INSTALLATION/OPERATING INSTRUCTIONS TEMPERING VALVE HOT C GASKET STANDARD PIPE TAP MIXED HOT COLD HOT INLET INLET 3/4" 1" 1 1/4" 3/4" 1 1/4"

Similar documents
Motorized Tempering Valves with Transformers for

2-Way Motorized Valves

Motorized Stainless 2-Way Valves

FOR TECHNICAL ASSISTANCE

DIFFERENTIAL PRESSURE RELIEF REGULATOR TYPE A4AL Port Size 3/4"- 4" (20-100mm) For Ammonia, R-22, R134a, R404a, R507 and other common refrigerants.

EC-TMV & 5EF-TMV Thermostatic Mixing Valve Installation Instructions

FOR TECHNICAL ASSISTANCE

RSV16 Retro-Fit Cartridge Acorn Controls SV16 Valve Cartridge

RELEASING PRESSURE IN THE HYDRAULIC SYSTEM,

INSTALLATION/OPERATING INSTRUCTIONS TSC

Model 2008 I Battery Operated Irrigation Timer with 3/4 in. Anti-Siphon Valve

Installation and Maintenance Instructions

Technical Instructions

Technical Instructions

INSTALLATION/OPERATING INSTRUCTIONS MCP

EBF-750 Deck-Mounted Battery Powered Sensor Operated Gooseneck Faucets

Installation Instructions To ensure that your installation proceeds smoothly--please read these instructions carefully before you begin.

EZ-IN Series Turbine Flowmeter

ROMAN TUB 3 VALVE LONG STEM AND TRIM INSTALLATION INSTRUCTIONS Valve Body No Trim Kit for Model No s: 1047, 1707, 1727

"WHERE TUBING AND FITTINGS COME TOGETHER"

SS-PAM PRESSURE ACTUATED MIXER Serial No. PGS0001 and higher ½ top inlets INSTALLATION INSTRUCTIONS 7 6

SAVE FOR CONSUMER INSTALLATION / OWNER S MANUAL. Includes: Tools: Mystic - Pull-Out Kitchen Faucet LKMY1041CR LKMY1041NK LKLFMY1041CR LKLFMY1041NK D 1

INSTALLATION MANUAL IMPORTANT CONSIDERATIONS TECHNICAL INFORMATION. Tools you may need

AEROMOTIVE Part # and F-Body Fuel System Kit INSTALLATION INSTRUCTIONS

HALLMARK INDUSTRIES INC

Installation For Service Only

Installation Instructions To ensure that your installation proceeds smoothly--please read these instructions carefully before you begin.

Installation Instructions

CV Control Valves Installation and Operation Manual

: 1250 gpm in the deck mode : 800 gpm while operating in the ground base - Dual Inlet : 1000 gpm while operating in the ground base - Single Inlet

Operators Manual. Model 3370 Air Cooled Recirculator rev.8/98

Air Trap TATSU2. Copyright 2013 by TLV CO., LTD. All rights reserved ISO 9001/ ISO M-02 (TATSU2) 7 August 2013.

SRC. An Outdoor Reset Control for Sub-Atmosphere Steam Systems OUTDOOR TEMPERATURE

GBP784B INSTALLATION TOOL

Force Test Stands Series TS MODELS TSA750, TSA750H, TSB100, TSC1000 & TSC1000H. User s Guide

PT-516 Pumping Trap Installation and Maintenance

Refrigerating Specialties Division 1. BULLETIN DN23-05B Type A4A-DN, A4AK-DN, A4AE-DN, A4AR-DN. January 2007 Installation and Service Information

Installation Instructions

CONTENTS. VIKING PUMP, INC. A Unit of IDEX Corporation Cedar Falls, IA USA SECTION TSM 710.1

TECHNICAL INSTRUCTIONS

SPL HICAS ELIMINATOR KIT

Free Float Air Trap G8

INSTRUCTION MANUAL. Keep this manual in a safe place for future reference BALANCED PRESSURE THERMOSTATIC STEAM TRAPS LV SERIES

Force Test Stands Series ES MODEL ES05

BASYS INSTALLATION INSTRUCTIONS FOR ELECTRONIC CAPACITANCE SENSING LAVATORY FAUCETS EFX-3XX Pedestal, Sensor Activated Lavatory Faucets

Operators Manual. Recirculating Chiller /06/08

FK75 / FK95 Quick Installation Guide

Single-Valve Powerstation

MODEL G300 BRAKE BLEEDER

TK08 TUNING KIT TECHNICAL MANUAL FOR 16/26/27/28 SERIES SHOCKS Revised 6/25/14 Tech Line: (952) Fax (952)

INSTALLATION, OPERATION & MAINTENANCE MANUAL

SAVE FOR CONSUMER INSTALLATION / OWNER'S MANUAL. Single Handle Kitchen Faucet Model # LK2500. Important! You choose the flow rate!

