Laboratory Exhaust Systems

Similar documents
Laboratory Exhaust Systems

Laboratory Exhaust Systems

Energy Recovery Laboratory Exhaust

Energy Recovery Laboratory Exhaust

Laboratory Exhaust Systems. Vektor -H High Plume

Air Measuring Products. AMS Thermal Dispersion Pressure Differential

Centrifugal Cabinet Fans Model BCF. Belt Drive Low-Profile

Tube Axial Inline Fans

Air Measuring Products AMD AMS IAQ

HIGH VELOCITY FUME EXHAUST FANS

PennBarry Fan Guide Specification. Laboratory Exhaust System: Model vplume

2. Backward inclined / backward curved centrifugal wheel fans. 3. Axial / backward curved mixed flow impeller bifurcated fans.

High Performance Axial Fans

Tubular Centrifugal Fans

High Performance Axial Fans

First Inline fan in the industry to be UL/cUL Listed Power Ventilator for Smoke Control Systems

Centrifugal Roof Supply Fans Models RSF and RSFP. Forward Curved

Centrifugal Roof Supply Fans Models RSF and RSFP. Forward Curved

AMD-42V Air Measuring Station with VCD-42V Control Damper

AMD-42 Air Measuring Station with VCD-42 Control Damper

Propeller Hooded Roof Fans

Centrifugal Cabinet Fans Model BCF Belt Drive Low-Profile

TUBULAR CENTRIFUGAL INLINE FANS

INLINE CENTRIFUGAL DUCT FANS Direct and Belt Driven Models ZIDK and ZIBK

AMD-42-TD. Thermal Dispersion Air Measuring Station with VCD-42 Control Damper. Application and Design. Ratings. Features and Control Options

AMD-33 Air Measuring Station with VCD-33 Control Damper

Centrifugal Cabinet Fans Model BDF. Belt Drive Duct Fan

UTILITY BLOWERS. Models: BIUB / BIUBR / BIUBSH BAUB / DFC / FCUB. The Industrial Choice.

Direct Gas-Fired Heating

Mixed Flow Inline Fan Model EQB

AMD-33. Air Measuring Station with VCD-33 Control Damper. Application and Design. Features & Control Options

Centrifugal Inline Fans Models SQ-M and BSQ-M. Direct and Belt Drive

LINEA Low Discharge Roof Exhausters

CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Models VUDK and VUBK

Centrifugal Exhaust Fans Series C. Roof Upblast and Sidewall

MSK-1B 1 SERVING 31 - HVAC ADDITION DALTON HIGH SCOOOL RENOVATION REL

Roof Upblast and Sidewall Exhaust

Insulated Control Damper. 1/2 in. (13mm) 1/2 in. (13mm) 12 x 12 (305 x 305) 8 x 12 (203 x in. W x 120 in. H (3658mm x 3048mm) 5 in.

AMD-23-TD. Thermal Dispersion Air Measuring Station with VCD-23 Control Damper. Application. Ratings. Features and Options

Fan Efficiency Grades and System Effect and Their Effects on HVAC Systems

Thermal Isolation. Break

Insulated Control Damper. 1/2 in. (13mm) 1/2 in. (13mm) 12 x 12 (305 x 305) 8 x 12 (203 x 305) 5 in. (127mm) Parallel

Fumex. Upblast Roof Exhauster Technical Specifications BULLETIN FX17

Roof Upblast and Sidewall Exhaust

FOR USE IN SOLUTION AIR HANDLING UNITS

ZEPHYR CABINET. Single & Twin Unit Cabinet Fans. Moving Your Way BULLETIN ZC15 TABLE OF CONTENTS

Model VCD-18. Ratings. Blade Operation. Size Limitations. Features & Options

Introduction to Johnson Controls Dampers

TURNING AIR INTO SOLUTIONS. UTILITY SETS DCV BCV BCVR BCVSH BAV DDF FCV

Centrifugal Inline Fans Models SQ and BSQ Direct and Belt Drive

Twin City Fan & Blower

Baked Enamel, Epoxy, Hi Pro Polyester, Industrial Epoxy, Kynar/Hylar (70%) Permatector. Single or Reverse Flange 8 x 6 (203 x 178)

Thermal Isolation Break. Frame Type Channel Quick Connect Single or Reverse Flange Blade Action Parallel Opposed Parallel Opposed Parallel Opposed

Insulated Control Damper. 12 x 7 (305 x 178) 8 x 7 (203 x 178)

CENTRIFUGAL WALL EXHAUSTERS Models VWDK and VWBK

FBV-43. Vertical Face & Bypass Control Damper Ultra Low Leakage Aluminum Frame Construction. Application and Design. Size Limitations.

