UPS5000-E (25-75 kva) Series

Similar documents
Huawei Network Energy, Powering the Future. Huawei UPS Solutions HUAWEI TECHNOLOGIES CO., LTD.

Indoor Integrated Power System

Power+ CLASSIC. 20/30 kva, 3x208 Vac

MKN-DSP SERIES - THREE PHASE

Huawei Micro Grid Solar Solution

Three-phase UPS system DPA UPScale ST kw The modular UPS designed for lowand medium-power applications

Symmetra PX 250/500. Scalable from 100 kva kw to 500 kw, parallel capable up to 2,000 kw

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Technical Data Sheets

APM30 System Description

Symmetra PX 96/160. Scalable from 16 kw to 160 kw Modular, scalable, high-efficiency power protection for data centers

magellan commercial UPS solutions Magellan Power Modular - Flexible UPS

D Series: UPS UPTO - 300KVA - Three / Three Phase

HAIRF UPS. X5 Series KVA

gimagination at work Technical data sheet Uninterruptible Power Supply LP Series 6 & 10 kva GE Digital Energy

Technical Data Sheets

Three Phase UPS Systems Range: 10 to 500kVA

TLE Series UPS 400/500 kw With eboost Technology

kVA. Liebert NX. Enterprise-Scale UPS Protection For Medium And Large Data Centers

G V Series UNINTERRUPTIBLE POWER SYSTEMS. Phone: Fax: Web:

Symmetra PX 100 kw. Scalable from 10 kw to 100 kw Modular, scalable, high-efficiency power protection for data centers

POWER+ PREMIUM CBS. BS-EN Emergency electrical installations Electric power systems Emergency lighting Escape lighting

Galaxy VM. From 160 kva to 1000 kva. Three-phase power protection. Galaxy VM trusted partner for your business continuity. schneider-electric.

TLE Series UPS 160/200/225/250 kw with eboost Technology

POWER+ CLASSIC 20/30 KVA, 3X208 VAC WITH INTERNAL BATTERIES. GAMATRONIC, A SolarEdge Division

POWER+ CLASSIC 20/30 KVA, 3X208 VAC WITH INTERNAL BATTERIES. GAMATRONIC, A SolarEdge Division

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

3ph UPS NS3000 series kVA

Technical data sheets

W Datasheet: UPS AVARA Modular kVA (1-8 x 15kvA)

TECHNICAL DATA SHEET KVA UPS Systemss

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Technical Data Sheets

Technical Data Sheets

Technical Data Sheets

n Lower energy costs and carbon footprint n Cooler operation extends internal component life n High input power factor of 0.99

Symmetra PX. Industry-leading efficiency, availability, and performance for small, medium, and large data centers and mission critical environments

TLE Series UPS 750/1000 kw With eboost Technology

Technical Data Sheets

Series. On-line, Single-phase Parallel Redundant UPS System. 6 and 10 kva Rack Mount. Your Tailored Power Solutions Provider TM

Three-phase UPS system. DPA UPScale ST kw Best-in-class modular UPS for maximum availability

Est FlexiPower Mini UPS FPX Mini kVA

Technical Data Sheet. Uninterruptible Power Supply. Digital Energy. imagination at work

Galaxy VM. From 160 kva to 1000 kva, 160 kva or 200 kva modular approach. Three-phase power protection

EFFEKTA Power Supplies

Features and Benefits

Galaxy VM. From 160 kva to 1000 kva Three-phase power protection. apc.com/products

PowerWave 33 Efficient power protection for today s IT and process-related work environments

Technical data sheet VH UL. Digital Energy Uninterruptible Power Supply. GE Digital Energy Power Quality

SmartOnline SUT Series 3-Phase 208/120V 220/127V 30kVA 30kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option

PowerValue 11/31 T kva

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

SmartOnline S3MX Series 3-Phase 380/400/415V 60kVA 54kW On-Line Double-Conversion UPS

