Analysis of the Volt/VAr Control Scheme for Smart Distribution Feeders

Similar documents
Physical Design of a Volt/Var Implementation

Y9. GEH2.3: FREEDM Cost Benefit Analysis based on Detailed Utility Circuit Models

Presented By: Bob Uluski Electric Power Research Institute. July, 2011

IEEE-PES Chicago Chapter Presentation November 11, Smart Grid. Mike Born. Principal Engineer, Capacity Planning

Adaptive Power Flow Method for Distribution Systems With Dispersed Generation

Assessing Feeder Hosting Capacity for Distributed Generation Integration

B-4: Reducing Peak Demand through Distributed Grid Edge Control

Galapagos San Cristobal Wind Project. VOLT/VAR Optimization Report. Prepared by the General Secretariat

SCE's Experience Distribution Volt/VAR Control:

Technology Roadmap for zzzzzzzzz Grid Automation

Effect of prime mover speed on power factor of Grid Connected low capacity Induction Generator (GCIG)

Conservation Voltage Reduction (CVR) Phillip Anderson P.E. Engineering Project Leader Research, Development & Deployment

New York Science Journal 2017;10(3)

Influencing the Portfolio through the Distribution System Case Study- Pullman, WA

The Effect Of Distributed Generation On Voltage Profile and Electrical Power Losses Muhammad Waqas 1, Zmarrak Wali Khan 2

MIPSYCON 2014 Can a Grid be Smart without Communications? A Look at an Integrated Volt Var Control (IVVC) Implementation

Enhancement of Power Quality in Transmission Line Using Flexible Ac Transmission System

A Transient Free Novel Control Technique for Reactive Power Compensation using Thyristor Switched Capacitor

Voltage Sag Mitigation in IEEE 6 Bus System by using STATCOM and UPFC

VOLTAGE STABILITY IMPROVEMENT IN POWER SYSTEM BY USING STATCOM

Grid Management Voltage Control Distribution Grid Voltage Regulation with DER. Michael Sheehan, P.E. IREC Pacific Northwest Solar Partnership

CIS-IEEE 2017 Conference Renewable Energy Session Renewable Energy s Impact of Power Systems

CHAPTER 1 INTRODUCTION

OPTIMUM ALLOCATION OF DISTRIBUTED GENERATION BY LOAD FLOW ANALYSIS METHOD: A CASE STUDY

IJRASET 2013: All Rights are Reserved

Field Verification and Data Analysis of High PV Penetration Impacts on Distribution Systems

SMART MICRO GRID IMPLEMENTATION

Integrated System Models Graph Trace Analysis Distributed Engineering Workstation

International Conference on Advances in Energy and Environmental Science (ICAEES 2015)

Impact of electric vehicles on the IEEE 34 node distribution infrastructure

PV Grid Integration Research in the U.S.

INSTALLATION OF CAPACITOR BANK IN 132/11 KV SUBSTATION FOR PARING DOWN OF LOAD CURRENT

Network Reconfiguration for Loss Reduction and Voltage Profile Improvement of 110-Bus Radial Distribution System Using Exhaustive Search Techniques

DEMAND RESPONSE ALGORITHM INCORPORATING ELECTRICITY MARKET PRICES FOR RESIDENTIAL ENERGY MANAGEMENT

IEEE PES Volt/Var Control Task Force (VVCTF)

DISTRIBUTED GENERATION FROM SMALL HYDRO PLANTS. A CASE STUDY OF THE IMPACTS ON THE POWER DISTRIBUTION NETWORK.

RThe renewable energy plays an important role in our live

United Power Flow Algorithm for Transmission-Distribution joint system with Distributed Generations

STABILIZATION OF ISLANDING PEA MICRO GRID BY PEVS CHARGING CONTROL

Impact of Plug-in Electric Vehicles on the Supply Grid

RYERSON UNIVERSITY CENTRE FOR URBAN ENERGY. Bala Venkatesh, PhD, PEng Professor and Academic Director

COMPARISON OF DIFFERENT SOFTWARE PACKAGES IN POWER FLOW AND SHORT-CIRCUIT SIMULATION STUDIES. A Project

Design and Implementation of Reactive Power with Multi Mode Control for Solar Photovoltaic Inverter in Low Voltage Distribution System

EPRI Intelligrid / Smart Grid Demonstration Joint Advisory Meeting March 3, 2010

Laboratory Experiments for Enhanced Learning of Electromechanical Devices

Energy Security Electrical Islanding Approach and Assessment Tools. Dr. Bill Kramer Senior Research Engineer Distributed Energy Systems Integration

FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE

PV2GRID - A next generation grid side converter with advanced control and power quality capabilities

Session 8: Distributed Energy Resources Utility Concerns, Grid Impacts and Mitigation Strategies October 21, 2015 Santiago, Chile

Development of Electrical Power System Simulator.

