminal) Motor Current Ranges Programmable: 1A, 2A, 4A, 8A. (or >8A use an external 5A secondary current transformer). Frequency Display 45-65Hz Three 7 segment digits, 0.4in high, high intensity red. Two LEDs to indicate relay trips. Displayed Values Running: Load: (calibrated to read 100). Stopped: Peak Load. Status messages: Start, Stop. Set-up: Trip Levels, Start & Trip delays, Hold ON/OFF Diagnostics: Peak Load, Volts (RMS), Amps (RMS), Watts or kw (auto-ranging), Relays Trip Delays Trip Hold (latch) Start Delay Analog Output Option 1 NC, 1 NO contacts rated 10A @ 28VDC or 120VAC, 5A @ 240VAC. AC pilot duty-rating C150. 0-25s in 0.1s increments. ON/OFF select, pushbutton Reset, terminals for external Reset contacts 0-250s (0-9.9s in 0.1s increments) 0-10V or 4-20mA max. load 450 Ohms (jumper selectable). Enclosure 1.772in _ 3.071in _ 4.252in - Noral/Lexan - Gray (RAL 7035). Weight 6.5oz (184g) Wire sizes Upper terminals: 2x2.52mm (AWG 14) or 1x42mm (AWG 12). Lower terminals: 1x2.52mm (AWG 14). (Crimp ferrules, pins or tabs should be used) Mounting Environment 35/36mm DIN rail. Optional front panel adapter, or NEMA 4X enclosure. Operating temperature: -20 C to +50 C 11. DIMENSIONS 1 2 V A P/Reset 4.606 (117mm) 3.071 (78mm) 1.772 (45mm) 11

12 12. MOUNTING BRACKET DIMENSIONS

Publication: PTM4 11-10 Phone: 940.723.7800 Fax: 940.723.7888 www.brunelcorp.com 1304 Twin Oaks Street Wichita Falls, TX 76302