Installation, Operation, and Maintenance Manual. Automatic Fire Damper

Similar documents
Installation, Operation and Maintenance Manual

I-BFV.KIT Butterfly Valve Gear Operator Replacement

Utility Distribution System

AF Series Spring Return Direct Coupled Actuator

Electrical Control Panel

Installation, Operation and Maintenance Manual

Battery Control Center - Diesel

READ AND SAVE THESE INSTRUCTIONS. High Velocity Restaurant-Duty Utility Set Belt Driven for Roof Mounting

FSAF24(-S) US, FSAF120(-S) US

Direct Gas-Fired Heating

LF Series Spring Return Direct Coupled Actuator

READ AND SAVE THESE INSTRUCTIONS. Centrifugal Downblast Exhaust Fan Belt Driven for Roof & Wall Mounting

Standard Installation Combination Fire/Smoke Damper Models: FS1, FS2, FT1, FT2, FA1, FA2, TA1, TA2 Fire Damper Models: MD19, MD39, MA19, MA39

Installation, Operation, and Maintenance Instructions

Mounting Installation Instructions LM, NM, AM, GM

Your Global Flow Control Partner. Series 70 24V On/Off Electric Actuator Operation and Maintenance Manual

Series 70 24V On/Off Electric Actuator Operation and Maintenance Manual

M436A/M836A,B Damper Motors

Utility Distribution Systems Installation, Operation, and Maintenance Manual

MC-351, 421, 431, MC-4311

Installation, Operation and Maintenance Manual

MODEL SCA Installation and Operation Manual Important:

Standard Installation Combination Fire/Smoke Damper Models: FS1, FS2, FT1, FT2, FA1, FA2, TA1, TA2, FS2C2 Fire Damper Models: MD19, MD39, MA19, MA39

MA-5200 Series MA-5300 Series

Dodge Engineering & Controls, Inc. Toll Free (877) Fax: (978) EN44 and EN88 Non-Spring Return Electronic Actuators

ACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS

Standard Installation Fire/Smoke Damper Models: FR1, FR2 Smoke Damper Models: SR1, SR2

INSTALLATION, OPERATION AND MAINTENANCE MANUAL WALL EXHAUST FANS BELT DRIVE XBL FANS

M Remote Mounting Kit

Belimo is the Worldwide Leader in Fire and Smoke Actuation

Centrifugal Cabinet Fans Model BCF Belt Drive Low-Profile

MAx-305 & MAx-318 Series MAx-405 Through MAx-419 Series Two-Position Actuators

OIL FIELD ELECTRIC ACTUATOR INSTRUCTION MANUAL SPECIAL APPLICATIONS ACTUATORS Q 6.0.1

Installation Instructions

Emergency Smoke Control Centrifugal Roof Exhaust Fans

Installation Instructions

Dimensions [All numbers in brackets are in millimeters.] K4-2 US (supplied) 1/2" Centered (Default) 3/4" Centered (Field Selectable)

AMB24-3(-S) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V

RECEIVING AND HANDLING INSTALLATION SUPPLEMENTS WARRANTY SAFETY WARNING:

Propeller Hooded Roof Fans

NFB24, NFB24-S, NFX24, NFX24-S On/Off, Spring Return, 24 V

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual

RP-4000 Reserve Power Control

Standard Installation Combination Fire/Smoke Damper Models: FS1(SS), FS2(SS) Fire Damper Models: MD19(SS)

X4 Installation and Operation Manual - POWER FLAME INCORPORATED

Y20EBA Linkage Kit, M100 to Barber-Colman 1/2 to 1-1/4 Inch Valves

MA40-704X Series MA41-707X Series MA41-715X Series

M100F Incremental Motor Actuator R81F Interface Board

A25 Series Warm Air Control with Manual Reset

READ AND SAVE THESE INSTRUCTIONS. Centrifugal Upblast Exhaust Fan (Standard & High Pressure Exhaust) Belt Driven for Roof & Wall Mounting