POWER FACTOR CORRECTION USING SHUNT COMPENSATION

A STUDY ON ENERGY MANAGEMENT SYSTEM FOR STABLE OPERATION OF ISOLATED MICROGRID

ANFIS CONTROL OF ENERGY CONTROL CENTER FOR DISTRIBUTED WIND AND SOLAR GENERATORS USING MULTI-AGENT SYSTEM

A SIMPLE CONTROL TECHNIQUE FOR UNIFIED POWER FLOW CONTROLLER (UPFC)

Optimal Placement of Distributed Generation for Voltage Stability Improvement and Loss Reduction in Distribution Network

PV2GRID - A next generation grid side converter with advanced control and power quality capabilities Elias Kyriakides

TRANSNATIONAL ACCESS USER PROJECT FACT SHEET

INTELLIGENT DC MICROGRID WITH SMART GRID COMMUNICATIONS: CONTROL STRATEGY CONSIDERATION AND DESIGN

LOCAL VERSUS CENTRALIZED CHARGING STRATEGIES FOR ELECTRIC VEHICLES IN LOW VOLTAGE DISTRIBUTION SYSTEMS

Power Flow Simulation of a 6-Bus Wind Connected System and Voltage Stability Analysis by Using STATCOM

Workshop on Design and Implementation of Power Converters with EMC/EMI Modelling for Micro Grid & Electric Vehicle Applications

DC Voltage Droop Control Implementation in the AC/DC Power Flow Algorithm: Combinational Approach

Cost Benefit Analysis of Faster Transmission System Protection Systems

Performance Analysis of Transmission Line system under Unsymmetrical Faults with UPFC

International Journal Of Global Innovations -Vol.2, Issue.I Paper Id: SP-V2-I1-048 ISSN Online:

Dynamic Behaviour of Asynchronous Generator In Stand-Alone Mode Under Load Perturbation Using MATLAB/SIMULINK

Design Modeling and Simulation of Supervisor Control for Hybrid Power System

Performance Analysis of 3-Ø Self-Excited Induction Generator with Rectifier Load

A Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design

Electric Vehicles Coordinated vs Uncoordinated Charging Impacts on Distribution Systems Performance

Dual power flow Interface for EV, HEV, and PHEV Applications

Available online at ScienceDirect. Procedia Technology 21 (2015 ) SMART GRID Technologies, August 6-8, 2015

Tutorial 1 Aug 21 st, Sable A 9-12pm

Transportation Electrification Public Input Workshop. August 3, 2016

Maintaining Voltage Stability in Power System using FACTS Devices

Next-generation SCADA and Control Technologies for Large-scale Use of Photovoltaic Generation on Electric Power Grid

Load Analysis and Multi Body Dynamics Analysis of Connecting Rod in Single Cylinder 4 Stroke Engine

Distribution System Analysis for Smart Grid

Accidental Islanding of Distribution Systems with Multiple Distributed Generation Units of Various Technologies

Smart- Grid Ready PV Inverter

Implementation of FC-TCR for Reactive Power Control

Power System Stability Analysis on System Connected to Wind Power Generation with Solid State Fault Current Limiter

Characterization of Voltage Rise Issue due to Distributed Solar PV Penetration

Design Issues and Practical Solutions for Electric and Hybrid Electric Vehicle Propulsion Systems

Academic Course Description

Transforming the US Electric Grid

Optimization of Seat Displacement and Settling Time of Quarter Car Model Vehicle Dynamic System Subjected to Speed Bump

Impact of High Photo-Voltaic Penetration on Distribution Systems. Design Document

