CABINET - CURRENT TRANSFORMER Indoor - Outdoor 240 Volts Amperes Maximum

Similar documents
CABINET - CURRENT TRANSFORMER Indoor - Outdoor 240 Volts Amperes Maximum

CABINET - INSTRUMENT TRANSFORMER Indoor - Outdoor, 480 Volt Maximum 1200, 1600, 2000 Ampere

ENTRANCE EQUIPMENT ER D PAGE 1 OF 5

10 Commercial, Industrial, Agricultural Services

SECTION PANELBOARDS

AMENDMENT ELECTRIC SERVICE MANUAL 2014

Customer Requirements Meter Socket Configurations

Section 6 Electric Metering: Residential

15-kV Wall-Mount Switchgear Three-Phase Indoor/Outdoor 600 Amp S&C Mini-Rupter Switch

SERVICE ENTRANCE - UNDERGROUND Single & Three Phase 200, & 320/400 Amp

COMMERCIAL QUICK REFERENCE

15-kV Live Terminal 600 Amp Group Operated Pad-Mounted Metal-Enclosed Outdoor Switchgear 140 Amp (Max) Clip Mount Current-Limiting Fuses

Approved Contractor Construction e-guide Residential Commercial

35-kV Thru-Bushings F Series (bolt-in) for Air-Insulated to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

GE 8000-Line Motor Control Centers

Recreational Vehicle Park Electrical Products & Accessories

CON EDISON EQUIPMENT

15 kv and 25 kv Thru-Bushings

Applications. Trim are flat gauge steel per code. Standard painted finish ANSI 61 gray. Directory card with plastic cover on front of trim

TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES

15-kV Safefront 200 Amp Primary Capacitor Station Pad-Mounted Outdoor

35-kV Safefront SuperWell Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current Limiting Fuses

Electric & Gas Service Requirements (Greenbook) Overview

35-kV Safefront 200 Amp Primary Metering Station Pad-Mounted Outdoor

INSTRUCTIONS FOR THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH

CABINET OPTIONS AND DESIGNATORS CODE LETTERS

Design Standard. Purpose: Design Standard:

25 kv Apparatus Bushings

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

MARWELL CORPORATION Manufacturer of UL Listed Meter Socket Adapters

35-kV 200-kV BIL Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

9. Non-Residential Services (Commercial, Industrial, and Agricultural)

CT Metering. CT Metering. Meter Mounting Equipment

PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide

35-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

A. Submit manufacturer's literature and technical data before starting work.

Wisconsin Area Catalog

Current Transformer, Termination & Disconnect Cabinets WE Energies Approved


Breakers and switches. Enclosed switches Heavy duty safety switches Fusible and non-fusible Amperes

Duke/MEG Approval Meter Equipment Group

35-kV Safefront 200 Amp SuperWell Primary Metering Station Pad-Mounted Outdoor

Heavy Duty Safety Switches

OVERHEAD SERVICE. Items to consider

Mini Power-Zone Unit Substation Product Description. Product Description. Features. Typical Applications

Approved Meter Sockets and Cabinets

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

fastfax Rock Solid TM Load Centers General Information

Accessories. Accessories. Meter Mounting Equipment

15-kV Live Terminal Primary Metering Station Pad-Mounted Outdoor

35-kV Safefront 200 Amp SuperWell Primary Capacitor Station Pad-Mounted Outdoor

15-kV Safefront 200 Amp Primary Transformer Station Pad-Mounted Outdoor

SECTION VII METERING INSTALLATIONS

15-kV Safefront 600 Amp Primary Transformer Station Pad-Mounted Outdoor

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear

15-kV Safefront 200 Amp Source Isolated Cable Switching Station Pad-Mounted Non-Fusible

ELECTRICAL METERING RESIDENTIAL

35-kV Safefront Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current-Limiting Fuses