OWNER S MANUAL SELF-PRIMING PORTABLE UTILITY PUMP

Manufacturing Facility is ISO9001:2000. Welded Steel Pipe Conform to ASTM A53. Threads Conform to ASME B1.20.1

ECONOMAIR SERIES CYLINDERS

Installation Instructions

M Installation Guide. PRECISION Manifold Series. Introduction. A. Assemble Manifold Components

INSTALLATION INSTRUCTIONS FOR THE 45RM1, 45RM2, 45RM4, 45FS1, 45UVFS1 FIBER OPTIC FLAME SCANNERS

INSTALLATION/OPERATING INSTRUCTIONS VSP. A Variable Speed Pump Control

Installation Instructions / Warranty

Installation Instructions

Watts Series CSM-91. Grooved/Flanged Flow Measurement/Balancing Valves. Installation and Operating Instructions. Table of Contents. 1.

BMK-30. Heavy-Duty By-Pass Filtration System Installation and Servicing Instructions

Tri-Clover Manual and Air Actuated Fractional Valves

Manual. Economy Glycol Feeder. Installation Maintenance Repair Manual

OWNER S MANUAL. Submersible Sump Pumps Models: XQS33 (1/3 HP Sump Pump) XQS50 (1/2 HP Sump Pump) Suzhou Xin Qi Electric Co.,ltd

AEROMOTIVE Part # A3000 Regulator Assembly INSTALLATION INSTRUCTIONS

STAINLESS STEEL FORGED FITTINGS 3000lb 304/304L & 316/316L Forged Stainless Steel Fittings Product Specifications

ORIGINAL INSTRUCTIONS G715A. Pneumatic-hydraulic Riveter E. Warner Ave Santa Ana, CA

TECHNICAL SERVICE MANUAL

GA-160 Gas Amplifier

Installation Instructions / Warranty

UniTorq UTQ Quarter-Turn Actuator Installation and Operation Manual

MaxLite LED Linear HighBay Fixtures

Model 8309WC Barrier Free Shower & Eye/Face Wash

AEROMOTIVE Part # INSTALLATION INSTRUCTIONS

DO NOT INSULATE BELOW THIS LINE. * For sizes 1/2" to 1 1/2" add 2 1/2" to 'C' dimension.

INSTALLATION MANUAL IMPORTANT CONSIDERATIONS TECHNICAL INFORMATION. Tools you may need

INSTALLATION INSTRUCTIONS FOR THE PHOENIX FIBER OPTIC FLAME SCANNERS

DeZURIK AFR3 Filter Regulator Used on Pneumatic Cylinder Actuators

TK08 TUNING KIT TECHNICAL MANUAL FOR 16/26/27/28 SERIES SHOCKS Revised 6/17/14

Split Body Valves with Bellows Seal Series Globe Valves Series Angle Valves Series Way-Valves

MODEL 900 IMPELLER-TYPE FLOW METER

Installation Instructions

Installation Guide. Marking and Inspection Gauge. Marking Gauge. Inspection Gauge E 1. Marking and inspection gauges are combined into one gauge.