Sidewall Propeller Fans Direct Drive. Exhaust / Supply

SQUARE INLINE CENTRIFUGAL FANS

VCD-23. Flange Options. Size Limitations

CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Model VRBK

Model DFD-230 Multi-Blade Fire Damper Steel 3V Blades UL555 3 Hour Fire Resistance Rating

AMCA Seal Assures rating of Sound and Air performance. 2 year fan housing warranty, 1 year motor warranty

Model SMD-302M. Modulating Smoke Damper. Application. Steel Airfoil Blades UL 555S Leakage Class II. Ratings. Size Limitations.

Plenum Fans. Models APM and APH. Belt and Direct Drive

Document number AMS & AMD Damper Series for Honeywell Spyder Controller Installation, Operation, and Maintenance Instructions

READ AND SAVE THESE INSTRUCTIONS

TURNING AIR INTO SOLUTIONS. LOW PROFILE UPBLAST PROPELLER ROOF VENTILATORS. LUD/LUB (Standard) LUBMO (Motor Out of Airstream) LUBSH (UL Smoke & Heat)

Propeller Upblast Roof Fans

Filtered Kitchen Supply Packaged Ventilator

Centrifugal Utility Fans

Model VCD-40. Extruded Airfoil Blade Control Damper Narrowline Frame Construction. Application. Ratings. Flange Options.

VCD-23 Low Leakage CONTROL DAMPER

HVAC Control & Balancing Dampers

COMMERCIAL DUTY PLENUM FANS

TURNING AIR INTO SOLUTIONS. COMMERCIAL DUTY PLENUM FANS EPLFN EPLQN

Defining Innovation. mixed flow fans. TYPE QSL (Standard) QSLR (Restaurant) QSLSH (Smoke and Heat) QFE (Fume Hood Exhaust)

Inline and Roof Mounted Fans

SMD-201M. Application. Modulating Smoke Dampers Steel 3V Blades UL 555S Leakage Class I. Ratings. Operational Rating. Size Limitations.

Demand Based Static Pressure Reset Control for Laboratories

Element D Services Heating Ventilating and Air Conditioning ODG010107

Model VCD-20. Control Damper. Application. 3V Blade. Ratings. Flange Options. Size Limitations. Blade Operation. Features and Options

MODELS STXD & STXDe DIRECT DRIVE CENTRIFUGAL ROOF EXHAUSTERS

Mixed-Flow Blowers Page Specifications and Dimension Data Performance Data Sound Data

Model SEVCD-33. Low Leakage Airfoil Control Damper. Application and Design. Ratings (See page 3 for specific limitations) Blade Operation

HCD-135. Industrial Control Damper. Application and Design. Ratings (see page 2 and 3 for specific limitations) Standard Construction.

Mancoolers Models MCY, MCB, MCP

Tubular Centrifugal Inline Fans Page Introduction... 2 Construction Features... 3 Specification and Dimension Data TCN-D (Inline Fan- Direct

Model FSD-211. Application. Combination Fire Smoke Damper Steel 3V Blades UL 555S Leakage Class I UL /2 Hour Fire Resistance Rating.

Air Moving Solutions. low pressure mixed flow fans. QCLB QCLBR (Restaurant) QCLBSH (Smoke & Heat)

DESIGN GUIDELINES FANS PAGE 1 of 7

Model VCD-33. Low Leakage Airfoil CONTROL DAMPER. Flange Options. Blade Operation. Size Limitations

Bulletin VX05 VANEAXIAL FANS

ROUND CENTREX Centrifugal Inline Fans

Centrifugal Inline Fans

Model CFSD-211. Corridor Ceiling FIRE SMOKE DAMPER Steel 3V Blades UL 555S Leakage Class I

Air Moving Solutions. VENTILATING SETs BCV BCVU5 BCVU2 BCVSH BAV FCV

CEILING & INLINE/CABINET VENTILATORS

Installation, Operation, and Maintenance Instructions

Model VCD-43 Extruded Airfoil Blade Control Damper

MODEL TXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER

Transcription:

Laboratory Exhaust Systems Vektor -HS, Vektor -MS and Vektor -CS with Variable Geometry Nozzle September 017

Vektor -HS, Vektor -MS and Vektor -CS Greenheck s Variable Geometry Nozzle exhaust systems allow for the safe use of a variable frequency drive to adjust the lab exhaust fan flow based on actual system demand. As exhaust airflow adjusts through the high plume exhaust fans, our integral flow monitoring station and preprogrammed controls adjust the nozzle position to maintain a safe exit velocity per ANSI Z9.5. This is an ideal energy saving solution for laboratory and fume exhaust systems with high variability in peak and downtime demand such as school and university teaching laboratories. Benefits Maintains safe discharge velocity per design or ANSI Z9.5 (000 ft./min. or 15. m/s) Integral flow monitoring with fan venturi Preprogrammed nozzle control to monitor fan airflow and adjust nozzle position Reduces or eliminates need for bypass air which can further reduce system sound levels Assists in overall sound reduction during non-peak conditions such as nights and weekends Typical payback less than two years and may be eligible for local utility rebates Quick single cable connection provides easy installation Wheel Type Vektor-HS Vektor-MS Vektor-CS Centrifugal (Backward Inclined) Mixed Flow (Backward Curved) Centrifugal (Backward Inclined or Airfoil) Peak Airflow & 6,000 cfm (44,00 m /hr),000 cfm (54,400 m /hr),000 cfm (54,400 m /hr) Pressure (per fan).5 in. wg (870 Pa) 10 in. wg (,490 Pa) 10 in. wg (,490 Pa) Drive Type Belt drive Direct or belt drive Direct or belt drive Housing Construction Fans Per Common Plenum Construction Certifications Belts and drives sealed from contaminated airstream AMCA Spark B Bifurcated housing isolates drive components from contaminated airstream AMCA Spark B or C Up to Up to 4 Up to 4 AMCA Spark B explosion resistant construction - AMCA Air Performance - Florida Product Approval & NOA Certification - UL 705 Listed for Electrical - Texas Department of Insurance RV-88 AMCA Spark B or C explosion resistant construction - AMCA Sound and Air Performance - UL 705 Listed for Electrical Reduce Energy Reduce Cost Reduce Sound Drive components isolated from contaminated airstream AMCA Spark B or C AMCA Spark B or C explosion resistant construction - AMCA Sound and Air Performance - UL 705 Listed for Electrical - OSHPD-050-10 Vektor Variable Geometry Nozzle Patents Manufactured by Greenheck Fan Corp. U.S. and Foreign Patents Pending Vektor-HS, Vektor-MS and Vektor-CS are Listed for Electrical UL/cUL 705 File no. 40001 Vektor-HS Vektor-MS Vektor-CS

Variable Geometry Nozzle System 1 Variable Geometry Nozzle (VGN) with adjustable blades maintain a programmed discharge velocity. Durable blade edge seals Bearings are maintenance free Stainless steel axles 1 4 Greenheck supplied VGN controller adjusts nozzle based on individual fan volume. Preprogrammed logic relates volume to velocity and actuator position Single controller can direct up to four fans Modulating actuators with position feedback are housed in weather tight enclosure and easily removable access panel. 5 NEMA-R enclosure for indoor or outdoor mounting Feedback to Building Management System (BMS) for airflow and alarm VGN Controller for Single or Multiple Fans Factory-mounted pressure transducer provides real-time electronic signal of fan volume. 5 Sure-Aire non-invasive flow measurement uses pressure differential to provide accuracy within %. Velocity by Demand The VGN Controller accepts input signal from Building Management System (BMS) for on-the-fly set point velocity adjustments. React to changing conditions such as wind speed, wind direction, or laboratory sensor readings. Velocity range of,000 to 4,000 fpm Fan speed controlled by BMS through VFD supplied by others. All Vektor models: Meet ANSI and ASHRAE laboratory design standards Assemblies are vibration tested to AMCA standard 04-05 Can withstand 15 mph (41 kph) windload without guy wires

