The Combustex Pilot Pro 800 Pilot Burner Assembly with Ignition & Flame Failure Monitor

Similar documents
The Combustex Pilot Pro 500 Ignition System with Pilot Tip and Flame Sensor

The Combustex Pilot Pro 900 Ignition System with Pilot Tip and Flame Sensor

Igniter, BMS & Valve Parts Directory Contact Us Toll Free:

G600 Series Replacement Intermittent Pilot Ignition Controls

E Series CE Approved Intermittent Pilot Ignition Control

Heating and Gas Installations - December 2014

PAGE 1. TES Operation & Testing Guidelines: Tes Trouble shooting

BG1600M Intermittent Pilot Ignition Control

SECTION 3.00 WARNING WARNING ENGINE STARTUP AND SHUTDOWN PRESTART INSPECTION

Section 3 Technical Information

INSTALLATION MANUAL ACL 5500 COMBUSTION SAFETY CONTROLLER

G76x Direct Spark Ignition Controls

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin LowNOx Commercial Gas Electronic Spark Ignition Sequence

X4 Installation and Operation Manual - POWER FLAME INCORPORATED

Purging Air From Divider Block Lubrication Systems

G72x Series Direct Spark Ignition Controls

ACL HIGH EFFICIENCY BURNER ASSEMBLY PATENTED BURNER WARNING

INSTALLATION/OPERATION/MAINTENANCE INSTRUCTIONS FOR ARCHON MODELS WD2010L, WD2010, WD2010H WASHDOWN STATIONS. ARCHON Industries, Inc.

PROFIRE 1100i IGNITION FLAME SAFETY CONTROLLER

DELUGE VALVE MODEL: SD-DVA TECHNICAL DATA : VALVE OPERATION TRIM DESCRIPTION DESCRIPTION PRESSURE THREADED OPENING

TYPE E Main Valve Sizes 3 /8 through 12

Features Enclosed Burner. Enclosed Burner. No visible flame. Controlled Combustion environment with natural draft design

Proposition 65 Warning This product contains chemicals known to the State of California to cause cancer or birth defects or other reproductive harm.

97311T. Features T Enclosed Burner with Touch Screen Control Panel. No visible flame. Touch Screen Control Panel

Manifold Isolation Valves

Biogas safety control equipment

HLP M10 HLP M10 (AFTER SERIAL # )

Ideal Installation. I & M Mark 67 (1/2 6 ) Control Line. Installation & Maintenance Instructions for Mark 67 Pressure Regulators

Operating Manual. Safety/Process Flare Pilot

MAINTENANCE MANUAL FOR THERMOSTATIC TEMPERATURE REGULATING VALVE TRAC STYLE P

Skotch Trifecta Oil Valve System

ECLIPSE AIR HEAT BURNERS Series AH, DAH, TAH & CAH

Installing the Integral Platen Blow Off Valve

Start Up Instructions for the Kiln, Page 1 of 2

ANDERSON GREENWOOD SERIES 500 PILOT OPERATED SAFETY RELIEF VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

2010+ Camaro Triple-Threat Wet Nitrous System

IGNITION FLAME SAFETY CONTROLLER

TILLOTSON LTD., CLASH INDUSTRIAL ESTATE, TRALEE, CO. KERRY, IRELAND PHONE: FAX:

Welker Sampler. Installation, Operation, & Maintenance Manual. Model GSS-4HP

1600 PSI ELECTRIC PRESSURE WASHER

SD Bendix MV-1 Modutrol DESCRIPTION

Temperature Sensor Series

DELUGE VALVE DATA SHEET

LANDFILL GAS ELEVATED (CANDLESTICK) FLARE SYSTEM

Applies to: Models F, B, FE, and BE with spark pilot

Q= C. v P S Refer to Table 1 for part numbers and shipping weights. Accessories: Table 1: Valve Part Numbers and Specifications

Blow Off Valve Retrofit Kit

SD Bendix SR-5 Trailer Spring Brake Valve DESCRIPTION PORTS. 1-1/2" or 3/4" NPT Spring Brake Reservoir Mounting (SPR BK RES)

AIR CLEANER GENERAL REMOVAL. 1CAUTION Do not run engine without filter element in place. Debris could be drawn into the engine causing damage.

