www. ElectricalPartManuals. com Instructions for Load Break Air Switch, Type LBF, for Power Centers

Similar documents
www. ElectricalPartManuals. com INSTRUCTIONS "INERTEEN AND OIL INSULATED FEEDER SWITCHES DESCRIPTION INSTALLATION MAINTENANCE

Instructions for Replacing

www. ElectricalPartManuals. com Instructions for Cast Resin Bushing, 15 KV & Below

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications

www. ElectricalPartManuals. com

www. ElectricalPartManuals. com INSTRUCTIONS INTERLOCKED MOTOR-DRIVEN OPERATING MECHANISM For No-Load Tap Changers DESCRIPTION OPERATION MAINTENANCE

WLI Medium Voltage Switchgear Renewal Parts

15-kV Wall-Mount Switchgear Three-Phase Indoor/Outdoor 600 Amp S&C Mini-Rupter Switch

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

www. ElectricalPartManuals. com INSTRUCTIONS NO LOAD TAP CHANGER TYPE WSB-4 INSTALLATION OPERATION MAINTENANCE

Installation Sheet January, 2016 Supersedes February, 2013

CR193 Vacuum Limitamp* Contactors

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Copper Vertical Break Switch kv A.

Typical Specification

Aluminum Vertical Break Switch kv A.

Medium Voltage Metal-Enclosed Switches

Installation Sheet January, 2016 Supersedes June 2013

www. ElectricalPartManuals. com

CA Breaker Instruction Manual

Cutler-Hammer. Instructions for Potential Transformer and Auxiliary Control Power Disconnecting Means for Use in Ampgard Lineups, 7.2 kv I.B.

A. Submit manufacturer's literature and technical data before starting work.

Operators/Accessories. Type V2-CA Aluminum. Vertical Break Switch. Ordering Information Furnish: Available Accessories. Standard Operator Features

ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ Phone Fax

Essential Loads also use stand by generator systems mostly in process industries as they relate to high restarting times or high down times.

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Horizontal Circuit Switchers

Horizontal Circuit Switchers

S&C Loadbuster Disconnect Switches. Outdoor Distribution (14.4 kv through 34.5 kv)

15-kV Live Terminal 600 Amp Group Operated Pad-Mounted Metal-Enclosed Outdoor Switchgear 140 Amp (Max) Clip Mount Current-Limiting Fuses

www. ElectricalPartManuals. com INSTRUCTION BOOK h'o. AIR CIRCUIT BREAKER Types 50-DB-ISOE and 50-DB-2501 j,," ,,,,< W_,;wkiiii i!t;s..;._.:...:..,fk.

Service Instructions. Syntron Light-Capacity Electromagnetic Model: F-T01-A DF-T01-A

SWITCHGEAR DIVISION PRODUCT PROFILES

Instructions for Installation, Operation and Maintenance of Low Voltage Power Circuit Breakers Types DSII and DSLII

Medium Voltage Metal-Enclosed Switches

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

SERVICE AND REPAIR PARTS NEMA SIZE 5, SINGLE POLE, NORMALLY OPEN, P/N SERIES NEMA SIZE 5A, SINGLE POLE, NORMALLY OPEN, P/N SERIES

S&C Loadbuster Disconnects

Florham Park, NJ USA Call (ASCO) for sales or service

C1000 Series Automatic Cap Bank

Design Standard. Purpose: Design Standard:

SERVICE AND REPAIR PARTS NEMA SIZE 3, SINGLE POLE, NORMALLY OPEN, P/N SERIES NEMA SIZE 4, SINGLE POLE, NORMALLY OPEN, P/N SERIES

S&C Recloser Bypass Disconnects

The need for continuous power supply and its reliability has increased rapidly over the years, especially in all those areas where uninterrupted

Florham Park, NJ USA Call (ASCO) for sales or service

SPECIFICATION BULLETIN

ELECTRICAL HAZARD EXAMPLES

www. ElectricalPartManuals. com lncoming-6900 through 69,000 volts Outgoing-2400 through 13,800 volts Ratings:

www. ElectricalPartManuals. com Operator s Manual

SafeGear TM Motor Control Center Arc resistant metal-clad construction

Operator s Manual Series ATB Automatic Transfer & Bypass Isolation Switches 150, 260, and 400 amp sizes A. Rating Label.

Protective Link Expulsion Fuse Type Prolink, Oil Immersed, PTAP-APR925 IZUA Technical Guide 15 kv, 23 kv, & 35 kv

Electric Tube Bender User s Manual.

