Typical Specification

Similar documents
Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break

Padmount Solid Dielectric Switchgear Catalog

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12

Submersible Vacuum Fault Interrupters

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Solid Dielectric, Single Phase Reclosers

SERIES G100 / G110 SPECIFICATION 15KV & 25KV SUBMERSIBLE & VAULT MOUNTED SF 6 -INSULATED VACUUM LOAD INTERRUPTING SWITCHES

Solid Dielectric, Three Phase Reclosers Catalog O-vs18

Cobra-S. Catalog Cobra-S

solutions RUS accepted

Solid Dielectric, Triple Option Reclosers Catalog O-vst14

Solid Dielectric, Single Phase Recloser

Underground Distribution Switchgear

Underground Distribution Switchgear

Horizontal Circuit Switchers

SERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES

Solid Dielectric Load Break Switch SPECIFICATION. 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER

100 / 110 DRYWELL FUSE SPECIFICATION

Underground Distribution Switchgear

Horizontal Circuit Switchers

Solid Dielectric, Three Phase Reclosers CATALOG VS11

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

Three-Phase Pole Mounted Recloser

15-kV Wall-Mount Switchgear Three-Phase Indoor/Outdoor 600 Amp S&C Mini-Rupter Switch

Elastimold. Cable Accessories. Underground Distribution Switchgear. Molded Vacuum Switches and Fault Interrupters

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

OPERATION AND MAINTENANCE OF TRAYER 4000 SERIES PADMOUNTED VACUUM FAULT INTERRUPTER

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications

Publication No.: PSG

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

A. Submit manufacturer's literature and technical data before starting work.

Contents. PG6 Single Side Access Padmount PufferPak Switch. SG6 Subsurface PufferPak Switch. PT6 Pole Top PufferPak Switch

SWITCHGEAR DIVISION PRODUCT PROFILES

University of Houston Master Construction Specifications Insert Project Name

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

SECTION PANELBOARDS

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

RUS accepted Catalog O-vst18

Solid Dielectric, Independent Pole Operated Reclosers Catalog O-vst16

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

SPECIFICATION BULLETIN

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

Product Specification Guide. Title: Southern States 362 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

OPERATION AND MAINTENANCE OF TRAYER 3000 SERIES PADMOUNTED VACUUM FAULT INTERRUPTER

Underground Distribution Switchgear

Product Specification Guide. Title: Southern States 72 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

FEBRUARY 14, 2017 Elastimold Solid dielectric switchgear customer presentation

Product Specifications for Aluminum Vertical Break Switches

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

Medium Voltage Metal-Enclosed Switches

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

Specification Guide. for RMVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

Design Standard. Purpose: Design Standard:

TYPE PSI/II PADMOUNT SWITCHGEAR 15KV 25KV

Medium Voltage Metal-Enclosed Switches

35-kV Safefront SuperWell Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current Limiting Fuses

VersaRupter 5-38 kv Load Interrupter Switch. Technical Guide

35-kV Thru-Bushings F Series (bolt-in) for Air-Insulated to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

15-kV Live Terminal 600 Amp Group Operated Pad-Mounted Metal-Enclosed Outdoor Switchgear 140 Amp (Max) Clip Mount Current-Limiting Fuses

Molded Current-Limiting Fuse

COOPER POWER CA280012EN

35-kV Safefront Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current-Limiting Fuses

Detail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2 General Order

Product Specifications for Phase Over Phase GOABS(r)

16.13 Unit Substation to 15kV Construction Standards Page 1 of 7

STANDARD SPECIFICATION FOR TYPE PLD LIVE-FRONT/DEAD-FRONT PAD-MOUNTED SWITCHGEAR 15kV 25kV A. General

Using new Magnetically Actuated Vacuum Interrupter technology for safe and reliable medium voltage circuit breaker switching in mines

STANDARD SPECIFICATION FOR LIVE-FRONT 15KV AND 25KV PSI/II PAD-MOUNTED SWITCHGEAR

S Fault Interrupters. Type CI; Three-Phase Installation and Operation Instructions. Service Information