SPECIFICATIONS ATTENTION OPERATION DESCRIPTION

D-4070 Two Stage Pneumatic Actuator

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual

Mount directly to 1.05 jackshafts. AF230 US (p. 02) AF230-S US (p. 20) AF24-S US (p. 18)

INSTALLATION, OPERATION AND MAINTENANCE MANUAL WALL EXHAUST FANS BELT & DIRECT DRIVE XB, HV, HVA, ADD, DDS, DDP

TROUBLESHOOTING GUIDE FOR HEAT PUMP BOOSTERS MODELS: HPB11, HPB15, & HPB22

Document number AMS & AMD Damper Series for Honeywell Spyder Controller Installation, Operation, and Maintenance Instructions

Installation, Operation and Maintenance Manual

MS Series MS Series MS Series

COOKSON OWNER'S MANUAL

Minimum 90 in-lb Torque. Applications. NFB, NFX Series At A Glance. NFB and NFX Series Spring Return Direct Coupled Actuator

GMX On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 100 to 240 VAC

Screw. (Note 4) Spacer for 1" filter ILL. 3. Screw

AMB24-3(-S) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V

Model FD-350. Static Rated Fire Dampers 3 Hour Fire Resistance Rating. Application. Ratings. Construction Standard Optional.

INSTALLATION VARIABLE FREQUENCY DRIVE THREE PHASE ALX SERIES SPUN ALUMINUM EXHAUSTERS

Installation, Operation and Maintenance Manual

Pro Island Ventilation Hoods

TS-E TURBO STEAM ELECTRIC COUNTERTOP CONVECTION STEAMER PARTS AND SERVICE MANUAL

Quarter Master Chief Series 92 Actuator

Series 41 and 81 Modutrol IV Motors

Fire, Smoke, and Combination Fire Smoke Dampers

CFSD Series. Product Description

OPEN/CLOSE SERVICE ELECTRIC ACTUATORS OPERATION AND MAINTENANCE MANUAL COMMERCIAL AND INDUSTRIAL VALVES AND AUTOMATION

M Damper Mount Linkage Kit Installation. Item Description Quantity Item Description Quantity Nuts 2

M9216 Series Electric Spring Return Actuators

Mounting Installation Instructions NKQ, GK

Vane Axial Fans Models VAB and VAD. Belt and Direct Drive

LMB24-3 (-S)(-T) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V

Centrifugal Cabinet Fans Model BDF. Belt Drive Duct Fan

AMCA International. Guide for Commissioning and Periodic Performance Testing of Fire, Smoke and Other Life Safety Related Dampers

INSTALLATION MANUAL. Melink Corporation (513) Revision

Surepowr Series 100 Installation Manual

Instruction Manual for Barber-Colman Series EA Electric High Torque Actuators

AM-676, AM , AM-690-R, AM-692, AM-693-R, AM-762, and AM-763

General Description. Product Specification. Document Digital Temperature Interlock

INSTRUCTION SHEET Replacement of Prefco McCabe Link Dampers with EMB2 MultiProducts Motor with Belimo FSxx Series

ANDCO Eagle Actuator Instruction Manual

Centrifugal Roof Supply Fans Models RSF and RSFP. Forward Curved

Prefco Internal Pulley-Cable with Multiproducts Motor and damper blade springs Replacement with Belimo FS Series Actuators

COMBINATION FIRE/SMOKE DAMPER - CLASS F MODEL BMFSD (3 HR) / MODEL BEMFSD (1½ HR)

Installation, Operation and Maintenance Manual

TS93 EMF T/PT/TDE. Surface applied door closer

VA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service

Centrifugal Roof Supply Fans Models RSF and RSFP. Forward Curved

COOKSON OWNER'S MANUAL

ENERGY RECOVERY VENTILATOR

Screw. (Note 4) Spacer for 1" filter ILL. 3. Screw

Transcription:

Installation, Operation, and Maintenance Manual Automatic Fire Damper Part # 458295 Designed to close in fire situations. Reset by activating the reset switch. UL Listed Constructed in Accordance with NFPA9 Table of Contents Automatic Fire Damper Function...............................Page 2 Operation: Fire, Test, Daily....................................Page 2 Controls...................................................Page 3 Options....................................................Page 3 Installation.................................................Page 4 Electrical Requirements......................................Page 4 Wiring Diagram Selections....................................Page Maintenance...............................................Page 7 Start Up...................................................Page 7 Trouble Shooting............................................Page 8 GREENHECK P.O. BOX 410 SCHOFIELD, WISCONSIN 5447-0410 PH. 715-359-171 www.greenheck.com

Automatic Fire Damper Function The automatic fire damper is a thermostatically controlled resettable fire damper designed to prevent the spread of fire into the kitchen exhaust ductwork. The thermostat is designed to provide automatic closure in the event of a fire where duct temperatures exceed 280 F. These conditions would typically exist after the first line fire suppression system failed to extinguish the fire. The damper will then close and shut off the exhaust fan along with any make-up air equipment, preventing the fire from entering the duct. The damper is reset by activating the reset switch after the thermostat has cooled to a temperature less than 250 F. When the damper is fully open, power to the exhaust fan and make-up air will be restored. Testing the damper requires activating the test switch, typically mounted on the face of the hood, or in a separate control panel. The damper will then close, as if the thermostat had reached 280 F. To return to normal operation simply activate the reset switch. The Automatic Fire Damper is not intended to function as an air controller. All fire dampers connected to a common fan will function simultaneously allowing the fan to be on only when all dampers are fully open. Many local code authorities do not recommend, or allow the use of fire dampers. For this reason, consult your local code authorities for specific requirements. Operation: Fire, Test, and Daily Fire: 1. At a thermostat temperature of 280 F, the damper will close, and any exhaust fan(s) and makeup air connected to the damper(s) will shut off 2. The damper will remain closed until the reset switch is activated and the thermostat has cooled to less than 250 F. Reset: 1. The damper(s) will open when the reset switch is activated. 2. When the damper is fully open the indicator will light and power will be provided to the exhaust fan and connected make-up air. Test: 1. The damper will close when the test switch is activated. 2. The indicator light will shut off. 3. The power to the exhaust fan and the connected make-up air will be disconnected. 4. The damper(s) will open when the reset switch is activated. 5. The indicator will light and power will be provided to the exhaust fan and connected makeup air when the damper is fully open. Daily: 1. Fan control and operation will not effect the open damper(s) 2. The indicator light will signify normal operation of the system with an open damper(s). 3. The user may test the damper nightly to shut off all fans and close the damper(s), eliminating nightly drafts of air through the ductwork. 2

Damper Control Panel Fig. 1 Controls Options The damper is controlled from the damper control panel (see Fig. 1) The damper control panel is located either on the hood or in a remote location. The damper control panel has a reset/test switch, and an open indicator light. The reset/test switch is a three position momentary switch. Reset controls the opening of the damper, and test controls the closing of the damper under daily conditions. The indicator light shows when the damper is completely open and power is restored to the exhaust fan and make-up air. The exhaust fan and make-up air unit only function when the damper is completely open. Damper Control Panel: Hood Mounted Remote Mounted, two gang electrical box with a switch and indicator light Control Box: Hood mounted* Remote mounted-the mounting plate will be sent attached to the 8"x8"x4" control box. * Figure 2 shows typical placement of the hood mounted controls. 3

Control Box 120/0/1 12.00 Damper Control Panel Actuator and Linkage Assembly 7.9 Thermostat (inside junction box) Typical Installation of Hood Mounted Controls Fig. 2 Installation Consult with local code authorities for specific requirements concerning exhaust fire dampers. Access to the control box, thermostat, actuator, and linkage must be available for possible maintenance. Linkage is adjusted at the factory, and should not need readjustment. If adjustment is needed, refer to the actuator field installation instructions. Electrical Requirements: Standard electrical requirements assume one hood per fan. If there are multiple hoods on a single fan, a special wiring diagram will be needed in order to wire the hood correctly. Consult factory if a special wiring diagram is needed. Figure 3 shows how the electrical logic of the system allows for multiple dampers to function simultaneously. All wiring must be in accordance with NEC (National Electric Code NFPA#70) guide lines and local building codes. 120v, 10 Amps is required in addition to the hoods existing electrical requirements. The number of electrical connections needed depends on the particular hood system ordered. 4

