SYSTIMAX 360 ipatch G2 Fiber Ultra High Density (UHD) Shelf, LC InstaPATCH Distribution Panel Instructions

Similar documents
SYSTIMAX 360 ipatch G2 Fiber Ultra High Density (UHD) Shelf, MPO Distribution Panel Instructions

SYSTIMAX 360 ipatch InstaPATCH Fiber Shelf Instructions

SYSTIMAX 360 ipatch G2 High Density Sliding Fiber Shelf Instructions

ipatch Ready Upgrade Kit for SYSTIMAX 360 Fiber Shelves Instructions

SYSTIMAX G2 4U Fixed Rear Access Combination Shelf Instructions

SYSTIMAX SMB-4-3/4, SMB-8-1/2 Shelf-Mounted Cable Bracket Kits and 1000G2-XCPB Expanded Cable Protector Kit

SYSTIMAX 360 FTP Evolve Panel Instructions

SYSTIMAX GS3 and 1100GS6 Evolve Modular Panel Instructions

FIBER CONNECTOR SAFETY WARNINGS

Instructions for Use - Opt-X 1000i Enclosure

Instructions for Use - Opt-X Ultra Enclosure Directives Enceintes Opt-X Ultra MC Instrucciones de Uso Caja Opt-X Ultra MR

Fiber Connector Shelf (CCS)

8400 Series Fiber Distribution System

OFS Fitel LST1U-072/7 and LSTLW Instruction Sheet (LaserWave) Fiber Optic Comcode: Termination Shelf Installation

Pretium Wall-Mountable Housing (PWH-02P/-04P/- 06P/-12P and FZB-02P-JB)

LSS1U-144/7 FIBER OPTIC SPLICE SHELF INSTALLATION GENERAL CUSTOMER SERVICES REFERENCES TOOLS REQUIRED

PATCHMAX GS3, GS6 and PowerSUM Modular Panels

Opticom Rack Mount Fiber Enclosures

Environmental Distribution Center (EDC-06P-NH)

Universal Splice Tray Installation Instructions

IBER DISTRIBUTION FRAME (FDF) FOR EXCHANGE SIZE 900MM x 2200MM x 300 MM

FL2000 Termination/Splice Panels User Manual

OFS LSS1U-864/ Instruction Sheet Fiber Optic Comcode: Splice Shelf Installation

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

LSW Connector Module User Manual

PanView iq (PViQ) Fiber Tray

Fiber optic splice closure

Fiber Splice Panel Rack Mount User Manual

Instructions for 2-row monitoring only

OFE-CLS-Type Outside Plant (OSP) Fiber Optic Closures Instructions

Instructions for 2-row monitoring only

Instruction, EDGE8-04U Quick Start Guide

UNP-U-Type Universal Panel Instructions

VHM-P (Non-Locking) and VHM-PL (Locking) Variable Height Arm with Slide-In Mounting Plate

Instruction Sheet 39mm Patch Panel MT RJ Jack Kits [ ], [ ], and [ ]

OFS 400A FIBER OPTIC INTERCONNECT Instruction Sheet UNIT (FOIU) Comcode INSTALLATION

LEXUS GX TOWING HITCH Preparation

FOSC-400A4 INSTALLATION INSTRUCTION

Assembly Instructions

BUDI-S-SP. Building distributor. Introduction. Seals. Kit content. Accessories. TC-957-IP Rev A, Feb Wrap around cable seals

2-row and All-row systems included.

Panduit PreConfigured Industrial Distribution Frame (IDF) Installation Instructions Part Numbers ZDF and ZDF

Installing the Switch

E Series Enclosures Installation Instructions (UL /UL2416 E Series Equipment Cabinet/Rack)

Fiber Optic Splice Module

(Refer to qualified personnel)

LPC Series Fiber Panel 12/24 Fiber Rack-Mount Enclosure Installation Instructions

Mini-OTE 400. Mini-OTE 400. Content 1 General 1.1 General product information 1.2 Cable types 1.3 Symbols in this guide.

