Liebert Hipluse U UPS;80-400kVA; 380/400/415V Detailed Specification

Similar documents
1.1 GENERAL CHARACTERISTICS

Eaton 93PS 8-40kW UPS Technical Specification Manufacturer s declaration in accordance with IEC

PowerValue 11/31 T kva

POWER kva

POWER kva Nominal output power (Cos φ0,8) kva Nominal output power (Cos φ1,0) kw >88 Efficiency (AC AC)

POWER kva

EFFEKTA Power Supplies

TECHNICAL DATA SHEET KVA UPS Systemss

POWERTRONIX QUASAR 5-40 KVA

TECHNICAL DATA SHEET B8033FXS kva 3Ph(In) 3Ph(Out)

Liebert GXT & 6000VA RT230 Rack-Tower models GUIDE SPECIFICATIONS 1.0 GENERAL

Technical Data Sheets

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

TECHNICAL DATA SHEET B8031 FXS kva 3Ph(In) 1Ph(Out)

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Technical Data Sheets

Three Phase UPS Systems Range: 10 to 500kVA

Technical Data Sheets

Technical Data Sheets

Technical Data Sheets

Technical Data Sheets

MKN-DSP SERIES - THREE PHASE

Technical Data Sheets

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Technical Data Sheets

Technical Data Sheet. Uninterruptible Power Supply. Digital Energy. imagination at work

Technical Specifications. Sentinel PRO 700 VA up to 3000 VA 1000 VA ER-2200 VA ER-3300 VA ER

TLE Series UPS 400/500 kw With eboost Technology

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

gimagination at work Technical data sheet Uninterruptible Power Supply LP Series 6 & 10 kva GE Digital Energy

Marketing Management Team of Europe

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

un I Jet ИБП ABB Conceptpower DPA 500 ( квт) - технические спецификации. Юниджет

TLE Series UPS 160/200/225/250 kw with eboost Technology

CENTAURI ENERGY SERVER TECHNICAL DATA kw POWER

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Technical data sheet VH UL. Digital Energy Uninterruptible Power Supply. GE Digital Energy Power Quality

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

kVA. Liebert NX. Enterprise-Scale UPS Protection For Medium And Large Data Centers

TECHNICAL DATA SHEET INFINITY kva 3Ph(in) 3Ph(out)

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Industrial PFC UPS System

EATON 9315 UPS 200 TO 300 KVA Specifications

TELECOM- MUNICATIONS DEVICES INDUSTRIAL EMERGENCY DEVICES. (Servers Farms, ISP/ASP/POP)

TELECOM- MUNICATIONS DEVICES INDUSTRIAL EMERGENCY DEVICES. (Servers Farms, ISP/ASP/POP)

LIEBERT APM 3-PHASE UPS: 15-90KVA/KW, 60HZ, VAC, SINGLE & DUAL INPUT - SITE PLANNING DATA

Technical Specification SENTINEL PRO

POWER+ PREMIUM CBS. BS-EN Emergency electrical installations Electric power systems Emergency lighting Escape lighting

Liebert GXT VA RT230 Rack-Tower model GUIDE SPECIFICATIONS 1.0 GENERAL

Master MPS kva kva 3:1 3:3 VFI TYPE

Master Plus kva

Master Plus kva

Presentation Soft starters 0 Altistart 48 soft start - soft stop units

TLE Series UPS 750/1000 kw With eboost Technology

E-15 Uninterruptible Power Systems (UPS)

ConceptpowerTM Modular kVA

Galaxy VX. 380 V, 400 V, 415, and 440 V UPS System Technical Specifications 12/

Standard specification Galaxy PWi, three-phase, 10 to 200 kva

Technical data sheets

BMPM/ BMPT Series. 3: kva VFI TYPE. Efficiency Control System (ECS) Robust and reliable Galvanic isolation High overload capacity

Liebert APM UPS. For a 30 to 150 kva / kw (50 or 60Hz) Modular Digital Uninterruptible Power Supply (UPS) System. V nd February 2010

Three Phase UPS Systems

Liebert Hipulse E The High-ECO-Availability UPS. AC Power Systems

10 20KVA 3Ph/1Ph KVA 3Ph / 3Ph

DELPHYS GP. Green Power 2.0 range 160 to 1000 kva/kw

Liebert. FP 50Z kva

Master MPS kva kva 3:1 3:3 VFI TYPE

INDUSTRIAL PROCESSES TELECOM- MUNICATIONS DEVICES EMERGENCY DEVICES INDUSTRIAL

Aurora Single Phase Emergency Lighting Inverters

Models. Output current max.* Output Power max. Low Line : VAC High Line: VAC 24 VDC / 12 A 240 W. Back up battery