Manifold Isolation Valves

Flow Control Valve Instruction Manual

Watts Series CSM-61. Flow Measurement/Balancing Valves Sizes: 1 1 4", 1 1 2", 2", 2 1 2", and 3" (32, 40, 50, 65 and 80mm) Installation Instructions

Thermostatic Floor-Mounted Bathtub Mixer

DISCONTINUED. Installation. Aerada 900 Series Futura Faucet. With Accu-Zone (AZ) Infrared Control

Maximum Flow: 600 GPM (3800 LPM) Portable Base 1250 GPM (4800 LPM) Direct Mount. Maximum Pressure: 200 PSI (1380 Kpa, 13.8 BARS)

CRD610 Automatic Fitting Inserter

Hydraulic Transmission Jacks

MODEL 200 MULTI-JET FLOW METER

AquaSense TM ZTS6200EV Series

Old Proportioning Pumps

OWNERS MANUAL INSTALLATION AND OPERATING INSTRUCTIONS REPAIR PARTS LIST

Installation Manual TWM Performance Short throw shifter 2001 and up Hyundai Accent

11 GALLON PORTABLE AIR TANK

Full Flow Drinking Water System Model: 3MFF100

Transcription:

INSTALLATION/OPERATING INSTRUCTIONS NIPPLE A MIXED OUTLET INSERT "O" RING MIXER VALVE BODY COLD OUTLET B SPRING COLD INLET C O L D FAIRFIELD, N.J. R H O T INLET GUIDE PISTON C GASKET BONNET ADJUSTING SCREW CLEARANCE REQUIRED FOR ELEMENT REPLACEMENT BONNET ASSEMBLY VALVE SIZE 1/2" 3/4" 1 1/4" 1 1/2" 2" 2 1/2" A 4 3/4" 5 1/2" 6 3/8" 1/2" B 8" 8" 11 1/4" 19" 23" 25" 2 3/4" C 5" 5" 6" 6" CLEARANCE FOR ELEMENT REPLACEMENT " " 12" 19" 24" 24" 28" STANDARD PIPE TAP MIXED COLD OUTLET INLET INLET 1/2" 1/2" 1/2" 3/4" 1 1/4" 1 1/2" 2" 2 1/2" 3/4" 1 1/4" 1 1/2" 2" 2 1/2" 3/4" 1 1/4" 1 1/2" 2" PRESSURE DROP CHART \ PRESSURE LOSS 1 P.S.I. 2 P.S.I. 5 P.S.I. 10 P.S.I. 15 P.S.I. 20 P.S.I. 4 5 6 9 9 12 15 14 16 20 1 19 24 19 22 29 12 1 2 38 44 52 14 19 29 41 48 5 20 31 65 91 110 130 51 0 115 10 190 226 3" 4" 9" 10 1/4" 29 1/8" 3 6 1/2" 28" 28" 3" 4" 3" 4" 2 1/2" 4" 59 92 8 131 183 209 135 21 296 33 GALLONS PER MINUTE 251 405 1

INSTALLING THE FIRST read and examine all the instructions and piping diagrams in this section and the / examples on pages 4, 5, and 6. The tempering valve MUST be installed as described below. If you have any questions, contact us at our Fairfield, New Jersey facility (93)-55-4004. VALVE ORIENTATION The valve can be installed in any position. It is not necessary to pipe the valve so it is vertical or horizontal. Choose a location with at least 28" of clearance in front of the adjusting screw (#6 on the diagram below). This will allow access to internal components in the future. CONNECT THE PORT The inlet port is clearly marked "" on the valve body. Connect the hot water supply source to the port as shown at #1 on the diagram below. The hot water supply source MUST be able to provide water at least 20 F hotter than the desired outlet temperature even under maximum flow conditions. INSTALL THE THERMAL HEAT LOOP The cold water line to the hot water supply source MUST have a Thermal heat loop as shown at #2 on the diagram below (see pages 4 and 5 for explanation). The Thermal heat loop can be installed either up or down, but must be a minimum of 32 inches as measured from center to center. The Thermal heat loop prevents the higher temperature water in the hot water supply source from backing up and entering the cold water inlet side of the Heat-Timer tempering valve. As this heat transfer will occur when there is little or no flow in the system, check valves or spring checks can NOT be used (see pg. 6). TEMPERED 3 COLD 1 4 TEMPERED 6 5 OPTIONAL POSITION 2 SAMPLE INSTALLATION DIAGRAM FOR LEGEND = THERMOMETER = GATE VALVE = = CHECK VALVE 2

