Liebert Hipluse U UPS;80-400kVA; 380/400/415V Detailed Specification Conformity And Standard General safety requirements for UPS EMC requirements for UPS Table 1-1 Conformity and standard Normative reference EN62040-1/IEC62040-1/AS62040-1 EN62040-2/IEC62040-2/AS62040-2 (C3) Method of specifying the performance and test requirements of UPS EN62040-3/IEC62040-3/AS62040-3 (VFI SS 111) The product standards in this table incorporate relevant compliance clauses with generic IEC and EN standards for safety (IEC/ EN/AS60950), electromagnetic emission and immunity (IEC/EN/AS61000 series) and construction (IEC/EN/AS60146 series and 60529) Environmental Requirements Table 1-2 Environmental requirements Operating Temperature C 0 ~ 40 C 80 ~ Maximal temperature for 8hr day C 40 C (derate power by 1.5% per C between 40 C and 50 C Mean Temperature for 24hr C Maximum 35 C Relative humidity 95% at 20 C Altitude of operation Storage temperature and transport temperature m 1000m asl (derate power by 1% per 100m between 1000m and 2000m) C -25 C to 70 C Over-voltage level Overvoltage level 2 Pollution level Pollution level 2 Grid system TN, TT, IT (4-pole switch configured) Mechanical Characteristics Dimensions (W D H) Weight (kg) Ventilation Table 1-3 Mechanical characteristics 80/100/120 (6P) 160 (6P) 160 (12P) 200 (6P) 300 (6P) 900 855 1028 998 2125 1250 855 1366 996 1240 855 1356 996 900 1200 1200 1000 1300 By internal intake fans Airflow m 3 /h 1890 3180 Protection level Color Cable entry IP20 ZP7021 Bottom (top optional)
Dimensions (W D H) 900 855 640 855 1240 855 855 640 855 1028 998 2125 766 976 2116 1356 996 706 966 2112 768 998 2116 1540 855 900 1000 000 Overall net weight Ventilation Airflow 300 (12P) Overall dimension Weight (kg) 200 (12P) 120 (12P) 1740 855 00 1 2280 855 650 50 1 1300 300 700 1950 950 1400 400 m3/h h 2550 By internal intake fans 2910 22 Protection level 5350 IP20 Color ZP7021 Cable entry Bottom (top optional) Dimensions (W D H) 400 (6P) Overall dimension Weight (kg) Ventilation Airflow 400 (12P) (12P) Rectifier Inverter Rectifier Inverter 640 855 1225 855 1055 855 190 1595 855 1045 855 768 998 2116 1356 996 1166 966 2145 2280 855 1166 966 2145 2280 855 2640 855 300 1200 200 1 2000 350 1300 300 1600 600 Overall net weight 2200 200 m3/h 6150 150 By internal intake fans Protection level IP20 IP21 (optional) Color ZP7021 Cable entry Bottom (top optional) Cabling top or bottom from Tables show the standard weight, that is, any option is excluded. Electrical Characteristics (Input Rectifier) Table 1-4 Rated mains voltage Vac Electrical characteristics (input rectifier) 80 (6P) 100 (6P) 120 (6P) 120 (12P) 380, 400, or 415 Three phase without neutral Input voltage tolerance 1 % ±15, (maxmally from 290Vac to 498Vac) Frequency Hz 50 or 60 Input frequency tolerance Hz 45 ~ 65 160 (6P) 160 (12P) 200 (6P) 200 (12P)
80 (6P) 100 (6P) 120 (6P) 120 (12P) 160 (6P) 160 (12P) 200 (6P) 200 (12P) power 2 kva 95 119 143 140 191 186 239 233 current 2 A 145 181 217 212 289 282 362 353 Power 3 kva 110 137 165 161 220 214 274 268 current 3 A 166 208 249 244 333 325 416 406 Duration of progressive s 5 ~ 300 power walk-in 4 1. mains at -15% nd suggested battery elements the UPS maintains the output rated voltage at rated load but cannot guarantee float charge to battery; the battery does not discharge. 2. IEC620-3 (5.2.2): UPS, rated load, input rated voltage 380V, no current to battery. 3. IEC620-3 (5.2.2): UPS, rated load or overload, input rated voltage 380V, battery on boost charge with maximal allowed current. 4. Set y dedicated setting software 300 (6P) 300 (12P) 400 (6P) 400 (12P) (12P) Rated mains voltage Vac 380, 400, or 415 Three phase without neutral Input voltage tolerance 1 % ±15, (maxmally from 290Vac to 498Vac) Frequency Hz 50 or 60 Input frequency tolerance Hz 45 ~ 65 power 2 kva 365 586 A 551 51 885 current 2 Power 3 kva 420 730 current 3 A 634 1106 Duration of progressive s 5 ~ 300 power walk-in 4 1. mains at -15% nd suggested battery elements the UPS maintains the output rated voltage at rated load but cannot guarantee float charge to battery; the battery does not discharge. 2. IEC620-3 (5.2.2): UPS, rated load, input rated voltage 380V, no current to battery. 3. IEC620-3 (5.2.2): UPS, rated load or overload, input rated voltage 380V, battery on boost charge with maximal allowed current. 4. Set y dedicated setting software Electrical Characteristics (DC Intermediate Circuit) Table 1-5 Electrical characteristics (DC intermediate circuit) 80 100 120 160 200 300 400 Voltage range for inverter operation 320 ~ 490 Recommended number of lead-acid cells 1,2 pcs 192 (380Vac) 198 (400Vac) 204 (415Vac)
