Dynamic Resistance Measurement for Circuit Breakers Applying high DC current

Similar documents
An Overview of Dynamic Contact Resistance Measurement of HV Circuit Breakers

Safe, fast HV circuit breaker testing with DualGround technology

Close-Open (Short-Circuit) Time Results Interpretation

Power systems Protection course

BCM application note Travel measurement in circuit breaker monitoring

Introduction to Circuit Breaker. Working Principle of Circuit Breaker

MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI

Extra-High-Voltage SF 6 Gas-Insulated Switchgear

Circuit Breaker and Transducer: Where do I connect? Robert Foster Application Engineer Megger Paradise, CA 95969

Understanding the benefits of using a digital valve controller. Mark Buzzell Business Manager, Metso Flow Control

Modeling of Lead-Acid Battery Bank in the Energy Storage Systems

School of Electrical and Information Engineering. ELEC High Voltage. University of Sydney. Dr Keith Mitchell. Engineering

Diesel PM collection for marine emission using hole-type electrostatic precipitators

Reducing. with Current. arc flash note 2. points of interest. Why Use Current Limiting Fuses. By mike lang, Principal field engineer

A Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design

The Heating Mode Of Cable Transformer With Cooling System

Air-insulated switchgear UniGear type ZS1

Ultra Fast Earthing Switch UFES retrofit Overview

MEDIUM VOLTAGE PRODUCTS. Fault Current Limiters I S. -limiter and FC-Protector The worldʼs fastest switching devices

GE Arc Vault TM Protection System. By Mark Clapper GE Specification Engineer. Introduction. What Variables Contribute To An Arcing fault?

Pretest Module 29 High Voltage Unit 1

Extracting Valuable Information from HV Circuit Breaker Testing. Charles Sweetser - OMICRON MIPSYCON 2014

Proposal to establish a laboratory for combustion studies

Overcurrent protection

Miniature circuit breaker Application guide

Modeling the Lithium-Ion Battery

A starting method of ship electric propulsion permanent magnet synchronous motor

[Rao, 4(7): July, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

3.2. Current Limiting Fuses. Contents

Investigating The Effect of Switching and tripping on Flashover and Breakdown in Circuit Breaker

MOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E.

ADVANCES in NATURAL and APPLIED SCIENCES

IEEE Insulated Conductors Committee. Subcommittee B, Cable Accessories

Voltage Sag Mitigation in IEEE 6 Bus System by using STATCOM and UPFC

Circuit breaker interlocking and operation requirements SIEMENS

ABB AG - EPDS. Ultra-Fast Earthing Switch UFES active internal arc protection

The research on gearshift control strategies of a plug-in parallel hybrid electric vehicle equipped with EMT

Lecture 2. Power semiconductor devices (Power switches)

FUSE: SAFE & RELIABLE

FUSES. Safety through quality

Basic Electrical Parameters of Reed Switch Products

A Theoretical, Computational, and Experimental Analysis of an Interdigital Armature in a High Velocity Railgun

Arc flash hazard mitigation

POWER DISTRIBUTION SYSTEM ANALYSIS OF URBAN ELECTRIFIED RAILWAYS

Application Note. First trip test. A circuit breaker spends most of its lifetime conducting current without any

EXPERIMENTAL STUDY OF DYNAMIC THERMAL BEHAVIOUR OF AN 11 KV DISTRIBUTION TRANSFORMER

Summary of Revision, IEEE C , Guide for Breaker Failure Protection of Power Circuit Breakers

EE064D: Circuit Breakers & Switchgears: Design, Testing, Commissioning, Maintenance, Repair & Troubleshooting

*Corresponding author. Keywords: Quick vacuum circuit breaker, Opening and closing coil, Repulsion mechanism, reliability.

