INSTALLATION MANUAL ACL 5500 COMBUSTION SAFETY CONTROLLER

Similar documents
INSTALLATION MANUAL FOR ACL 3200 FLARE STACK /INCINERATOR IGNITION SYSTEMS WARNING

ACL HIGH EFFICIENCY BURNER ASSEMBLY PATENTED BURNER WARNING

PROFIRE 1100i IGNITION FLAME SAFETY CONTROLLER

Installation Manual. ACL3200 Flare Stack / Incinerator Ignition Systems

PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS. v1.1 Revised Nov 29, 2016

A1500, A1500NF SPEED SWITCH SINGLE SET POINT - SELF CONTAINED. Introduction

MAXIGARD A2000 SPEED SWITCH. Introduction

G76x Direct Spark Ignition Controls

GeniSys 24V. Model Advanced 24 Vdc Burner Control. Description / Applications

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION

IMI vibration switch USER MANUAL INSTALLATION - OPERATION - MAINTENANCE

G600 Series Replacement Intermittent Pilot Ignition Controls

SERIES VAC Microprocessor Based Direct Spark Ignition Control FEATURES DESCRIPTION APPLICATIONS THE TOTAL SOLUTION FOR GAS IGNITION CONTROL

ACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS

FM200 FLOW/NO-FLOW MONITOR INSTALLATION AND TECHNICAL MANUAL 120 VAC MODEL 6/1/2017

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin LowNOx Commercial Gas Electronic Spark Ignition Sequence

Battery Control Center - Diesel

The Combustex Pilot Pro 900 Ignition System with Pilot Tip and Flame Sensor

Model 550 Series Vibration Switches

Generator Start Control Module

Generator Start Control Module

G72x Series Direct Spark Ignition Controls

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

The Combustex Pilot Pro 500 Ignition System with Pilot Tip and Flame Sensor

Series BFM Bulk Flow Monitor 1A FUSE RED LED RELAY. Part Number BFM-1 BFM-2 BFM-3 BFS-1

Troubleshooting Manual

Modulating Furnace Information. Warning on Meter Setting - Read First!

SAVANNAH EI & DELUXE SYSTEM TROUBLE SHOOTING GUIDE

HYGRODYNAMICS DIGITAL DEW POINT MONITOR PC BOARD MODEL 6392N & 6392N2 TABLE OF CONTENTS

E Series CE Approved Intermittent Pilot Ignition Control

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

R & D SPECIALTIES ROTROL I USER'S MANUAL

A5000GEC-24VDC ZERO SPEED SWITCH

X4 Installation and Operation Manual - POWER FLAME INCORPORATED

GENSET CONTROL MODULE LEVEL 0 A120A. User selectable time delays for engine start and engine stop (cool down).

ARCHITECTURAL CONTROL SYSTEMS, INCORPORATED ST. LOUIS, MISSOURI

ESC Series Engine Shutdown Control

American Flame AF-4000 Series Intermittent Pilot Ignition System Trouble Shooting Guide

GCU-10. Automatic Engine Control Unit Operators Manual

GENSET CONTROL MODULE A121H / A241H. User selectable time delays for engine start and engine stop (cool down).

LX-80 COMMERCIAL POOL & SPA CONTROL INSTALLATION INSTRUCTIONS

Installation, Operation & Maintenance Manual Control Panels for Automatic Self-Cleaning Strainers Model 596 and Model 2596

SECOND GENERATION Use this guide with unit serial number prefix beginning with BWF using Terra Power separator.

VC-4820 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL

WARNING. Murphy W-Series Engine Panels General Installation Instructions. Installation Accessories

Valcom Failsafe Unit. 1620ESv2 SERIES. Operation and Maintenance Manual

U S A INSTALLATION GUIDE EP400 / E8-B

This Manual is prepared for the use of trained Vulcan Service Technicians and should not be used by those not properly qualified.

Instruction Manual for the 110 VAC Draw-off Controller System

GENSET CONTROL MODULE A121A / A241A

GENSET CONTROL MODULE LEVEL 1 A121CM / A241CM. Special logic to re-establish cranking following a false start.

