HWP Protection Board

Similar documents
OUTDOOR UNIT CONTROLLER (OUC)

Application Engineering

Application Engineering

Fan Coil Unit (FCU) Fan Motor Control

LG Air conditioning CAC and Multi Split unit Fault code sheet Universal and Multi Split Units

LG Air Conditioning Universal & Multi Split Fault Codes Sheet. Universal and Multi Split Units

HP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control

PRECISION UK Ltd DUPLEX AGSS PLANT

No Operation of air conditioner Explanation

MB A 12V/24V DC PROGRAMMABLE DUAL BATTERY ISOLATOR

P445 Series Electronic Lube Oil Control

D M S 760 C01 A A 1 1

Fault Codes. J control

Electronic Refrigerator Diagnostics

Two temperature sensors to protect against freezing and high head pressure in both the indoor evaporator and the outdoor condenser

REVISION HISTORY REVISION HISTORY

5220 AUTOMATIC MAINS FAILURE MODULE OPERATING MANUAL

BRIVIS DUCTED INVERTER SERVICE MANUAL DRCi

Easy Start. 364 (3 ton) Soft Starter 368 (6 ton) Soft Starter. Installation Manual

ZIP Economizer Fault Detection and Diagnostics (FDD) Table

Multi-colour LED Status Light - using it as a diagnostic tool:

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER. Models

Modulating Furnace Information. Warning on Meter Setting - Read First!

Northwest RV Supply Manual Compliments of Printed From TROUBLESHOOTING

DIFFERENTIAL THERMOSTAT

Ultrafryer Low Oil Level Model E3RL-14/8 Operation Instructions for Remote U-23 with Auxiliary Controls

XCITE Owner s Manual. Reso-not TM Damping System XCITE 1502C HYDRAULIC POWER SUPPLY

Part # Features & Applications Specifications Cross Reference

EasyStart. 364 (3 ton) Soft Starter 368 (6 ton) Soft Starter. Installation Manual

eapu Reference Guide System Component Information (For serial numbers starting with 37)

Technical Information and Diagnostic Guide

SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED TYPE

Variable speed application guidelines

Operators Guide: RoboSign Stop/Go Traffic Control System

Idle Free Systems, Inc. Reference Guide System Component Information

OnCommand Troubleshooting Guide Hayward Industries

Advanced EasyStart Troubleshooting

Secondary Coolant 301

Wiring diagrams on page 29 are for reference only. For detailed vehicle wiring refer to Navistar documents.

2.8 Liter VR6 2V Fuel Injection & Ignition, Engine Code(s): AAA m.y

SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Compact Wall Mounted Wall Mounted / Floor Compact Cassette / Slim Duct INVERTER MULTI

VC-4820 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL

CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS

GLM SERIES CONTROL Users Manual Rev:

Lastolite Lastolite Lumen8 F200 Lumen8 F400 Stored Energy Guide Number (m/100iso) Recycling Time (100%) Flash Duration Flash Power

¼ to 1HP Chiller Service Manual

Indoor air quality sensor.

Application Engineering Europe

R & D SPECIALTIES ROTROL I USER'S MANUAL

SELECT DIAGNOSTIC GUIDE. INST028 Doc 3.02

Table of Contents. For latest version, visit:

MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES M450

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 20 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

Power Inverter. User s Manual. Diamond Series CPD1200EILCD

24V 3A EN54 Ancillary Power Supply

Operators Guide: RoboSign Stop/Go Traffic Control System

Driftsinstruks. Utopia kontroller feilkoder PCP-2HTE og PC-ART. Vi håper de får stor glede av et Novema kulde produkt!