Elegance Electrician s Installation Guide

Modular Metering. Canadian Version

New York City Apartment Metering Meter Sockets / Load Centers

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

W Series Cast Junction Box Options Boxes Available for Raintight, Watertight, or Submersible Applications

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Horsepower Ratings 240V AC 1 Phase, 2 Phase, 3 Phase, Ampere Catalog List Ship Wt.* Catalog List Ship Wt.* Indoor Type 1 Outdoor Type 3R

Cleaning Flooded Gear

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS

Instrument Rated Metering Equipment

7. SERVICES OVER 600 VOLTS

DTE Energy Area Catalog and Consumers Energy Multi-Position Sockets

UNDERGROUND SERVICES - SECONDARY

Switchgear Skid, C1192

Cleaning Flooded Gear

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

ComEd Service Area Meter Mounting Equipment

Volt Instrument Transformers

TABLE OF CONTENTS. Manufacturers of Quality Electrical Enclosures. Page: Page:

Detail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2 General Order

SAFETY SOCKET BOX. Note 8 3" MIN. 3" Max. (200 A)

Mipco Connections for Refrigerated Containers. No One Does It Like Mipco. The Mipco. Advantage. Reliability. Safety. Easy Installation & Service

MP Meter-Pak Meter Centers

Indoor or Outdoor 2400 to 14,400 Volts 600 to 14,400 Kvac, 3 Phase, 60 Hz

Variable Transformers Series to Amperes

STATE OF NEW JERSEY DEPARTMENT OF TRANSPORTATION TRENTON, NEW JERSEY 08625

P-2 D2P and EWP Factory Sealed Circuit Breaker Panelboards: Explosionproof, Dust-Ignitionproof, Watertight, Corrosion-Resistant

BUSWAY Low Voltage (Pow-R-Flex)

PSU EN54-4 Power Supplies

MEG Approval Meter Equipment Group

100-Ampere Busway. Effective November 2005 New Information. Elbow, Busway and Cable Tap Box. Technical Data TD E

15-kV Safefront Mini-Switch Source Isolated Pad-Mounted Switchgear 140 Amp (Max) Clip-Mounted Current-Limiting Fuses

Medium Voltage Metal-Enclosed Switches

REC Municipal Meter Mounting Equipment

Underwriters Laboratories Inc. Marking Guide. Panelboards. July 2004

Product Specification Sheet #3LD2.1

Meter Installation. -and- Padmount Transformer Guide

Metering and Service Installation:

10. METERING General Requirements

Product Guide. enclosed NEMA STARTERS

Benefits. Safety. Durability. Performance. Russellstoll. Heavy Industrial/ Marine

Transcription:

PAGE 1 OF 5 USE: 1. For commercial and industrial installations purchased and installed by the Customer. 2. For use on the following services: 1 phase 3 wire 240 volts, 3 phase 3 wire 240 volts, 3 phase 4 wire 120/208 volts, 800 amperes maximum. 3. To enclose 600 volts insulation class current transformers on indoor or outdoor meter installations. 4. For installing 2 or 3 current transformers only with provisions to bypass, remove, or replace while energized. LATEST REVISION: PREVIOUS REVISION 04-01-17 ORIGINATED 03-94 PREVIOUS NUMBER ER 15-446-A, 07-14-88 Updated Milbank catalog numbers and specified connection locations for Line and Load in Specifications section. SPECIFICATION: 1. GENERAL: 1.1 All current carrying parts should be designed on the basis of 1,000 amperes per square inch capacity for copper and 700 amperes per square inch for aluminum. 1.2 Dimensions shown are minimum. 1.3 Spacing between opposite polarity live parts and between live parts and ground mounted on the same surface not over 600 volts shall be a minimum of 2 inches and 1 inch, respectively, in accordance with the National Electrical Code, 408.56, latest revision. 1.4 Cabinets shall be marked by the manufacturer with the voltage, current rating, number of phases for which they are designed, and with the manufacturer s name or trademark so as to be visible after installation, without disturbing interior parts or wiring, in accordance with National Electric Code, 408.58, latest revision.