Eaton s Cooper Power Systems catalog Medium-voltage vacuum circuit breakers

Design Build Deliver. Metal Enclosed Switchgear, 5-35kV 1200 A Maximum Loadbreak, 4000 A Maximum Non-Loadbreak

15 kv and 25 kv Thru-Bushings

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

Types VSA12, VSA12B, VSA16, VSA20, and VSA20A; three-phase; air-insulated; electronically controlled recloser

Electrical Switchgear Replacement Montgomery County Community College

C1000 Series Automatic Cap Bank

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment)

35-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

SECTION MOTOR CONTROL

25 kv Apparatus Bushings

Visible Break Load break switches can in cor po rate a visible break of all three phases.

15-kV Safefront Mini-Switch Source Isolated Pad-Mounted Switchgear 140 Amp (Max) Clip-Mounted Current-Limiting Fuses

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

Type MOST oil switch

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS

FIXED POWER FACTOR CORRECTION EQUIPMENT 5KV CLASS MEDIUM VOLTAGE SECTION Z

Westinghouse Electric Corporation Distribution and Control Business Unit Assemblies Division Bloomington, Indiana

DEAD-FRONT PAD-MOUNTED SWITCHGEAR 15kV 25kV

Medium Voltage Equipment 5-15 kv GM-SG and 38 kv GM38 Metal-Clad Switchgear General

35-kV 200-kV BIL Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

Extensible Unit - VCE2a

Visible Break Load break switches can in cor po rate a visible break of all three phases.

7. SERVICES OVER 600 VOLTS

Transcription:

Engineered to Order Built to Last Typical Specification VAULT VRPFI, TWO POSITION, ROTARY PUFFER SWITCHGEAR PART 1- GENERAL 1.1 DESCRIPTION A. The switch shall consist of manually operated load interrupting, SF6 insulated, 600A rotary puffer switches and manually operated vacuum interrupter fault interrupting tap switches, electronically controlled. 1.2 QUALITY ASSURANCE A. Manufacturer Qualifications: The chosen manufacturer shall have at least 20 years experience in manufacturing SF6 insulated medium voltage switchgear. The manufacturer of the switches shall be completely and solely responsible for the performance of the load break switch and fault interrupter as well as the complete integrated assembly as rated. B. The manufacturer shall furnish certification of ratings of the load break switch, fault interrupter and the integrated switch assembly upon request. C. The switch shall comply with requirements of the latest revisions of applicable industry standards, including: (a) IEEE C37.71, IEEE C37.74, IEEE C37.60, IEEE 386, IEC 60265-1 D. The switch manufacturer shall be ISO 9001:2008 and ISO 14001:2004 certified. 1.3 DELIVERY, STORAGE, AND HANDLING A. Load break switches and fault interrupters shall be shipped preassembled at the factory. No field assembly shall be required. B. The contractor, if applicable, shall handle, transfer and move the switches in accordance with manufacturer s recommendations. PART 2- PRODUCTS 2.1 SWITCH CONFIGURATION A. Each switch shall be equipped with 3-phase load switch ways and 3-phase vacuum interrupter tapped way(s), as indicated on the one-line diagram. B. Switches shall be designed for front access to cables and operators. 2.2 SWITCH CONSTRUCTION A. General All switch components and entrances shall be assembled in a totally welded mild steel tank. Entrances shall be internally connected by copper conductors capable of handling momentary and continuous current duty. The switch shall contain no electrically floating metallic parts or components. Construction shall be a deadfront design. Switch tanks shall be painted ASA70 light gray using a corrosion-resistant epoxy paint. - 1 of 5 -

