ULTRASONIC FLOW SENSOR IFX-M4-01

Similar documents
ULTRASONIC FLOW SENSOR QALCOSONIC FLOW 2

IFX-M4-03 IFX-M4-03_D_E_2017_05_REV.0

ULTRASONIC METER FOR HEATING AND COOLING SKU-03

Model TUR-200D Turbine Flowmeter

Liquid Turbine Flow Meter OwnerÊs Manual

SonoSensor 30 Ultrasonic flow sensor

SonoSensor 30 Ultrasonic flow meter for heating and cooling applications

Datasheet PDCSY-MW-U. Technical Overview. Features. Product warranty and total quality commitment.

Options guide. Electromagnetic flowmeters. M9xx

MULTICHANNEL ULTRASONIC FLOW METER AFLOWT UF

SonoMeter 30 Energy Meters

Octave Water Meter Installation Manual

Compact Heat Meters. Features. -A Pulsed output. -B M-Bus output. Accessories. UK Sales Tel: International Tel:

Datasheet PDCSY-MW-CHM. Technical Overview. Features. Product warranty and total quality commitment. General Information.

Flowmeter Ultrasonic Flow Metering / Dosing Device. Operating Manual

WZMC-402 Ultrasonic Apartment Energy Meters

WATER METERS OCTAVE ULTRASONIC WATER METER INSTALLATION & USER GUIDE

Flowmeter F I Gardex. Connection and installation instructions. Application. Benefits. Design and mode of operation

Fluidic Oscillation Compact Heat Meter of High-Tech Composite

A Member of the. Integrated Metering Technologies

SonoMeter 30 Energy Meters

WATERFLUX 3070 Quick Start

Model 1000 Vortex Meter

tprime TM Series 280T

WATERFLUX 3070 Technical Datasheet

Ultrasonic heat meter

Superstatic 749. Fluidic Oscillation Compact Heat Meter

A Member of the. Integrated Metering Technologies

zelsius Installation and operating manual All that counts. EnergyMetering

F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide

Fuel level sensors Strela - Users manual. Fuel level sensors Strela. Users manual

SHARKY FS 473 ULTRASONIC FLOW SENSOR

ULTRAFLOW type 65-S/65-R

WATERFLUX 3070 Technical Datasheet

ULTRASONIC FLOWMETER / HEATMETER

Type Operating Instructions. Bedienungsanleitung Manuel utilisateur

Accurate measurement of compressed air consumption and detection of leaks. Measuring the individual consumption per customer / cost centre

Orifice flowmeter F O N4

ECONOMISER SERIES E2T USER MANUAL

Range of Ultrasonic Flowmeters.

ELECTROMAGNETIC FLOW METER AFLOWT MF Modification Lite M OPERATION MANUAL PART I

WaterMAG. Electromagnetic Flowmeter for Water Applications. Model MCB10A OVERVIEW APPLICATIONS FEATURES. No. SS2-MCB

STEEMCO-MAS Flowmeter for Steam

zelsius Installation and operating manual All that counts EnergyMetering

ULTRASONIC HEAT METER

Electromagnetic flowmeters Series FLOMID Electromagnetic flowmeter for conductive liquids

HIGH POWER SOLENOID DRIVER 1

ManuFlo Page 1 MANU ELECTRONICS PTY LTD Flow Measurement Products Rev PK KMS501W & KMS502F- TW. Electromagnetic TRADEWASTE Flowmeters FEATURES:

DY-LWGY Liquid turbine flow meter

BERMAD Waterworks. Insertion Flow Meter Device (IFM)

HYDRUS ULTRASONIC METER

SBMD 75 - BMD 200 BMD BMD 600

STEEMCO Flowmeter for Steam

Series 46 Self-operated Regulators Differential Pressure and Flow Limiters Type 46-5 Type 46-6

Heat Meter Integrator

INLINE Flow sensor for hazardous area II 1 G/D - II 2 D - II 3 GD - I M1

EW447-EW452 Series Mechanical Heat Meters FOR HEATING AND COOLING APPLICATIONS

유량계전문제조업체. Electro Magnetic FLOWMETER

HYDROMETER. Operating Instructions Edition 03/ Revision 05. Ultrasonic flowmeter type SHARKY 475 [ ] A5E HYDRO.PS.022.Q5.