SIT Pilot Assembly Retrofit - # 308 (Replaces R. Shaw Pilot Asbly) (SKU # )

INSTALLATION, OPERATION AND MAINTENANCE MANUAL (IOM)

High Tension Spark Igniter (HTSI)

Auto-Flo Air-Assist Automatic Dispensing Valve

DO NOT INSULATE BELOW THIS LINE. * For sizes 1/2" to 1 1/2" add 2 1/2" to 'C' dimension.

TECHNICAL DATA. Viking Technical Data may be found on Style: 90 Degree Pattern (inlet to outlet)

Voltmaster Centrifugal Trash Pumps

Field proven low emissions. State-of-the-art low NOx firing - adjustable for application flexibility

MODERUSTIC Battery Operated Remote Control Electronic Safety Pilot System IPI Intermittent Pilot Light For Fire Pits or Fireplaces

G821L/G822L Series Integrated Function Direct Spark Ignition Controls

OCTOPUS SELECTION & INSTALLATION GUIDE

SD Bendix E-10PR Retarder Control Brake Valve DESCRIPTION. OPERATION - Refer to Figure 2

Hydraulics. Part B, Section 1. This section covers the following unit configurations. 3700V

SD Bendix MV-3 Dash Control Module DESCRIPTION. Bottom View

TECHNICAL DATA 1-1/2 (dn40)

Specifications of STICKTITE and PILOTPAK Nozzles

Troubleshooting Electronic Ignition

Installation for L1100, L1200, L1200N Series Liquid Level Switches and DVU150, DVU175, and DVU2105/2115/2120 Series Dump Valves. GENERAL INFORMATION

Specifications of STICKTITE and PILOTPAK Nozzles

100% OUTSIDE AIR MAKE-UP UNITS WITH DISCHARGE TEMPERATURE CONTROL & c.pco DIRECT DIGITAL CONTROL MODULE

GAS BURNERS TYPE JR Forced Draft Burners 3450 RPM motor and squirrel cage blower Leakage test, pilot and main gas cocks Gas electric pilot and gas ign

TROUBLESHOOTING. 1. What is the model and serial number? If you don t know, how old is it? Give description.

Q35 Series Automatic Vent Damper System

Parts List. Item # Part # # Reqd. Description

Description. Rhino SD2/XD2 Type-H Control Modules. S 55-Gallon Drum with Pneumatic Changeover S 55-Gallon Drum with Electric Changeover

M Installation Guide. PRECISION Manifold Series. Introduction. A. Assemble Manifold Components

INSTALLATION DATA 712 Series Pilot

Troubleshooting Manual

Electric Trolling Motor

SEASONAL MAINTENANCE CHECKLISTS Johnson Controls

Material Description Quantity UOM

HOT AIR LANCE PART MANUAL Rev. A

Welker Jet Top Entry Control Valve

Fuel System Diagnosis

Start-up Instructions

MODEL RCW NON-INTERLOCK PREACTION SYSTEM

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

Operation of the FFBH is enabled and disabled by the Automatic Temperature Control Module (ATCM).

PRESSURE CABINETS PROBLEM CAUSE SOLUTION

PowerLevel s e r i e s

Pilot Capacities/Specifications

Introduction. System Components

FABER BURNER ROUTINE MAINTENANCE

NXd Diesel Stacker System Instructions

SYMPTOM POSSIBLE CAUSES CORRECTIVE ACTION

SAVANNAH EI & DELUXE SYSTEM TROUBLE SHOOTING GUIDE

Auto-Flo Panel Reinforcement Automatic Dispensing Valve

Modulating Furnace Information. Warning on Meter Setting - Read First!

4.2 Component Identification

EXOTHERMIC CUTTING EQUIPMENT

5020 Series Injector

Transcription:

OPERATIONS MANUAL The Combustex Pilot Pro 800 Pilot Burner Assembly with Ignition & Flame Failure Monitor Safe, reliable ignition and flame failure protection combined with a proven, completely self-powered pilot head.