Skotch Trifecta Oil Valve System

6 & 12 Volt Battery and Systems Tester with 100 Amp Load

Application Engineering

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

Irrigation Components International, Inc.

SERVICE MANUAL RRG SERIES HEAVY DUTY GAS GRIDDLE - NOTICE - ML ML ML RRG Shown

Model 930 Power Control System Instruction Manual

INSPECTOR LINE LOAD SIMULATOR INSTRUCTION MANUAL TASCO, INC.

REV 1.7 PROFIRE 2100 MANUAL BURNER MANAGEMENT SYSTEM

Replacement Parts. Screw-on alligator clip 4 Flex probe adapter SST-13 P3. Blow molded case User Guide

Operating Manual. Safety/Process Flare Pilot

MODEL 422 Submersible Pump Controller

Operations Manual. Zero Speed Switch Sensor Model ZS09P

FHC-1D user manual. Features

PF 3100 ION PILOT CARD PRO.FIRE

SHAVED-DX. Installation Manual & Operation Instructions. Trouble Shooting Reverse Polarity Wiring Problems

INSTALLATION AND OPERATING MANUAL

Automatic Changeover Medical Manifold Installation, Operation and Maintenance Manual

INSTALLATION AND OPERATING MANUAL

MANUAL Model: PT 12/24-60 Solar Converters Inc. - Rev. F

XCITE Owner s Manual. Reso-not TM Damping System XCITE 1502C HYDRAULIC POWER SUPPLY

CMD-4000 SERIES REV. A 4+ FUNCTION REMOTE CONTROL DOOR LATCH OPENER SYSTEM INTRODUCTION

Grout Pump Automatic & Manual Troubleshooting Gas Wiring Diagram

Application Engineering

702 AUTOMATIC START MODULE OPERATING INSTRUCTIONS

IGNITION FLAME SAFETY CONTROLLER

WARNING. Murphy W-Series Engine Panels General Installation Instructions. Installation Accessories

ENFORCER TM 6201-IQ ELECTRONIC SIREN

CIVACON GROUND VERIFICATION RACK MONITOR SYSTEM and ASSOCIATED EQUIPMENT

General Installation Instructions for Valves and Gates

GSC300. Auto Start Engine Controller. Installation and User Manual for the GSC300 Auto Start Engine Controller. Full Version

INSTALLATION INSTRUCTIONS FOR Owner's Copy FILTERED AND REGULATED POWER SUPPLY VOLTS DC INPUT: Hz.

The Combustex Pilot Pro 800 Pilot Burner Assembly with Ignition & Flame Failure Monitor

INSTALLATION AND OPERATING

1. AC VOLTS: Displays generator output in voltage. 2. AC FREQUENCY: Displays the speed of the generator set in Hertz.

SPC-PANEL Simplex, Single Phase Pump Control Panel

SERVICE MANUAL. K Series Gas Kettles 2/3 Jacketed Stationary and Tilting - NOTICE - K40GL Shown

Q35 Series Automatic Vent Damper System

ANALOG CONTROL PANEL

SD Bendix M-21 and M-22 AntiLock Modulator Assembly DESCRIPTION M-21 MODULATOR M-22 MODULATOR

VTC1000 Series Voltage Converter. Installation & Operation Manual

Third Generation NITE Phoenix

INSTRUCTIONS FOR THE RELIANCE Fast/Tran TM ARL0909 & ARL0909R

Process switches and PLC circuits

The function of this Dynamic Active Probe has divided into three preferences on the screen main Menus:

MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM

G821L/G822L Series Integrated Function Direct Spark Ignition Controls

L5000 Plus. Installation & Setup Guide

SBC V In-Car Charger Dual Input (Solar MPPT & DC)

Transcription:

5500 COMBUSTION SAFETY CONTROL INSTALLATION MANUAL FOR 5500 COMBUSTION SAFETY CONTROLLER WARNING This manual must be read in its entirety before installation of this controller. Installation must be performed by a qualified technician and must adhere to the standards set by the local regulatory authorities. is not responsible for the misuse or incorrect application of this product. 805 Main Ave. West - Box 2002 Sundre, Alberta T0M 1X0 - Phone: (403) 638-5234 - Fax: (403) 638-4973 - Email: aclmfg@telus.net Website: www.aclmfg.com