Operator s Manual Series ADTS Automatic Delayed Transition Transfer Switches, amps

www. ElectricalPartManuals. com CPL Station Arrester Controlled Protective Level Page 1 Indoor-Outdoor Altitude 0-10,000 feet KV

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

IB-FAS3 Mar Type FAS THRU 115Kv Amp 61 KA Momentary. Vertical-Break, Gang-Operated Outdoor Air Disconnect Switch.

UNION SERVICE SPECIFICATION NUMBER SU A

! WARNING I.L D WARNING GENERAL INFORMATION

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

Specifications. S&C Alduti-Rupter Switches with Power Fuses Outdoor Distribution (14.4 kv through 46 kv)

www. ElectricalPartManuals. com TRI-PAC circuit breakers current limiting protectors for. lighting, power and distribution circuits

S&C Switch Operators Types AS-1A and AS-10

VersaRupter 5-38 kv Load Interrupter Switch. Technical Guide

10 Commercial, Industrial, Agricultural Services

Westinghouse Electric Corporation Distribution and Control Business Unit Assemblies Division Bloomington, Indiana

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Catalog 14A January 2013

COOPER POWER SERIES. Manually-Operated M-Force Switch Installation and Operation Instructions. Switches and Disconnects MN008003EN

Copper Double Break Switch

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

50 Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO)

PAD-MOUNT SWITCHGEAR 15kV 25kV 35kV

Medium voltage switchgear SafeGear HD 63 ka arc resistant metal-clad switchgear. ABB Group February 25, 2015 Slide 1

www. ElectricalPartManuals. com It'll Cutler-Hammer WLI Medium Voltage Switchgear Renewal Parts Renewal Parts Data Page 1

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure

STATE OF NEW JERSEY DEPARTMENT OF TRANSPORTATION TRENTON, NEW JERSEY 08625

Operator s Manual Series ATS Automatic Transfer Switches 600 through 1200 amps

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

35-kV Safefront SuperWell Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current Limiting Fuses

Specifications. S&C Mini-Rupter Switches Indoor Distribution (4.16 kv through 25 kv) Manually Operated Styles

University of Houston Master Construction Specifications Insert Project Name

Benefits. Safety. Durability. Performance. Russellstoll. Heavy Industrial/ Marine

Explosion Proof Receptacle - Integral Circuit Breaker - Class 2 Division 1-30 Amp 480VAC

Underground Distribution Switchgear

the safe, reliable, and efficient choice for MV switchgear

Operator s Manual Series ADTS Automatic Delayed Transition Transfer Switches 150 through 4000 amp. Rating Label. Nameplate A

M-Force three-phase switch

www. ElectricalPartManuals. com

COOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN

SIEMENS-ALLIS. Medium Voltage. Metalclad Switchgear. www. ElectricalPartManuals. com

ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ Phone Fax

Instructions for De-Ion Air Circuit Breakers Types DM2R, DM2F

NX indoor current-limiting fuses

CENTERLINE 2100 Motor Control Centers 600A, 800A, and 1200A Bolted Pressure Contact Switch

TYPE PSI/II PADMOUNT SWITCHGEAR 15KV 25KV

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

Longest Life Product for Electric Furnace Applications! 100,000 Operations No Routine Maintenance Required!

Transcription:

Instructions for Load Break Air Switch, Type LBF, for Power Centers The Westinghouse Type LB 1 F Switch is an air insulated, gang operated, three pole, two position link type load interrupter switch. The switch is mounted in a separate free standing compartment which can be bolted to air cooled or liquid filled power center transformers. See Fig. 1. LBF Switches, 5 KV or 15 KV, will interrupt load currents of 600 amperes. LBF Switch In addition, the will close on fault currents of 61, 000 amperes at 5 KV and 40,000 amperes at 15 KV. At times a feeder selector switch and an LBF switch are combined within a single enclosure. In these cases the feeder selector switch is located in a separate compartment immediately to the rear of the LBF Switch in the same housing. OPERATION LBF Switch. The small operating mechanism door must be unlocked and the operating handle withdrawn from the receptacle at the right hand of the opening. Insert the handle into the socket provided in the operating cam and move the handle to the desired position. The operating mechanism is powered by torsion bars, and will not move the blades until the handle is advanced beyond a certain point. At this time, the blades will move at a predetermined speed which is independent of the operator. Feeder Selector Switch. In specific cases, a no load feeder selector switch is coupled to an LBF Switch. To operate the feeder switch, first place the LBF Switch in the open position, using the procedure outlined above. A mechanical interlock is thus released so that the main LBF Switch door can be opened, revealing the feeder switch operating handle. Pivot the feeder handle hand grip to disengage the locking pin, and rotate the handle 180 in the direction indicated to select the proper feeder. Since the feeder switch is a no load switch, speed of operation is not essential to opera- I.L. 47-066-lSA tor safety. However, to insure good contact when changing feeders, first disengage the contacts, then rapidly and forcefully rotate the operating handle to the desired feeder position. Fuses. To gain access to the fuses, first place the LBF Switch in the open position. This action releases the mechanical interlock so that the main LBF Switch door can be opened, revealing the fuses in the bottom portion of the compartment. Use caution at this point to be certain the transformer is not energized by an additional source of power, either high voltage or low voltage. The switch cannot be reclosed until the main door has been closed. INSTALLATION During the installation of the switch, a general inspection should be made for shipping or handling damage. The switch should be operated several times to check the alignment and operating mechanism. blade Check the key interlock if supplied to be certain the switch and breaker interlocks are keyed alike. MAINTENANCE Effective February, 1966 Supersedes I. L. 47-066-18, December, 1965 The LBF Switch and feeder selector switch, if supplied should be inspected a minimum of once a year. The following points should receive special care during the inspection: 1. Main Switch blade contacts. 2. Quick-break blade contacts. 3. Arc chutes. All blades with burned or pitted contacts should be replaced to insure trouble free operation. Arc chute erosion, and/or burned quick- break blade contacts would indicate burned arc chute contacts, requiring replacement of the arc chutes.

Fig. 1 Load Break Air Switch, Type LBF RENEWAL PARTS If renewal parts are required, order from the nearest Westinghouse Sales Office, giv- Westinghouse Electric Corporation Power Transformer Division, Sharon, Pa. ing description of parts wanted, with transformer serial number and rating as stamped on transformer instruction plate. Printed in U. S. A. (W.E.)

Fig. I..::LEAR POLYCARBONATE COVER EPOXY CASE 'for Interrupter, witch for. d Power Centers.lvfofded Power Sit irch (One Col'er l?cmm ecl) GENERAL INFORMATION The molded power switch is a three-pole, air insulated. current interrupter switch with a molded epoxy case. The switch may be used with either air cooled or liquid filled transformers and bolted to pad mounts or power centers. The switch is designed to be manually operated to interrupt load currents of 600 amperes at 15 K V. The switch will close on fault current of 40,000 amperes RMS asymmetric at 15 KY. It has been designed in accordance with the A.N.S.l. and N.E.M.A. standards. The design of the switch requires operation within a metal enclosure. DESCRIPTION The basic components of the molded power switch are as follows: Molded Epoxy Case - The switch blades and interrupting arc-chutes are enclosed by an epoxy case and polycarbonate covers. This arrangement provides additional insulation between phases and ground such that the required open air distances are reduced. The covers are vented to permit any ionized gases to escape. See Figure l. Effective June, 1972 I. L. 4 7-066-29 Main Blades and Contacts - The main blades are copper with the contact ridge formed in one end. They are equipped with silver-tungsten pre-arc contacts to make their performance burn free. Sec Figure 2, Page 2. Load Interrupter - These are comprised of a quick-break blade, torsional spring and arc-chute. Operating Mechanism - The operating mechanism consists of a power spring connected to the crank. When the manual crank is turned, energy is stored in the spring until a predetermined position is reached. At this time the manual crank is released and the energy is transmitted to the blades by glass-polyester connecting rods. OPERATIONS With the switch in the closed position, the current flows in the main blades. For operations. the small operating mechanism door must be unlocked and the operating handle removed. Insert the socket of the handle over the operating shaft of the mechanism. By moving the handle in the desired direction, the power spring is stretched until a certain point is reached. At this time, the stored energy of the spring releases the operating handle and snaps open the main contact blades. The current continues to flow in the quick-break blade until a predetermined position of the main blade is reached. At this point, the torsional spring at the pivot snaps open the quick-break blade. The arc drawn within the arc-chute is quickly extinguished by the heat of the arc releasing a blast of de-ionized gas from the gas generating material within the arc-chute, and the high speed of the blade by combination of the main blade speed and rotation by the torsional spring. Closing operations are similar with quick-break and main blades making initial contact on silver-tungsten contacts. STORAGE AND HANDLING When storing these switches, they should remain in their original packing cases. They should be protected from weather, dust and similar conditions. Care should be taken when unpacking the switch to prevent damage. Dust, moisture, and packing material should be removed from the contacts, interruption chambers, and blades.