KEY FEATURES Heavy-duty low temperature piezo electric igniter, providing reliable self-powered ignition. Failsafe thermocouple-powered gas valve ensures the pilot flame is proven before the main fuel valve will open. Integral Venturi System aspirates combustion air through a built-in flame arrester. Built-in automatic lockout eliminates the need for costly auxiliary controls Unique 316 SS pilot assembly easily installs and retracts through a standard 1 NPT collar. Low fuel consumption design enables feasible natural gas or propane-based operation. Stainless steel and aluminum construction. High temperature Mica Ignition lead channeled through the mixing tube eliminates lead deterioration. TECHNICAL SPECIFICATIONS Operating Temperature Materials and Parts Valve Seals Gauge Ports Supply / Output Ports Max. Working Pressure Min. Working Pressure Mounting Supply Pressure Pilot Fuel Consumption Ignition Environment Rating Power Insertion Length Main Gas Direct Feed -40 C to +40 C Anodized Aluminum, 316 SS Buna N Standard, Viton Optional 1/8 NPT 1/4 NPT 30 PSI 5 PSI 1 Male NPT Filtered 20 PSI Natural Gas or Propane 7 SCFH, 7,000 BTU/Hr. 15KV Low Temperature Piezo Class 1, Div. 2 Hazardous Location Self-powered - 30mV Thermopile Multiples of 1 ft. or Custom Built 750,000 BTU/Hr.

The Combustex Pilot Pro 800 Pilot Burner Assembly with Ignition & Flame Failure Monitor OPERATIONS MANUAL Combustex recommends that this manual be read thoroughly before attempting installation or operation of the Pilot Pro 800. SAFETY FIRST. Operational Description Parts List & Diagram Installation Guidelines Start-up Procedure Operating & Lighting Procedure Maintenance Requirements Troubleshooting Guide p 1 p 2 p 3 p 8 p 9 p 11 p 11 The Pilot Pro 800 Pilot Burner System provides the three primary functions required to establish and maintain the pilot and main burner reliably and safely: Pilot flame ignition and confirmation before allowing main burner on. Venturi aspiration for proper fuel/air mixing (for pilot flame). Both pilot and main fuel gas shutoff and lockout after flame fail. A clean natural gas or propane supply is required on the supply port. When the pilot fuel gas valve is depressed, it allows gas to feed the pilot and holds the lower valve open. After the pilot is lit and the thermocouple has reached sufficient temperature (usually within 15-20 seconds), the lower valve will remain latched upon release of the push button. The output port will remain closed until the flame has been confirmed and the push button has been released. Within one minute of flame failure, the thermocouple will cool off and release the lower valve. The main supply port is now blocked. The remaining output signal now bleeds to atmosphere through the pilot burner ensuring no pressure in either pilot or main lines.

2 of 13 10 9 2 4 22 24 1 27 11 8 23 25 0.375 3 5 12 1.000 2.000 7 DETAIL C SCALE 1 : 1.5 Item Qty. Description Part No. 1 1 Top Body 1064 2 1 Upper Gas Valve Assembly 1065 3 1 Lower Gas Valve Assembly 1066 4 1 Igniter Push Button & Body Assembly 1067 5 1 Piezo Igniter Assembly 1068 6 1 Ignition Lead Wire Assembly 2004-(1 through 6) 7 1 Pilot Jet 1075 8 1 Pilot Valve 1097-1 9 1 Pilot Gauge 1077 10 1 Output Gauge 1078 11 1 Supply Gauge 1079 12 1 Flame Arrestor 1080 13 1 Bottom Body 1081 14 4 1/4-20 x 1 1/4 Socket Cap Screws 1082 15 1 7/8 x 0.049 SS Tubing 1083-(1 through 6) 16 1 Venturi 1084 17 1 24 Thermocouple 1085 17 1 36 Thermocouple 1086 17 1 48 Thermocouple 1087 17 1 72 Thermocouple 1088 18 1 Burn Tip 1089 A 19 2 Burn Tip Dowel Pin 1090 20 1 Thermocouple Set Screw 1098 21 1 Venturi Set Screw 1101 22 1 1/8 NPT Street Elbow 1094 23 1 Lower Valve Gasket 1095 24 1 Upper Valve Gasket 1096 25 1 Lock Nut 1097-2 26 1 Ceramic Retainer Spring 1098 A 27 1 Pilot Valve O-ring 1099 Part number suffix indicates insertion length. E.g. 2004-2 = 2 ft. insertion length. 21 16 15 1, 1.5, 2, 3, 4, 5, 6 (FEET) or CUSTOM 6 19 18 26 20 C 17 SECTION VIEW 13 14 BOTTOM VIEW