Enabling High Penetrations of Distributed Solar through the Optimization of Sub-Transmission Voltage Regulation

TECHNICAL IMPACTS OF ELECTRIC VEHICLES CHARGING ON AN ITALIAN DISTRIBUTION NETWORK

ITT Technical Institute. ET3480T Power Systems Onsite Course SYLLABUS

The hierarchical three layer protection of photovoltaic generators in microgrid with co-ordinated droop control for hybrid energy storage system

Simulation of real and reactive power flow Assessment with UPFC connected to a Single/double transmission line

GRAND RENEWABLE ENERGY 2018

How New Microgrid Technologies Enable Optimal Cooperation Among Distributed Energy Resources

Remarkable CO 2 Reduction of the Fixed Point Fishing Plug-in Hybrid Boat

Complex Power Flow and Loss Calculation for Transmission System Nilam H. Patel 1 A.G.Patel 2 Jay Thakar 3

Modeling, Control Design, Estimation and Diagnostics Algorithms MATLAB/Simulink, dspace, Microsoft Office

Sl. No. Subject Description Level of Study 01 Power Different types of converters, inverters. 6 th Sem Electronics 02 Power System I& II

Developing tools to increase RES penetration in smart grids

Transcription:

Analysis of the Volt/VAr Control Scheme for Smart Distribution Feeders Mahti Daliparthi, Marsela Jakub-Wood, Anjan Bose, and Anurag Srivastava The School of Electrical Engineering and Computer Science Washington State University Pullman, WA Abstract With ongoing smart grid activities, there are a number of active demonstration projects in different parts of USA. In the northwest, an ongoing demonstration project is conducted by Avista Utilities to improve the reliability and efficiency of the distribution system. This project includes automated management of distribution system and bi-directional communication capabilities between the devices in the field and the control center. With the added communication capacity, the newly installed equipment coupled with the distribution automation system has the ability of enhanced monitoring and control as well as the potential to decrease the overall power demand. This research explores one aspect of the smart grid in distribution automation called the Volt-VAr Control (VVC) scheme. Voltage regulation over a distribution feeder serves the purpose of achieving a flat voltage profile and maintaining the permissible voltage (plus or minus 5% of rated voltage) at the end-use customer. VAr control allows power factor correction in near real time. To accurately predict the benefits and plan Volt/VAr control, an accurate representation of the load models is essential. The benefits of VVC include reduction of losses, maintenance costs, operating costs, voltage variation, and increase in the power delivery capacity of existing equipment. Resulting analysis of the VVC control shows demand savings of 2-3% for every 2.5% voltage drop. I. INTRODUCTION Distribution utilities are under the increased pressure to maintain quality of power delivered to the end use customer in this digital era where the demand is increasing day by day. Integration of renewable energy as an alternate generating source also requires enhanced control on the distribution system. Intelligent distribution automation techniques must be developed to achieve efficiency, reliability, and security for the power grid. Volt/VAr control (VVC) scheme [1] is one such concept that allows reducing voltages in permissible range along the feeder and allows power factor correction in near real-time to reduce peak power demand and minimize losses on the system. This also increases the efficiency and lifetime of equipment. Voltage control can also lead to Conservation Voltage Reduction (CVR), defined as the reduction of energy consumption due to the reduction of feeder voltage. Studies of CVR in [2] and [3] have established that a 1% reduction in voltage leads to 1% reduction in the power demand. According to the ANSI standards, the range for voltages at the distribution transformer terminals must be within 114 and 126 volts [4]. CVR is accomplished by line drop compensation (LDC), where the tap settings of the voltage regulators are automatically adjusted to maintain the end of line (EOL) voltage within specified voltage. CVR studies by Pacific Northwest National Laboratory have concluded that the behavior of the end-use loads must be accurately modeled to represent the effects of CVR on a feeder [2]. Load models are classified into two broad categories: static and dynamic. This paper focuses on static load models because in voltage reduction studies, it is sufficient to use only these models as the steady-state real and reactive powers are functions of bus voltages at a fixed frequency [5]. Near real-time power factor correction is achieved through the systematic switching of the switched capacitors on the feeders. This is the most effective way of meeting the load VAr requirements on the system. Fixed banks are installed to meet the minimum load requirements while switched banks are added or removed as the load increases or decreases [6]. With the added communication feature of the smart grid, the switched capacitor can now receive power factor information from the beginning of the feeder, broadening its power factor correction reach. Avista Utilities requires the end of line voltage at the primary side of the distribution transformer to be at 120V and power factor to be above 95% lagging. Previous literature on VVC schemes concentrate only on developing an algorithm and proving the theory for prototypical feeders using typical load parameter values [7],[8],[9]. This paper uses actual field load data for every five-minute interval to quantify the benefits of VVC over a period of time for a given feeder. Different ways to improve the accuracy of the scheme have also been explored. Operation of switched capacitor banks to achieve greater energy benefits is analyzed. Load parameters using statistical approaches for an accurate representation of the loads on the distribution feeder have also been determined. These different techniques help to achieve a more accurate study of the benefits of the VVC scheme under different scenarios. The rest of this paper is organized as follows: Section II describes the Smart Grid implementation plans in Pullman, WA. The detailed procedures for VVC scheme are explained in Section III. Section IV discusses the significant factors that affect VVC and some concluding remarks are given in Section V. 978-1-4673-2308-6/12/$31.00 2012 IEEE