Huawei UPS2000-G Solutions

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

POWER kva

On-line, Single Phase, Double Conversion UPS

TECHNICAL DATA SHEET INFINITY kva 3Ph(in) 3Ph(out)

SmartOnline SVTX Series 3-Phase 380/400/415V 20kVA 18kW On-Line Double-Conversion UPS, Tower, Extended Run, SNMP Option

Master Plus kva

KEOR HP. THREE-PHASE UPS from 100 to 800 kva GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

CENTAURI ENERGY SERVER TECHNICAL DATA kw POWER

POWER kva Nominal output power (Cos φ0,8) kva Nominal output power (Cos φ1,0) kw >88 Efficiency (AC AC)

POWER kva

Liebert NX TM. 250kVA kVA Transformer-free. High Efficiency, Scalable On-line UPS

SmartOnline SUT Series 3-Phase 208/120V 220/127V 20kVA 20kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Est ComPower Mini UPS (3 Phase) CPX Mini 10 50kVA

Modular UPS «AGIL» Stay on! Changing the rules for critical business continuity :

Series. Full Three Year Warranty. On-line, Single-phase Parallel Redundant UPS System. 6 and 10 kva Tower. Your Tailored Power Solutions Provider TM

EAST GROUP COMPANY PROFILE. Energy storage solutions. About us. Grid-connected PV systems. Our Products. Our Team. UPS solutions

TECHNICAL DATA SHEET B8033FXS kva 3Ph(In) 3Ph(Out)

TECHNICAL DATA SHEET B8031 FXS kva 3Ph(In) 1Ph(Out)

KEOR HP. THREE-PHASE UPS from 100 to 800 kva GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

Standalone three-phase UPS system. PowerWave kw Unmatched power performance

DELPHYS GP. Green Power 2.0 range 160 to 1000 kva/kw

» Sophisticated» Reliable» Intelligent

NterpriseIP Solution Adaptive, high-availability power system for IP Telephony. Business-Critical Continuity for Communications

SmartOnline SUT Series 3-Phase 208/120V 220/127V 40kVA 40kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option

Industrial PFC UPS System

Phase Modular Finally the benefits of Modular ups are for all

TELECOM- MUNICATIONS DEVICES INDUSTRIAL EMERGENCY DEVICES. (Servers Farms, ISP/ASP/POP)

MASTERYS IP+ 10 to 80 kva

n Lower energy costs and carbon footprint n Cooler operation extends internal component life n High input power factor of 0.99

Technical Data Sheets

True double-conversion online single-phase UPS. PowerValue 11 RT 1 10 kva Single-phase UPS for critical applications

EMERGENCY ELECTRO- MEDICAL INDUSTRIAL PLCS DEVICES. (Lights/Alarms)

YOUR POWER IN SAFE HANDS. E Series UPS

Liebert Hipulse E The High-ECO-Availability UPS. AC Power Systems

10 20KVA 3Ph/1Ph KVA 3Ph / 3Ph

Technical Data Sheets

Liebert NXC. 10kVA - 60kVA. Compact, Efficient, and Reliable Power Solution

UPS SYSTEMS PDUs SURGE PROTECTORS POWER INVERTERS DATACENTER UPS. Product Catalog

Symmetra PX. Symmetra PX250/500kW Scalable from 25kW to 500kW Parallel-capable up to 2000kW

Master Plus kva

Standard 1000VA, 2000VA & 3000VA Universal Tower/Rack Mount LB Extended Models 900VA, 1700VA & 2500VA

Master MPS kva kva 3:1 3:3 VFI TYPE

Eaton 93PS 8-40kW UPS Technical Specification Manufacturer s declaration in accordance with IEC

Transcription:

Battery Integrated Uninterruptible Power System UPS5000-E (25-75 kva) Series HUAWEI TECHNOLOGIES CO., LTD.