3 of 13 The mounting location chosen on the vessel should be determined by Operator accessibility and visibility Accessibility / entry into the fire tube Ease of tubing installation The recommended mounting configurations of the Pilot Pro 800 are Parallel Mount - Front side of the fire tube directly below the main burner with the tip of the pilot approximately 1.5 Inches behind the end of the main burner. (See drawing p. 4) Angle Mount - Where the flame arrestor impedes front mounting, the side entry is necessary. (See drawing p. 5) Either mounting method will require a 1 NPT union and nipple welded to the vessel to accept the male thread of the Pilot Pro 800 body. Adjust the length of this to suit standard lengths wherever possible. Use an approved aluminum thread lubricant when installing the unit. When the igniter length exceeds 48, it should be supported at about midpoint with either a J bracket or cross support. Installation as per the included P&ID drawings is recommended. A clean, steady gas supply is required for optimum reliable operation. It is recommended that a filtered instrument regulator be installed upstream at the point where the instrument gas is tapped off the main supply. The Pilot Pro 800 is not rated for sour gas service. One can expect lower reliability and higher maintenance when operated on this type of fuel. Where only sour or wet fuel is available, it may be advantageous to operate the pilot and instruments from an auxiliary propane source. When wet fuel may be present, an installed coalescing filter will reduce fouling problems. To help alleviate freeze-ups associated with wet fuel, the following precautions can be taken. Keep the lines as short as possible, and slope them back towards a drip pot located in a heated enclosure. Run fuel supply lines under the vessel insulation or heat and insulate fuel lines via other methods. Use lower supply pressures to reduce the pressure drop across the pilot valve.

5 10 0 15 SUPPLY PSI 5 10 0 20 30 15 OUTPUT 25 PSI 20 30 25 5 10 0 15 PILOT PRESSURE PSI 20 30 25 Pilot Pro 800 Operations Manual 4 of 13 Combustex Pilot Pro 800 Parallel Mount Pilot Burner Installation Back View Side View A Notes A dimension (length from outside end of a 1 collar to the tip of main fuel nozzle) required when ordering prefabricated units. Size to standard lengths when possible. End of Pilot Pro 800 igniter unit should be approximately 1.5 behind main burner. Mount level or pointed down. Avoid pointing unit upwards.

5 of 13 Combustex Pilot Pro 800 Side Angle Mount Pilot Burner Installation Top View Side View A A 45 Notes A dimension (length from outside end of a 1 collar to the tip of main fuel nozzle) required when ordering prefabricated units. Size to standard lengths when possible. End of Pilot Pro 800 igniter unit should be approximately 1.5 behind main burner. Do not exceed an angle greater than 45 degrees. Mount level or pointed down. Avoid pointing unit upwards.

6 of 13 Combustex Pilot Pro 800 Clean Dry Natural Gas Installation LLSD 1. 7. TI 5. 4. TC HTSD 2. PI 10B 10A 8. PRV 6A ESDV 6C TCV MAIN FUEL GAS 6B BDV VENT Bill of Materials 1. Pilot Pro 800 Controller (Igniter, Flame Failure Protection & Pilot Assembly) 2. 0-30 Psi Pressure Regulator 3. Pneumatic Level Switch 4. Pneumatic High Temp. Shut Down 5. Pneumatic Temperature Control 6. Combustex Series 100 1 Temp Control Valve 7. Temperature Indicator 8. 1 Pressure Regulator 9. Pressure Gauge 10. (A, B) Manual Block Valve