DEEP SEA ELECTRONICS PLC

HGM501 Gen-set Controller USER MANUAL. Smartgen Technology

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL

SHORT-STOP. Electronic Motor Brake Type G. Instructions and Setup Manual

DEEP SEA ELECTRONICS PLC

Envirotainer RAP e2 Container Operations Manual

Service Manual. 9. Maintenance. 9.1 Precautions before Maintenance. discharge resistance or plug of soldering iron. Installation and Maintenance

Vission 20/20 micro-controller. Operation and service manual

12. Troubleshooting Items to be checked first. Samsung Electronics

TZT-701 Thermostat Installer Manual

VC-30 / VC-40 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL

6. Troubleshooting. 6-1 Basic items for trouble shooting. Samsung Electronics 17

CAS. Product Specifications

HEAVY DUTY POWER RELAYS FEATURES

HPP1 MK5 Owner s Manual

TECHNICAL BROCHURE BSPDDRIVE. Aquavar SPD (Single Pump Drive) SIMPLEX VARIABLE SPEED PUMP CONTROLLER FOR SUBMERSIBLE AND CENTRIFUGAL PUMPS

BATTERY BOOSTER/CHARGER MODEL NO: DIGICAR 900

Hoshizaki America, Inc.

Air Cooled Packaged Units

SERVICE MANUAL (DOMESTIC & INTERNATIONAL)

9. Maintenance. 9.1 Precautions before Maintenance. Service Manual. electrolytic capacitor after power off. maintenance safely.

Light Source User Guide

DRAFT. Technical Data OPA Ducted Three Phase Packaged Air Conditioners. 47 kw 96 kw

PSK203/PSK223/PSK233. Digital Thermostats for Low Temperature Refrigerating Units 1 GETTING STARTED PSK203 PSK223 PSK233

! WARNING To avoid risk of electrical shock, personal injury, or death, disconnect power to range before servicing, unless testing requires power.

MCC Automatic Start-Stop Microcomputer Charger Control

SDM72 Start on Demand Modules

HPP1 MK5 Owner s Manual

SECOND GENERATION Use this guide with unit serial number prefix beginning with BWF using Terra Power separator.

MINE CHARGER INSTALLATION AND OPERATION MANUAL MODEL NUMBERS: MSP MSQ MSR MSS

1-50 KVA SINGLE-PHASE SERVO REGULATOR INSTRUCTIONS FOR USE SERVO SINGLE-PHASE VOLTAGE REGULATOR

Customer Training Catalog Training Proposal. Training Description for Network Energy COMMERCIAL IN CONFIDENCE 1

1333 (SERIES B & C) TROUBLESHOOTING GUIDE

2. Milk does not heat and the heater is not hot. a. Is there power getting to the pasteurizer heater? Check the incoming voltage to the contactor

1 This instrument must only be used by a competent and trained person and operated in strict accordance with the instructions.

ECHO Enhanced Controller Hook Count Application *** Infrared Photo Sensors *** GCA 110 ECHO Controller. Version 3.5

PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS. v1.1 Revised Nov 29, 2016

Control. Part B, Section 2. This section covers the following unit configurations. 3400V 3500V. Voltage 4. Pump Piston (E, F, G)

HGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology

Section 3 Technical Information

! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to oven before servicing, unless testing requires it.

Transcription:

February 2009 HWP Protection Board Features and Operation This board provides the system protection features necessary to keep our HWP (Water Sourced Heat Pump) units safe in the instances when they are NOT fitted with a sophisticated electronic thermostat that would provide equivalent protection. An example of such a thermostat is our SAT-2 or its successors. When an HWP unit has one of these Protection Boards fitted, a simple thermostat or a Building Management system can be used to request Cooling or Heating. The Protection Board will act independently of the external control system, to prevent potentially damaging situations occurring, such as rapid cycling of the compressor or running when the condensate drain tray is full of water etc. The HWP Protection Board does not control the Indoor fan. Therefore it cannot provide Fan Run-On if an Electric Heat Element has been fitted. A Fan Run-On timer must also be fitted when installing an Electric Heat Element. Unlike the SAT-2 thermostat, the HWP Protection Board cannot specifically identify most faults it detects, because it has no display and no ability to communicate with an external display device. It does however have three LEDs on its Printed Circuit Board (PCB). These LEDs help with fault diagnosis and serve the following functions: Green Amber or Yellow Red Indicates the Board is Powered Up Condensate / Drain Tray Float switch tripped There is a fault which has stopped the compressor As can be seen from the above table, the Yellow LED is specific to just one fault; the Drain Tray Float Switch (if fitted). The Red LED however does not specify which fault caused the compressor to stop. It simply indicates the existence of a fault. It is up to the Service Person to investigate the possible causes, which are: High Discharge temperature (DT) Low Indoor Coil temperature (ID) Low Suction temperature (LST) Measured by the Red sensor connected to the plug labelled DT on the HWP Protection Board. This safety feature works in both cycles to protect against high discharge temperatures caused by partial loss of refrigerant. Measured by the Yellow sensor connected to the plug labelled ID on the HWP Protection Board. This fault only applies in Cooling cycle. The sensor has no function in Heating cycle. Measured by the Blue sensor connected to the terminal labelled LST on the HWP Protection Board. Protects against excessively low Suction temperature in Heat cycle. This could result in the circulating water freezing and damaging the Tube-in-Tube heat exchanger. (Table continued on next page)

High Pressure switch trip (HP) Condensate (Water) Float switch trip (WF) Water Circulation Verification trip (CIR PUMP) If the 200 250VAC signal applied to the HP terminal disappears for more than 0.5 sec, the compressor will stop for at least 3 minutes. This safety feature works in both cycles. Repeated HP trips ( 3 times within 2 hours) will result in lockout. If the 200 250VAC signal applied to the WF terminal disappears for more than 0.5 sec, the compressor will stop for at least 3 minutes. This safety feature works in both cycles. Repeated trips ( 3 times within 2 hours) will result in lockout. If the 200 250VAC signal applied to the CIR PUMP spade terminal disappears for more than 0.5 sec, the compressor will immediately lockout. Notes in relation to these safety related inputs described above: a) Each must be in the safe state BEFORE the compressor can start. All inputs require a stable period without on/off fluctuations before they are considered valid. In the case of the Water Circulation Verification input, it must be closed and remain that way for 30 seconds before the compressor is allowed to start. This ensures that no air pockets are circulating around the water system. b) The term lock-out, means the compressor will not start again until either the power is removed and reinstated, OR the thermostat s Compressor request signal (connected to the COMP ON spade terminal) is removed and reapplied. c) References in this document to 200-250VAC Control and Fault input signals require the voltage to be measured relative to the N3 input terminal. N3 is NOT internally connected to Neutral on the HWP Protection Board. Ensure N3 is connected to Neutral when wiring the board to a unit. d) A sensor fault is a possibility. This is distinct from it measuring an out of range temperature. A sensor needs to be continuously faulty (either open or short circuit) for 3 minutes before it is recognized as faulty. The ERROUT connector: Roughly in the middle of the HWP Protection Board is a small, white coloured, 2-pin connector labelled ERROUT. On temperzone unit wiring diagrams it is called the FAULT OUTPUT. A temperzone Fault Relay (our part number 201 000 105) can be attached to this connector and wired into an end-user provided fault circuit. This enables indication of a fault without necessarily looking at the LEDs. DIP switch functions: In the bottom right hand corner of the HWP Protection Board is a bank of small switches (called DIP switches). Only the first 3 of these switches perform a function. Switch Switch ON function Switch OFF function 1 Enables Reverse-Cycle operation Selects Cool-only operation. 2 The Fault Output (ERROUT) is activated each time a fault occurs. The Fault Output (ERROUT) is activated only when lockout occurs. 3 An LST sensor trip occurs at a temperature of approx. 1 C on REV0C, and 2 C on REV0D HWP boards An LST sensor trip occurs at a temperature of approx. 2 C on REV0C, and 3 C on REV0D HWP boards