Fig. 3 L1 120V G H MASTER CONTROL CABINET 1 1 R1 R2 T1 3 8 5 7 T2 T3 OPTIONAL THERMOSTATS "RESET" 5 4 S1 "TEST" R1 5 R1 7 R1 11 9 LS1 LS2 LS3 LS(last) OPTIONAL ACTUATOR MOUNTED LIMIT SWITCHES OPTIONAL FACTORY WIRING OR DEVICE FIELD WIRING OR DEVICE ONE THERMOSTAT REQUIRED FOR EACH FIRE DAMPER (ACTUATOR) SHORT CIRCUIT AND OVERLOAD PROTECTION PROVIDED BY OTHERS L2 T(last) 8 R1 2 2 10 3 R2 2 7 R "RESET" 9 A1 12 A2 A3 A4 A5 A A7 A8 12 AUX 11 G "OPERATIONAL" S2 E1 TO SLAVE CONTROL CABINET N LEGEND T1 thru T(last) - 280 THERMOSTAT R1-3PDT RELAY S1-3-POSITION SWITCH MOMENTARY-OFF-MOMENTARY R2 - DPDT RELAY R - INDICATING LIGHT - RED - "RESET" A1 - DAMPER ACTUATOR #1 A2 - DAMPER ACTUATOR #2 A3 - DAMPER ACTUATOR #3 A4 - DAMPER ACTUATOR #4 A5 - DAMPER ACTUATOR #5 A - DAMPER ACTUATOR # A7 - DAMPER ACTUATOR #7 A8 - DAMPER ACTUATOR #8 AUX - AUXILIARY S2 - FAN SWITCH LS1 thru LS(last) - ACTUATOR MOUNTED LIMIT SWITCH G - INDICATING LIGHT - GREEN - "OPERATIONAL" E1 - EXHAUST FAN CIRCUIT 5

Wiring Diagram Selection Chart The correct wiring diagram was shipped with your system. If this is missing, the chart below indicates which wiring diagram to use for each situation that would standardly occur with the Automatic Fire Damper assuming one hood per fan. Please use the information below to select the appropriate wiring diagram drawing. These drawings are available on the Greenheck website, (www.greenheck.com) When selecting the drawings take into account these options: Control Box (Control Cabinet) Control Panel (Damper Switches) Hood Switches {Light(s), Fan(s), Heater(s)} Number of Duct(s) = Number of Damper(s) Drawing Numbers Chart Conditions: Control Control Panel One Damper Two Dampers Hood Switches Box (Damper Switches) (Drawing) (Drawing) *** *** *** M24778 M24782 *** *** --- M24777 M24781 *** --- --- M2477 M24780 --- --- --- M24775 M24779 *** = Hood Mounted Controls --- = Remote Mounted Controls 1. If Control Box,Damper Control Panel (Damper Switch(s)), and Control Panel (Hood Switches) are all hood mounted use drawing: For one Exhaust Damper - M24778 For two Exhaust Damper(s) - M24782 2. If Control Box and Damper Control Panel (Damper Switch(s)) are hood mounted but the Hood Control Panel (Hood Switch(s)) are remote mounted use drawing: For one Exhaust Damper - M24777 For two Exhaust Damper(s) - M24781 3. If the Control Box is hood mounted but both the Control Panel(s) are remote mounted use drawing: For one Exhaust Damper - M2477 For two Exhaust Damper(s) - M24780 4. If the Control Box, Damper Control Panel (Damper Switch(s)), Hood Control Panel (Hood Switch(s)) are all remote mounted use drawing: For one Exhaust Damper - M24775 For two Exhaust Damper(s) - M24779