7 of 13 Modifications Adjust pilot regulator to 10-15 Psi Combustex Pilot Pro 800 Propane / Wet Fuel Gas Installation Adjust pilot adjustment needle valve in the Pilot Pro 800 body to 5-7 Psi Ensure switching valve actuates at unit output pressure These adjustments will reduce the pressure drop across the pilot adjustment needle valve, minimizing freeze-up with wet fuel gas and pressure fluctuations due to propane compressibility during low temperature operations. 3. HTSD HTSD 8. P/S FFSD P/S 1. 6. SV 2. PRV TC FUEL GAS 9A 7. PRV PI 5A ESDV 4. TC 5C TCV 9B MAIN FUEL GAS Bill of Materials PROPANE SET @ 7 PSI 2. PRV 1. Pilot Pro 800 Controller (Igniter, Flame Failure Protection & Pilot Assembly) 2. 0-30 Psi Pressure Regulator 3. Pneumatic High Temp. Shut Down 4. Pneumatic Temperature Control 5. Combustex Series 100 1 Temp Control Valve 6. 3-way Switching Valve 7. 1 Pressure Regulator 8. Pressure Switch 9. (A, B) Manual Block Valve

8 of 13 NOTE: It is the responsibility of the operator to ensure that the fire tube is purged of combustible mixtures prior to lighting any pilot. Due to the possibility of a control valve leak, the main fuel gas block valve should be closed for the required time to purge the fire tube. Check the integrity of all fittings. Purge the air and debris out of the lines up to the unit. The pilot adjustment valve has been factory set for use with a 20 Psi supply, and should not require adjustment. If a different supply pressure is used, adjust the pilot needle valve for a pilot pressure of 4-6 Psi. Adjust for a 4-5 flame. Too large or small of a flame may affect the thermocouple operation.

9 of 13 1. Ensure the main fuel gas valve is closed and the fire tube is air purged. 2. Open the pilot line manual block valve. 3. Verify approximately 20 Psi supply pressure to the unit. 4. Depress the pilot gas push button and hold. 5. Tune the pilot pressure to approximately 6 Psi by turning the pilot adjustment needle valve. 6. Depress the ignition push button repeatedly until the pilot flame is confirmed. 7. Continue to hold the pilot gas push button for approximately 10 seconds. 8. Release the push button and verify the presence of output pressure (output pressure should match supply pressure). 9. Slowly open the main fuel gas valve to ignite the main burner. PILOT GAS PUSHBUTTON 5 10 0 15 OUTPUT PSI 20 30 25 5 10 0 15 PILOT PRESSURE PSI 20 30 25 IGNITION PUSHBUTTON 15 10 SUPPLY 20 5 0 PSI 30 25 PILOT ADJUSTMENT OUTPUT PORT SUPPLY PORT

10 of 13 For trouble free operation, a maintenance and inspection schedule should be kept. Every 3 months test the ignition and shutoff features. The unit should lockout the pilot and main gas within one minute after flame fail. Should this not occur, refer to the troubleshooting guide. Once a year remove and dismantle the upper and lower valves. Inspect, clean and replace components as necessary. The flame arrestor should be inspected for blockages, built-up residue and heat damage. All seams and seals around the flame arrestor and igniter body should be free of cracks or holes that might let a flame escape. If any of these conditions are found, the element should be cleaned or replaced prior to returning to service. Inspect, clean and replace the ignition components as required. Combustex offers a service kit for the Pilot Pro 800 complete with 1 year recommended spare parts. This package contains the following items: Item Qty. Description Part No. 2 1 Upper Gas Valve Assembly 1065 3 1 Lower Gas Valve Assembly 1066 5 1 Piezo Igniter Assembly 1068 6 1 Ignition Lead Wire Assembly 2004-(1 through 6) 9 1 Pilot Gauge 1077 10 1 Output Gauge 1078 11 1 Supply Gauge 1079 12 1 Flame Arrestor 1080 17 1 Thermocouple (24, 36, 48 or 72 ) 1085 18 1 Burn Tip 1089 A 19 2 Burn Tip Dowel Pin 1090 20 1 Thermocouple Set Screw 1098 21 1 Venturi Set Screw 1101 23 1 Lower Valve Gasket 1095 24 1 Upper Valve Gasket 1096 26 1 Ceramic Retainer Spring 1098 A Part number suffix indicates insertion length. E.g. 2004-2 = 2 ft. insertion length.