PAGE 2 OF 5 CABINET - CURRENT TRANSFORMER 2. SPECIFICATIONS FOR INDOOR OR OUTDOOR CABINET: 2.1 Cabinet: 2.1.1 Minimum Dimensions: 40 Inches High 8 Inches Deep 28½ Inches Wide - without Insulator Barriers 24 Inches Wide - with Insulator Barriers 2.1.2 Material - Minimum 14 gauge steel with enamel finish or 0.10 inch aluminum. 2.1.3 Front cover or door to be hinged and provided with sealing device so constructed that one (1) padlock seal will effectively prevent opening or partially opening of the cover or door.

PAGE 3 OF 5 2.2 Connections shall be made as follows: Line Connections shall be made on the top connection plate, and Load Connections shall be made on the bottom connection plate. 2.3 Current Transformer Primary Connection Plate: 2.3.1 Material - 1/4" x 4" x 5" copper, or 1/4" x 5" x 5" aluminum. 2.3.2 Drilled and tapped for current transformer, cable lug, and bypass jumper bolts. 2.3.3 Drawing shows 6 plates for mounting 3-600 volt class current transformers. When only 2 current transformers are required, omit neutral and provide center phase link. 2.4 Neutral Connection plate: 2.4.1 Material - Copper or aluminum, 24" or 28 ½" cabinet. 2.4.2 Drilled and tapped for cable lug bolts, #10-24 brass potential tap screw, and drilled for mounting bolts. 2.5 Bolts: 2.5.1 Material - Steel, zinc plated, ½" - 13 thread, with flat washer and hex head nuts. 2.5.1.1 For mounting CT's- 2-1/2" long, 8 req d for 2 CT's, 12 req d for 3 CT's. 2.5.1.2 For mounting terminal lug- 2-1/2" long, 4 req d for 2 CT's, 6 req d for 3 CT's. 2.5.1.3 For mounting terminal lug & bypass jumper--3" long, 4 req d for 2 CT's, 6 for 3 CT's. 2.5.1.4 For mounting two hole terminal lugs on neutral plate--3" long, 2 req d. 2.5.2 Material - Steel, zinc plated, 1/4" - 20 x 1-1/2" for mounting insulator bus, 8 req d. 2.5.3 Material - Steel, zinc plated, #10-24 x ½" with washer, for potential tap in neutral plate, 1 req d. 2.6 Lugs: Two hole cable terminal lug furnished for 2-500 KCM or larger copper conductors per phase: 6 req d for 2 CT's, 8 req d for 3 CT's 2.7 Knockouts Hubs: Size and location by Customer when req d.

PAGE 4 OF 5 CABINET - CURRENT TRANSFORMER

PAGE 5 OF 5 3. ADDITIONAL SPECIFICATIONS FOR OUTDOOR CABINET: 3.1 Cabinet: 3.1.1 The door or front cover shall be made rain tight and the top shall be protected with a rain shield. 3.1.2 Rain tight screened vent shall be located in upper portion of the cabinet. 3.1.3 All conduit shall enter the cabinet through the sides or bottom or through the rain tight hub on the top. 3.1.4 All hardware shall be rust resistant. 4. APPROVED MANUFACTURERS Manufacturer Phases Wire Number of CT's Catalog Number Indoor / Outdoor Erickson Electrical Equip. Co. 475 Bonnie Ln. Elk Grove Village, Illinois Milbank Manufacturing Co. 4801 Deramus Kansas City, Missouri 64141 1 or 3 3 2 283-1* 3 4 3 283-2* 1 3 2 NIPM-813 3 3 2 NIPM-833 3 4 3 NIPM-834 * - Optional vent kit (CAT#VENTKIT) must be ordered and installed for outdoor installations.