5500 COMBUSTION SAFETY CONTROL 46

5500 SAFETY COMBUSTION CONTROL 5500 PROVIDES SINGLE & THREE TRIALS FOR IGNITION FLAME MONITORING INDICATION OF: PILOT ON, POWER ON, & MAIN ON FIRST OUT ANNUNCIATION & SHUTDOWN FOR: POWER FAIL HI PRESSURE HIGH TEMPERATURE FLAME FAIL LOW PRESSURE PROOF OF CLOSURE REMOTE SHUTDOWN LOW LEVEL AUXILLARY 1 REMOTE STOP AND START CAPABILITIES SINGLE OR DUAL BURNER CAPABILITIES PRE-PROGRAMMED LOGIC (NO PROGRAMMING NECESSARY) Power supply 12/24 VDC, 120/240 VAC 50/60 Hz, low power consumption, suitable for solar applications Flame out response time of 0.8 seconds CSA approved for Class I, Div 2 location CSA approved C22.2 No 199-M89. Combustion safety controls and solid-state Ignitors for Gas & Oil burning Equipment CSA B149.3-10 compliant, meets NFPA Standards Type 4x enclosure, corrosive resistant and weatherproof 1

5500 COMBUSTION SAFETY CONTROL APPLICATION The 5500 Combustion Safety controller is designed to ignite and prove a continuous pilot while monitoring and annunciating multiple heater shutdowns for all types of gas fired heaters and industrial sized burner applications. THEORY OF OPERATION The 5500 utilizes a single ignitor/flame rod to provide both flame acknowledgment and ignition at the pilot tip. When the 5500 starts its ignition sequence, fuel gas travels to the pilot tip where the ignitor/flame rod is located and sparking. Once the gas is lit, the flame becomes a current path for flame acknowledgment and the unit stops sparking. After the pilot has been proven for 20 seconds (factory set) the 5500 will allow gas to the main burner. If the pilot flame is extinguished, the current path is broken and the ignitor/flame rod starts sparking within 1 second to attempt to re-light the pilot. The main is shut off during this re-light period. If a flame is not established within the 5 second sparking period, the controller will immediately drop the output to solenoid #1 pilot gas valve. The controller will attempt to light 2 more times with 15 seconds between each trial when equipped with three trial module. If the flame is still not lighting, the flame fail will then be displayed on the annunciation panel. If any of the shutdowns are tripped, the controller will not attempt any re-light, solenoid outputs will de-energize immediately and that specific shutdown will then be indicated on the annunciation panel. The shutdown must be cleared before the controller will allow an ignition cycle. In an application where the 5500 is used to ignite and monitor two burners, ignition will occur at both pilots simultaneously when a start is initiated. If a flame is not established at both pilots during the 5 second trial for ignition the solenoid #1 outputs will drop out closing both pilot valves and a flame fail will be indicated on the annunciator panel (slow flash for pilot #1 and quick flash for pilot #2). If both pilots have been proven for a period of 20 seconds solenoid #2 outputs will be energized allowing the main burner valves to open. During normal operation should either pilot be extinguished there will be a 5 second trial for re-ignition at that pilot, and the main solenoid outputs will be shut off during the trial for ignition period. If a flame is not re-established during the 5 second period the remaining pilot solenoid output will be de-generized closing the pilot gas outputs immediately and will not attempt any re-light. The specific shutdown will then be indicated on the front annunciator panel. The shutdown must be cleared before the controller will allow an ignition cycle. 2 46