B. Load Break Switch Each switching way is to be equipped with an internally mounted operating mechanism capable of providing quick-make, quick-break operation in either switching direction. The mechanism must be capable of delivering sufficient torque and shall be provided with latches for each position to assure load interrupting, fault closing and momentary ratings. All switch positions are to be clearly identified, padlockable and adaptable to keylock schemes. The operating mechanism shall be actuated from outside the switch tank with an operating handle. The operating shaft shall be made of stainless steel providing maximum corrosion resistance. A double "O" ring type operating shaft seal shall be used for a leak resistant, long life seal. Switch contacts shall be of a rotary puffer design made with copper alloy contacts with silver plating to assure permanent, low contact resistance. Each rotating contact simultaneously disengages from two fixed contacts, thus providing two break points per phase giving improved interrupting capability compared to single break contact systems. Contact travel shall be 90 degrees to assure efficient arc extinction and a wide open contact gap. Arcing is confined away from the main contact surfaces. The stationary contacts shall be supported independent of the cable entrance bushings, eliminating possible misalignment. Auxiliary blades used for load interruption are not acceptable. C. Vacuum Interrupters The vacuum interrupter shall consist of vacuum bottles and a spring-assisted operating mechanism. The mechanism used shall be designated "Model FI" for three phase operation only. The mechanism shall consist of three vacuum bottles mechanically linked to a single springassisted operating mechanism. The vacuum interrupter operating mechanism shall consist of the support assembly, linkage, spring latch mechanism, and solenoid utilized for electronic tripping. Maximum interrupting time shall be three cycles (50 msec). The movable contact shaft shall be flagged to indicate the contact position, open or closed. This contact position indicator shall be fully visible through viewing windows supplied in the switch tank. Each tap phase is to be equipped with an individual 600A vacuum interrupter fully enclosed in an SF6 insulated switch tank. Electrical opening shall be by a solenoid that is activated from sources external to the switch tank. Closing (reset) of the vacuum interrupter shall be mechanical with the use of an external operating handle. The mechanical linkage assembly shall provide for a "trip-free" operation which allows the vacuum interrupter to interrupt independent of the operating lever. 2.3 DESIGN RATINGS A. Load Break Switches The switch shall be rated (choose appropriate column): SELECTION OF RATINGS IEEE/IEC Maximum Design Voltage, kv 15.5 27 Impulse Level (BIL) Voltage, kv 110 125 Continuous Current, Amperes 630 630 Load break Current, Amperes 630 630 One Minute Withstand (dry), AC kv 34 40 Production Test Rating 34 40 15 Minute Withstand, DC kv 53 78 Momentary Current, ka, ASYM 25 20 Fault-Close Current, ka, ASYM 25 20-2 of 5 -

One Second Current, ka, SYM 16 12.5 Mechanical Endurance, Operations 2000 2000 Load Break Operations at 600 Amperes 500 500 B. Vacuum Interrupters The vacuum interrupter assembly shall be rated (choose appropriate column): SELECTION OF RATINGS IEEE/IEC Maximum Design Voltage, kv 15.5 27 Impulse Level (BIL) Voltage, kv 95 125 Continuous Current, Amperes 600 600 Load break Current, Amperes 600 600 One Minute Withstand (dry), AC kv 34 40 Production Test Rating 34 40 Symmetrical Interrupting Rating, ka 16 12.5 Asymmetrical Interrupting Rating, ka 25 20 IEEE C37.60 Fault Interrupting Duty Percent of Maximum: Interrupting Rating Approx. Interrupting: Current Amps No. of Fault: Interruptions 2.4 CABLE ENTRANCES 15-20% 2000 44 45-55% 6000 56 90-100% 12000 16 Total Number of Fault Interruptions: 116 A. Load Break Puffer Switches Cable entrances shall be tested to IEEE 386 and be, as indicated on the switch drawing: 600 amp G&W Quik-Change disconnectable apparatus bushing, 600 amp Apparatus bushing, 600 amp Universal bushing, or 200 amp Deepwell bushing. B. Vacuum Interrupters Cable entrances shall be tested to IEEE 386 and be, as indicated on the switch drawing: 600 amp G&W Quik-Change disconnectable apparatus bushing, 600 amp Apparatus bushing, 600 amp Universal bushing, or 200 amp Deepwell bushing. - 3 of 5 -