UNIVERSITY OF CALCUTTA Centre for Research in Nanoscience and Nanotechnology JD-2, Sector-III, Salt Lake City Kolkata

POWER+ CLASSIC 20/30 KVA, 3X208 VAC WITH INTERNAL BATTERIES. GAMATRONIC, A SolarEdge Division

POWER+ CLASSIC 20/30 KVA, 3X208 VAC WITH INTERNAL BATTERIES. GAMATRONIC, A SolarEdge Division

Liebert PowerSure PSI UPS

MGE TM Galaxy TM 7000 GFC

QUEENSLAND URBAN UTILITIES

EAST GROUP COMPANY PROFILE. Energy storage solutions. About us. Grid-connected PV systems. Our Products. Our Team. UPS solutions

Liebert GXT & 10000VA RT208 Rack-Tower models, Dual Inverter GUIDE SPECIFICATIONS

Master MPS kva kva 3:1 3:3 VFI TYPE

PowerScale kva Technical Specifications

PowerWave 33 Efficient power protection for today s IT and process-related work environments

INVEOR "Smart connections." on five levels

OFFICE SIEL ENERGY SYSTEMS LTD NITESCO LLC

Specification for 70mm pole pitch Air circuit breaker up to 1600 A

Onfiniti. 1 Phase UPS

PowerScale TECHNICAL SPECIFICATIONS

tel: Enhanced Power Services Limited Industrial PLCs Electro Medical Devices

Document: PRODSPEC-140 Revision: G DCN No Date: October 1, 2014 Product: 10-amp EnerGenius NRG Battery Charger

E-15 Uninterruptible Power Systems (UPS)

UPS Multi Sentry 10-20kVA

LDX-C120 Series is a 120 W integrated DIN Rail Battery Charger / DC UPS Power Supplies, suitable for wide variety of industrial applications.

Liebert GXT & 10000VA RT208 Rack-Tower models, Dual Inverter GUIDE SPECIFICATIONS 1.0 GENERAL

ИБП Liebert ITA (5-6 ква) - руководство по эксплуатации. Юниджет

UCS-CHR24V55W. Combined Power Supply & Battery Charger. Data Sheet

Keatec Energy Catalogue 2018 Telecommunications

Technical data sheets

MERU Solar Off-Grid Inverters

Power+ CLASSIC. 20/30 kva, 3x208 Vac

USER MANUAL. IPS home inverters with UPS function. IPS home inverter manual

MODULAR THREE-PHASE AND SINGLE-PHASE UPS SYSTEM

Transcription:

Liebert Hipluse U UPS;80-400kVA; 380/400/415V Detailed Specification Conformity And Standard General safety requirements for UPS EMC requirements for UPS Table 1-1 Conformity and standard Normative reference EN62040-1/IEC62040-1/AS62040-1 EN62040-2/IEC62040-2/AS62040-2 (C3) Method of specifying the performance and test requirements of UPS EN62040-3/IEC62040-3/AS62040-3 (VFI SS 111) The product standards in this table incorporate relevant compliance clauses with generic IEC and EN standards for safety (IEC/ EN/AS60950), electromagnetic emission and immunity (IEC/EN/AS61000 series) and construction (IEC/EN/AS60146 series and 60529) Environmental Requirements Table 1-2 Environmental requirements Operating Temperature C 0 ~ 40 C 80 ~ Maximal temperature for 8hr day C 40 C (derate power by 1.5% per C between 40 C and 50 C Mean Temperature for 24hr C Maximum 35 C Relative humidity 95% at 20 C Altitude of operation Storage temperature and transport temperature m 1000m asl (derate power by 1% per 100m between 1000m and 2000m) C -25 C to 70 C Over-voltage level Overvoltage level 2 Pollution level Pollution level 2 Grid system TN, TT, IT (4-pole switch configured) Mechanical Characteristics Dimensions (W D H) Weight (kg) Ventilation Table 1-3 Mechanical characteristics 80/100/120 (6P) 160 (6P) 160 (12P) 200 (6P) 300 (6P) 900 855 1028 998 2125 1250 855 1366 996 1240 855 1356 996 900 1200 1200 1000 1300 By internal intake fans Airflow m 3 /h 1890 3180 Protection level Color Cable entry IP20 ZP7021 Bottom (top optional)