ARC CHUTE I SILVER TUNGSTEN..-r-r PRE-ARC CONTACTS QUICK-BREAK - BLADE TORSIONAL---\-'--+-1+' SPRING Fir<, :! i\tlain Blade and Quick-Break Blade CONTACT RIDGES When welding, sanding, drilling, filing or sawing operations are performed nearby, the casing and mechanism should be covered and kept clean. ADJUSTMENTS Each switch has been adjusted and tested at the factory. Additional adjustments should not be necessary; however. the following inspections may be made to insure adjustments have not been altered during shipment and handling. a. To assure contact along the entire length of the contact ridge in the main blades, a 2-mil feeler gauge shouldn't slip between the main blades and the stationary contact. b. Adjust contact pressure on both ends of the main blades by tightening the bolts. 75 turn past the position where play is eliminated. c. Before tightening the mounting bolts of blade assembly, main contact and arc-chute, adjust alignment to assure that all parts close and open smoothly. It is recommended that the connecting rods be disconnected for this operation. d. Adjust the adjusting bolts in the stop so that, with the switch open, the tip of the main blades extend 13.25 inches from the epoxy mounting surface; and closed, the blades are 1.06 inches above the epoxy mounting surface. e. At least two no-load operations of the mechanism should be made to insure smooth operations of the switch. Westinghouse Electric Corporation Small Power Transformer Division South Boston, Virginia MAINTENANCE Inspection and Cleaning - It is recommend, that the switch be inspected at a minimum of eac. 50 current interruptions or once a year, whichever occurs first. The epoxy case, arc-chute, quick-break blade, and main blade should be cleaned of dust or any foreign material which might be deposited on them. The contact ridge on the main blades should not be filed or abraded, which could cause excessive wear and perhaps galling on the stationary contact. The quick-break blade should be inspected to determine if excessive carbon, damage or blade misalignment has occurred to either the blade or the silver-tungsten contacts. If either is damaged, the arc-chute should be assumed to be damaged; therefore, both the arc-chute and the quickbreak blade should be replaced. If excessive carbon deposits are found, replace the arc-chutes. Misalignment may be corrected by slightly bending the blade back into its original position so that the blade strikes the slit in the arc-chute. The torsional spring at the pivot of the blade should be inspected to determine if it is broken. If it is broken, it must be replaced before the switch is placed in service. The stationary contacts, pre-arc contacts, main blades, and contact ridge should be inspected for damage or misalignment. If damage has occurred, the part should be replaced. If misalignment is discovered, disconnect the glass-polyester connecting rod, loosen and move stationary contact in line with the blade. Tighten the stationary contact bolts and connect the connecting rod. Inspection of the glass-polyester connecting rod should be made around the pins. If cracks or breaks are found, the rod must be replaced. The mounting bolts should be inspected to determine if vibration has loosened them. They should be tightened until they hold the switch firmly in place. When inspections are complete, refer to "Adjustments" on this page. Replacement Schedule - It is recommended that the main blades, arcing blades, arc chutes and stationary contacts be replaced at the completion of 500 operations because of mechanical wear. The periodic inspection suggested in "Inspection and Cleaning" may indicate replacement of certain parts prior to this mechanical limit because of varying service and environmental conditions. When replacement is made, refer to "Adjustments" on this page. RENEWAL PARTS If renewal parts are required, order from the nearest Westinghouse Sales Office, giving description of parts wanted, with transformer serial number and rating as stamped on transformer instruction plate. Printed in U. S. A.

