Transformer bushings, type GOH. Technical guide

Similar documents
1ZSE en, Rev. 7. Transformer bushings, type GOB Technical guide

1ZSE en, Rev. 9. Transformer bushings, type GOB Technical guide

Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide

Resin Impregnated Paper Bushing, Oil to SF 6. , Type GSBK

1ZSE EN, REV. 7. Oil SF 6. bushings type GOEK Technical guide

1ZSE en, Rev. 3. Wall bushings, type GSA-AA Technical guide

Bushings for High Voltage AC Applications

1ZSE EN, REV. 4. Wall bushings type GSA-AA Technical guide

Transformer bushings, type GSA-OA Technical guide

1ZSC AAA en, Rev. 6. Resin impregnated paper bushing, oil to SF 6., type GSBK Technical guide

1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide

1ZSE en, Rev. 9. Transformer bushings, type GSA-OA Technical guide

Transformer bushings, type GOA 250. Installation and maintenance guide

Motor-drive mechanism, type BUL. Technical guide

HVDC bushing without oil side porcelain Type GOF, for outdoor mounting. Installation and maintenance guide

en, Rev. 10. Transformer bushings, type GOH Installation and maintenance guide

OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) kV to 550kV up to 5000A IEC

Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st New RIS transformer bushings The paper-free solution

OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) kV to 550kV up to 5000A IEC

PABS. AIR-TO-SF 6 - Gas-insulated bushing IEC STANDARDS ANSI STANDARDS AN ALSTOM COMPANY

1ZSC ABJ EN, REV. 1. Gas insulated wall bushings type GGFL Technical guide

en, Rev. 7. Transformer bushings, type GOM Installation and maintenance guide

INSTRUCTION MANUAL CRS Combined insulation bushing

High Voltage Surge Arresters Buyer s Guide Section PEXLIM R

dfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide

Medium voltage products. KEVCD A combined current and voltage sensor Instructions for installation, use and maintenance

Product Information. Neutral Wall Bushing GOFL

Micafil transformer oil-sf 6 bushings GARIP / RTKG kv. Power and productivity for a better world TM ABB

PNO Condenser Bushings from 52 kv to 420 kv Oil-to-air - Oil-Impregnated Paper

Zinc Oxide Surge Arrester EXLIM R

Transformer High Current Bushings Type CFPT & CFCT 36kV up to 40kA IEC

ACCESSORIES FOR LPOF, HPPT AND XLPE HIGH VOLTAGE CABLE SYSTEMS PRODUCT CATALOGUE

INTRODUCTION. The plug-in connection on the cables and lightning arrestors, allows for easy installation and replacement.

Zinc-Oxide Surge Arrester TEXLIM Q-C

Type HS PEXLIM-P Surge Arresters Maximum System Voltage 123 kv to 800 kv

A of 3. Edition : Date : Page : Document No. Amendments :

Zinc Oxide Surge Arrester PEXLIM Q

Current transformers. Outdoor operation SF 6 -gas insulated. JGF ( ) kv

BUSHINGS: GENERAL INFORMATION

Bushing Insulators according to DIN and UNEL Standards

Inductive voltage transformers

Inductive voltage transformers

Bus bar Bushings up to 1.1kV and from 1.6kA to 4kA for Liquid Filled Transformers:

B kv Gas-insulated Substations

A of 14. Edition : Date : Page : Document No. Amendments :

kv А

NXPLUS C Single busbar. Maintenance-free for lifetime

KECA 80 C85 Current Sensor Instructions for installation, use and maintenance

VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified

DM Condenser bushings, kV DURESCA

Surge arrester POLIM-H..SD

OTCF. Grid Solutions. Capacitor Voltage Transformers 72.5 kv to 800 kv. Quality Product Design. Seismic Withstand Capability.