Paddle-wheel flow controller for On/Off control

Insertion magnetic inductive flowmeter

Silvertel. Ag Features. Multi-Stage Charging. Battery Reversal Protection. Reduced Power Consumption. Wide DC or AC Input Voltage Range

Ag Features. Multi-Stage Charging. Solar Panel or DC Input. Maximum Power Point Tracking (MPPT) Very Low Power Consumption

F111.X Flow Sensor for Hot Tap Installation INSTRUCTION MANUAL. 1. Introduction Safety Instructions Unpacking Description.

Inline Flow meter for compressed air and gases DN15 (1/2 ) - DN80 (3 )

F-2600 SERIES INLINE VORTEX FLOW METER

SITRANS F M flow sensors 711/A and 711/911E

SITRANS F flowmeters SITRANS F US. SITRANS FUT1010 Ultrasonic flowmeter. Overview. Application

RADIO FREQUENCY SYSTEMS

Paddle-wheel flow controller with optical principle for On/Off control

Heat / Chill Meter PolluCom M Installation and Operating Instructions. PolluCom M. Installation and Operating Instructions. M H 1210 INT, Page 1

Note: Boldrin reserves the right, to modify the gas meters without changing the request concerning accuracy and security. page 2

Condensed Version of Operator s Manual For The VI/VP700 Series Flowmeter and VI800 Series Flowmeter

Fluidic Oscillation Compact Heat Meter

F-2500 SERIES VORTEX METER

WATERFLUX 3000 Technical Datasheet

TEK-F LUX 1400A. Electromagnetic Flowmeter. Flow Level Temperature Pressure Valves Analyzers Accessories TekValSys FLOW

VFM4070C SWIRLMAX. Vortex Flowmeter OUTLINE FEATURES OPERATING PRINCIPLE STANDARED SPECIFICATION. General Specification. Sensor Specification

FLS F6.60 MAGMETER FLOW SENSOR INSERTION FLOW SENSORS APPLICATIONS MAIN FEATURES

Magnetic-inductive flow meter EPS / UMF2. Technical data sheet

ENGLISH. A Member of the

MEASURE TODAY. ENSURE TOMORROW. SpireMag Series T-MAG Electromagnetic BTU Meter

tekson TS Series Low Cost Ultrasonic Water Energy Flow Measurement

Paddle-wheel flow controller for On/Off control

Vortex Flow Sensors VA Di also suitable for applications in condensation and particle laden gases. Drawing 1

Sentinel Panametrics Custody Transfer Gas Ultrasonic Flowmeter

Table of Contents General safety instructions 1. Planning information 1.1 Areas of application 1.2 Measuring principle 1.3 Operational safety 2. Assam

OPTIMASS 2000 Technical Datasheet

Make sure that no hazardous fumes can build up in the piping and in the meter during commissioning, decommissioning and dismantling.

Sentinel. Panametrics Custody Transfer Gas Ultrasonic Flowmeter. GE Sensing. Applications. Features

Isoil Industria a worldwide supplier of electromagnetic flowmeters Total flow control. Accurate to the drop.

Screw-type and measuring capsule heat meter with IrDA interface and an interface for retrofitting external modules or with integrated communication.