All wiring diagrams are for one hood per fan. If there is more than one hood per fan then a special wiring diagram will be needed in order to wire the hood correctly. Consult factory if a special wiring diagram is needed. * All field connections must use UL listed conduit and fittings. Maintenance Start Up Access to the control box, thermostat, actuator, and linkage must be available for maintenance. The actuator linkage is adjusted at the factory and should not need readjustment. If adjustment is needed, refer to the actuator field installation instructions. The Automatic Fire Damper is designed to be a maintenance free damper (there is no link to replace). Testing the damper at least once a week is recommended to ensure proper function in the event of a fire. Visually verify that the damper is opening and closing when testing. Check the wiring connections to ensure proper installation. Open the damper by pressing the reset switch in the control panel. Allow 20 seconds for the damper to fully open. Make sure both the indicator light and fan are on. Visually verify that the damper behind the filters is open. Activate the test switch. Make sure both the indicator light and the fan light are off. Visually verify that the damper is closed. 7

Ventilation Trouble Shooting Exhaust: If the hood is not exhausting properly, check the exhaust air volume. If the air volume is lower than the design value or the hood is not exhausting all the smoke, look for: A broken or slipping belt in the exhaust fan. Improper rotation of the fan wheel. Open duct inspection panel Check the fan discharge for blockage or screen and remove. Discharge direction-it should be away from prevailing winds and upwards rather than downwards toward the roof. If the system has an exhaust duct damper, check to be sure it is open. Make-Up Air: Adequate make-up air must be supplied by mechanical means to replace all the air exhausted from the kitchen. Automatic Fire Damper Damper not opening: Is the damper reset? - Activate the reset switch and visually verify that the damper is opening. Is the power being supplied to the damper circuit? - To verify power is being supplied to the damper circuit, measure the voltage across terminals 1&2 in the control box to be sure the proper line voltage is being supplied. Are the relays and switch working properly? - Relays are located in the control box - R1 will engage when the reset switch is actuated, R2 will engage momentarily when the test switch is activated, disengaging R1. If the relays are not functioning properly the problem may be a faulty relay or reset/test switch. Is the damper stuck? - Check the damper to make sure it is free from obstruction. Is the actuator getting power? - Proper line voltage should exist across terminals L1 and L2 on the back of the actuator when the power is on and the reset switch is activated. The actuator may be faulty if it is receiving power and not in the open position. If the actuator is not receiving power verify the thermostat is providing contact. Indicator Light is not on: Is the light bulb burned out? - Remove the control panel switch cover to confirm that the light bulb is functional. Is power being supplied to the exhaust fan? - Power supplying the fan starter supplies the indicator light. It is possible the fan overload breakers have tripped. Is the limit switch making contact? - Verify that the actuator limit switch (terminals C. and N.O. in back of the actuator) is making contact when the damper is open. Is the damper linkage adjusted properly? - Refer to the actuator installation instructions. Damper is not closing: Is the damper linkage adjusted properly? - Refer to the actuator installation instructions. Is the damper blade clear of obstructions? Has the actuators internal spring failed? - The actuators internal spring should rotate its shaft to the normal position when power is not being applied. (contacts L1 and L2) 8

Field Installation Instructions for Siebe/Barber-Colman MA & MC Series UL Listed Electric Actuators with Two Position Control VENCO PRODUCTS These instructions apply to the external field installation of Barber- Colman actuators on Greenheck models VCD Control Dampers, FSD Fire/Smoke Dampers, and SMD Smoke Dampers when they are duct mounted or sleeved. Barber-Colman actuators rotate to their energized position when power is applied and spring return to their fail position when power is interrupted, except for the MC-431 which drives under power in both directions. The MA-318 and MA-418 model actuators, when installed on models FSD fire/smoke and SMD smoke dampers in accordance with these instructions, comply with the requirements of NFPA 90A and UL Standards 555 and 555S. Smoke or Fire/Smoke dampers are normally arranged to operate automatically in response to heat, signals from a heat or smoke detector, or a building alarm system. Installation must be acceptable to the authority having jurisdiction. Damper Shaft 17 20 18 9 15 1 21 19 8 7 8 7 9 1 14 13 4 5 2 3 Part No. Qty. Description 1 1 Actuator 2 1 Mounting Bracket 3 1 Mounting Plate 4 4 1/4-20 x 1 /2" Threadstud 5 3 1/4-20 x 3 /4" Threadcutting Screw 10 1/4-20 Spinlock Nut 7 3 1/2" Crankarm 8 3 5/1-18 x 1 /2" Bolt 9 3 5/1-18 Spinlock Nut 10 1 1" Crankarm 11 1 3/8-1 x 2 1 /2" Carriage Bolt Part No. Qty. Description 12 1 3/8-1 Spinlock Nut 13 2 Linkage Adjustment Pin 14 2 1/4" E-ring 15 1 Drive Link 1 1 Stand Off Bracket 17 4 1/4-20 x 1 /2" Thread Cutting Screw 18 1 Ball Bearing 19 1 1/4 x 1 /2" Knurl Pin 20 4 1/4-20 x 1 /2" Hex Bolt 21 2 #10 Tek Screw Greenheck Part Number: 454199-8/11/94 9