Combined instrument transformers

EMPAC Metal enclosed capacitor bank for wind applications

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A

Condenser Bushings. OIL-TO-AIR - Oil-Impregnated Paper ANSI STANDARDS IEEE C AND IEEE C AN ALSTOM COMPANY

Medium Voltage Products. KEVA 24 B20; KEVA 24 B21 Voltage Sensors Instructions for installation, use and maintenance

Inductive voltage transformers

Inductive voltage transformers

MEDIUM VOLTAGE PRODUCT. KECA 80 C85 Current Sensor Instructions for installation, use and maintenance

43-SDMS-01 SPECIFICATIONS FOR

B kv T&D GAS INSULATED SWITCHGEAR

GENERAL. CONSTRUCTION External

MICAFIL RIP Transformer Bushings AirRIP / RTKF kv

LV Bushing Oil to Air Dry Insulation PTAB-SLV832

SERIES TAP-CHANGER

High Voltage Surge Arresters Buyer s Guide Section PEXLIM P-Y

Type POLIM-S Surge Arresters Maximum System Voltage 2.52 to 245 kv

R-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism

INSTRUCTION MANUAL BR 25 FOR RAILWAY APPLICATION 5COR BR25AT REV00

MEDIUM VOLTAGE PRODUCT. KECA 250 B1 Current Sensor Instructions for installation, use and maintenance

MEDIUM VOLTAGE PRODUCT. KECA 80 D85 Current Sensor Instructions for installation, use and maintenance

TEKNISK RIKTLINJE TR05-10E

en, Transformer bushing, type GSA-OA Installation and maintenance guide...

Solid Dielectric Load Break Switch SPECIFICATION. 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER

Combined Current and Voltage Instrument Transformer CVS-P-24-O Technical Specifications

M-RING 24. SF6 Insulated Ring Main Unit Metal-Enclosed (LSC2A)

Surge arrester POLIM-H.. ND

023 : 2006 CEB STANDARD. 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications

Outdoor vacuum breaker for railway applications - FSK II

Combined instrument transformers

3EQ Composite Housed Surge Arresters

3EP1 Surge Arrester. Metal-oxide surge arrester without series gaps for high-voltage systems up to U m. = 170 kv

1ZVN A. Application manual

TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH

3EQ Composite Housed Surge Arresters Saving Money and Space, Gaining Reliability

Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st Dry-type transformers Innovative Technology

Voltage limiting device HVL

1ZSC AAX EN, Transformer bushing, type GSC Installation and maintenance guide

Certified for best-in-class performance, reliability, and safety. Trihal sets a new standard for dry-type cast resin transformers

High Voltage Bushing Wells for Pad Mounted Distribution Transformers Technical Guide

INSTRUCTION MANUAL RELAY FOR ON LOAD TAP CHANGER APPLICATIONS OR-25 5COR OR25 REV03

CABLE SYSTEMS. Accessories and Systems for Medium and High-Voltage Cables up to 300 kv.

Transformer Bushings Type COT COT kv to 245 kv up to 3150 A IEC 137

Current accuracy class. Sensor principles

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure

produces and delivers products worldwide can provide the optimal solution for your requirements. are dedicated to supplying you with

On-load tap-changers, types UCG, UCL, UCC and UCD with motor-drive mechanisms, types BUE and BUL Spare Parts List

Transcription:

Transformer bushings, type GOH Technical guide

This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical information required to assist them in their selection of the appropriate transformer bushing. The guide should be used in conjunction with the Selection Guide to allow the optimum selection to be made. The technical information pertaining to bushings manufactured by ABB has been divided into separate documents, with one document for each type. The information provided in this document is intended to be general and does not cover all possible applications. Any specific application not covered should be referred directly to ABB, or its authorised representative. ABB makes no warranty or representation and assumes no liability for the accuracy of the information in this document or for the use of such information. All information in this document is subject to change without notice. 2

Table of Contents Design 4 Shed form 4 Terminals 5 Test tap 5 Testing 5 Test tap adapter 5 Dimensions 6 Electrical data 7 Common specifications 7 Conductor loading 8 Connection 9 Ordering particulars 9 Recommendations for positioning _ 9 3