5500 SAFETY COMBUSTION CONTROL INSTALLATION 5500 controller c/w mounting hardware M-50A pilot mixer & nozzle 10 ground wire 10 high voltage wire complete with connectors 6.5 non-metallic flex complete with connectors Ignitor/flame rod complete with mounting hardware Speed control valve ½ conduit seal Flame current test leads Operator s manual The 5500 can be mounted in a Class I, Div 2 area; usually close to the burner. The 10 of high voltage lead, (longer length not recommended) must be run in the non- metallic flex (provided) or free air. If the high voltage lead is run in the non-metallic flex, a conduit seal (provided) must be installed. Note: Lead length in excess of 10 or use of metal or metallic sheathed conduit may result in a diminished ignitor rod voltage. A ground wire (also supplied) must be connected between the ground lug on the burner assembly and the bonding ground terminal on the main circuit board. Note: If the controller must be mounted farther away from the burner assembly, the ignition module, which is mounted on the main circuit board, may be mounted in or near the burner housing using the optional, CSA approved, 5000R remote mount kit. Do not coil excess high voltage lead inside controller enclosure. High voltage noise may damage sensitive components. When the 5500 is used in a dual burner application at least one of the ignition modules must be remotely mounted as the controller housing will not accommodate two ignition modules. (Dual Burner kit needed for dual burner applications) 5500 COMES COMPLETE WITH MOUNTING The 5500 is available in 12/24 VDC and 120/240 VAC. Voltage requirements must be specified when ordering. The supply voltage of each unit is clearly marked inside the door on the specification label and on the circuit board beside its respective terminal. Incorrect polarity on 12/24 VDC units may result in damage to circuit board components. The terminal marked ground is for supply or system ground and the terminal marked bonding ground is strictly for the ground wire to the burner assembly. It is important that a ground wire (supplied) be connected between the bonding ground terminal and the burner assembly to provide an uninterrupted path for the flame acknowledgment current. POWER CONNECTION There are four solenoid output terminals on the main circuit board marked pilot solenoid and main solenoid, 2 for burner #1 and 2 for burner #2. The output voltage at these terminals is always the same as the controller supply voltage. The pilot solenoid output connects to the pilot or low fire solenoid and is energized when a start is initiated. Main solenoid, (main burner) energizes only after the pilot or low fire flame has been proven. The time delay between proof of flame and energizing of main output is factory set at 20 seconds. The solenoid outputs are rated at 5A 250V each. SOLENOID OUTPUTS 3

5500 COMBUSTION SAFETY CONTROL S/D INPUTS & ALARM ANNUNCIATION The shutdown input provides a means of connecting other shutdown devices for High pressure, Low pressure, High temperature, Low level and Axillary 1 where necessary for additional protection. Jumpers are installed at the factory and should only be removed to utilize each individual shutdown. If any of the S/D devices go to a fault condition their contacts will open, de-energizing the solenoid outputs, shutting down fuel to the burner and disabling the re-light sequence. The fault will be annunciated on the front of the controller. Once the fault condition is corrected the system can be restarted by pressing the stop/reset and then the start buttons. Note: If a restart is attempted without clearing the fault condition the controller will not attempt a re-light. 18 awg wire is recommended for all the shutdowns for ease of wiring. Must be dry contacts. REMOTE S/D (STOP) The remote S/D function is available when the jumper is removed and a momentary normally closed contact button or remote relay contact (N/C) is utilized. Note: Must be dry contacts. REMOTE START The remote start function is available when a momentary normally open contact button or remote relay contact (N/O) is utilized. When contacts close momentarily the unit initiates starting sequence. PROOF OF CLOSURE (P.O.C) This feature allows controller to use valves with proof of closure switches for ensuring main valve is closed before initiating an ignition. When valve switch contacts are in an open state indicating the valve may be open, the controller will not start. The contacts must be closed in order for controller to start. Once start is initiated, the contacts from proof of closure switch can then change state. TEMPERATURE CONTROL The temperature control option is provided to allow the use of a temperature switch to turn the main solenoid output on & off, controlling the main gas valve to the burner. This does not override the shutdown logic of the output. When using this option, the temperature switch must have dry contacts. When not in use, a jumper must be installed as per drawings. ALARM STATUS Alarm status is provided from a set of normally open/normally closed dry contacts which change state when a pilot flame is detected. If the pilot goes out due to any of the shutdowns or fails to re-light, the contacts return to normal or alarm state. NOTE: A jumper must be placed between terminal numbers 34 and 36 when the 5500 is being used for a single burner application. 4 46