Assembly Instructions

MF 9690, 9790, Challenger 660, 670

Ortronics. Mighty Mo. GX Cabinets. Designed to Perform, Configured to Fit

Patching & Splicing Shelf. 4.2 Side cable termination directly on the shelf using cable termination plate. IFC cable/break-out cable

Panduit PreConfigured ZDF48-RA Industrial Distribution Frame (IDF) Installation Instructions

HP BladeSystem c7000 Carrier-Grade Options Installation Guide

INSTALLATION INSTRUCTIONS

3875 Cypress Drive Petaluma, CA Fax

VHM-P (Non-Locking) Variable Height Arm with VESA Mounting Plate for 75 x 75mm or 100 x 100mm applications

PLEASE READ THIS INSTRUCTIONS CAREFULLY, BEFORE YOU START INSTALLATION

CORNING. CamSplice User Guide 2. TOOLS AN MATERIALS 1. GENERAL 3. LOADING CAMSPUCE INTO TOOL

icon User s manual Table of Contents section 6 icon module installation and removal

Universal Storage - Drawer and Overfile Stack Units

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

MODEL ELC-12/40-CVM-D BATTERY CHARGER

3713 TRUCK MOUNT. Installation Instructions for Personal Plow. CAUTION Read this document before installing the snowplow.

MIGHTY MO CABLE MANAGEMENT SYSTEM

DS1 Plug-In Digital Signal Cross-Connect (PIX-DSX-1) 19-Inch Shelf Kit Installation Instructions

FIST-FPS. Front Patching Shelf. Contents. 1 Introduction. 3 Installation of the shelf. 2 General. 1 Introduction

WAVETRAX USER MANUAL

Southwest Windpower Instruction Sheet AIR-X Circuit Replacement Kit

TECHNICAL DOCUMENT. PCNC Mill Enclosure Door Switch Kit. Installation

TOYOTA AVALON INTERIOR LIGHT UPGRADE Section TOYOTA II - Installation AVALON Procedures

UNPWM-U-Type Universal Wall Mount Patch Panel Instructions

FIST-GPS2-J. 19 2HU Splicing, Patching and Storage shelf. 5 Fiber routing. 1 Introduction. Contents. 2 General. 6 Storage. 3 Installation of the shelf

19 1HU Splicing and Front Patching Shelf

ES Series Enclosures Installation Instructions (UL /UL2416 ES Series Equipment Cabinet/Rack)

AUDIO KIT P/N APPLICATION BEFORE YOU BEGIN KIT CONTENTS. Verify accessory fitment at Polaris.com.

Part Name/Description Part Number Quantity Instruction Kit Metalfor Flow Sensor

RMK HANDLEBAR KIT P/N ; ; APPLICATION BEFORE YOU BEGIN KIT CONTENTS. Verify accessory fitment at Polaris.com.

FOSC-100 B/H FOSC-100 B2/H

Rostselmash Torum 740

CIRRUS AIRPLANE MAINTENANCE MANUAL

INSTALLATION INSTRUCTIONS

Chapter 3. Installing Equipment

Installation Instructions RD/HD

LEXUS GS 350/450h ILLUMINATED DOOR SILLS Preparation

IMPORTANT SAFETY INSTRUCTIONS

INSTALLATION INSTRUCTIONS

TOYOTA im INTERIOR LIGHT KIT Preparation

Accessories for FIST Racks and Shelves

Cab Kit Installation Instructions

2015 Mustang Lightbar (All Models) CDC#

Virginia Panel Corporation s 2100 Series/Gemini User s Manual. Installations, Operations and General User s Guide

AccessNET INSTALLATION NOTES BT LLU HDF1B BT ITEM CODE Issue: 2 Date: 16/07/02 Document Number: 6426/3/128/00

Assembly Guide ELECTRIC. Model Numbers: C1. (English) /14/11

Conflicts. Toyota Avalon Interior Light Upgrade. Part Number Accesory Code: IL2. Color Applicability/Trim Level.