II. PULLMAN DISTRIBUTION SYSTEM Located in the Pacific Northwest, Pullman, Washington is part of the Smart Grid Demonstration project funded by the Department of Energy and led by Avista Utilities. One of the goal of this project is to achieve a flat voltage profile on the system by voltage optimization. Over 13,000 Smart Meters have been installed for every customer in Pullman as part of this project. Deployment of these meters in an Advanced Metering Infrastructure (AMI) makes power and voltage readings readily available. The town of Pullman is fed by thirteen feeders with newly installed automated line switches, reclosers, and fixed and switched capacitor banks. Two feeders out of these thirteen feeders have been considered in this study, which will be referred as Pullman Feeder 1 (PF1) and Pullman Feeder 2 (PF2). The configuration for feeder PF1 with the 'smart' equipment is shown in Fig. 1. There is one fixed capacitor with 200 kvar rating per phase and two switched capacitor banks with 300 kvar rating per phase. The components of load diversity are as follows: 41.68% residential, 57.86% commercial and 0.47% industrial loads. PF2 shown in Fig. 2, has three newly installed switched capacitor banks and automated reclosers. The loads are divided as 75.19% residential, 24.57% commercial, and 0.24% industrial. Figure 1: Pullman Feeder 1 III. Figure 2: Pullman Feeder 2 VOLT/VAR CONTROL SCHEME A. VVC OFF To quantify the benefits of Volt/VAr control, simulation results of VVC OFF and ON weree compared. Procedure for VVC OFF is shown in the flowchart below in Fig. 3. SynerGEE, a commercial distribution software tool was used for the analysis [10]. In order to automate the simulation procedure, a Component Object Model (COM) of SynerGEE called Solver is utilized and linked to SynerGEE using Visual Basic. As illustrated in the flowchart, the VVC OFF simulation starts by taking the load input data for a five minute time interval, T. Then, the loads are allocated uniformly based on the connected kva of every section. Load allocation is used to distribute load throughout a model, based on demands specified at the feeder source. To accomplish this, all the distributed loads are adjusted on a feeder so that the total load into a feeder after a by-phase analysis matches the demands specified in the feeder. The value of these distributed loads is determined by running a load-flow analysis, then looking at the difference between the specified feeder demand values and the actual power into the feeder. This mismatch is divided among the sections and phases [11]. After all the loads have been allocated, a load flow analysis is conducted and the power demand and voltages are recorded. B. VVC ON The VVC ON simulation adjusts the taps of the voltage regulator and the settings of the switched capacitors based on the rules set by the user. The voltage regulator uses LDC, a controller that monitors the voltage at the feeder and raises or lowers the taps to maintain the specified EOL voltage. This is done by using an internal model of the impedance of the distribution line to match the line impedance. The R and X values are settings of the regulator which can be adjusted for the desired compensation [12].