Instructions: Tools Required: Wrenches: (1) 3 /8", (2) 1 /2", (1) 7 /1", and (1) 9 /1" (1) Hammer 1. Install the stand off bracket to the damper. Dampers with a jackshaft 1a. Mount the stand off bracket onto the jackshaft bracket with (4) 1 /4-20 X 1 /2" thread cutting screws. Use the orientation shown on this page. Dampers without a jackshaft (Shaft Extension) 1b. Mount the stand off bracket spanning across the damper frame flanges, positioned over the control shaft. Use the orientation shown to the right. The damper shaft must be centered in the stand off bracket. Fasten to the damper frame with (4) #14 Tek screws or equal, supplied by others. Be sure not to run the screws into the damper linkage, which is between the flanges. Orientation of Stand Off Bracket for a jackshaft driven damper Orientation of Stand Off Bracket for a directly driven damper Damper A 2. Fasten the mounting plate to the mounting bracket using (4) 1 /4"- 20 x 1 /2" thread studs and (4) 1 /4"-20 spinlock nuts through the matching four hole pattern on the mounting bracket labeled A on the illustration. Note that the mounting plate has only one pattern that will match the mounting plate pattern. 3. Mount the mounting bracket to the stand off bracket using (4) 1 /4-20 x 1 /2" bolts and (4) 1 /4-20 Spinlock nuts included with this kit. Use the outer four holes of the mounting bracket for jackshafted models and the inner four holes for directly driven models. 4. If the damper has a 1 /2" dia. damper shaft, mount the ball bearing into the mounting bracket with two #10 Tek screws. The Tek screws are required to keep the thrust forces from pushing the bearing out of the mounting bracket. If the damper shaft is 1" in diameter then no ball bearing is required. A Mounting Plate Damper Shaft 5. Mount the actuator to the mounting plate in the corresponding holes using (3) 1 /4-20 x 3 /4" thread cutting screws. Note that the actuator must be mounted with the shaft in the horizontal position. 21/4" Power Return Power Position Fail Position Counterclockwise to Fail Position 10