Instructions for Interrupter, Molded Power Switch for Pad Mounts and Power Centers Fi;;. 1 CLEAR POLYCARBONATE COVER EPOXY CASE /'.folded Po11 rr S11 itch (One Cm er Rrmm ed) GENERAL INFORMATION The molded power switch is a three-pole, air insulated, current interrupter switch with a molded epoxy case. rhe switch may be used with either air cooled or liquid filled transformers and bolted to pad mounts or power centers. The switch is designed to be manually operated to interrupt load currents of 600 amperes at 15 K V. The switch will close on fault current of 40,000 amperes RMS asymmetric at 15 KY. It has been designed in accordance with the A.N.S. I. and N.E.M.A. standards. The design of the switch requires operation within a metal enclosure. DESCRIPTION The basic components of the molded power switch are as follows: Molded Epoxy Case - The switch blades and interrupting arc-chutes are enclosed by an epoxy case and polycarbonate covers. This arrangement provides additional insulation between phases and ground such that the required open air distances are reduced. The covers are vented to permit any ionized gases to escape. See Figure I. Effective June, 1972 I. L. 47-066-29 Main Blades and Contacts -The main blades are copper with the contact ridge formed in one end. They are equipped with silver-tungsten pre-arc contacts to make their performance burn free. See Figure 2, Page 2. Load Interrupter - These are comprised of a quick-break blade, torsional spring and arc-chute. Operating Mechanism - The operating mechanism consists of a power spring connected to the crank. When the manual crank is turned, energy is stored in the spring until a predetermined position is reached. At this time the manual crank is released and the energy is transmitted to the blades by glass-polyester connecting rods. OPERATIONS With the switch in the closed position, the current flows in the main blades. For operations, the small operating mechanism door must be unlocked and the operating handle removed. Insert the socket of the handle over the operating shaft of the mechanism. By moving the handle in the desired direction, the power spring is stretched until a certain point is reached. At this time, the stored energy of the spring releases the operating handle and snaps open the main contact blades. The current continues to flow in the quick-break blade until a predetermined position of the main blade is reached. At this point, the torsional spring at the pivot snaps open the quick-break blade. The arc drawn within the arc-chute is quickly extinguished by the heat of the arc releasing a blast of de-ionized gas from the gas generating material within the arc-chute, and the high speed of the blade by combination of the main blade speed and rotation by the torsional spring. Closing operations are similar with quick-break and main blades making initial contact on silver-tungsten contacts. STORAGE AND HANDLING When storing these switches, they should remain in their original packing cases. They should be protected from weather, dust and similar conditions. Care should be taken when unpacking the switch to prevent damage. Dust, moisture, and packing material should be removed from the contacts, interruption chambers, and blades.

ARC CHUTE SILVER TUNGSTEN ---J-+i-'+jlJ PRE-ARC CONTACTS QUICK-BREAK BLADE TORSIONAL--+-+ Y+: SPRING muun FiJI. l Afain Blade and Quick-Break Blade CONTACT RIDGES When welding, sanding, drilling, filing or sawing operations are performed nearby, the casing and mechanism should be covered and kept clean. ADJUSTMENTS Each switch has been adjusted and tested at the factory. Additional adjustments should not be necessary; however, the following inspections may be made to insure adjustments have not been altered during shipment and handling. a. To assure contact along the entire length of the contact ridge in the main blades, a 2-mil feeler gauge shouldn't slip between the main blades and the stationary contact. b. Adjust contact pressure on both ends of the main blades by tightening the bolts. 75 turn past the position where play is eliminated. c. Before tightening the mounting bolts of blade assembly, main contact and arc-chute, adjust alignment to assure that all parts close and open smoothly. It is recommended that the connecting rods be disconnected for this operation. d. Adjust the adjusting bolts in the stop so that, with the switch open, the tip of the main blades extend 13.25 inches from the epoxy mounting surface; and closed, the blades are 1.06 inches above the epoxy mounting surface. e. At least two no-load operations of the mechanism should be made to insure smooth operations of the switch. Westinghouse Electric Corporation Small Power Transformer Division South Boston, Virginia MAINTENANCE Inspection and Cleaning - It is recommended that the switch be inspected at a minimum of each 50 current interruptions or once a year, whichever occurs first. The epoxy case, arc-chute, quick-break blade, and main blade should be cleaned of dust or any foreign material which might be deposited on them. The contact ridge on the main blades should not be filed or abraded, which could cause excessive wear and perhaps galling on the stationary contact. The quick-break blade should be inspected to determine if excessive carbon, damage or blade misalignment has occurred to either the blade or the silver-tungsten contacts. If either is damaged, the arc-chute should be assumed to be damaged; therefore, both the arc-chute and the quickbreak blade should be replaced. If excessive carbon deposits are found, replace the arc-chutes. Misalignment may be corrected by slightly bending the blade back into its original position so that the blade strikes the slit in the arc-chute. The torsional spring at the pivot of the blade should be inspected to determine if it is broken. If it is broken, it must be replaced before the switch is placed in service. The stationary contacts, pre-arc contacts, main blades, and contact ridge should be inspected for damage or misalignment. If damage has occurred, the part should be replaced. If misalignment is discovered, disconnect the glass-polyester connecting rod, loosen and move stationary contact in line with the blade. Tighten the stationary contact bolts and connect the connecting rod. Inspection of the glass-polyester connecting rod should be made around the pins. Tf cracks or breaks are found, the rod must be replaced. The mounting bolts should be inspected to determine if vibration has loosened them. They should be tightened until they hold the switch firmly in place. When inspections are complete, refer to "Adjustments" on this page. Replacement Schedule - It is recommended that the main blades, arcing blades, arc chutes and stationary contacts be replaced at the completion of 500 operations because of mechanical wear. The periodic inspection suggested in "Inspection and Cleaning" may indicate replacement of certain parts prior to this mechanical limit because of varying service and environmental conditions. When replacement is made, refer to "Adjustments" on this page. RENEWAL PARTS If renewal parts are required, order from the nearest Westinghouse Sales Office, giving description of parts wanted, with transformer serial number and rating as stamped on transformer instruction plate. Printed in U. S. A.