Design The bushing is built up around a solid aluminium bolt which serves as a conductor for both the current and for the heat losses. Cooling flanges are milled directly in the conductor. The upper insulator, lower insulator and mounting flange are held between the end plates by spring pressures. Sealing is accomplished by oil-resistant rubber gaskets. The radial seal at the bottom end consists of an O-ring made in a special fluorocarbon rubber. This material is very resistant to high-temperature transformer oil, and has good flexibility in the lower temperature range. The annular space between the condenser body and the porcelain is filled with transformer oil. A gas-filled expansion space is left at the top. The oil level can be checked by means of a dipstick in the oil filling hole. Both insulators are made in one piece of high quality electrical porcelain. The mounting flange is manufactured of corrosion-resistant aluminium alloy. The mounting flange is protected by painting with twocomponent primer and a grey-blue finishing coat of paint. The bushings are delivered oil-filled and ready for use. The bushing can be vertically or horizontally mounted. If the bushing is horizontally mounted, special measures have to be taken to ensure sufficient oil filling in the bushing and communication with an expansion space. Further information can be obtained on request. Shed form The shed form for all GOH bushings is of the anti-fog type with alternating long and short sheds. For each pair of sheds the ratio between nominal creepage distance and the axial length is 3.35 and the ratio between protected and nominal creepage distance is 0.40. According to IEC 815 the creepage factor C.F. is <3.0 and the profile factor P.F. is >1.1. For special customer demands regarding creepage distance, other shed forms may be used. Outer terminal plates Lifting eye Porcelain insulator air side Oil filling and venting hole with sealing plug M8 Air side oil plug for separate expansion tank Mounting flange Oil side oil plug for connection to transformer Porcelain insulator oil side Spring device Oil side terminal with cooling flanges Fig. 1. Transformer bushing type GOH. Fig. 2. Shed form. goh_0013 goh_0002 4

Terminals The contact surfaces are plated with a tin/zinc alloy. The oil end is provided with threaded holes. The threads are provided with self locking thread inserts. The oil end has two contact surfaces milled directly in the conductor. The air end is equipped with four drilled flat terminals, welded to the conductor. Test tap The outer conducting layer of the condenser body is connected to an insulated test tap on the flange. During operation the test tap cover must be screwed on in order to earth the outer layer to the flange. The max. test voltage of the tap is 2 kv, 50 Hz for 1 minute. Max. service voltage is 600 V. Testing During the manufacture and on its completion the bushing is subjected to a number of routine tests. A tightness test is carried out on the assembled bushing after the final drying and impregnation. The test is made with an oil overpressure of 180 kpa (1.8 bar) for 12 hours at ambient temperature. No sign of leakage is allowed. Each bushing is subjected to a final electrical routine test. The test is made at room temperature with the bushing submerged in oil. Capacitance and tan δ are measured in steps up to the power frequency withstand voltage, which is maintained for one minute. Capacitance and tan δ are also measured at decreasing voltage at the same voltage levels as before the one minute test. Measurements for detection of internal partial discharge (PD measurements) are also made. These measurements are carried out at the same time as the power frequency withstand test. PD measurements are made in steps up to the full test voltage and down. It is always demonstrated that the PD value is max. 5 pc at test voltage equal to the rated system voltage. Type tests have been carried out according to IEC 137 and IEEE. Type test reports are available on request. Test tap adapter For testing, a special test adapter is required for permanent connection of the test tap to the measuring circuits. Fig. 3. Oil end. Fig. 4. Test tap. Fig. 5. Test tap adapter, 2769 531-A. goh_0003 (780643) goh_0010 goh_0011 5

Dimensions The dimensions in axial direction are the same for standard GOH 170/10, 170/16 and 170/25. Fig. 6. Dimensions. goh_0004 Type Min. creepage distance (mm) Cantilever withstand load (N) GOH Total Protected Operation 1 min. test 170/10 760 300 1500 10000 170/16 760 300 1500 10000 170/25 760 300 1500 10000 6