ISE/N Automatic valve

ORIMAS Mass Flowmeter

LCMass Series Mass Flow Sensor

Ultrasonic Flowmeter. M-1500 Plus Non-invasive Inline DSP Ultrasonic Flowmeter. Operating Principle. Features

Electromagnetic flowmeters Series FLOMAT Insertion electromagnetic flowmeter for conductive liquids

SERIES FLMG MUNICIPAL/INDUSTRIAL MAGMETER INSTRUCTIONS

1/2-2 INSTALLATION INSTRUCTIONS

Pro-V Multivariable Flowmeter Model M24 In-line Vortex

Transcription:

ULTRASONIC FLOW SENSOR IFX-M4-01 TECHNICAL DESCRIPTION, OPERATING INSTRUCTION IFX-M4-01 2012-09-10

TABLE OF CONTENTS 1. APPLICATION... 3 2. TECHNICAL DATA... 4 3. PACKAGE CONTENT... 6 4. OPERATING PRINCIPLE... 6 5. MARKING AND SEALING... 6 6. SAFETY... 7 7. INSTALLATION... 7 8. CALIBRATION... 8 9. TRANSPORTATION AND STORAGE... 8 10. WARRANTY... 9 Appendix A.... 9 Appendix B1... 10 IFX-M4-01 V01 2012-09-10 2

1. APPLICATION Ultrasonic flow sensor IFX-M4-01 is designed as sub-assembly of heat meter. IFX-M4-01 is used for measuring fluid flow rate in heating systems and conversion it into electrical pulse signal. As a component of heat energy meter the IFX-M4-01 flow sensor could by used for commercial account of energy quantity in district heating plants, in factories, in single or multi family houses. IFX-M4-01 corresponds to essential requirements of the Technical Regulation for Measuring Instruments, dated 30 March 2006 (transposing in the NB s country law Directive 2004/22/EC of 31 March 2004 on measuring instruments): - Annex I Essential requirements - Annex MI-004 Heat meter, IFX-M4-01 meets the requirements according to accuracy class 2 of EN1434. IFX-M4-01 meets the requirements according environmental class C of EN1434-1. Ambient temperature: 5...55 o C Mechanical environment class: M1 Electromagnetic environment class: E2 Type reference example for technical documentation and order placing: Type Sensor IFX-M4-01 0-0-25-A* -1*-10*- 0* Permanent flow rate, m 3 /h Mounting length, mm Code 3.5 260 25 6 260 32 10 300 40 15 270 50 25 300 65 40 350 80 60 350 100 Supply Power: Internal Lithium battery External power source 3,6 VDC Code A B Length of connection cable, m : Code None 0 3 m 3 5 m 5 10 m 10 15 m 15 20 m 20 40 m 40 60 m 60 80 m 80 100 m 100 125 m 125 150 m 150 175 m 175 200 m 200 Remark: * - marked numbers are used only for order coding. (It is not used for meter marking). IFX-M4-01 V01 2012-09-10 3