Instructions for Load Break Air Switch, Type LBF, for Power Centers The Westinghouse Type LBF Switch is an air insulated, gang operated, three pole, two position link type load interrupter switch. The switch is mounted in a separate free standing compartment which can be bolted to air cooled or liquid filled power center transformers. See Fig. 1. LBF Switches, 5 KV or 15 KV, will interrupt load currents of 600 amperes. LBF Switch In addition, the will close on fault currents of 61, 000 amperes at 5 KV and 40, 000 amperes at 15 KV. At times a feeder selector switch and an LBF switch are combined within a single enclosure. In these cases the feeder selector switch is located in a separate compartment immediately to the rear of the LBF Switch in the same housing. OPERATION LBF Switch. The small operating mechanism door must be unlocked and the operating handle withdra\:vti from the receptacle at the right hand of the opening. Insert the handle into the socket provided in the operating cam and move the handle to the desired position. The operating mechanism is powered by torsion bars, and will not move the blades until the handle is advanced beyond a certain point. At this time, the blades will move at a predetermined speed which is independent of the operator. Feeder Selector Switch. In specific cases, a no load feeder selector switch is coupled to an LBF Switch. To operate the feeder switch, first place the LBF Switch in the open position, using the procedure outlined above. A mechanical interlock is thus released so that the main LBF Switch door can be opened, revealing the feeder switch operating handle. Pivot the feeder handle hand grip to disengage the locking pin, and rotate the handle 180 in the direction indicated to select the proper feeder. Since the feeder switch is a no load switch, speed of operation is not essential to opera- I.L. 47-066-lBA tor safety. However, to insure good contact when changing feeders, first disengage the contacts, then rapidly and forcefully rotate the operating handle to the desired position. feeder Fuses. To gain access to the fuses, first place the LBF Switch in the open position. This action releases the mechanical interlock so that the main LBF Switch door can be opened, revealing the fuses in the bottom portion of the compartment. Use caution at this point to be certain the transformer is not energized by an additional source of power, either high voltage or low voltage. The switch cannot be reclosed until the main door has been closed. INSTALLATION During the installation of the switch, a general inspection should be made for shipping or handling damage. The switch should be operated several times to check the alignment and operating mechanism. blade Check the key inter lock if supplied to be certain the switch alike. and breaker interlocks are keyed MAINTENANCE Effective February, 1966 Supersedes I. L. 47-066-18, December, 1965 The LBF Switch and feeder selector switch, if supplied should be inspected a minimum of once a year. The following points should receive special care during the inspection: 1. Main Switch blade contacts. 2. Quick-break blade contacts. 3. Arc chutes. All blades with burned or pitted contacts should be replaced to insure trouble free operation. Arc chute erosion, and/or burned quick - break blade contacts would indicate burned arc chute contacts, requiring replacement of the arc chutes.

Fig. 1 Load Break Air Switch, Type LBF RENEWAL PARTS If renewal parts are required, order from the nearest Westinghouse Sales Office, giv- Westinghouse Electric Corporation Power Transformer Division, Sharon, Pa. ing description of parts wanted, with transformer serial number and rating as stamped on transformer instruction plate. Printed in U. S. A. (W.E.)