5500 SAFETY COMBUSTION CONTROL SPECIFICATIONS DC ONE BURNER TWO BURNER VOLTAGE 12 VDC 24VDC 12 VDC 24 VDC CURRENT 0.206A 0.139A 0.292A 0.200A POWER 2.472W 3.336W 3.504W 4.80W SOLENOID OUTPUT RATINGS OPERATING TEMPERATURE 5 amp 250 V Per Output 5 amp 250 V Per Output -40 C to 60 C -40 C to 60 C FLAME SENSITIVITY 1 micro amp minimum 1 micro amp minimum FLAME FAILURE RESPONSE TIME 0.8 seconds maximum 0.8 seconds maximum SPARK RATE 25 sparks per second 25 sparks per second ONE BURNER TWO BURNER VOLTAGE 120 VAC 240 VAC 12 VDC 24 VDC CURRENT 0.306A 0.156A 0.292A 0.200A POWER 36.72W 37.44W 3.504W 4.80W FREQUENCY 50/60 HERTZ 50/60 HERTZ SOLENOID OUTPUT RATINGS SPECIFICATIONS AC 5 amp 250 V Per Output 5 amp 250 V Per Output OPERATING TEMPERATURE -40 C to 60 C -40 C to 60 C FLAME SENSITIVITY 1 micro amp minimum 1 micro amp minimum FLAME FAILURE RESPONSE TIME 0.8 seconds maximum 0.8 seconds maximum SPARK RATE 25 sparks per second 25 sparks per second 5

TC 200 TEMPERATURE CONTROLLER Terminal Layout for Temperature Control Type K Thermocouple Type K Thermocouple Yellow Red Yellow Red + - + - T/C 1 T/C 2 Type K Thermocouple inputs See note #1 12 / 24 VDC in 12 / 24 VDC in + - + - - I / P + - M / A + + - + - 4-20 MA 4-20 MA I / P Output Set Point Driven Transmitter Output Supply from Main Output of Controller + - Solenoid S Relay 1 -Dry Contacts Opens at or above set point Example: When used w/ 5100 & 5500 Controller To HT input on Controller Relay 2 -Dry Contacts Opens at or above set point Power Supply POS NEG + - 12/24 VDC 12/24 VDC GRD Note #1 4-20mA (1) may be programmed to provide 4-20mA from setpoint. See 4-20mA output specifications. 4

5500 COMBUSTION SAFETY CONTROL 5500 12/24 VDC 1 Burner System MUST BE DRY CONTACTS. MUST BE IN CLOSED POSITION INITIALLY FOR BURNER TO START Note: Run #18 AWG for shutdowns TC 200 R L Y 1 HP LP HT LL Burner #1 S/D Valve P.O.C. Temp Switch Remote Start Button Remote Stop Button Aux. S/D #1 To PLC or RTU for Remote Status 1 Proof of Closure 2 Proof of Closure 5 Remote Start 6 Remote Start 9 Hi Press S/D 10 Hi Press S/D 13 Hi Temp S/D 14 Hi Temp S/D 15 Lo Level S/D 16 Lo Level S/D 17 Aux 1 S/D 18 Aux 1 S/D 19 Alarm Status NO 20 Alarm Status COM 21 Alarm Status NC 3 Temp Control 4 Temp Control 7 Remote S/D 8 Remote S/D 11 Lo Press S/D 12 Lo Press S/D RLY 2 BURNER #1 Power Supply 12/24 VDC 22 23 24 12/24 VDC Positive 12/24 VDC Negative System (Power Supply) BURNER #2 (Optional) SV SV 1 or 2 Valve System SV Burner #1 Pilot 25 Power 26 Alarm 27 Valve 28 29 Bonding 30 Solenoid #2 Positive + (Main) 31 Solenoid #2 Negative - 32 Solenoid #1 Positive + (Pilot) 33 Solenoid #1 Negative - Note: Solenoid O/P Voltage Equal to Supply Voltage 34 Power 35 Alarm 36 Valve 37 38 Bonding 39 Solenoid #2 Positive + (Main) 40 Solenoid #2 Negative - 41 Solenoid #1 Positive + (Pilot) 42 Solenoid #1 Negative - Note: Jumper between 34 & 36 when not in use Pneumatic Control Box Ignition Module To Ignitor/Flame Rod Prewired in Control Box Red Blue Brown Yellow To Ignitor/Flame Rod Note: If remote mounting of ignition module is preferred, the 5000R remote mount kit is available upon request 6 46