2. TECHNICAL DATA 2.1. The measured parameter is a fluid volume that is converted into normalized pulse sequence. 2.2. Table of the flow sensors flow rates, lengths, connection thread (flanges) and the pressure losses P, at q =q p : Permanent flow rate, q p Length, mm Connection Limits of flow rate, m 3 /h Pressure losses lower permanent upper p, at q p, q i q p q s MPa, less than Fig. No. A appendix 3,5 260 Thread G 1 1/4 0,035 3,5 7,0 0,004 Fig. A1 6,0 260 Thread G 1 1/4 0,06 6,0 12,0 0,01 Fig. A1 10,0 300 Thread G 2 0,1 10,0 20,0 0,01 Fig. A2 15,0 270 Flange DN50 0,15 15,0 30,0 0,012 Fig. A3 25,0 300 Flange DN65 0,25 25,0 50,0 0,02 Fig. A4 40,0 350 Flange DN80 0,4 40,0 80,0 0,018 Fig. A4 60,0 350 Flange DN100 0,6 60,0 120,0 0,018 Fig. A4 2.3. Flow measurement threshold 0,2 q i 2.4. Admissible measuring error according to EN1434 (class 2): E f = (2+0,02q p /q) 2.5.Table of default settings of the pulse value depending on the permanent flow rate and sensor size: Permanent flow q p, m3/h 3,5 6 10 15 25 40 60 Pulse value, liter/ pulse 0,02 0,02 0,05 0,05 0,2 0,2 0,5 Other pulse value settings could be selected according user needs by ordering the flow sensor. The pulse value is also indicated on the label of the flow sensor. 2.6. The two modes of output pulse transmission are possible: passive (open drain) and active. The output pulses can be selected by choosing the location of the jumper JP (appendix B) 2.6.1. The passive output pulse transmission mode is set when jumper JP is located on the 2 and 3 pins (lower position). The circuit of connection to the device output pulse terminal is shown below. The drain supply voltage ranges +3... +24 V The maximum drain current 30 ma The output pulse circuit meets OD class requirements. Load resistance R D must be chosen in accordance to avoid of exceeding the maximum drain current. 2.6.2. The active output pulse transmission mode is set when jumper JP is located on the 1 and 2 pins (upper position). Such pulse transmission mode is recommended to use for transferring pulses to heat energy calculator. The voltage ranges during the pauses between pulse transmissions +3,0 + 3.6 V The voltage ranges during the pulse transmission 0... + 0,6 V The output pulse circuit meets OD class requirements. IFX-M4-01 V01 2012-09-10 4

2.6.3. In the case of normal operating of the flow sensor the output pulses are transmitted in meander style frequency packages every second. The period of signal is not shorter than 4 ms, the durations of the high and low level signal are not shorter than 2 ms. In the cases of the opposite flow, q < 0,2 q i or empty pipe condition the logical signal level is high and no pulse transmission appears. In the case of device error the logical signal level is low. The external devices that can analyze the output pulse signal level (for example: heat energy calculator ML311) can detect the situation of device error if the low signal level lasting longer than 2 second. 2.7. Device status testing. Visually the device status can be tested by pushing the test button (that is located on the inner device panel - see appendix B) and observing the indication of green and red light emission diodes (LED). Other way of recognizing the device status is possible by analyzing the logical status of pulse output signal and direction (D) output signal: Device status Green LED (1) Red LED (1) Output pulse Direction output (D) Error output (E) 1. Normal flow Blinking light No light Transmission of pulses Low level Low level 2. Opposite flow Blinking light Blinking light High level High level Low level 3. Empty pipe Steady light No light High level Low level High level 4. Device error No light Steady light Low level Low level High level 5. q > 1,1 q s No light Blinking light Amount of pulses Low level Low level corresponds to q = 1.1 q s 6. q < 0,2 q i Steady light Blinking light High level Low level Low level Remark: 1. LED indication begins when the button is pushed down. Status signals E (Error) and D (Direction) are passive signals and should be wired using the open drain output signal connection diagram such shown in 2.6.1 p. 2.8. When the measured flow rate exceeds maximal flow q s per +10 %, the flow sensor transmits the amount of pulses which corresponds to the flow rate q s +10 % and indicates corresponding overflow status code. 2.9. The flow sensor is powered: - From an external power source DC 3,6V ±0,2V (average current less than 35 μa), or - From internal +3.6V lithium battery, size C, with up to 12 years lifetime. 2.10. Table of flow sensor weight, corresponding with the nominal diameter: Permanent flow q p, m3/h 3,5 6 10 15 25 40 60 Weight, less than, kg 3,0 3,0 4,0 10,0 14,0 15,0 17,5 Dimensions of the flows sensors and its connection flanges is presented in the A appendix. 2.11. Environmental conditions: - ambient temperature 5 o C to 55 o C, - ambient humidity < 93, - atmospheric pressure 86 kpa to 106,7 kpa, - fluid temperature 10 o C to 130 o C, - fluid pressure <1,6 MPa. 2.12. Degree of protection IP65 or IP67 (with separate order) 2.13. The flow sensor meets the requirements according to 89/336/EEC, EN50082-2, EN50081-2 IFX-M4-01 V01 2012-09-10 5