Dimensions (W D H) 900 855 640 855 1240 855 855 640 855 1028 998 2125 766 976 2116 1356 996 706 966 2112 768 998 2116 1540 855 900 1000 000 Overall net weight Ventilation Airflow 300 (12P) Overall dimension Weight (kg) 200 (12P) 120 (12P) 1740 855 00 1 2280 855 650 50 1 1300 300 700 1950 950 1400 400 m3/h h 2550 By internal intake fans 2910 22 Protection level 5350 IP20 Color ZP7021 Cable entry Bottom (top optional) Dimensions (W D H) 400 (6P) Overall dimension Weight (kg) Ventilation Airflow 400 (12P) (12P) Rectifier Inverter Rectifier Inverter 640 855 1225 855 1055 855 190 1595 855 1045 855 768 998 2116 1356 996 1166 966 2145 2280 855 1166 966 2145 2280 855 2640 855 300 1200 200 1 2000 350 1300 300 1600 600 Overall net weight 2200 200 m3/h 6150 150 By internal intake fans Protection level IP20 IP21 (optional) Color ZP7021 Cable entry Bottom (top optional) Cabling top or bottom from Tables show the standard weight, that is, any option is excluded. Electrical Characteristics (Input Rectifier) Table 1-4 Rated mains voltage Vac Electrical characteristics (input rectifier) 80 (6P) 100 (6P) 120 (6P) 120 (12P) 380, 400, or 415 Three phase without neutral Input voltage tolerance 1 % ±15, (maxmally from 290Vac to 498Vac) Frequency Hz 50 or 60 Input frequency tolerance Hz 45 ~ 65 160 (6P) 160 (12P) 200 (6P) 200 (12P)

80 (6P) 100 (6P) 120 (6P) 120 (12P) 160 (6P) 160 (12P) 200 (6P) 200 (12P) power 2 kva 95 119 143 140 191 186 239 233 current 2 A 145 181 217 212 289 282 362 353 Power 3 kva 110 137 165 161 220 214 274 268 current 3 A 166 208 249 244 333 325 416 406 Duration of progressive s 5 ~ 300 power walk-in 4 1. mains at -15% nd suggested battery elements the UPS maintains the output rated voltage at rated load but cannot guarantee float charge to battery; the battery does not discharge. 2. IEC620-3 (5.2.2): UPS, rated load, input rated voltage 380V, no current to battery. 3. IEC620-3 (5.2.2): UPS, rated load or overload, input rated voltage 380V, battery on boost charge with maximal allowed current. 4. Set y dedicated setting software 300 (6P) 300 (12P) 400 (6P) 400 (12P) (12P) Rated mains voltage Vac 380, 400, or 415 Three phase without neutral Input voltage tolerance 1 % ±15, (maxmally from 290Vac to 498Vac) Frequency Hz 50 or 60 Input frequency tolerance Hz 45 ~ 65 power 2 kva 365 586 A 551 51 885 current 2 Power 3 kva 420 730 current 3 A 634 1106 Duration of progressive s 5 ~ 300 power walk-in 4 1. mains at -15% nd suggested battery elements the UPS maintains the output rated voltage at rated load but cannot guarantee float charge to battery; the battery does not discharge. 2. IEC620-3 (5.2.2): UPS, rated load, input rated voltage 380V, no current to battery. 3. IEC620-3 (5.2.2): UPS, rated load or overload, input rated voltage 380V, battery on boost charge with maximal allowed current. 4. Set y dedicated setting software Electrical Characteristics (DC Intermediate Circuit) Table 1-5 Electrical characteristics (DC intermediate circuit) 80 100 120 160 200 300 400 Voltage range for inverter operation 320 ~ 490 Recommended number of lead-acid cells 1,2 pcs 192 (380Vac) 198 (400Vac) 204 (415Vac)