VGN vs Bypass Damper System Performance VAV Laboratory Exhaust Fan System Operation Laboratory exhaust fans have requirements not found in general exhaust ventilation applications. These safety requirements increase overall energy consumption making laboratory exhaust fans notorious energy consumers. To reduce costs, laboratories commonly utilize variable air volume (VAV) designs, but how the exhaust fan system is designed and controlled can mean additional energy cost reductions. Exhaust Fan System Options System with Bypass Damper Fan speed and fan exhaust volume are held constant while the bypass air damper draws outdoor air and modulates to maintain a set static pressure in the ductwork as laboratory airflow demand varies. Advantages: Constant plume height Disadvantages: Constant fan volume without reduction in fan energy Controls for bypass damper 1 Operating Sequence 1. Static pressure sensor to detect system pressure changes*. Building Management System (BMS) or controller monitors duct pressure*. Bypass Damper - Signal to modulating bypass air damper to balance duct system pressure OR. VFD Control - Signal to VFD adjusts fan volume to balance duct system pressure * Supplied by others System with VFD Control Incorporates a variable frequency drive (VFD) to vary the exhaust fan motor speed, maintaining static pressure in the ductwork. The exhaust fan(s) and their discharge outlet nozzle(s) are sized such that the ANSI required,000 fpm discharge velocity is maintained at the lowest airflow from the laboratory. Fan operates at minimum velocity only during minimum lab flow and at higher velocity and horsepower in all other conditions. Advantages: Maintains outlet velocity even at lowest performance Disadvantages: Over sizes fan motor and electric wiring Higher first cost Higher sound levels Higher velocities and overall power requirements 4

Variable Geometry Nozzle (VGN) Performance System with VGN Control VGN technology works in conjunction with an exhaust fan, VFD and building management system to maintain a minimum outlet velocity as laboratory airflow demand changes. When airflow demand changes, the fan speed is adjusted through a VFD to maintain static pressure in the ductwork, and simultaneously the nozzle outlet area modulates by adjusting the two nozzle blades. By modulating the outlet area, a constant discharge velocity can be maintained. Exhaust system operates at varying RPM, volume and power. Advantages: Maintains outlet velocity even at lowest performance Lower sound levels at maximum volume Minimizes horsepower Disadvantages: Higher first cost 6 4 5 7 Operating Sequence 1. Static pressure sensor to detect system pressure changes*. Building Management System (BMS) or controller monitors duct pressure*. Signal to VFD adjusting fan volume to balance duct system pressure 1 4. Sure-Aire flow measurement signal to VGN controller 5. Nozzle controller 6. Signal to variable geometry nozzle maintaining set discharge velocity 7. Feedback sent back to BMS, including airflow and alarms * Supplied by others Supplied by Greenheck Performance Comparison Example The following table contains information for fan selections made based on the three operating methods discussed. The selection criteria for these selections are as follows: Maximum airflow: 10,000 cfm External static pressure 1 in. wg Minimum airflow: 5,000 cfm Minimum discharge velocity of,000 fpm Exhaust System Fan Size/ Nozzle Dia. (in.) Motor HP Minimum Operating Point Brake HP Discharge Velocity (fpm) dba @ 5 ft. Maximum Operating Point Brake HP Discharge Velocity (fpm) dba @ 5 ft. Bypass Damper 4 / 4 5 4.9,185 78 4.9,185 78 VFD Control 4 / 17 10.1,165 70 9. 6,9 80 VGN Control 4 / Variable 5 1.8,000 70 4.8,000 77 Selections were made using a direct drive, bifurcated inline laboratory exhaust fan with mixed flow impeller. Vektor fans with the Variable Geometry Nozzle have a lower brake horsepower and reduced sound, while maintaining a safe nozzle discharge velocity. 5