3. PACKAGE CONTENT Components included in the complete Quantity Remark 1. Flow sensor IFX-M4-01 1 2. Set of additional connection flanges 1 * 3. Technical description, operating instruction of IFX-M4-01 1 4. Pulse cable (length from 3 m to 200 m) 1 ** 5. 3,6V lithium battery, 8Ah, size C 1 * REMARK: * - included on demand only ** - cable length depending on the order. Standard length 3 m. 4. OPERATING PRINCIPLE 4.1. The ultrasonic flowmeter IFX-M4-01 is microcontroller based device that consists of flow sensor and electronic part mounted on the flow sensor. Flow measurement is based on the time-of flight measurement method. Fluid volume is calculated according the formula: V KH * KM * (1/t + - 1/t - ) *T, where: V - measured fluid volume, m 3 ; T time of integration, s; t + - measured upstream time of flight of ultrasonic pulse, s; t - - measured downstream time of flight of ultrasonic pulse, s; KH hydrodynamic correction factor; KM coefficient that depends on the flow sensor dimensions. Measured flow rate is converted into the pulses quantity that is transferred in output pulse terminal. 5. MARKING AND SEALING 5.1. Marking of sensor There are following information on the front panel of sensor number of EC-type examination certificate, manufacturer s trade mark, identity marking (type designation and type number), serial number, year of manufacture, thread size of the end connections (in) or nominal diameter of the flange (mm), meter factor (pulse value of volume), limits of the temperature, limits of flow rate (q i, q p, q s ), arrow indicating the direction of the flow, maximum admissible working pressure (PN class), accuracy class, climatic, electromagnetic and mechanical environment, enclosure protection class, voltage level for external power supply Numbers of terminal pins are marked close to the terminal. 5.2. Security seals: Manufacturer seals: - One or two seals on ultrasonic transducers mounted in flow sensor (Appendix A, Figure A4). - One or two seals on the bolts of cover protecting ultrasonic transducers (Appendix A, Figures A1, A2 and A3). Calibration seal: - Seal on the inner cover inside electronic box (Appendix B1). Mounting seal: - Seal on the bolt on top cover of the electronic box (Appendix A). IFX-M4-01 V01 2012-09-10 6

6. SAFETY 6.1. Risk factors during the flowmeter installation and service is a heat conveying fluid flowing within flow sensor with inner pressure up to 1,6 MPa and temperature up to 130 0 C. To eliminate this risk the service and installation works must be performed by qualified staff. Mounting of the flowmeter is permissible only after ensuring of absence of heat conveying fluid in the pipeline. 6.2. By connecting the flow sensor to the external pulse registration device which is powered via AC 230V check the proper grounding of external device. 7. INSTALLATION 7.1. The dimensions of the flow sensor and its connection flanges are presented in appendix A. The wiring of signal cables is presented in appendixes B. 7.2. Check installation of the flow sensor corresponds to the notes on the label of calculator (Flow sensor placed in forward or return line). 7.3. It is necessary to rinse out the flow sensor installation place in pipeline before installing the flow sensor. It is recommended to use any piece of pipe as a substitute for the flow sensor during pipe installation and rinsing out. 7.4. Flow sensor meets requirements of mechanical class M1 (minimal vibrations, fixed mounting place). Avoid mounting of flow sensor near the sources of possible vibration (pumps, etc.). 7.5. Requirements for flow sensor installation in pipeline: - For flow sensors with threaded end connection G1 1/4 (q p = 3,5 m 3 /h and 6,0 m 3 /h): no requirements for straight pipeline length in upstream and down stream directions. - For flow sensors with threaded end G2 (qp = 10 m3/h) and flanged connection DN50 DN100 (qp = 15,0 m3/h... 60,0 m3/h): - upstream straight pipeline length must be not less 5DN and downstream straight pipeline length must be not less 3DN when flow disturbance is pipe elbow (1 or 2 elbows); - upstream straight pipeline length must be not less 10DN and downstream straight pipeline length must be not less 3DN when flow disturbance is valve, pump or other; 7.6. Avoid the flow sensor installation near after the pumps which can cause cavitations. 7.7. Flowmeter can be mounted both vertically and horizontally in pipelines. Vertically mounting of the flowmeter is allowed only if flow direction in the pipeline is from down to up. 7.8. The direction of the sensor installation (is indicated with the arrow on the label of flow sensor) must mach with the flow direction in pipeline. 7.9. When flow sensor is mounted in horizontal pipeline, it is recommended to turn electronics box on the one side of flow sensor as shown in (Fig. 1 b,c,d): - for flow sensors with q p = 3,5... 15,0 m 3 /h; - if there is a possibility of the increase of fluid temperature above 100 0 C; - flow sensors with q p = 25,0...60,0 m 3 /h should be turned in downward position of ultrasonic transducers (Fig 1 d). a b c d IFX-M4-01 V01 2012-09-10 7