Toyota Prius Interior Light Upgrade

WLP Series Wall Mounts (WLP Series Low Profile Wall Mount Enclosure) Installation Instructions

BLACK BOX. Fully assembled, ready-to-use wallmount cabinets. Elite Wallmount Cabinet User s Manual. Customer Support Information

Transcription:

Instruction Sheet 860564707 Issue 2, January 2014 SYSTIMAX Solutions SYSTIMAX 360 ipatch G2 Fiber Ultra High Density (UHD) Shelf, LC InstaPATCH Distribution Panel Instructions General The SYSTIMAX 360 fiber optic shelves, UHD-1U and UHD-2U, are 19-inch (483mm) wide rack mounted, ultra high density (UHD) shelves that accommodate 360 InstaPATCH distribution modules (DM). The 1U shelf includes one sliding tray that accommodates four distribution modules. The 2U shelf includes three sliding trays that accommodate four distribution modules each for a total of twelve distribution modules. This product is intended for indoor use or can be used outdoors in a suitable protective enclosure. Ordering information is listed below: Material ID Part No. Description 760188342 360G2-iP-1U-96F-LC-DM-LS-UHD 360G2 ipatch 1U 96F-LC distribution module, LazrSPEED, UHD shelf 760188359 360G2-iP-1U-96F-LC-DM-TS-UHD 360G2 ipatch 1U 96F-LC distribution module, TeraSPEED, UHD shelf 760188417 360G2-iP-2U-288F-LC-DM-LS-UHD 360G2 ipatch 2U 288F-LC distribution module, LazrSPEED, UHD shelf 760188425 360G2-iP-2U-288F-LC-DM-TS-UHD 360G2 ipatch 2U 288F-LC distribution module, TeraSPEED, UHD shelf For test data go to: http:///webtrak How to Contact Us SYSTIMAX 360 ipatch G2 Fiber LC UHD Shelves To find out more about CommScope products, visit us on the web at http:/// For technical assistance: - Within the United States, contact your local account representative or technical support at 1-800-344-0223. Outside the United States, contact your local account representative or Authorized Business Partner. - Within the United States, report any missing/damaged parts or any other issues to CommScope Customer Claims at 1-866-539-2795. Outside the United States, contact your local account representative or Authorized Business Partner. This product is covered by one or This product is covered by one or more of the following U.S. patents or their foreign equivalents: 5,923,807, 6,245,998. The ipatch System is covered by U.S. patents 6,285,293, 6,522,737 and 8,344,900 2014 CommScope, Inc. All rights reserved Page 1 of 10

860564707 Instruction Sheet Tools Required Phillips head screwdriver Isopropyl alcohol Lint-free wipes or tissues. Separately Orderable Parts Verify parts against the parts list below: Material ID Part Number Description 760161463 UHD-CBL-BRKT-3/8-NPT Shelf mounted bracket for 3/8 cables 760161471 UHD-CBL-BRKT-1/2-NPT Shelf mounted bracket for 1/2 cables 760058685 RMB-6-3/8 BRACKET Rack mounted bracket (RMB) for 3/8 cables 760058677 RMB-6-1/2 BRACKET Rack mounted bracket for 1/2 cables 760058701 RMB-5-3/4 BRACKET Rack mounted bracket for 3/4 cables 760159822 N/A 12-pair designation label Note: Contact your local account representative for ordering numbers for modules or panels. Important: Limits for ipatch panel connections to panel bus ipatch LC fiber shelves are limited to a maximum number of rack units (RUs) and will not support a fully populated rack or cabinet. ipatch LC fiber shelves support 26 rows per rack/cabinet, such as configured for (26) 1U shelves, (13) 2U shelves, (10) 2U UHD shelves, or any combination thereof. Limit the chain of ipatch panels connected to each cable bus port to a maximum of five (5) panel bus connectors (including controller). Start a new chain with every 6th connector in the rack system. CAUTIONS Isopropyl alcohol is flammable, and can cause eye irritation on contact. If eye contact occurs, flush with water for at least 15 minutes. In case of ingestion, consult a physician. Use only in well ventilated areas. Disconnected optical components may emit invisible optical radiation that can damage your eyes. Never look directly into an optical component that may have a laser coupled to it. Serious and permanent retinal damage is possible. If accidental exposure to laser radiation is suspected, consult a physician for an eye examination. Wearing safety glasses during installation of this shelf is recommended. Although standard safety glasses provide no protection from potential optical radiation, they offer protection from accidental airborne hardware and cleaning solvents. Page 2 of 10