Power System Stability Analysis on System Connected to Wind Power Generation with Solid State Fault Current Limiter

Alvin Xu & Johnny Wang, ABB Xiamen Switchgear Co,. Ltd., November, 2016 ABB lead the intelligent revolution Intelligent technology (Part 2)

INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY

Selective Coordination

/12/$ IEEE. M. Bashir M.Sc student, Student Member, IEEE Ferdowsi University of Mashhad Mashhad, Iran

Maximizing the Power Efficiency of Integrated High-Voltage Generators

Circumstances affecting the protection against electrode potential rise (EPR)

New fem model for thermal analysis of medium voltage fuses

A Battery Smart Sensor and Its SOC Estimation Function for Assembled Lithium-Ion Batteries

A Systematic Approach to High-Voltage Circuit Breaker Testing

Cost Benefit Analysis of Faster Transmission System Protection Systems

Study on the Performance of Lithium-Ion Batteries at Different Temperatures Shanshan Guo1,a*,Yun Liu1,b and Lin Li2,c 1

Application of Simulation-X R based Simulation Technique to Notch Shape Optimization for a Variable Swash Plate Type Piston Pump

Application Note: Protection of Medium-Power Motors With SIPROTEC Compact 7SK80

Analysis of Switch Gear and Validation

Study of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank

Experimental investigations of pressure pulsations damping in screw compressor system

COMPARISON OF DIFFERENT METHODS FOR EXCITATION OF SYNCHRONOUS MACHINES

Using an SMC-50 Solid-State Smart Motor Controller for Pump Protection

Grounding systems for power supply facilities

Original. M. Pang-Ngam 1, N. Soponpongpipat 1. Keywords: Optimum pipe diameter, Total cost, Engineering economic

Dual-Rail Domino Logic Circuits with PVT Variations in VDSM Technology

Breaking new ground. A circuit breaker with the capacity to switch 15 large power plants

Product Specification

Basic Electrical Parameters of Reed Switch Products

Learning Module 6: Medium Voltage Power Circuit Breakers. 101 Basic Series

123/145kV SF6 Gas-Insulated Switchgear incorporating VCB. 145kV-1250~2000A-31.5kA

Journal of Engineering Sciences and Innovation Volume 2, Issue 4 / 2017, pp

Shock Tube for analysis of combustion of biofuels

Module 6. Actuators. Version 2 EE IIT, Kharagpur 1

PROTECTION OF THREE PHASE INDUCTION MOTOR AGAINST VARIOUS ABNORMAL CONDITIONS

RESPONSE OF A MEDIUM VOLTAGE CURRENT LIMITING FUSE OF SMALL SIZE TESTED AS GENERAL PURPOSE AND FULL- RANGE TYPE.

Investigation & Analysis of Three Phase Induction Motor Using Finite Element Method for Power Quality Improvement

Selective Coordination Enforcement:

FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE

Thermal Analysis of Laptop Battery Using Composite Material

Problem 1 (ECU Priority)

Power/Vac Vacuum Replacement Breakers for GE Magne-Blast Type AM & AMH Breakers

ZX2 Gas-insulated medium voltage switchgear

Western Canada BLRBAC Conference Selecting the Right Power Supply and Electrode for a Recovery Boiler ESP

4.28±0.05V 2.4±0.1V. W :29.0mm T :11.1mm

TURBOGENERATOR DYNAMIC ANALYSIS TO IDENTIFY CRITICAL SPEED AND VIBRATION SEVERITY

ZX-Family Gas-insulated medium voltage switchgear

Dual Power. Protection. Protection

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6

THE IMPACT OF BATTERY OPERATING TEMPERATURE AND STATE OF CHARGE ON THE LITHIUM-ION BATTERY INTERNAL RESISTANCE

Power Conditioning of Microgrids and Co-Generation Systems

Effect Of Bearing Faults On Dynamic Behavior And Electric Power Consumption Of Pumps

20th. SOLUTIONS for FLUID MOVEMENT, MEASUREMENT & CONTAINMENT. Do You Need a Booster Pump? Is Repeatability or Accuracy More Important?

Interrelation between Wavelengths of Track Geometry Irregularities and Rail Vehicle Dynamic Properties

Transcription:

Dynamic Resistance Measurement for Circuit Breakers Applying high DC current A. Secic - Project Leader, DV Power - Sweden, B. Milovic - Application Engineer, DV Power - Sweden ABSTRACT Presented is the dynamic resistance measurement (DRM) method for circuit breakers by using a high frequency DC/DC converter as a power source generating several hundred s amperes. Injecting high DC current through the breaker contacts and simultaneously monitoring the voltage drop across the main contact during the operation of the breaker was reported first in 1993 [1][2]. The DRM test requires a circuit breaker analyzer with a high-resolution measurement. The point of a position change from main to arcing contacts can be observed from the resistance plot. The resistance curve, as a function of a contact travel can be used to reveal potential problems related to the arcing contact condition [3]. Also, the actual length of the arcing contacts can be calculated if measuring the motion. This paper explains the benefit of injecting as high current as possible, but not less than 100A, to provide a reliable voltage drop reading, thus allowing exact detection of the arcing contact performance. After reviewing the characteristics of the dynamic resistance curve, the measuring system and parameters, the paper deals with relevant values that can be extracted from the resistance curve for detecting contact anomalies, wear, and/or misalignment. Finally, case studies are presented and test results are discussed. Keywords: HV Circuit Breaker testing, diagnostic, maintenance, dynamic resistance measurement, arcing contacts 1. INTRODUCTION A power circuit breaker (CB) is electromechanical device used in the transmission and distribution power systems, intended to switch on and off electric currents in power on state. Circuit breakers are used for routine operations and protection of other equipment. Figure 1.1 shows a Generic component-oriented model of a high voltage (HV) circuit breaker [4]. This is a general model that can be used to represent different types of HV circuit breakers - from old bulk oil to modern SF6 single self-blast CB's. There are many different types of circuit breakers, but, as presented model shows, all those different types consist of the same basic components: Breaker Control unit, Operating Mechanism and Interrupter Unit. The interrupter consists of moving and stationary contacts (immersed in some kind of insulation media oil, gas, etc). These parts are at high voltage potential and are the active part in the electric power network. Figure 1.2 shows moving and stationary contacts for SF6 circuit breaker. Main requirements on the interrupter are: To act as much as possible as an ideal conductor in the closed position (Z CB->0); To act as much as possible as an ideal insulator in open position (Z CB-> ); To be capable to perform fast open / close operation when in the closed / open position, with: - Minimal damage to contacts - Minimal over-voltages produced during operation Figure 1.1. Generic component-oriented model of HV CB 1

Materials from which the contacts are made are subject to wear and erosion. A contact wear and erosion is unavoidable consequence of a current interruption process and formation of electrical arc. An electric arc is a form of gas discharge very complicated and complex electrical and thermal process, characterized by the appearance of plasma. Plasma refers to a state of matter and refers to electrically conductive ionized gas containing charged particles: electrons, positive and negative ions. Figure 1.2 Moving and stationary contacts Special attention should be paid to the chioce of materials in the CB contact design. The reasons are the HV CB needs to carry currents up to 4000 A (or even 40 ka for units installed in nuclear power stations), to withstand (up to 3 sec) and break currents of up to 100 ka with 250 ka peak under abnormal conditions. Experimental results obtained show erosion of the contacts made of heterogeneous (sintered) materials is significantly smaller than in homogeneous (pure metal) materials. For example, let s compare contacts made of Copper/Tungsten (Cu/W) as heterogeneous material to pure Copper (Cu) contacts. In pure Cu contacts a pond of melted material is formed around an arc root from which the metal vaporizes. Arc roots tend to avoid cooling blasts of vaporized metal. This results in a very unstable movement of arc roots on the molted surface of the electrode. Even without vaporization, this causes removal of the contact material in a liquid form. This process leads to intensive erosion. At heterogeneous material, such as Cu/W, the arc forms its roots on the material with higher vaporization temperature. The fact that copper vaporizes before tungsten even starts to melt, leads to a conclusion that tungsten affects cooling of the arc root significantly. That is the reason there is no creation of a pond of a melted material on the electrode in this case and erosion of the contacts takes place mostly through vaporization, without droplets such as in homogeneous materials [6]. It has been observed that the temperature at the center of the arc, when one is subjected to forced cooling, reaches up to 25,000 C (Just as a reference - the Sun surface temperature is approximately 5,500 C). It may sound like contradiction, but temperature at the center of the arc is lower (around 4 times) when there is no forced cooling. The reason is the forced cooling reduces arc diameter affecting current density of the plasma and increases the temperature [5]. Such a high temperature causes vaporization of the contact material which is the main reason for contact erosion. Contact erosion and wear occurs as a result of contacts bouncing when a circuit breaker change of state under normal load or a fault current interruption. Mechanical impact also causes deviations on the contacts. Contact erosion process is too complex to be described mathematically. Such a description would require taking into account a large number of input parameters. On the other hand, considerable research, mainly of experimental nature, has been done in order to better understand and explain this phenomena. Figure 1.3 Measured materials rate of erosion due to arcing in SF6 [5] That is the main reason why the overall contact system of circuit breakers consists of two distinct contact elements: Main contacts with a primary role to conduct currents when the breaker is in a closed position and arcing contacts designed to be the first to touch and the last to part. Any electrical arc formed during the breaker operation will happen on the arcing contacts. This is not a case for vacuum circuit breakers, due to arc s specific behavior in a vacuum surrounding. In such an environment, there are no ionized gases from the arc s surrounding ambient and the positive arc column is composed only of metal vapors that have been boiled off the electodes. That's the 2