11 of 13 Problem: Unit Fails to light i. Fault - Fuel Gas Failure Ensure that dry, clean fuel gas is available at the supply port. Interconnected safety shutdown devices such as high temperature or low-level switches may be holding the supply off. On newly installed units, ensure that the supply and output lines have been purged of dirt and debris. Fuel gas freeze-ups can be minimized with coalescing filters, insulated lines, or via preheating the fuel. Supply lines run under the vessel insulation or through the heater bath will eliminate the problem on most installations. ii. Fault - Internal Orifice is plugged Remove the unit and check for gas coming from the pilot jet when the fuel gas push button is depressed. If there is no gas present at this orifice, remove the pilot jet and clean the #75 orifice. If the problem persists, remove the pilot adjustment valve and the pilot jet and check for debris within. After lighting, adjust the pilot to the desired flame level. Typically, a 4-6 pound pilot is desirable. An instrument filter regulator installed upstream on the supply will eliminate particle fouling, while a coalescing filter upstream will minimize condensate fouling. iii. Fault - Spark Failure The piezo igniter unit will snap each time the push button is depressed. If not, the unit should be replaced or repaired. To confirm the spark is present at the igniters tip, the unit should be removed and sparking confirmed visually. The most common reason for spark failure is ignition lead wire deterioration. To test the piezo igniter, remove the ignition lead from the unit and hold a screw driver contacting the aluminium housing and within 1/4 of the piezo tip. If the spark fails to jump at least 1/4, replace the piezo assembly. Reconnect the ignition lead wire, and carry out the same procedure at the opposite end of the wire to confirm lead integrity. Replace if required. Problem: Intermittent Flame Failure i. Fault - High Temperature Bath Shutdown Ensure that the high temperature shutdown switch is set properly and that the temperature control circuit is functioning properly. When the high temperature switch is tripped, it will lock out gas to the Pilot Pro 800, and it may appear as a flame failure as the switch will eventually reset and allow a re-light. ii. Fault - Interconnected Device Shutdown Determine if any interconnected shutdown devices are shutting down the unit intermittently. Tattle tale pop out devices can be installed temporarily in the vents of the devices to determine the faulty one.

12 of 13 iii. Fault - Poor Flame Contact Should the unit shutdown for no apparent reason shortly after the main burner turns on, it may be the pilot flame is being pulled away from the thermocouple. To confirm if this is occurring, try running the pilot only, with the main burner blocked in for a period of time. If the unit operates normally under this situation, but shuts down once the main flame gas is opened, the problem is likely excessive draft being drawn by the main burner. Ensure that end of pilot is approximately 1.5 behind the main burner. iv. Fault - Inconsistent Gas Supply Ensure that the fuel gas is dry and clean. Refer to the Fuel Gas Fail and the Internal Orifices Plugged sections above for more details. Problem: Unit lights, but output will not match supply pressure i. Fault - Thermocouple Failure Confirm visually that the flame is striking the thermocouple. The unit should be capable of latch within 30 seconds of flame ignition. Under normal flame conditions, the thermocouple should have an output of 30mV. Replace the thermocouple if the output is low or takes an extended period of time to climb. ii. Fault - Coil Failure Should the thermocouple test positive, the lower gas valve assembly should be removed and cleaned. If this fails to work, the unit should be replaced.

13 of 13 The Canalta, Combustex Burner Ignition & Control Systems and Pilot Pro names and logos are trademarks of Canalta Controls Ltd. All other trademarks are the property of their respective owners. Due to Canalta s commitment to quality and innovation, all product designs, specifications and information materials, including the contents of this publication, are subject to change without notice. Responsibility for the proper selection, maintenance and use of any product remains with the customer. SAFETY FIRST. 2011-2015 Canalta Controls Ltd. All rights reserved. Unauthorized reproduction in whole or in part is prohibited.