Recommended float charge voltage 2.25V/el. 1 Recommended boost charge voltage 2.35V/el. 1 Maximum voltage on manual charge 2.40 V/el. 1 End-of-discharge voltage 2.45V/el. 1 80 100 120 160 200 300 400 432 (380Vac) 446 (400Vac) 459 (415Vac) 451 (380Vac) 465 (400Vac) 479 (415Vac) 461 (380Vac) 475 (400Vac) 490 (415Vac) 471 (380Vac) 485 (400Vac) (415Vac) Max boost charge duration 3 min 480 ~ 1800 Freshening charge duration 3 h 1 ~ 36 Boost-float threshold current 3 A 0.001C ~ 0.025C Ripple voltage superimposed 4 % 1 1. (According to ated voltage). 2. Fact y set for rated 380V, different cells number and voltage per cell may be set by configuration software. 3. Set y software. 4. Batt y disconnected, RMS percentage value referred to DC voltage Voltage range for inverter operation 400 ~ 625 Recommended number of lead-acid cells 1,2 pcs 240 (380Vac) 246 (400Vac) 252 (415Vac) Recommended float charge voltage 2.25V/el. 1 540 (380Vac) 553 (400Vac) 567 (415Vac) Recommended boost charge voltage 2.35V/el. 1 Maximum voltage on manual charge 2.40 V/el. 1 End-of-discharge voltage 2.45V/el. 1 564 (380Vac) 578 (400Vac) 592 (415Vac) 576 (380Vac) 590 (400Vac) 605 (415Vac) 588 (380Vac) 603 (400Vac) 617 (415Vac) Max boost charge duration 3 min 480 ~ 1800 Freshening charge duration 3 h 1 ~ 36 Boost-float threshold current 3 A 0.001C 10 ~ 0.025C 10 Ripple voltage superimposed 4 % 1 1. (According to ated voltage). 2. Fact y set for rated 380V, different cells number and voltage per cell may be set by configuration software. 3. Set y software. 4. Batt y disconnected, RMS percentage value referred to DC voltage Electrical Characteristics (Inverter Output) Table 1-6 Electrical characteristics (inverter output) 80 100 120 160 200 300 400 Rated mains voltage 1 Vac 380, 400, or 415 Three phase with neutral
Frequency 2 Hz 50 or 60 80 100 120 160 200 300 400 Rated Power at cos = 0.9 kva 80 100 120 160 200 300 400 Rated Power at cos = 1 kw 72 90 108 144 180 270 360 450 Three-phase transient overload 3 Min, I/In 60, 1.10 10, 1.25 1, 1.5 Maximal non linear load allowed 4 100% Pn Voltage stability, steady State test 3 % ±1 Voltage stability, transient test 5 % ±5 Maximum rate of change of frequency 6 Hz/s 3 1. Factory set 380V, 400 or 415 voltages with software setting. 2. Factory set at 50Hz 60 Hz with software setting. 3. IEC62040-3 (5.3.2). 4. IEC62040-3 (ANNEX E). 5. IEC62040-3 (5.3.1), also for 0% ~ 100% ~ 0%, load transient, restore time 20ms to 1%. 6. Factory set at 0.1Hz/s; up to 3Hz/s with software setting Electrical Characteristics (Bypass Input Mains) Table 1-7 Electrical characteristics (bypass input mains) 80 100 120 160 200 300 400 Rated mains voltage 1 Vac 380, 400, or 415 Three phase with neutral Rated current 380Vac 400Vac 415Vac A 121 151 181 243 304 456 607 759 116 145 174 231 289 434 578 723 112 140 167 222 278 416 556 695 Bypass voltage tolerance 2 % Default upper limit: 15%; default lower limit: -20% Delay time to recognise bypass voltage returned to s 2 window Inverter output voltage window % ±5 Frequency 3 Hz 50 or 60 Input frequency tolerance 4 Hz 45 ~ 65 Maximum frequency slew rate 1.3In Current rating of neutral cable Protection, bypass line - ms I/In The bypass line should be protected using an external device in the input distribution system. This device should be sized to discriminate with the load protection. 10 14.3 20 12.6 50 11.0 1. Factory set 380V. 400 or 415 voltages with software setting. 2. Other values in -20% ~ 15% with software setting. 3. Factory set at 50Hz 60 Hz with software setting. 4. Other values -5% ~ 5% with software setting 100 10.0 200 9.0 8.0 1000 7.1 2000 6.6 0 5.7
Electrical Characteristics (System Performance) Table 1-8 Electrical characteristics (system performance) 80/100/120 (6P) 120 (12P) 160 (6P) 160 (12P) 200 (6P) 200 (12P) No load losses kw 2.17 2.48 2.75 3.30 3.50 4.15 kw 8.24 8.92 9.63 11.89 11.12 13.91 300 (6P) 300 (12P) 400 (6P) 400 (12P) (12P) No load losses kw 3.90 4.65 4.70 6.67 8.25 kw 19.33 21.8 28.2 31.6 39.6 Electrical Characteristics (ECO Mode) Table 1-9 Electrical characteristics (ECO mode) 80/100/120 (6P) 120 (12P) 160 (6P) 160 (12P) 200 (6P) 200 (12P) kw 2.34 2.64 2.97 3.52 3.55 4.20 300 (6P) 300 (12P) 400 (6P) 400 (12P) (12P) kw 5.23 5.91 7.10 8.96 9.32