CONTENTS 02 Solution Overview 03 Customer Benefits 09 System Architecture and Key Components 12 Typical Configuration 13 System Parameters 14 Global Services

Solution Overview UPS5000-E Battery Integrated Solution Rated capacity: 25-75 kva The three-phase uninterruptible power supply solution is applicable to small- and medium-sized data centers or high-density areas. The integrated UPS adopts online double conversion design and system with a leading efficiency up to 96%. The UPS is fully modular with hot-swappable modules. Redundancy is also supported. UPS5000-E-75K-BF UPS and batteries integrated in one cabinet Modular and redundant Efficient double conversion technology, system efficiency up to 96% High power density design 1.0 output power factor (kva = kw) Front maintenance, can be installed against a wall Battery modular design Battery module fault displayed locally 02

Customer Benefits: Simple Efficient Reliable 01 All Modular Design Simple installation: Site survey and battery wiring are not required. Professional installation, complex wiring, long labor hours Huawei battery integrated UPS Traditional battery rack solution The power module, bypass module, battery module, and control module all use modular and integrated design. Compared with traditional UPS and battery rack solutions, the integrated UPS is installed by inserting modules onsite and does not require site survey or wiring. A common engineer can finish installation and wiring, greatly reducing labor hours for site installation and wiring. 02 Battery Modular Pre-integration Batteries pre-integrated before delivery Hot-swappable terminals Wiring not required onsite 03

03 Simple Maintenance Power module Battery module Bypass module Control module The power module, battery module, bypass module, and control module are all hot-swappable. Online maintenance is supported. A common engineer can finish replacement and maintenance in 5 minutes. 04 Intelligent Battery Management Without Manual Inspection Battery module overtemperature alarm Fuse blown for protection if battery module is abnormal Fault displayed locally, easy to locate the faulty module Intelligent equalized charging, float charging, and temperature compensation Battery hibernation can be enabled, preventing battery lifespan from being shortened due to long-time float charging 04

Customer Benefits: Simple Efficient Reliable 01 Space Saving >> Power Module: High Power Density 25 kva power module The power density increases exponentially Structure patent design Heat sink design Occupying 2 U space, improve space use by 50% compared with the industry >> Highly Integrated, Saving Footprint Traditional UPS Battery rack Battery integrated UPS Huawei battery integrated solution saves 50% footprint compared with a traditional solution. 05

02 Efficient and Energy-saving >> >> High efficiency at low load rate Due to redundancy configuration to ensure reliability and excessive configuration at the initial stage to meet the power demand in 3-5 years, the UPS system of traditional datacenter often operates at load rate of 10%-50% and the operating efficiency is far below the value claimed. It's estimated that the UPS loss takes up 6%-10% of the total power consumption in datacenter Huawei UPS can keep high efficiency operation at low load rate: Up to 96% at 40% rated load and up to 95% at 20% rated load Efficiency 100% 95% 90% 85% 80% 75% 70% 65% 60% 55% 50% 0% 20% 40% 60% 80% 100% Load rate >> Intelligent hibernation design When the load rate is very low (below 10%-15%), intelligent hibernation can be enabled and some power modules will switch to "standby" state to boost load rate and improve operating efficiency To ensure reliability, at least one power module serves as redundancy module and when load increases dramatically, the sleep module will be awaked instantly 100% 75% 50% 25% 0% Load Module Module Module Module Module Module Module Module 06

Customer Benefits: Simple Efficient Reliable 01 Redundancy Design, Eliminating Single Point of Failure Redundancy design for energy control unit, communication buses to eliminate single point of failure Fault-tolerant design for fan system: 30% load can be driven when 2 fans fail and 50% load when 1 fan fails Redundant Energy Control Units Control module CAN2 Control module CAN2 CAN1 CAN1 Dual communication system design, single bus system failure, will not affect the normal operation of the system. Power module Power module Power module 3 power module running 2 power module running Power module redundancy design, a single power module failure, will not affect the normal operation of the system. 20% Load rate 20% Load rate 30% Load rate 20% Load rate 30% Load rate Fan fault tolerance design, Single fan faults with load 50%,two fan faults with load 30% 07