CONNECT THE OUTLET PORT The OUTLET port is clearly marked "OUTLET" on the valve body. The tempered water supply to the system should be taken from the brass pipe on the OUTLET port as shown at #3 on the diagram (opposite page). To adjust the valve properly, install a thermometer (# on diagram opposite page) in the tempered water line a minimum of 6 to 10 feet downstream from the outlet end of the tempering valve and before any tempered water supply feeds. CONNECT THE TEMPERED RETURN LINE The tempered water return line must be connected so it will return to the cold water supply of BOTH the hot water supply source AND ALSO the cold water inlet side of the tempering valve as shown at #4 of the opposite page diagram. (For an explanation of this piping arrangement, see page 4). A circulating pump MUST be installed on this return line, and MUST run continuously. The temperature of the tempered water circulating return line should be at least less than the outlet temperature of the valve. If the return line does not drop the, the water temperature at the outlet will begin to rise. It is beneficial to install a thermometer in the return line as close to the connection of the main cold water line as possible. CONNECT THE COLD PORT The cold water line to the valve must be taken from the main cold water supply line AFTER the tempered water return line as shown at #5 on the opposite page diagram. This is due to the fact that when there is no flow, no cold water can enter the system. By bringing the cooler return water into the cold port, the valve can maintain the correct water temperature (see pg. 4). WARNING The Heat-Timer tempering valve is a primary tempering valve and is NOT designed or recommended to be used as a "Failsafe" or "Anti-Scald" valve. For safety, it may be required to install separate anti-scald and safety devices. ADJUSTING THE First check that the valve has been installed in the manner described in the previous section. Then, carefully follow these steps to correctly adjust the outlet water temperature: 1. Turn adjusting screw (#6 on diagram opposite page) into the valve body (clockwise) until only approximately 3/4" of the screw extends from the end of the bonnet. 2. If possible, open the control valve on the cold water supply line to the tempering valve. 3. Next, open the control valve on the outlet end of the tempering valve. 4. Open a few faucets on the tempered water line and keep them running while adjusting the valve. 5. Now, open the control valve from the hot water supply source to the tempering valve. 6. Note the temperature of the tempered water circulating return line. It must be at least F cooler than the desired outlet temperature. If not, turn off the return pump, and allow the system to cool to this point.. Turn the adjusting screw out (counterclockwise) the recommended number of turns (chart below). Each turn will change the outlet water temperature approximately. 8. Wait two minutes after turning the screw before reading the temperature of the outlet tempered water. 9. Repeat steps and 8 until the desired outlet temperature is attained. Valve Size Adjusting Screw Turns 1/2 1/2 Turn at a time 3/4 1/2 Turn at a time 1 1/2 Turn at a time 1-1/4 1 Turn at a time 1-1/2 2 Turns at a time 2 2 Turns at a time 2-1/2 3 Turns at a time 3 3 Turns at a time 4 3 Turns at a time 3

TEMPERED COLD TEMPERED COLD TEMPERED TEMPERED CIRCULATING RETURN LINE OPTIONAL POSITION = THERMOMETER LEGEND : CIRC. RETURN INTO COLD, BEFORE COLD TO AND. : CIRC. RETURN TO ONLY. = GATE VALVE = CHECK VALVE = PROBLEM: When the circulating return line is piped only into the hot water supply source (as in the diagram above), the temperature of the system water will tend to be much hotter than the desired water temperature during periods of low or no flow. The system water temperature will return to normal once flow is reestablished. However, after repeated incidents, the thermostat may be damaged. The tempering valve requires that the temperature of the water at the cold port be at least less than the desired outlet water temperature. This is due to the fact that the tempering valve's function is to mix hot water with cold water to provide a constant outlet temperature. The piping diagram will not allow there to be any cold water available at the cold inlet port when there is little or no flow. When there is no flow, none of the fixtures in the system are using water. Since the pipes can not expand to take more water into the system, this means that none of the cold water from the street can enter the system. Therefore, the system water will pass out of the outlet of the valve, travel around the piping, and then return into the hot water supply source. Each time the water passes through the hot water supply source, it will get hotter and hotter. As no cold water can be mixed in, the temperature of the outlet will begin to rise. SOLUTION: By piping the circulating return line into the cold water line before the cold water supply, this situation is avoided. The cold port of the valve will see the water temperature of the circulating return line. As the system water travels through the pipes, even with no flow out, it will lose some of its temperature to the piping and the building. In most cases, the water temperature will drop at least the required. The valve will then be able to mix the hot water supply temperature with the cooler return temperature to make the desired outlet temperature. NOTE: If the desired outlet temperature is 120 F, this means the temperature of the water at the cold port can be as high as 113 F. 113 F is not normally considered to be cold. However, to the valve trying to make 120 F, it will be cold enough to mix in some of the hot water supply temperature. 4