Figure 3: Flowchart for VVC OFF Procedure Capacitor banks are installed at strategic locations along the feeder as a source of reactive power. Fixed banks provide constant VAr support and switched banks are place in and out of service based on the load variations. The procedure for VVC ON is shown in the flowchart in Fig. 4. The simulation starts with taking the input data for a fiveminute interval, T, running a load allocation and load flow analysis. The power factor is calculated using the load flow results. If the power factor is less than 95% lagging, then the largest switched capacitor bank is turned ON. After power factor correction, the regulator LDC is set by specifying the EOL voltage. Then, the load flow analysis is run again with the new settings, and the results from this are recorded. Figure 4: Flowchart for VVC ON procedure To quantify the benefits for each five minute interval, the savings are calculated as shown in ( 1) and ( 2). Δ kw represents the change in power demand and % ΔV represents the percentage change in voltage. % Δ 100 ( 1 )

% Δ 100 ( 2 ) After developing the basic algorithms, the challenges in implementing these studies for practical purposes were analyzed. Load models have a direct correlation in estimating savings in power demand. Placement and control of capacitor banks also play an important role as explained in the following section. IV. FACTORS AFFECTING VVC SCHEME A. Load Models The types of loads on a feeder have a direct impact on the benefits of VVC. Static load models are widely represented by the ZIP model where the real and reactive powers are functions of voltage and the coefficients of that relationship are constant impedance (Z), constant current (I) and constant power (P): S=S 0 Z V I V PQ V V where S is the actual apparent power, S 0 is the apparent power at a reference voltage V 0, and Z+I+PQ=1 [13]. It is important to note that the ZIP model is realistic only for V near unity and the coefficients can assume negative V 0 values if they are computed from measurements. From (3), it can be observed that a constant impedance model results in the most energy savings since the apparent power is proportional to the square of voltage as illustrated in Fig. 5. For a 100%I load model, the energy savings were lower than 100%Z model and even lesser savings for 100%P load model. Typical ZIP values were also identified from previous literature as 30%Z, 70%P for a residential customer, 50% Z, 50% P for commercial and 20% Z, 80% P for an industrial customer [3]. Results using these settings are shown in Figure 6 and Figure 7 for a 24-hour period. With an EOL of 120 V, the average energy savings are 2% for a voltage reduction of 2% for PF1 and PF2. Previous literatures have used constant ZIP parameters throughout the entire simulation. However, because load characteristics change according to various external elements, using constant ZIP parameters would unreliably estimate the benefits of the smart grid. Thus, this paper describes the method established in order to obtain ZIP parameters for varying time and temperature conditions. To find ZIP parameters for each feeder at small time intervals, a least squares parameter estimation technique has been developed. The power demand is dependent on voltage, time of day, day of week, and temperature. Taking these three factors into account, the flowchart in Fig. 8 explains the procedure to estimate the ZIP parameters from feeder load data. Validation of these parameters is still a challenge. (3) Figure 5: Energy Savings for Different Load Models Figure 6: PF1 Energy Savings Figure 7: PF2 Energy Savings B. Switched Capacitors Operation The rules followed by Avista Utilities to control the switch capacitors are as follow: Turn ON switch caps if the power factor is below 95% lagging Turn OFF switch caps if the power factor is below 98% leading However, with these rules on PF1 and PF2 the capacitors never turned ON as power factor was always above 98% lagging. The limits of the control were made stricter and the new rules were changed to the following: Turn ON switch caps if the power factor is below 98% lagging Turn OFF switch caps if the power factor is below 98% leading