860564707 Issue 2, January 2014 Step 1 Verify Parts Loose Parts Furnished with Shelf Quantity 1 Rear door Description 2 Hardware covers 4 12-24 x 3/8 screws 4 M6 x 12 screws 1 Hook-and-loop kit 2 Port designation labels 2 Adapter designation labels 1 ipatch Assembly Shelf assembly with panel bus jumper 1 Corrugated tubing 8 Flat retainer clips 1 Shelf installation instruction sheet 1 Fiber cleaning instruction sheet ipatch kit Port labels Shelf Hardware cover Rear door Sliding tray support brackets (2 places) 1. Verify parts shipped with this unit against the parts listed in the table and shown in figure above (2U shelf shown). Note: Remove tray support brackets on both sides of shelf prior to installation for 2U shelves. Step 2 Configure Mounting Brackets and Mount Shelf Flip left bracket for ETSI configuration 1. Remove tray support brackets, as shown in Step 1, on both sides of shelf prior to installing 2U shelves. 2. Configure mounting brackets on shelf to match type of equipment rack shelf is being installed on. Note: Shelf brackets are factory configured for 19-inch (483mm) rack mounting. Mount Shelf to Equipment Rack Flip both brackets for 23 (584mm) configuration 3. Align tabs on mounting brackets (two per bracket) with holes on front of equipment rails as shown on next page. 4. Install shelf to front of equipment rails and secure with supplied hardware; four 12-24 x 1/2 screws for 19-inch (483mm) rack and 23-inch (584mm) racks and four M6 x 12 screws for ETSI racks. Page 3 of 10

860564707 Instruction Sheet 5. Snap hardware covers over front of mounting brackets. Equipment rail UHD 2U shelf Snap hardware cover (2 places) Mounting bracket 12-24 screw (M6x12 for ETSI) (4 places) Step 3 Tray Features and Functions Tray 3 Forward Position Spring stop latch Tray 1 Spring plunger Rear Position 1. Each tray can slide to the front and to the rear. The trays have three positions: home, forward, and rearward and have a built-in mechanism to prevent them from being pulled too far either way. 2. The recommended sequence for populating the trays is 1-3 for the 2U. Tray 1 is at the bottom and tray 3 is at the top. 3. Pull spring plunger to slide a tray to the rear position until the tray stops. 4. Tray can be removed from the front by lifting the spring stop latch located at the right center of the shelf (when viewed from rear) as shown. Page 4 of 10

860564707 Issue 2, January 2014 Step 4 Connect Panel Bus Jumper 1. Pull and turn the left spring plunger to the open position, as shown in Step 3. 2. Pull a sliding tray rearward until it stops. 3. Connect the keyed female 10-pin connector on the panel bus jumper into the nearest cable bus port on panel bus as shown. 4. Install spare port built into jumper cordage into panel bus frame by turning it at an angle, inserting into frame, and turning it back perpendicular to frame. 5. Plug each panel bus jumper onto backplane kit and other end to panel bus located on rack. Use provided flat retainer clips to position panel bus jumper routing. ipatch kit black ribbon cables are already positioned. Note: The connector is keyed. The polarized tab on the jumper connector fits into the opening in the header connector on the panel bus. Important: Make sure that the jumper connector is fully seated in the header connector on the panel bus. Page 5 of 10