TEMPERED COLD TEMPERED COLD TEMPERED TEMPERED CIRCULATING RETURN LINE OPTIONAL POSITION LEGEND = THERMOMETER : COLD TO TEMP. VALVE BEFORE THERMAL LOOP. = GATE VALVE = : COLD TO TEMP. VALVE AFTER THERMAL LOOP. = CHECK VALVE PROBLEM: When the cold water is piped into the tempering valve after the thermal loop (as in the diagram above), the temperature of the system water will tend to be much hotter than the desired water temperature during periods of low or no flow. The system water temperature will return to normal once flow is reestablished. However, after repeated incidents, the thermostat may be damaged. The tempering valve requires that the temperature of the water at the cold port be at least less than the desired outlet water temperature. If the temperature of the water at the cold port rises to within, or even rises above the desired outlet water temperature, the valve will have no cold water to mix in with the hot water. In fact, when both the hot and the cold port have water temperatures above the desired outlet temperature, the outlet temperature must rise. In other words, the outlet temperature of the valve can not be lower than the input temperatures. The piping arrangement will cause the temperature of the water at the cold port to rise when there is little or no flow. When no cold street water can be introduced into the system (because no water is being taken out of the fixtures), the heat from the hot water supply source will radiate up into the cold port of the valve. Eventually, the temperature of the cold port will increase to the point where the desired outlet temperature will begin to rise. Once this occurs, the system water will keep getting hotter and hotter until a fixture is opened and cold street water is reintroduced. SOLUTION: By piping the cold water to the tempering valve before the thermal loop, this situation is avoided. The heat from the hot water supply source can not radiate through the 32" minimum pipe loop. The water temperature at the cold port of the valve will therefore remain at the same temperature as the circulating return line during low flow conditions. (see SOLUTION on previous page). 5

TEMPERED COLD TEMPERED COLD TEMPERED TEMPERED OPTIONAL POSITION LEGEND = THERMOMETER : THERMAL LOOP ON COLD INLET TO. : CHECK VALVE ON COLD INLET TO. = GATE VALVE = CHECK VALVE = PROBLEM: As discussed on the previous page, when there is no flow, the heat from the hot water supply source can radiate up into the cold port of the valve. Once this occurs, the outlet water temperature will get hotter and hotter. The piping arrangement uses a check valve to prevent this flow of heat into the cold port of the valve. However, a check valve will not prevent the temperature of the cold port from rising when there is no flow out of the system fixtures. In fact, the check valve will have no effect because there is no flow. A check valve is designed to prevent the flow of water in a certain direction. A check valve would stop hot water from flowing backwards from the hot water supply source into the cold port of the valve. But, the check valve can not prevent the heat from the hot water supply source from radiating back through the piping into the cold port of the valve. Since the check valve can not stop the heat from radiating, the temperature of the cold port will rise during no flow conditions until it reaches within of the desired outlet temperature. Then the outlet temperature will begin to rise. SOLUTION: By piping the cold water to the tempering valve through the thermal loop, the heat from the hot water supply source can not radiate into the cold port (see SOLUTION on previous page). 6

REPLACING THE Select the correct replacement thermostat for your valve by referring to the chart: Valve Size Thermostat Length Heat-Timer Catalog# 1/2-1/4 910000-00 3/4-1/4 910000-00 1 11 910001-00 1-1/4 18 910002-00 1-1/2 23 910003-00 2 23 910003-00 2-1/2 2 910004-00 3 2 910004-00 4 2 910004-00 Then carefully follow the instructions to install the new thermostat: 1. Turn off all water to and from the tempering valve. 2. Place a bucket under the bonnet to catch any water and to prevent internal valve parts from falling on the floor. 3. Use a hex wrench to unscrew the bonnet assembly from the valve body. Be extremely careful to avoid any hot water which may remain in the valve and which could cause severe burns. 4. Remove the thermostat, piston, and spring from the valve body. 5. Check if the piston can slide freely inside the valve body. If it does not, then remove the piston and polish it with an emery cloth. DO NOT polish the inside of the valve body. 6. Assemble the thermostat, piston, and spring outside the valve body. Slide the piston down the thermostat body so that the thermostat guide end of the piston is positioned as shown. Then slide the spring down the thermostat so it rests on the piston.. Put the bonnet gasket onto the bonnet as shown. 8. Slide the thermostat, piston, and spring into the valve body. Make sure the end of the thermostat slides into the hole in the mixer (located in the valve body). 9. Screw the bonnet assembly into the valve body. Make sure the adjusting screw rests on the rod protruding from the thermostat. 10. Note the temperature of the tempered water circulating return line. It must be at least F cooler than the desired outlet temperature. If not, turn off the return pump, and allow the system to cool to this point (this may take several hours). 11. Follow the instructions on page 3 to adjust the valve to the desired temperature. "O" RING INSERT COLD SPRING NIPPLE MIXER VALVE BODY GUIDE PISTON GASKET BONNET ADJUSTING SCREW BONNET ASSEMBLY