reason there is no need for separation of main and arcing contacts for the vacuum circuit breakers and DRM test will not provide any information regarding the state of the contacts. On the other hand, the design of modern highvoltage puffer-type SF6 gas circuit breakers is based on the switching of two parallel contact sets. First, the low-resistance silver-plated contacts, or the main contacts, are specifically designed to carry the load current without any excessive temperature rise. The second, tungsten-copper arcing contacts operate at the breaker opening following the main contact part. The electrical arc starts after the separation of the arcing contacts. The tungstencopper material is designed to carry the arc until it is cleared at the next zero crossing. Offline timing tests and static resistance measurement will provide some diagnostic information about the state of contacts. By definition, a circuit breaker timing test is the process of measuring the mechanical operating times. These tests are also used to determine synchronization between phases, or within one phase for circuit breakers having more than one break unit per phase. Also, timing test on the circuit breaker can provide information about contacts bouncing. Closing of the contacts is usually followed by several bouncing cycles before the two contacts settle down in a close position. During bouncing period, each contacts separation is followed by the appearance of an electric arc that causes erosion of the contacts. Contacts bouncing should be reduced to a minimum by proper design since it directly affects contact's erosion. Several standards (IEC 60694, ANSI C37.09) are suggesting the measurement of the circuit breaker main contacts static resistance as a part of standard offline diagnostic test procedure. Collected results are providing information on state of the main contacts (damaged contacts, contact force lower then specified, polluted isolation medium, malfunction breaker is not in fully closed position, etc). Unfortunately, these tests on the circuit breaker interrupter unit do not provide any information about state of the arcing contacts. That s the reason for introducing a dynamic-contact resistance measurement method to be used as a tool to diagnose the condition of arcing contacts. The method has been validated by field tests performed on SF6 gas circuit breakers [7][8]. The new method is based on the breaker contact resistance measurement during an opening operation at rated contact speed. 2. MEASUREMENT TECHNIQUES 2.1 Battery as a power source for DRM test Regular 12 V car-batteries can be used as a source for current injection. Voltage drop measurement across breaker terminals was measured with the Circuit Breaker Analyzer instrument (analog channel - range 1 V). It is recommended to perform a trip-free test without battery to see if everything is connected properly and the breaker operates trip free. Figure 2.1 145 kv SF6 circuit breaker car battery was used as a power source for high current injection. Voltage drop was measured across breaking elements during tripfree operations. Disadvantages of this solution are weight, possibility of accidental battery short-circuiting as well as a poor contact connection. Figure 1.3 Increased contacts bouncing timing test on SF6 circuit breaker 123kV, manufactured in 1970s Deployment of the lead acid or other rechargeable batteries as a source presents technical problems that will prevent their use in practice. 3