Fig.1. Positioning of flow sensors: a) not recommended position; b) and c) recommended positions for flow sensors with threaded end connection G1 1/4 (q p = 3,5 m 3 /h and 6,0 m 3 /h), G2 (q p = 10,0 m 3 /h) and flanged connection DN50 (q p = 15,0 m 3 /h); d) recommended position for flow sensors with flanged connection DN65, DN80, DN100 (q p = 25,0 m3/h... 60,0 m3/h). 7.10. The flange gaskets must mach with the pipe diameter. During the installation gasket must be exactly centered with the center of the pipe cross-section to avoid sticking out gaskets inside the pipe. 7.11. The connection of the output pulse cable or battery power supply cable must be performed with the grounded cables with signal wires with the cross-section not less than 0.12 mm 2. These cables must be laid at least 0,5 meter from the high voltage power cables. The connection terminals and wiring of signal cables is presented in appendix B. It is recommended to use cable with external diameter of 4 6 mm. 7.12. Connection of power supply: - See connection diagram in appendix B2 if flow sensor is powered from external source, - Connect battery connector to contact BAT if flow sensor includes inner lithium battery (Appendix B1). 7.13. After installation flow sensor in the pipeline check the device status that is indicated via LEDs (after pushing the test button) and corresponding status on the indicator of heat/flow energy calculator. IMPORTANT! - Sensor can be installed in the pipeline only after completing welding works. - It is prohibited to carry out welding works on the pipeline, in which is mounted flow sensor. 8. CALIBRATION 8.1. It is recommended to perform calibration and testing of the flow sensor in the Test mode. The Test mode is set on by placing the 2,54 mm contact pitch jumper on the 13-14 pins in contactor J1. The contactor J1 is located under the cover on the right side in PCB board (Appendix B3). 8.2. For measuring the quantity of the output pulses during the flow sensor calibration it is recommended to use passive output pulse transmission mode (open drain electrical connection). This mode is set on by placing the jumper JP on the 2-3 pins. (see p.2.6.1. and appendix B3). 8.3. The recommended minimal quantity of the output pulses and measurement duration for flow sensor operation modes: Flow Pulse quantity Measurement duration of in Test mode Measurement duration in working mode 0.1 q p <q q s N 1000 T> 2 [min] T> 5 [min] qi q 0.1 q p N>500 T > 2 + 8 q i /q, [min], T > 5 + 10 q i /q, [min], The both conditions must be satisfied by performing the calibration and testing. 8.4. After the testing and calibration procedures the Test mode must be off by removing the jumper from the pins 13-14 in contactor J1. The access to the inner contactors in PCB board must be protected with the cover. The screw of the cover must be sealed with calibration seal. 9. TRANSPORTATION AND STORAGE 9.1. Packed equipment may be transported in any type of covered vehicle. Equipment should be anchored reliably to avoid shock and possibility to shift inside vehicle. 9.2. Equipment should be protected against mechanical damage and shock. 9.3. Equipment should be stored in dry, heated premises, where environment temperature is not lower than +5 o C. No aggressive chemical substances should be stored together because of corrosion hazard. IFX-M4-01 V01 2012-09-10 8