860564707 Instruction Sheet Step 5 Program the Order of Panels 1. After you have upgraded the shelves in the rack, you should restore power to the imvision controller for the rack and program the order of the panels. Note: For instructions, see the SYSTIMAX imvision Controller User Guide (860547876). Step 6 ipatch Upgrade Kit Removal Removing Upgrade Kit 1. Slide tray forward. 2. Use spudger to depress the release tab on one end of the ipatch upgrade kit and pull forward to release it. Repeat on other end, then pull the entire kit forward to remove it from the shelf. Note: If positioning the spudger is difficult, insert a small flat-blade screwdriver between the upgrade kit and trough bracket. Use the screwdriver blade to wedge space to position spudger. Caution: Pull kit away from shelf slowly to avoid damaging internal components. ipatch ready kit Wire end of spudger Release tab ipatch ready kit removed for clarity Removal Of Patchcords 1. Release the fiber connector by pulling on the connector body. 2. A spudger may be used for removal of patchcords. Page 6 of 10

860564707 Issue 2, January 2014 Step 7 Terminate Trunk Cables 96F trunk cable Shelf mounted bracket Shelf mounted bracket Secure subunits to shelf Cable gland 144F trunk cable High Density Trunks Rack mounted bracket 1. Secure incoming cables to 2U shelf using either the separately orderable shelf mounted brackets or the rack mounted brackets (RMB). For rack mounted brackets, follow instructions included with the brackets. 2. Mount trunk cables to rack mounted brackets or shelf mounted brackets as shown above. 3. Pull sliding tray to the rear to terminate trunk cable fanouts. Tighten locknut 24F trunk cable (4 places) Tie to T flange Cable gland (6 places) 24F trunk cable Cable gland Low Density Trunks Shelf mounted bracket, rotated front column Shelf mounted bracket, back column 1. When using 24F trunks, one trunk per module, secure 4 trunk cables (2 each side) aligned to each tray. Alternate adjacent cables between front column of shelf mount brackets and rear column of shelf mount brackets as shown. 2. Rotate shelf mounted brackets as shown to provide more room to route trunks. 3. Pull sliding tray to rear to terminate 24F trunk cable fanouts. Page 7 of 10

860564707 Instruction Sheet Step 8 Route Trunk Cable Fanouts D C B A D C B A Secure bundle Hook-and-loop tie (3 places) Cable Fanouts to ules A and B 3 (76mm) loops Tie loosely to slot Hook-and-loop tie (3 places) Cable Fanouts to ules C and D 1. Mate MPO connector(s) on DM with those on trunk cable or ruggedized fan out. 2. Create 3-inch (76mm) loops with cable to manage excess slack. Create 3-inch (76mm) counter clockwise loops with cables feeding distribution modules A and B, and clockwise loops with cables feeding distribution modules C and D. Note: Secure cables with hook-and-loop ties and bundle with cable tie to T shape bend limiters on sides. Step 9 Install Rear Door 1. Mount rear door to shelf by lining up one spring plunger to hinge hole and snapping-in the opposite side. 2. Pivot door to secure with thumb latches. Page 8 of 10

860564707 Issue 2, January 2014 Step 10 Tray Identification Front ID Rear ID 1. Break-off the tray identification numbers. Tray 1 Tray 1 Front Tray ID Rear Tray ID 2. Insert front tray ID between lenses, starting with tray 1 at the bottom. 3. Insert rear tray ID at center slot of each tray starting with tray 1 at the bottom. Page 9 of 10

860564707 Instruction Sheet Latch Fiber ring Tab Lance Slot 4. Install fiber ring by inserting tab under lance and engaging the front of the fiber ring to the front stiffener slot. Note: To remove the fiber ring, use a flat blade screwdriver to push on the latch to unlatch the fiber ring at the front. Step 11 Install Port Designation Label Patch cover Underside patch cover label 12-port label (or 2 row label) Port sleeve 1. To print a designation label, go to: http:///resources/labeling-templates and scroll down to the 360 UHD Shelves and select the proper label template. Note: Labeling website has three options for printing labels: 2-row label, 12-port label, or underside patch cover label. 2. Use Excel to record fiber routing information on designation label. 3. Print label on 8.5 x 11 (letter) paper provided. 4. Slide port label into lens port sleeve located at the front of the patch cover as shown. 5. For additional labeling, apply patch cover label to underside of patch cover. Page 10 of 10