Return 21/4" Fail Position 11 19 8 9 Steps a,b for dampers with 1 /2" shafts. Power 3" 13 7 10 Damper Shaft 12 15 c 14 14 13 Power Position Clockwise to Fail Position d Steps a,b for dampers with 1" shafts (substitute these parts in place of 7,8,9 &19) 8 7 9 21/4". Assemble the linkage. Parts needed for dampers with 1 /2" shafts: (Qty. 3) 1 /2" crankarms (#7) (Qty. 3) 5 /1" - 18 x 1 1 /2" bolts (#8) (Qty. 3) 5 /1" - 18 spinlock nuts (#9) (Qty. 1) 1 /4" x 1 /2" knurl pin (#19) (Qty. 1) Drive link (#15) (Qty. 1) Linkage adjustment pin (#13) (Qty. 2) 1 /4" E-ring (#14) (Qty. 1) 1 /4-20 spinlock nuts (#) Parts needed for dampers with 1" shafts: (Qty. 1) 1" crankarm (#10) (Qty. 1) 3 /8" - 1 x 2 1 /2" bolt (#11) (Qty. 1) 3 /8" - 1 spinlock nut (#12) (Qty. 2) Linkage adjustment pin (#13) (Qty. 1) 1 /2" crankarms (#7) (Qty. 1) 5 /1" - 18 x 1 1 /2" bolts (#8) (Qty. 1) 5 /1" - 18 spinlock nuts (#9) (Qty. 1) Drive link (#15) (Qty. 2) 1 /4" E-ring (#14) (Qty. 2) 1 /4-20 spinlock nuts (#) a. Assemble the shaft crankarms. For dampers with 1 /2" shafts: The crankarms must be placed as mirror images of each other, meaning the like sides face each other. The bolts and nuts are to be positioned as in the exploded view to the left. For dampers with 1" shafts: The 1" crankarm, part #10, must be in the position shown in the encircled exploded view shown above left. Position the bolt and nut as shown in the same diagram. b. For dampers with 1 /2" shafts: Insert the knurl pin through both of the small holes in the crankarms and tap it into place using a hammer. For dampers with 1" shafts: Insert the linkage adjustment pin (#13) into the crankarm slot. Position it 3" from the center of the damper shaft hole and fasten with a 1 /4-20 spinlock nut (see encircled diagram). c. Attach the drive link (#15) to the damper shaft crankarm(s) For dampers with 1 /2" shafts: Insert the knurl pin through one of the drive link holes. Fasten with an E-ring For dampers with 1" shafts: Insert the linkage adjustment pin (#13) through one of the drive link holes. Fasten with an E-ring d. Attach the drive link to the actuator crankarm with the linkage adjustment pin, a spinlock nut and an E-ring. Set the linkage adjustment pin at 2 1 /4" on the crankarm and secure it there with the spinlock nut. Fasten the other end through the empty drive link hole with the E-ring. 7. Note the damper shaft rotation for fail direction and orient the linkage appropriately as shown in the linkage illustration. The damper linkage is now in its fail position. Position the damper blades to their proper position (open or closed). Tighten the bolts. 8. Orient the actuator crankarm so that it will rotate through the full stroke of the actuator with the shaft crankarms rotating only 90 degrees with out power. Adjust the position as necessary. Tighten all of the crankarms. 11

9. Wire the actuator according to the appropriate wiring illustration that identifies the actuator s electrical connections. Wiring should be per an approved project or job wiring diagram and must comply with all applicable electrical codes Actuator Aux. Switch (-500 Models) NC Note: While the MC series actuator installs and links the same as the MA series, the wiring is different. A three wire control circuit is required because the actuator runs under power to both open and close the actuator. This actuator does not spring return. L1 or H L2 or G Thermostat or Switch COM NO H G 10.Apply power to the actuator. The damper blades should fully open or close and return to the fail position when power is disconnected, if they do not, adjustments can be made by resetting the crankarm position on the damper or actuator shaft, or adjusting the 2 1 /4" dimension discussed in Step #d. Wiring Diagram for MA Series Actuators Note: Motors in models MA-318 and MA-418 switch to a holding winding at the end of their stroke. Motor may overheat if stalled before cycling to the end of the power stroke. One SPDT switch can only control one actuator C1 R1 R B1 Aux. Switch B H AC Supply Actuator Part Number Power Supply Aux. VA Switch Running Holding MA-305 24 No 5 5 MA-305-500 24 Yes 5 5 MA-405 120 No 48 48 MA-405-500 120 Yes 48 48 MA-318 24 No 92 32 MA-318-500 24 Yes 92 32 MA-418 120 No 108 42 MA-418-500 120 Yes 108 42 MC-431 120 Yes 9 - SPDT Snap-Acting Control C Damper Actuator B-Rotates 0 to 180 R- Rotates 180 to 30 (0 ) Wiring Diagram for MC-431 G These terminals are marked L1 & L2 on line voltage actuators Warranty Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the purchase date. Any units or parts which prove defective during the warranty period will be replaced at our option when returned to our factory, transportation prepaid. Motors are warranted by the motor manufacturer for a period of one year. Should motors furnished by Greenheck prove defective during this period, they should be returned to the nearest authorized motor service station. Greenheck will not be responsible for any removal or installation costs. 12 Automatic Fire Damper IOM Rev. 1 FS