Electrical data The table below states the values according to IEC 137. Type tests, however, have shown that ANSI insulation class 34.5 kv is fulfilled. Nominal Rating Routine test Short time current Dynamic current capacitance Nominal Phase-to- Dry lightning Wet power between voltage earth voltage impulse frequency 1 min dry Reference I th I th I d conductor Type U r 1.2/50 AC 50 Hz current 1) 1 s 2 s Peak and test tap GOH kv, RMS kv, RMS kv kv, RMS kv, RMS ka ka ka ka C1 ±10 % (pf) 170/10 36 36 200 75 80 10 100 2) 100 2) 250 2) 400 170/16 36 36 200 75 80 16 100 2) 100 2) 250 2) 570 170/25 36 36 200 75 80 25 100 2) 100 2) 250 2) 765 1) See Conductor loading 2) Highest value according to IEC 137. Common specifications Application: Transformers Classification: Oil impregnated paper, capacitance graded, outdoor immersed bushing. Ambient temperature: +40 C to -40 C, minimum value acc. to temperature class 2 of IEC 137. 1) Altitude of site: < 1 000 m Level of rain and humidity: 1-2 mm rain/min. horizontally and vertically as per IEC 60-1. Pollution level: According to specified creepage distance and IEC 815. 2) Immersion medium: Transformer oil. 1) Oil level below bushing flange: Max. 25 mm Max. pressure of medium: 100 kpa over pressure. Mounting angle: Vertical or horizontal Markings: Conforming to IEC/ IEEE For conditions exceeding the standard specification above, please consult ABB Components. 1) See Conductor loading 2) IEC 815 "Guide for the selection of insulators in respect of polluted conditions." 7

Conductor loading The name plate value of current, also given in the designation of the GOH bushing, is a reference current and not the permissible current for the bushing. The permissible current is very much dependent upon the temperature conditions around the bushing. Knowing the temperature of the surrounding transformer oil and the ambient temperature of the air side of the bushing, one can calculate the permissible current by using the diagram in Fig. 7. This diagram is verified by thermal tests which are in accordance with IEC 137. t 1 t A1 t 0 t A2 t Highest temperature (hot spot) allowed on the bushing. In normal service this should not exceed 105 C. Ambient temperature on air side of the bushing. This depends greatly on whether the bushing is enclosed or not, and if enclosed, on how the enclosure is designed. Temperature of the oil around the bushing. With forced cooling t 0 is often relatively low compared to the maximum allowed temperature given in transformer standards. Mean daily ambient temperature around the transformer. Top oil temperature rise for the transformer. t 1 = Hot spot temperature of the bushing lead t A1 = Air temperature t 0 = Surrounding oil temperature t A2 = Mean daily ambient air temperature Current, ka Example: I = 11 ka t A2 = 30 C t = 55 K t 0 = t A2 + t t 0 = 30 + 55 = 85 C t A1 = 45 C t 1 = 105 C t 1 - t 0 = 105-85 = 20 K t 1 - t A1 = 105-45 = 60 K The permissible current is obtained from the diagram. For GOH 170/10 For GOH 170/16 For GOH 170/25 9.3 ka 15.2 ka 23.0 ka GOH 170/16 will in this case be chosen. Fig. 7. Current capacity goh_0015 8

Connection The connection to the aluminium terminals of the bushing shall be made by means of flexible connectors. No special treatment is needed for the tin/zinc plated contact surfaces. In order to maintain a sufficient contact pressure, the screws should be furnished with strong spring washers. Large flat washers must also be used in order to limit the specific load. For M12 and 1/2" UNC, a flat washer with a minimum thickness of 3 mm and a minimum outer diameter of 32 mm is recommended. Detailed instructions and recommendations for connecting are available in the installation and maintenance guide 2750 515-85. Ordering particulars When ordering, please state: Type and catalogue number for bushings. Additional accessories or modifications. Test required, in addition to the normal routine tests. Test tap adapter, if required. Designation Catalogue No. Insulator colour on air side GOH 170/10 LF 126 007-A Brown LF 126 007-B Light grey GOH 170/16 LF 126 008-A Brown LF 126 008-B Light grey GOH 170/25 LF 126 009-A Brown LF 126 009-B Light grey Recommendations for positioning The maximum stresses in the oil at the surface of the shield insulation must be limited to those values normal for insulated conductors and similar components in the same transformer. The adjacent recommendations are intended as guide lines when complete calculations are not carried out. Max D (See Fig. 6) 3) Area for uninsulated earthed details Nameplate with marking example. Fig. 8. Recommendations for positioning. goh_0006 goh_0014 9

Notes: 10

11

ABB Power Technology Products AB Components Visiting address: Lyviksvägen 10 Postal address: SE-771 80 Ludvika, SWEDEN Tel.+46 240 78 20 00 Fax +46 240 121 57 E-mail: sales@se.abb.com www.abb.com 1ZSE 2750-107 en, Rev. 1, 2000-04-15 Printed in Sweden by Globe, Ludvika, 2000