Quick Installation Guide Easy to Install Save Time Greenheck supplied control cabling between nozzle, transducer and VGN controller Pin connectors for error free and easy connections Controller preprogrammed from factory One controller for up to four fans Wiring Overview VGN Controller Box Mount VGN controller box upright with connectors down on structural support within 0 feet from center of fan plenum. 1 Pressure Transducer Box 5 pin cable Incoming Power Options: 10V, 08V, 40V, 480V 1PH, 15 Amp Circuit 4 VFD Connection: 4 VAC fan run signal from VFD to 1FNRUN and +4V NOTE: Repeat above steps for fan number,, 4 if applicable. BMS Connection: Analog BMS Communications: (all hardwire connections) Nozzle Feedback - connect to 1NZFB1 and COM, 1NZB and COM Fan Flow - connect to 1SURAR and COM NOTE: Repeat above steps for fan number,, 4 if applicable Alarm - connect to ALM1 and ALMCOM 8 pin cable Field Wiring GFC Provided Cables NOTE: Duct pressure modulation, fan speed, isolation damper and bypass damper control wiring is by others. Wired in Four Steps: 1. Connect 5 pin cable from nozzle to factorymounted pressure transducer box (repeat step for number of fans installed). Mount provided adhesive cable clips every 1 inches down fan stack and secure cable.. Connect 8 pin cable from pressure transducer box to VGN control box. Repeat step for number of fans installed and connect as labeled 1,,, 4 for corresponding fan. Each fan is provided with () 10 meter cables; use as required.. Run power wiring in conduit to VGN controller box. 4 VAC fan run contact BMS communications Proper incoming power 4. All wiring by others per local codes Check out Greenheck's video Vektor Variable Geometry Nozzle (VGN) Quick Install Guide at greenheck.com/resources/library/videos 6

The Greenheck Vektor Advantage Computer Aided Product Selection (CAPS ) Size options presented for side-by-side comparison Sort sizes by criteria such as fan RPM, energy consumption, sound levels and effective plume height at maximum and minimum operation Full submittal information, drawings, weight, fan curves and component details, print or PDF Revit and scaled AutoCAD drawings are downloadable as configured VK-HS Revit Drawing ecaps Engineer Application Suite ecaps is an online fan and louver selection tool designed specifically for HVAC engineers. It includes online fan and louver selection and a Toolbox with helpful guides, system effects simulator, and online fan courses. ecaps guides you to choose the best value fan or louver without needing to know a lot about HVAC or our specific model names. It's quick, easy and Greenheck's ecaps ensures your selection is the most appropriate for your application. Fume Exhaust Application Based selections in ecaps guide you through the key selection criteria Browser based - no installation, no admin rights required, always updated Fast - easy in, easy out - provides just enough information to populate a schedule Revit and AutoCAD drawings VK-MS Revit Drawing VK-CS Revit Drawing Operational Profile (CAPS ) Evaluate energy savings and payback period based on expected usage with customizable 4-hour laboratory operation profile. Complete fan system AMCA Licensed AMCA Licensed as a complete assembly including discharge nozzle Performance testing of air movement, energy consumption, and sound levels Laboratory Operation Profile Vektor-HS Vektor-MS Vektor-CS 7

Family of Lab Exhaust Systems High Plume - Effective means of creating a discharge plume height to prevent re-entrainment of chemical exhaust fumes into make-up air systems. Vektor-H High Plume Discharge Nozzle Compact design / sealed airstream components Up to 6,000 cfm and 4 in. wg Vektor-MH High Plume Nozzle Mixed flow wheel / bifurcated housing Compact design Up to 47,000 cfm and 11 in. wg Vektor-CH High Plume Nozzle Up to 56,000 cfm and 1 in. wg High Plume Dilution - Fan design that entrains and mixes outside ambient air into the exhaust airstream prior to exiting out the windband discharge. Potentially hazardous exhaust or exhaust fumes are diluted and dispersed quickly. Vektor-MD High Plume Discharge Nozzle with Entrainment and Dilution Mixed flow wheel / bifurcated housing Compact design Up to 8,000 cfm and 11.5 in. wg Vektor-CD High Plume Discharge Nozzle with Entrainment and Dilution Highest efficiency / easy service design Up to 1,000 cfm and 1.5 in. wg High Plume Variable Geometry Nozzle (VGN) - The discharge area automatically adjusts to maintain a constant discharge velocity and remain compliant to design codes. VGN maximizes effective plume heights during periods of reduced flow and lower discharge velocity fixed nozzles. Vektor-HS VGN discharge nozzle technology Variable volume flow constant velocity discharge Up to 6,000 cfm and.5 in. wg Vektor-MS VGN discharge nozzle technology Variable volume flow constant velocity discharge Mixed flow wheel / bifurcated housing Up to,000 cfm and 10 in. wg Vektor-CS VGN discharge nozzle technology Variable volume flow constant velocity discharge Up to,000 cfm and 10 in. wg Our Commitment As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties. Prepared to Support Green Building Efforts P.O. Box 410 Schofield, WI 54476-0410 Phone (715) 59-6171 greenheck.com 00.LAB.1016 R 9-017 RG Copyright 017 Greenheck Fan Corp.