5500 SAFETY COMBUSTION CONTROL 5500 12/24 VDC 2 Burner System MUST BE DRY CONTACTS. MUST BE IN CLOSED POSITION INITIALLY FOR BURNER TO START Note: Run #18 AWG for shutdowns HG HG LG Burner #2 S/D Valve P.O.C. HT LL Temp Switch Remote Stop Button Aux. S/D #1 To PLC or RTU for Remote Status Burner #1 S/D Valve P.O.C. Remote Start Button 1 Proof of Closure 2 3 4 5 6 9 10 11 12 13 Hi Temp S/D 14 Hi Temp S/D 15 16 17 Aux 1 S/D 18 19 Alarm Status NC 20 21 Proof of Closure Temp Control Temp Control Remote Start Remote Start 7 Remote S/D 8 Remote S/D Hi Press S/D Hi Press S/D Lo Press S/D Lo Press S/D Lo Level S/D Lo Level S/D Aux 1 S/D Alarm Status COM Alarm Status NO This output has dry contacts rated @ 5A, 250V Power Supply 12/24 VDC 22 23 12/24 VDC Positive 12/24 VDC Negative (Power Supply) 24 System BURNER #1 BURNER #2 25 26 27 28 29 Power Alarm Valve Bonding Note: Solenoid O/P Voltage Equal to Supply Voltage 30 Solenoid #2 Positive + SV SV (Main) SV SV 31 Solenoid #2 Negative - 1 or 2 Valve System 1 or 2 Valve System 32 Solenoid #1 Positive + SV (Pilot) SV 33 Solenoid #1 Negative - Burner #1 Pilot Burner #2 Pilot Ignition Module 34 35 36 37 38 39 40 41 42 Power Alarm Valve Bonding Solenoid #2 Positive + (Main) Solenoid #2 Negative - Solenoid #1 Positive + (Pilot) Solenoid #1 Negative - Note: Jumper between 34 & 36 when not in use 4 Terminal Plug (provided) Ignition Module Burner #2 To Ignitor/Flame Rod To Ignitor/Flame Rod Prewired in Control Box Red Blue Brown Yellow Field Wiring By Customer Max 50 Ft. Min #16 Guage Red Blue Brown Nema 4 Metal Box Provided Yellow High Voltage Ignition Wire Remote Mount Option 5000R To Ignitor/Flame Rod To Ignitor Rod 7

5500 COMBUSTION SAFETY CONTROL 5500 120/240 VAC 1 Burner System MUST BE DRY CONTACTS. MUST BE IN CLOSED POSITION INITIALLY FOR BURNER TO START Note: Run #18 AWG for shutdowns HP LP HT LL Temp Switch Remote Start Button Remote Stop Button Aux. S/D #1 To PLC or RTU for Remote Status Burner #1 S/D Valve P.O.C. 1 2 3 4 5 6 7 8 Remote S/D 9 10 11 12 13 Hi Temp S/D 14 15 16 17 Aux 1 S/D 18 19 Alarm Status NO 20 21 Proof of Closure Proof of Closure Temp Control Temp Control Remote Start Remote Start Remote S/D Hi Press S/D Hi Press S/D Lo Press S/D Lo Press S/D Hi Temp S/D Lo Level S/D Lo Level S/D Aux 1 S/D Alarm Status COM Alarm Status NC Power Supply 120/240 VAC 22 23 120/240 HOT 120/240 NEU (Power Supply) 24 System BURNER #1 BURNER #2 (Optional) SV SV 1 or 2 Valve System SV Burner #1 Pilot 25 26 27 28 29 30 31 32 33 Power Alarm Valve Bonding Solenoid #2 HOT Solenoid #2 NEU Solenoid #1 HOT Solenoid #1 NEU Note: Solenoid O/P Voltage Equal to Supply Voltage (Main) (Pilot) 34 35 36 37 38 39 40 41 42 Power Alarm Valve Bonding Solenoid #2 HOT Solenoid #2 NEU Solenoid #1 HOT Solenoid #1 NEU Note: Jumper between 34 & 36 when not in use (Main) (Pilot) Pneumatic Control Box Ignition Module To Ignitor/Flame Rod To Ignitor/Flame Rod Prewired in Control Box Red Blue Brown Yellow Note: If remote mounting of ignition module is preferred, the 5000R remote mount kit is available upon request 8 46