TROUBLESHOOTING If the outlet water temperature is always too hot and can not be adjusted: Check that the water temperature at the cold port of the valve is below the desired outlet temperature. The valve can not produce outlet water temperatures below the temperature of the cold port. If this is the case, see the condition If the outlet water temperature is too hot after periods of no or low flow (below). The water temperature at the cold port must be at least below the desired outlet temperature. If it is not, check if there are any valves or other flow restrictions to the cold port. If the cold water line into the tempering valve does not have any flow restrictions, check the condition If the piston does not move freely in the valve body (below). If the piston can move freely, the thermostat may have failed. Call the factory for additional support. If the outlet water temperature is too hot after periods of no or low flow: Check if the cold water line to the hot water supply source has the thermal heat loop (pg. 2). If the heat trap is installed correctly, check if the circulating pump is running continuously (pg. 3) and that the tempered water circulating return line is at least less than the desired outlet temperature during the low or no flow period. Finally, make sure the tempered water return line is properly connected to the cold water inlet of the valve and the hot water supply source (pg. 3). If the outlet water temperature is always cold and can not be adjusted: The piston may be installed upside-down. Unscrew the bonnet from the valve body as described in Replacing the Thermostat (pg. ). The thermostat guide portion of the piston must be positioned as shown. SPRING GUIDE PISTON If the outlet water temperature is not hot enough and can not be adjusted: Check the temperature of the water at the hot port of the valve. The hot water supply source must provide the valve with water 20 hotter than the desired outlet water temperature. If the temperature at the hot port is not sufficient, check the hot water line for any blockage or flow restrictions. Also check that the hot water source is activated and is working properly. If it is, see the last condition. If the outlet water temperature is not hot enough during high flow conditions: Check the hot water supply source. The hot water supply source must be able to provide the valve with water 20 hotter than the desired outlet temperature at all times. If the hot water supply source can not provide sufficient hot water in maximum flow conditions, the outlet water temperature will begin to drop. If the source of hot water is sufficient, check if there are any flow restrictions between the hot water supply source and the hot port of the valve. Finally, check the next condition. If the piston does not move freely in the valve body: Take out the thermostat, spring, and piston as described in Replacing the Thermostat (pg. ). Slide the piston into the valve body and make sure it can move freely. If it catches on the valve body, remove the piston and polish it with an emery cloth. DO NOT polish the inside of the valve body. 8 LIMITED WARRANTY Heat-Timer Corporation warrants that it will replace, or at its option, repair any products or part thereof which is found defective in material or workmanship within one year from the date of installation. The foregoing is in lieu of all other warranties, express or implied, and Heat-Timer Corporation specifically disclaims any and all warranties of merchantability or fitness for a particular purpose. Under no circumstances shall Heat-Timer Corporation, its authorized representatives, affiliated or subsidiary companies be liable for special, consequential or incidental damages. Except as specially stated in these terms and conditions of sale, the sole remedy with respect to any product or part sold or manufactured by Heat-Timer Corporation shall be limited to the right to replacement, or at Heat-Timer Corporations option, repair F.O.B., Fairfield, New Jersey. For Technical Support or Additional Product Information Contact: Heat-Timer Corporation 20 New Dutch Lane Fairfield, NJ 0004 Phone (93)55-4004 Fax (93)55-4052 http://www.heat-timer.com