10. WARRANTY 12.1. Manufacturer gives the warranty that equipment parameters will meet the technical requirements, listed in the paragraph 2 of this document, if transportation, storage and operation conditions will be followed. 12.2. Warranty period - 12 months from bringing into operation, but not more than 18 months from manufacturing date. Appendix A. Sizes and dimensions q p, m 3 /h L H B Connection 3,5 260 112 76 Thread G1 1/4 6,0 260 112 76 Thread G1 1/4 Fig. 1. Dimensions of flow sensors with q p = 3,5 m 3 /h; 6,0 m 3 /h. q p, m 3 /h L H B Connection 10,0 300 95 120 G 2 Fig. 2. Dimensions of flow sensor with q p = 10,0 m 3 /h. q p, m 3 /h L D1 H B Connection 15,0 270 125 130 145 DN50 IFX-M4-01 V01 2012-09-10 9

Fig. 3. Dimensions of flow sensor with q p = 15,0 m 3 /h (DN 50). q p, m 3 /h L D D1 H B Connection 25,0 300 180 145 180 205 DN65 40,0 350 195 160 195 210 DN80 60,0 350 215 180 215 230 DN100 Fig. 4. Dimensions of flow sensors with q p = 25 m 3 /h (DN 65), q p = 40 m 3 /h (DN 80), q p = 60 m 3 /h (DN 100), \ IFX-M4-01 V01 2012-09-10 10

Appendix B1 Connection terminals of flow sensor IFX-M4-01 Lithium battery 3,6V, 8Ah, size C Calibration seal Button for status indication Battery connection terminal BAT Pulse, status and external powering signal connection terminals: U+ external power supply (+3,6V) (used if there are no lithium battery installed), pulse output, GND ground (-). D direction signal (open drain), E error signal (open drain). LED for status indication (green and red) Pulse output signal configuration with jumper location (1-2-3): - connected (1-2) active output (used for transferring pulse to calculator, if they are powered from the same battery), - connected (2-3) open drain output. Cable sealant IFX-M4-01 V01 2012-09-10 11

Appendix B2 Connection of pulse cable Supply of flow sensor IFX-M4-01 from external (calculator) battery The internal battery is not installed, if IFX-M4-01 is powered from the external power supply Configuration of pulse output: - Jumper should be set on pins 1-2 (active output) when calculator and flow sensor is powered from the same battery. Red (+U) White ( ) GND Connection of a pulse cable: Red (U+) external supply (+3,6B) ; White ( ) pulse; (GND) Ground (-); IFX-M4-01 V01 2012-09-10 12

Appendix B3 Set up of Test mode and configuration of output pulse signals for calibration Test mode is set on by placing the jumper on the 13-14 pins in contactors J1 Configuration of output pulse transmission mode: Jumper on 1-2: Active mode Jumper on 2-3: Passive mode (open drain electrical connection) IFX-M4-01 V01 2012-09-10 13

Address: Isoil Industria spa Head office 20092 Cinisello Balsamo (MI) Italy 27, via F.lli Gracchi Phone +39-02-66027.233 Fax +39-02-6123202 E-mail: vendite@isoil.it oppure isothermic@isoil.it Web: www.isoil.com Service Isoil Industria spa 20092 Cinisello Balsamo (MI) Italy 27, via F.lli Gracchi Phone +39-02-66027.219 Fax +39-02-6123202 E-mail: assistenza@isoil.it IFX-M4-01 V01 2012-09-10 14