Control Inputs: There are only two control inputs. These are activated by a mains voltage signal in the range of 200-250VAC on to the relevant spade terminal. As was the case with the safety inputs (namely HP, WF and CIR PUMP), the voltage applied to the control inputs is relative to the N3 neutral connection. The Control input spade terminals are as follows: HEAT IN COMP ON If 200 250VAC is applied to this terminal it signifies to the HWP Protection Board that when the compressor next starts, it is to run in Heat cycle. If 200 250VAC is applied to this terminal it is a request for the compressor to start (or to Load ). On temperzone unit wiring diagrams this terminal is labelled COMP LOAD Mains voltage measured on the COMP ON terminal does not necessarily mean the compressor should be running. The compressor may be locked out due to a fault or waiting until the Anti-Rapid Cycle Timer has expired. Commissioning Mode: As with some other temperzone controls, a limited duration Commissioning mode is incorporated. When activated, delay times are dramatically shortened, saving time during commissioning or diagnostic tests. This mode will only last for about 25 minutes before normal operation is resumed. To activate, press and hold (for 10 seconds,) the small push-button labelled K1, located just above the DIP switches in the bottom right hand corner of the board. Models of HWP Protection Board: To date temperzone has used two versions of the HWP Protection board, both very similar. The identifying code is written on the PC Board, just below the DIP Switches. A simplified layout of the HWP Protection Board REV0C is shown below:

Summary of features provided by REV0C and REV0D boards: a) 3 minute Anti-Rapid Cycle control - Avoids short cycling the compressor b) Indoor Coil Freeze Protection - Stops Cooling if Indoor Coil < -1 C for 30 sec. c) Loss of Refrigerant Protection - Stops Compressor if Discharge temp >= 120 C d) High (Head) Pressure protection - Monitors HP switch (Mains voltage) input e) Low Suction temperature protection - Stops Heating if LST sensor < -1 or -2 f) Condensate overflow protection - Monitors the WF (Water Float) input g) No Compressor if Pump not running - Monitors Circulation Pump Verification input h) Starts/Stops Condensate Pump - Starts with Compressor. Stops 5 mins after Comp. i) Controls separate Fault Relay - Enables external indication of a fault Additional feature provided by REV0D boards: j) Water Circulation Pump control - A dry-contact relay to activate pump Our REV0D HWP Protection Board has one additional relay-switched output, absent on REV0C boards. This extra output activates and deactivates the Circulation Pump. A simplified layout of the HWP Protection Board REV0D is shown below: The PUMP IN and PUMP OUT spade terminals shown above are respectively the Pole and the Normally Open contact of the Circulation Pump relay. When multiple, individually controlled HWP units are installed on a site, the Circulation Pump relays from each of the Protection boards can be wired in parallel to the coil of the Circulation Pump contactor, so that any of the HWP units can start the pump. Then, only when none of the units are running will the circulation pump stop. N.B. In particularly cold environments, it may not be safe to stop the circulation pump at all for fear of the water freezing, in which case there should be an additional temperature controlled over-ride to keep the pump running even if no units were on.