02 Strong Adaptability in Power Grid, Load & Environment High grid adaptability 138-485 Vac wide input voltage range to minimize battery use: 485-305Vac for 100% load; 305-138 Vac for 100%-40% load (derating linearly) 6 kv/5 ka lightning protection design, reducing lightning-related failure rate Areas allowing load rate >50% Huawei UPS Input Voltage Range Typical UPS Input Voltage Range 100 150 200 250 300 350 400 450 500 Input Voltage Range (V) High load adaptability High output power factor of up to 1, 25% more load driven than traditional UPSs The application of PFC technology in modern IT devices like servers, storages, routers improves the input power factor to more than 0.95. And if they are powered by UPS with output power factor of 0.7-0.8, the investment on UPS will increase remarkably No derating for capacitive or inductive devices with a PF>0.5 PF=0.9 (leading) PF=0.7 (leading) PF=0.5 (leading) Ideal Active power (P) PF=1 φ PF=0.9 (leading) PF=0.7 (leading) PF=0.5 (leading) Huawei UPS Reactive power (Q) High environment adaptability No derating at 40 to ensure power continuity Conformal coating on PCB, improving adaptability to dusty or salty spray environment System normal operation After Airborne Hygroscopic Dust Test 08

System Architecture and Key Components 01 System Architecture and Composition 1 2 25 kva power module Static bypass module 1 6 3 4 Monitoring module Battery module 3 2 10 5 Battery switch 6 LCD 4 7 8 Air filter Maintenance bypass switch 9 8 5 9 Input switch 7 10 Monitoring unit (SNMP and RS485 communications in standard configuration) Dimensions (H*W*D): 2000 mm x 600 mm x 1100 mm 09

02 Key Components Power module The Power module with rated capacity of 25 kva/kw can eliminate all the nine common problems in public grid and output pure and stable sine wave. Dimensions (H x W x D): 86 mm x 442 mm x 620 mm Bypass module The bypass module can provide continuous power supply to load when overload. The bypass module of UPS5000-E features concentrated design and maximum output power 128kW. Dimensions (H x W x D): 130 mm x 442 mm x 620 mm Energy control module The ECM supports intra-rack parallel CAN communication and inter-rack parallel CAN communication. The intra-rack loadshare control and inter-rack loadshare control are isolated at ECM to achieve better expandability. Battery Module A battery module consists of ten B.B. 9 Ah batteries. An alarm will be generated if the battery module temperature is abnormal and the fuse will be blown for protection if the battery module is abnormal. If there is a fault, the fault indicator turns on locally. Dimensions (H x W x D): 160 mm x 108 mm x 786 mm 10

System Architecture and Key Components 03 Key Components (Optional) Battery Cabinet The battery cabinet meets the long-time power backup requirements. Each battery cabinet can house eight battery strings (each string contains four battery modules) and is equipped with a battery switch. A maximum of four battery cabinets can be connected. Dimensions (H x W x D): 2000 mm x 600 mm x 1100 mm >> Other Optional Components Component Function Antiseismic kit Reinforces the cabinet so that the cabinet meets the requirements of 9 degree seismic fortification intensity. IP21 component Prevents water from dropping into the cabinet, protecting the cabinet to IP21. Battery temperature sensor Feedbacks real-time temperature and humidity data to dynamic environment monitoring system. BSC cable Transmits bus synchronization signals in a dual-bus system. 11