5500 SAFETY COMBUSTION CONTROL 5500 120/240 VAC 2 Burner System MUST BE DRY CONTACTS. MUST BE IN CLOSED POSITION INITIALLY FOR BURNER TO START Note: Run #18 AWG for shutdowns HG HG LG Burner #2 S/D Valve P.O.C. HT LL Temp Switch Remote Stop Button Aux. S/D #1 To PLC or RTU for Remote Status Burner #1 S/D Valve P.O.C. Remote Start Button 1 2 3 4 5 6 9 10 11 12 13 Hi Temp S/D 14 15 16 17 Aux 1 S/D 18 19 Alarm Status NC 20 21 Proof of Closure Proof of Closure Temp Control Temp Control Remote Start Remote Start 7 Remote S/D 8 Remote S/D Hi Press S/D Hi Press S/D Lo Press S/D Lo Press S/D Hi Temp S/D Lo Level S/D Lo Level S/D Aux 1 S/D Alarm Status COM Alarm Status NO This output has dry contacts rated @ 5A, 250V Power Supply 120/240 VAC 22 23 120/240 HOT 120/240 NEU (Power Supply) 24 System BURNER #1 BURNER #2 25 26 27 28 29 Power Alarm Valve Bonding Note: Solenoid O/P Voltage Equal to Supply Voltage 30 Solenoid #2 HOT SV SV (Main) SV SV 31 Solenoid #2 NEU 1 or 2 Valve System 1 or 2 Valve System 32 Solenoid #1 HOT SV (Pilot) SV 33 Solenoid #1 NEU Burner #1 Pilot Burner #2 Pilot Ignition Module 34 35 36 37 38 39 40 41 42 Power Alarm Valve Bonding Solenoid #2 HOT Solenoid #2 NEU Solenoid #1 HOT Solenoid #1 NEU Note: Jumper between 34 & 36 when not in use (Main) (Pilot) 4 Terminal Plug (provided) Ignition Module Burner #2 To Ignitor/Flame Rod To Ignitor/Flame Rod Prewired in Control Box Red Blue Brown Yellow Field Wiring By Customer Max 50 Ft. Min #16 Guage Red Blue Brown Nema 4 Metal Box Provided Yellow High Voltage Ignition Wire Remote Mount Option 5000R To Ignitor/Flame Rod To Ignitor Rod 9

5500 COMBUSTION SAFETY CONTROL Flame Signal Test Procedure 1. Turn power off to controller 2. Remove High-Voltage Ignition wire from Ignition Module and insert meter leads with test harness as shown 3. Turn on power and initiate start sequence 4. Meter will give erratic readings during ignition period but should settle down between 1-2µA reading on meter 5. Adjust air shutter on pilot mixer and adjust pressure on regulator to achieve a flame signal close to 2µA which is optimum Meter 2.0 A DC Manufacturing Ignition Module CAUTION HI-VOLTAGE 12 vdc + Alarm Valve ignition wire Meter Leads Test Harness Red Ignitor/Flame Rod Metal Strain Relief Ceramic Insulator Black High Voltage Ignition Wire 1/8 " Gap Setting to inside edge of Nozzle sst Pilot Nozzle Adjustable Bracket Lug. M50 Mixer Air Shutter 1/8" Gas Connection 14 46