Terminal labelling and function: Power terminals: L L1 L2 PRI N2 SEC N N1 LIVE PUMP IN Output terminals: PUMP COMP PUMP OUT The main Phase AC feed in to the HWP board. Current from this terminal flows first through the 3.15A / 250V (5 x 20mm) fuse located under the grey plastic cover. This terminal is powered from the load side of the fuse. This terminal should be connected to the White input wire of the EMI filter (temperzone Part No. 201 000 037). N.B. The input side of the EMI filter has the Green/Yellow Earth wire exiting from it. This is the Phase AC returning to the EMI filter. The White wire from the output side of the EMI filter should be connected to this terminal. A 2-pin connector provided for the Primary side of the mains transformer (temperzone Part No. 201 000 032) This is the Neutral return for the transformer primary. The Black wire from the output side of the EMI filter should be connected to this terminal. A 2-pin connector to receive the low voltage (nom. 10V AC) from the Secondary side of the mains transformer. This secondary voltage is what powers the Green LED. The main Neutral AC feed in to the HWP board. A wire from this terminal should be connected directly to the incoming Neutral supply to the unit. An additional Neutral terminal provided for convenience. (Internally connected to the N terminal.) The Black neutral wire from the input side of the EMI filter could be connected to this terminal. A spade terminal on top of the large black (compressor) relay. A phase supply must be provided to this terminal of a voltage suitable for the compressor or its contactor. Only applicable to HWP-REV0D Protection Boards. The voltage applied to this terminal is switched out to the PUMP OUT terminal to activate the water Circulation Pump. The same voltage that is present on the L1 is switched out of this terminal via a relay on the HWP board, to power the Condensate Pump. This is activated when the compressor is running and continues for 5 mins after compressor stops. This occurs on both cycles Cool AND Heat. A spade terminal on top of the large black relay. It can power small compressors directly or the Compressor contactor. Only applicable to HWP-REV0D Protection Boards. This is used to activate the water Circulation Pump.

Operation Overview: The following description assumes there are no faults present to start with and that mains power is applied to the unit. Therefore ONLY the Green LED should be lit. N.B. Unless in Commissioning Mode, the HWP Protection Board will not start the compressor for about 2½ minutes after the mains power is applied to the board, regardless of control signal requests. This is a precaution against brief power outages rapid cycling the compressor, and placing high loads on the electricity supply network. STEP FUNCTION OR ACTION Number REV0C Boards only 1 For Cool cycle do not apply power to the HEAT IN terminal. For Heating mains power should be applied. N.B. A signal to this terminal does not start the compressor, it only indicates which cycle is wanted. 2 Apply Mains power to COMP ON. N.B. It is this signal which requests that the compressor start or stop (for both Heat and Cool cycles) 3 N.B. The Circulation Pump must already be running AND the CIR PUMP (Water Verification) input should have a signal back from the flow switch confirming water flow. FUNCTION OR ACTION REV0D Boards only For Cool cycle do not apply power to the HEAT IN terminal. For Heating mains power should be applied. N.B. A signal to this terminal does not start the compressor, it only indicates which cycle is wanted. Apply Mains power to COMP ON. N.B. It is this signal which requests that the compressor start or stop (for both Heat and Cool cycles) Assuming the compressor has been OFF for at least 15 mins. The PUMP OUT relay is closed (to start the water circulation pump) In which case the COMP output would be activated at this point. 4 The Protection Board waits for a stable signal on the CIR PUMP (Water Verification) input. 5 Compressor operation continues until the COMP ON signal disappears or a fault occurs, in which case the compressor stops. 6 The 3-minute Anti-Rapid Cycle Timer is started, preventing the compressor from If stable for 30 seconds the COMP output is activated. If the CIR PUMP signal is not returned and stable within 3 minutes a fault is counted. Three periods of CIR PUMP failure within 2 hours will result in Lock- Out. Compressor operation continues until the COMP ON signal disappears or a fault occurs, in which case the compressor stops. The 3-minute Anti-Rapid Cycle Timer is started preventing the compressor from restarting in less than 3 minutes. restarting in less than 3 minutes. 7 PUMP OUT remains active for 15 minutes after the compressor stops. 8 Cycle again with each COMP ON signal Cycle again with each COMP ON signal