Typical Configuration 01 Configuration scene Typical Configuration Long-time Power Backup Configuration 3+1 power modules 8-16 battery modules Battery integrated cabinet Battery cabinet Battery cabinet Battery cabinet Battery cabinet 36 battery strings 144 battery modules 2-4 battery strings 8 battery strings 8 battery strings 8 battery strings 8 battery strings Battery integrated cabinet: One to three 25 kva power modules, a maximum of four power modules can be configured with one module redundant. Battery module: One battery module contains ten B.B. 12 V 9 Ah batteries and one battery string contains four battery modules. Battery cabinet: Supports a maximum of eight battery strings, that is, 32 battery modules. >> Backup Time Table Unit: min 350 Battery Integrated Cabinet 300 250 1# Battery Cabinet 330 2# Battery Cabinet 3# Battery Cabinet 4# Battery Cabinet 235 200 150 100 50 0 25.6 9.9 5.6 88 44 26 161 74 49 107 68 144 88 25kVA 50kVA 75kVA 12

System Parameters Model UPS5000-E- (25-75kVA) -BF Capacity (kva/kw) 25kVA/kW 50kVA/kW 75kVA/kW Input Output Environment Others Mains Bypass Rated Voltage Output Frequency Rated Voltage Voltage Range Input Wiring Frequency Range Total Harmonic Distortion Input Power Factor 0.99 Rated Voltage Frequency Range Input Wiring Output Power Factor 1 Waveform Output Wiring 380/400/415Vac 138 to 485Vac 3Ph+N+PE 40 to 70 Hz <3% (100% linear load) 380/400/415Vac 50/60Hz (adjustable, 0.5 to 6Hz, ±2Hz by default) 3Ph+N+PE 380/400/415Vac Tracking the bypass input (Normal mode); 50/60Hz±0.05% (Battery mode) Sine wave; THDv<1% (linear load) 3Ph+N+PE System Efficiency Up to 96% Overload Capacity Operation Temperature 0 to 40 ºC Storage Temperature -40 to 70 ºC Relative Humidity 110% overload for 60min; 125% overload for 10min; 150% overload for 1min 0% to 95% (No condensing) Maximum Operation Altitude 0-1000m. Above 1000m, derating rate based on EN/IEC 62040-3 Noise System Expandability 4 Integrated Cabinet Power Backup Battery Cabinet (optional) Power Backup Battery Module <65dB Height Width Depth (mm) 2000 600 1100 Standard configuration 2 to 4 groups of battery (8 to 16 battery modules) Optional battery cabinet, 1 to 8 groups of battery (4 to 32 battery modules) per cabinet, max. 4 cabinets in parallels Support battery or empty battery for battery module, battery typical configuration: 10 12V 9Ah Weight (full version) 890kg 910kg 930kg Certifications Communications EN/IEC 62040-1, EN/IEC 62040-2, EN/IEC 62040-3, CE, CB, etc. SNMP, RS485, Dry contacts etc. 13

Global Services Huawei has professional UPS service engineers deployed globally, providing global technical support with rapid response speed. Huawei provides customized services that include: 7*24 remote support Software support Active prevention Hardware support Onsite support Others 140+ countries 129+ national spare parts centers 300+ regional warehousing centers 22,000+ servers 24*7 online service North Africa Russia Western Europe Northeast Europe Middle East & Central Asia China Headquarter Latin America West Africa India Southeast Asia & South Pacific South of South America Southeast Africa 14

Copyright Huawei Technologies Co., Ltd. 2017. All rights reserved. No part of this document may be reproduced or transmitted in any form or by any means without prior written consent of Huawei Technologies Co., Ltd. Trademark Notice, HUAWEI, and are trademarks or registered trademarks of Huawei Technologies Co., Ltd. Other trademarks, product, service and company names mentioned are the property of their respective owners. General Disclaimer The information in this document may contain predictive statements including, without limitation, statements regarding the future financial and operating results, future product portfolio, new technology, etc. There are a number of factors that could cause actual results and developments to differ materially from those expressed or implied in the predictive statements. Therefore, such information is provided for reference purpose only and constitutes neither an offer nor an acceptance. Huawei may change the information at any time without notice. HUAWEI TECHNOLOGIES CO., LTD. Huawei Industrial Base Bantian Longgang Shenzhen 518129, P.R. China Tel: +86-755-28780808 Version No.: M3-022334-20161215-E-2.0 www.huawei.com