2.5 VACUUM INTERRUPTER CONTROL An electronic assembly shall be provided to sense load and fault current on each phase of the load tap circuits. The electronic control shall be powered from the current transformers mounted inside the SF6 insulated switch tank. No external power source shall be required for overcurrent protection. The electronic control shall monitor the current on the individual phases of the load tap circuits using input from the internal current transformers. Electronic trip capability shall be selectable for each phase. Temperature range shall be -30 C to +50 C. Minimum trip selection shall be accomplished with selector knobs inside the electronic enclosure. Trip time current characteristics (TCC) shall be field selectable using a dip switch. Maximum time for power up and ready-to-trip when closing on a circuit shall be ten percent of the trip time or 1/2 cycle, whichever is greater. Trip selection may be made with the load taps energized. The electronic controller is preset for three phase trip. Single phase trip is not available. 2.6 FACTORY PRODUCTION TESTS The bulk SF6 gas supply and each individual switch shall be tested for moisture content. Each individual switch shall undergo a mechanical operation check and a leak test. The switch shall be factory filled with SF6 and AC hi-pot tested one minute phase-to-phase, phase-to-ground and across the open contacts. Circuit resistance shall be checked on all ways. Switches will be shipped factory filled with SF6 gas. Tank shall be designed to withstand 15 psig internal pressure and an external pressure of 14 psig without affecting the performance of the switch. 2.7 STANDARD COMPONENTS The following shall be included as standard: Welded steel tank painted light gray with stainless steel and brass fasteners. Lifting provisions. Gas pressure gauge and fill valve. Grounding provisions for switch tank and all cable entrances. Stainless steel three line diagram and corrosion-resistant nameplates. Parking stands. Switch operating handle(s) with padlock provision and end stops. Type 2 electronics package including ground fault trip and time delay selector switches (three phase only). 2.8 OPTIONS The following options shall be supplied: (check as appropriate): Stainless steel tank, type 304 or 316 Stainless steel enclosure, type 304 or 316 Temperature compensating pressure gauge Low pressure warning device SF6 density switch 4/0 brass ground lug Key interlock provisions Key interlocks to lock in open position Current transformers for load break ways Potential transformers for voltage monitoring and/or control power Automatic transfer control type ATC451-4 Motor actuators for remote switch operation Auxiliary switches for remote switch position indication Stationary switch controls for remote switch operation and SCADA integration Portable switch controls for remote switch operation Remote terminal units and communication packages for SCADA integration Operation counters Analog voltage sensors Digital voltage sensors 200A deepwell bushings - 4 of 5 -

2.9 LABELING 600A apparatus bushings 600A voltage sensing bushings 600A Quik-Change apparatus bushings 600A Universal bushings (through 25kV) Type 2 vacuum interrupter control including ground fault trip and time delay selector switches (three phase only) Type 3 vacuum interrupter control including ground fault trip, inrush restraint, programmable Vacuum fluorescent display (VFD) and RS232/485 port Type 4 vacuum interrupter control (same as Type 3 with laptop programming only) Clear window cover for Type 1, Type 2, Type 3 or Type 4 interrupter controls Submersible NEMA 6P enclosure for vacuum interrupter control SEL relays including 751A, 501, 551 and others External power / trip for vacuum interrupter control Refill kit consisting of regulator, hose and SF6 bottle A. Hazard Alerting Signs The exterior of the padmounted enclosure (if furnished) shall be provided with Warning--Keep Out--Hazardous Voltage Inside--Can Shock, Burn, or Cause Death signs. Each unit of switchgear shall be provided with a Danger--Hazardous Voltage--Failure to Follow These Instructions Will Likely Cause Shock, Burns, or Death sign. The text shall further indicate that operating personnel must know and obey the employer s work rules, know the hazards involved, and use proper protective equipment and tools to work on this equipment. Each unit of switchgear shall be provided with a Danger--Keep Away--Hazardous Voltage--Will Shock, Burn, or Cause Death sign. B. Nameplates, Ratings Labels, and Connection Diagrams Each unit of switchgear shall be provided with a nameplate indicating the manufacturer s name, catalog number, model number, date of manufacture, and serial number. Each unit of switchgear shall be provided with a ratings label indicating the following: voltage rating; main bus continuous rating; short-circuit rating; fault interrupter ratings including interrupting and duty-cycle faultclosing; and load break switch ratings including duty-cycle fault-closing and short-time. - 5 of 5 -