The capacitor switching is limited to once every 30 minutes. Fig. 9 shows the energy savings with more stringent power factor limits for PF2. The switched cap did turn ON at the peak load condition and the loss savings are higher with that capacitor ON as shown in Fig. 9. However, energy savings was not a significant advantage. The next step in this procedure is to find the optimal locations for the switched capacitor banks and also the optimal control strategy. The capacitor control can be based on VAr, voltage, or time of day, with the goal of minimizing the losses. V. CONCLUSION This technical paper described the Volt/VAr Control scheme to be implemented on the distribution feeders in Pullman, WA as part of the Smart Grid Demonstration Project. To quantify the benefits of voltage optimization, a procedure was developed, real-time feeder load data was used to simulate the Volt/VAr control in a distribution software, and results from these simulations were analyzed over a period of time. Other factors affecting the control scheme were also examined such as load parameter estimation and switched capacitor operation and control. It can be concluded with the current results that there is a 1% reduction in power demand for a 1% reduction in voltage. Future scope of this research is to use AMI data as feedback for voltage control and estimation of load models. ACKNOWLEDGMENT The authors would like to thank DOE for funding this ongoing research. The authors would also like to thank Avista Utilities for their collaboration with Washington State University and their help in making all the necessary data available. REFERENCES Figure 8: ZIP Modeling Technique Figure 9: Loss Savings for Different Capacitor Switches [1] Vesna Borozan, Mesur Baran, and Damir Novosel, "Integrated Volt/Var Control in Distribution Systems," in Power Engineering Society Winter Meeting, IEEE, vol. 3, 2001, pp. 1485-1495. [2] KP Schneider, FK Turner, JC Fuller, and R Singh, "Evaluation of Conservation Voltage Reduction on a national level," Pacific Northwest National Laboratory, 2010. [3] Greg Shirek, "Evaluating Conservation Voltage Reduction with Windmil," Milsoft Inc., 2011. [4] ANSI Standards, Voltage Ratings for Electric Power Systems and Equipment (60 Hz). [5] M. M. A. Salama, C. A. Can izares and J. Reeve N. Mithulananthan, "Distribution system voltage regulation and var compensation for different static load models," International Journal of Electrical Engineering Education, pp. 384-385. [6] E. Tom Jauch, "Smart Grid Volt/Var Management: Challenges of Integrating Distribution DG," 2012. [7] Jeff Doty, Jared Burns, Luis Perez, and Anjan Bose, "Preliminary Online evaluation of the smart grid additions to the Spokane distribution system," Washington State University, 2011. [8] Amit Narayan Kyle Anderson, "Simulating Integrated Volt/Var Control and Distributed Demand Response Using GridSpice," in Smart Grid Modeling and Simulation (SGMS), 2011 IEEE First International Workshop on, 2011, pp. 84-89.

[9] Richard Bravo Russell Neal, "Advanced Volt/VAr Control Element of Southern California Edison s Irvine Smart Grid Demonstration," in Power Systems Conference and Exposition (PSCE), IEEE/PES, 2011, pp. 1-3. [10] Stoner Software, SynerGEE Electric 4.0, 2011. [11] SynerGEE Inc., "SynerGEE Electric Technical Reference," 2011. [12] T.A. Short, Electric Power Distribution Equipment and Systems.: CRC Press, 2006. [13] Prabha Kundur, Power System Stability and Control.: McGraw-Hill Inc, 1993. [14] Electrical Power Research Institute, "Estimating cost and benefits of the Smart Grid," 2011. BIOGRAPHIES Mahti Daliparthi is a graduate power engineering student in the School of Electrical Engineering and Computer Science at Washington State University, Pullman, WA Marsela Jakub-Wood is a graduate power engineering student in the School of Electrical Engineering and Computer Science at Washington State University, Pullman, WA Anjan Bose (F 89) received the B.Tech. degree from IIT, Kharagpur, India, the M.S. degree from the University of California, Berkeley, and the Ph.D. degree from Iowa State University, Ames. He has worked for industry, academe, and government for 40 years in electric power engineering. He is currently Regents Professor and holds the endowed Distinguished Professor in Power Engineering at Washington State University, Pullman, where he also served as the Dean of the College of Engineering & Architecture from 1998-- 2005. Dr. Bose is a Member of the US National Academy of Engineering and a Foreign Fellow of the Indian National Academy of Engineering. He is the recipient of the Herman Halperin Award and the Millennium Medal from the IEEE, and was recognized as a distinguished alumnus by IIT Kharagpur and Iowa State University. Anurag K. Srivastava (S 00, SM 09) received his Ph.D. from Illinois Institute of Technology (IIT), Chicago, in 2005. He joined Washington State University as Assistant Professor in August 2010. He worked as an Assistant Research Professor at Mississippi State University from 2005-2010. His research interests include power system operation, control, security, and stability within smart grid and micro grid. Dr. Srivastava is member of the IEEE, Power and Energy Society (PES), IET, Sigma Xi, and Eta Kappa Nu. He is chair of the IEEE PES career promotion subcommittee and vice-chair of the IEEE PES student activities subcommittee and is active in several other IEEE PES technical committees..