Protection features during operation: The function of each protection input is described at the bottom of the first, and the top of the second page of this brochure. A summary of the software controlled protection features also appears on page 4. The combination of the temperature sensors and the switched safety inputs being interpreted by the Microcontroller, at the heart of the HWP Protection Board, provides a high level of risk reduction, acting against problems that may occur causing damage to the compressor and refrigeration system of an HWP unit. When faults recur 3 times within 2 hours the HWP Protection Board locks out the unit so that it will not run again until either the COMP ON signal, or the Mains Power is removed and then reapplied. Such lock-outs should not be treated as nuisances. They will have been caused by a problem that needs further investigation to determine the exact cause as the Protection Board cannot identify each individual fault. Some of these potential problems are not immediately obvious and as previously pointed out the HWP Protection Board has only 2 Fault LEDs. One has a specific function (Drain Tray Float Switch), the other indicates a number of possibilities when it is illuminated so a methodical approach is required when investigating faults. Troubleshooting: Some guidelines for fault diagnosis follow. This list does not represent all the possible problems. Hopefully it provides a starting point for the Service Person. In presenting this list we are presuming that the Air Conditioner is not running (although the fan may be blowing air) and that it has been in this state for some time (i.e. It has locked-out ). STEP DIAGNOSTIC ACTION POSSIBLE CAUSE 1 Is the Green LED illuminated? No - There is no power getting to the board, or the Protection Board is faulty. Test for Mains voltage across L2 and N2. If no voltage present, yet it is present between L and N1, fuse is blown. (5 x 20mm 250V / 3.15A Glass fuse) Yes - Progress to the next step. 2 Is the Amber (or Yellow) LED lit? No - Progress to the next step. Yes - The Float switch input WF is open circuit. The drain line may be blocked or the condensate pump is not working. 3 Is the Red LED illuminated? No - The Protection Board has not detected a fault. The thermostat may not be activating the COMP ON input. Check voltage at the COMP ON terminal. Yes - One (or more) protection feature has been activated. Check terminal N3 is connected to Neutral. If not, turn off the power and make a secure connection between N3 and a Neutral terminal. If N3 is connected, go to the next step.

4 Has the unit ever run before, or is the unit being commissioned for the first time in its present location? 5 Is there mains voltage present on the control and safety inputs? 6 There may be a sensor fault. Do you have any of temperzone s standard sensors (Part numbers 201 000 101 Red, 201 000 102 Yellow, or 201 000 103 Blue)? No - Check the control signal wiring to the HWP. Of particular interest is the connection of the Water Flow Verification CIR PUMP input. It would normally be connected to a flow switch and the water pump interlock. This wiring may be faulty or if this is a REV0D board the PUMPIN and PUMPOUT relay terminals may not have been wired to activate the water circulation pump. The installer, not temperzone, makes all this wiring. Yes - One (or more) of the protection features has been activated. Go to the next step. No - Adjust the thermostat so that it is calling for the compressor to run. Ensure power is connected to the thermostat, allowing it to operate. If one of the safety inputs has no mains voltage measurable on it, trace that safety circuit to determine the cause of the problem. E.g. Pressure switch / Water not circulating / Drain Tray full of water. Yes - Go to the next step. No - Disconnect each temperature sensor from the socket on the HWP Protection Board that it is plugged in to. Using fine probes or fine wire inserted into the connector holes, measure the resistance of each sensor. Typical resistances are as follows: Temp C Resistance Ω Temp C Resistance Ω -10 57.7 k 35 6.4 k -5 44.0 k 40 5.2 k 0 33.8 k 45 4.2 k 5 26.1 k 50 3.5 k 10 20.4 k 55 2.8 k 15 16.0 k 60 2.3 k 20 12.6 k 65 1.9 k 25 10.0 k 70 1.6 k 30 8.0 k 75 1.4 k Yes - Unplug each sensor in turn. Temporarily connect a known good sensor. Wait at least 30 seconds to see if the Red Fault light goes out. When the Red light goes out you have located the faulty sensor. For further technical assistance or to order spare parts, contact a temperzone office or your local temperzone agent. temperzone (Auckland) New Zealand Ph. +64 (9) 279 5250 Fax: +64 (9) 275 5637 temperzone (Sydney) Australia Ph. +61 (2) 8822 5700 Fax: +61 (2) 88225701