5500 SAFETY COMBUSTION CONTROL HE-ON BURNER 1/2" NPT Bulkhead -ON-Nozzle (Optimizer nozzle) Ignitor/flame rod Gap should be 1/8" to inside edge of nozzle -I-ON (Ignitor/Flame rod) Venturi Burner Barrel -M Series (Air fuel mixer) Fuel Connection Low pressure ring 3/4" NPT Bulkhead (For pilot) ------------ nozzle insert Auxiliary air inlet Air Shutter ------------ 2 piece nozzle supplied 1/2 " nipple By Customer (Recommended SCH 40/Reamed) M50 Pilot Mixer Pilot Assembly Note: This pilot assembly can be used as a stand alone unit using adjustable bracket or incorporated with our -HE-ON Burner assembly as shown. Simply unscrew 3/4 bulkhead located on -HE-ON Burner. HE-ON Burner Front View 3/4" NPT Bulkhead Pilot sight port Ignitor/flame rod gap should be 1/8" to inside edge of nozzle -I-ON (Ignitor/flame rod) Ignitor/Flame Rod gap should be 1/8" to inside edge of nozzle -I-ON Ignitor/Flame Rod Air dampening & Deflector blades (factory adjusted to 30 ) Field adjustable 3/4" NPT Bulkhead (For pilot) Detail of Flame Rod Positioning 15

5500 COMBUSTION SAFETY CONTROL PILOT ASSEMBLY Ignitor/Flame Rod Metal Strain Relief Ceramic Insulator Note: Do not drill out pilot orifice Approx 1/8 " Gap Setting to inside edge of Nozzle Pilot Nozzle Adjustable Bracket Lug. M50 Mixer Air Shutter 1/8" Gas Connection 1/2" Schedule 40 nipple (customer supplied) OPTIONAL PILOT ASSEMBLY SST Pilot Nozzle 3/4" Pipe 1 1/4" Strain Relief Connection Ignition Wire Connection Protective Shroud Air Shutter M50 Mixer 1/8" Gas Connection Control Box Dimensions Outside Dimensions Side View Mounting Dimensions 10" 11" 10" 11" 8" 6" 16 46 6" 6"

5500 SAFETY COMBUSTION CONTROL BMS Trouble Shooting Guide Fails to attempt ignition Blown fuse Supply voltage too low Poor power connections POC terminal not closed (5100 Only) Remote stop not closed (5100 Only) Replace fuse 4 amp max for 5100 and 5500 6.4 amp max for CSC 200 Ensure 11.5 volts minimum supply power for 12/24 or 119 VAC for 120/240 Check connections on terminal strips Ensure 12 volts on both terminals Ensure 12 volts on both terminals Fuel gas supply to pilot may be too high or too low Attempts ignition but doesn't light Pilot fuel gas supply should be set at 5 pounds Gap setting on ignitor/flame rod not correct Ignition cable defective or insulation worn Poor ground Pilot solenoid failure Plugged orifice on pilot Gap should be approx 1/8" and rod tip needs to be cut to a sharp point Check continutiy through the igniton cable, should read (0 Ohms) if not you will need to replace cable Ensure ground connections are good in BMS and at pilot/burner Check supply power to solenoid, and check gas flow through solenoid Clean out pilot orifice (Do not redrill) Weak or erratic spark Gap seting too wide or rod not cut to a point Ignition cable defective or insulation worn Poor ground Contaminated Ignitor rod or pilot nozzle Shorten gap setting to approx 1/8" and re cut the igntior rod tip. Replace Cable Check ground at both ends (BMS & ignitor tip) Remove pilot assembly clean rod and nozzle and re install

5500 SAFETY COMBUSTION CONTROL NOTES

5500 SAFETY COMBUSTION CONTROL NOTES

5500 SAFETY COMBUSTION CONTROL NOTES

Website: www.aclmfg.com Limited Warranty Seller warrants that the product hereby purchased is, upon delivery, free from defects in material and workmanship and that any product which is found to be defective in such workmanship or material will be repaired or replaced by Seller for a period of one year from purchase date. Warranty of such items do not include shipping, installation or set-up. Liability Statement Shall not be liable for any special, indirect, consequential or other damages of a like general nature, including, without limitation, loss of profits or production, or loss of expenses of any nature incurred by the buyer or any third party. 805 Main Ave West - Box 2002 Sundre, Alberta T0M 1X0 Phone: (403) 638-5234 - Fax: (403) 638-4973 E-mail: aclmfg@telus.net