Recommended float charge voltage 2.25V/el. 1 Recommended boost charge voltage 2.35V/el. 1 Maximum voltage on manual charge 2.40 V/el. 1 End-of-discharge voltage 2.45V/el. 1 80 100 120 160 200 300 400 432 (380Vac) 446 (400Vac) 459 (415Vac) 451 (380Vac) 465 (400Vac) 479 (415Vac) 461 (380Vac) 475 (400Vac) 490 (415Vac) 471 (380Vac) 485 (400Vac) (415Vac) Max boost charge duration 3 min 480 ~ 1800 Freshening charge duration 3 h 1 ~ 36 Boost-float threshold current 3 A 0.001C ~ 0.025C Ripple voltage superimposed 4 % 1 1. (According to ated voltage). 2. Fact y set for rated 380V, different cells number and voltage per cell may be set by configuration software. 3. Set y software. 4. Batt y disconnected, RMS percentage value referred to DC voltage Voltage range for inverter operation 400 ~ 625 Recommended number of lead-acid cells 1,2 pcs 240 (380Vac) 246 (400Vac) 252 (415Vac) Recommended float charge voltage 2.25V/el. 1 540 (380Vac) 553 (400Vac) 567 (415Vac) Recommended boost charge voltage 2.35V/el. 1 Maximum voltage on manual charge 2.40 V/el. 1 End-of-discharge voltage 2.45V/el. 1 564 (380Vac) 578 (400Vac) 592 (415Vac) 576 (380Vac) 590 (400Vac) 605 (415Vac) 588 (380Vac) 603 (400Vac) 617 (415Vac) Max boost charge duration 3 min 480 ~ 1800 Freshening charge duration 3 h 1 ~ 36 Boost-float threshold current 3 A 0.001C 10 ~ 0.025C 10 Ripple voltage superimposed 4 % 1 1. (According to ated voltage). 2. Fact y set for rated 380V, different cells number and voltage per cell may be set by configuration software. 3. Set y software. 4. Batt y disconnected, RMS percentage value referred to DC voltage Electrical Characteristics (Inverter Output) Table 1-6 Electrical characteristics (inverter output) 80 100 120 160 200 300 400 Rated mains voltage 1 Vac 380, 400, or 415 Three phase with neutral

Frequency 2 Hz 50 or 60 80 100 120 160 200 300 400 Rated Power at cos = 0.9 kva 80 100 120 160 200 300 400 Rated Power at cos = 1 kw 72 90 108 144 180 270 360 450 Three-phase transient overload 3 Min, I/In 60, 1.10 10, 1.25 1, 1.5 Maximal non linear load allowed 4 100% Pn Voltage stability, steady State test 3 % ±1 Voltage stability, transient test 5 % ±5 Maximum rate of change of frequency 6 Hz/s 3 1. Factory set 380V, 400 or 415 voltages with software setting. 2. Factory set at 50Hz 60 Hz with software setting. 3. IEC62040-3 (5.3.2). 4. IEC62040-3 (ANNEX E). 5. IEC62040-3 (5.3.1), also for 0% ~ 100% ~ 0%, load transient, restore time 20ms to 1%. 6. Factory set at 0.1Hz/s; up to 3Hz/s with software setting Electrical Characteristics (Bypass Input Mains) Table 1-7 Electrical characteristics (bypass input mains) 80 100 120 160 200 300 400 Rated mains voltage 1 Vac 380, 400, or 415 Three phase with neutral Rated current 380Vac 400Vac 415Vac A 121 151 181 243 304 456 607 759 116 145 174 231 289 434 578 723 112 140 167 222 278 416 556 695 Bypass voltage tolerance 2 % Default upper limit: 15%; default lower limit: -20% Delay time to recognise bypass voltage returned to s 2 window Inverter output voltage window % ±5 Frequency 3 Hz 50 or 60 Input frequency tolerance 4 Hz 45 ~ 65 Maximum frequency slew rate 1.3In Current rating of neutral cable Protection, bypass line - ms I/In The bypass line should be protected using an external device in the input distribution system. This device should be sized to discriminate with the load protection. 10 14.3 20 12.6 50 11.0 1. Factory set 380V. 400 or 415 voltages with software setting. 2. Other values in -20% ~ 15% with software setting. 3. Factory set at 50Hz 60 Hz with software setting. 4. Other values -5% ~ 5% with software setting 100 10.0 200 9.0 8.0 1000 7.1 2000 6.6 0 5.7

Electrical Characteristics (System Performance) Table 1-8 Electrical characteristics (system performance) 80/100/120 (6P) 120 (12P) 160 (6P) 160 (12P) 200 (6P) 200 (12P) No load losses kw 2.17 2.48 2.75 3.30 3.50 4.15 kw 8.24 8.92 9.63 11.89 11.12 13.91 300 (6P) 300 (12P) 400 (6P) 400 (12P) (12P) No load losses kw 3.90 4.65 4.70 6.67 8.25 kw 19.33 21.8 28.2 31.6 39.6 Electrical Characteristics (ECO Mode) Table 1-9 Electrical characteristics (ECO mode) 80/100/120 (6P) 120 (12P) 160 (6P) 160 (12P) 200 (6P) 200 (12P) kw 2.34 2.64 2.97 3.52 3.55 4.20 300 (6P) 300 (12P) 400 (6P) 400 (12P) (12P) kw 5.23 5.91 7.10 8.96 9.32