In addition, lack of current regulation makes it difficult to establish similar testing conditions, in different time intervals or on different CB phases, as well as later comparison of the results. 2.2 DRM at low contact speed There is an alternative method using a slow motion of the circuit breaker when a DC current is injected. The results of this approach do not represent a real situation because there are no breakers that will operate with such a low speed. Under this simulation the contact system will not behave as when the breaker is operated at normal velocity. Additional disadvantage is that this method is intrusive for some breaker mechanisms, since an adjustment to the operating mechanism is required. There is a potential risk of damaging the operating mechanism when restoring it back to service. 2.3 DRM at rated contact speed using micro ohmmeter as the power source Another successfully used strategy was performing the DRM tests at rated opening speed while simultaneously injecting current of at least 100 A. The Circuit Breaker Analyzer and Timer was used as both, the power source, the current and voltage drop recorder. Test object was 145 kv SF6 dead tank circuit breaker. Technical characteristics of a 200 A micro ohmmeter used as a power source were: load voltage of up to 7 V, and measuring accuracy of ±(0.1 % reading + 0.1 % full scale). Linear to rotary converter was used for a digital rotary transducer T1, with transfer function: 1 mm at contacts = 2.79 deg at transducer. Measured static resistance of the CB is 88.9 µω and this value shows no damage on the main contacts. Figure 2.3 DRM graph at 200A on 145 kv SF6 circuit breaker. The graph is far smoother and the point of main contact parting can be easily identified. The DRM results obtained at 200 A current indicated the main contacts separation at 19.6 ms. It means the arcing contact overlapping time is approximately 5.2 ms which is the expected time, and overlapping length is approximately 20.6 mm*. Resistance value obtained is around 1400 µω after the main contacts open. This resistance value is common for arcing contacts. First step noticed on the graph at 15 ms is probably due to a fact that the main contact resistance increases as the contacts start moving. Note: *Measured lenght of the arcing contact is approximatly 20,6 mm (57,6 deg), from 19,6 ms to 24,9 ms. Transducer: Emeta, MA306-10-2500-3, Model: #S108-B 2500 3. DYNAMIC RESISTANCE MEASUREMENT ON CIRCUIT BREAKER GROUNDED ON BOTH SIDES (BSG) Testing a high voltage circuit breaker which is not grounded on both sides can be hazardous due to high electric potential presence. DRM measurement can also be performed on a circuit breaker grounded on both sides. In this way higher level of personal safety and protection is achieved. Voltage drop across arcing contacts, in case of circuit breaker grounded on both sides, will be lower due to presence of parallel resistance that comes from the grounding cables and ground resistance. Even with decreased total resistance in cases when both sides of the circuit breaker are grounded, overlapping time does not change. Figure 2.2 DRM graph at 100A on 145 kv SF6 circuit breaker. It is often difficult to identify the point of main contact parting. The main contact separation point is not as obvious as in the second approach with 200A. Overlapping length of the main and arcing contacts is calculated manually, based on the obtained motion diagram and previously determined overlapping time. Considering the overlapping time is not changed, one can conclude grounding does not affect DRM results. 4

REFERENCES [1] F. Salamanca, F. Borras, H. Eggert, and W. Steingräber, Preventive diagnosis on high-voltage circuit breakers, in Proc. CIGRE Symp., Berlin, Germany, 1993, pp. 120 02. Figure 3.1 Overlapped DRM results on the same phase of CB, once without grounding and with ground resistance of 20 mohm and 10mOhm. 4. CONCLUSION Preventive maintenance on a high voltage (HV) breaker consists of several routine tests. The timing and motion tests are methods used to assess the breaker mechanical condition. When the timing and motion results indicate an abnormality, the DRM test can be an effective way to further diagnose the internal condition of the breaker contacts. Figure 2.3 depicts an example of a dynamic resistance measurement on a high voltage circuit breaker where transition from static resistance value to open contact is shown. Based on the above graphs (Fig 2.2 and Fig 2.3), it becomes clear that interpreting the DRM curve at 100 A may lead to a wrong diagnostic conclusion, especially for the main contact separation which occurs at approximately 19 ms. [2] M. Ohlen, B. Dueck and H. Wernli, in Proc. Dynamic Resistance Measurements A Tool for Circuit Breaker Diagnostics, Stockholm Power Tech Int. Symp. Electric Power Engineering, Sweden, Jun.18 22, 1995, vol. 6, pp. 108 113. [3] J. Levi, A simplified method for determing HV Circuit Breaker contact condition Dynamic Resistance Measurement, presented at the Doble Client Conf., Boston, MA, 2005. [4] Michael Stanek, "Model-Aided Diagnosis for High Voltage Circuit Breakers", A dissertation submitted to the Swiss Federal Institute of Technology Zurich for the degree of Doctor of Technical Sciences, Zurich, 2000 [5] Ruben D. Garzon "High Voltage Circuit Breakers: Design and Applications", Second Edition, Revised and Expanded, Taylor & Francis, New York, NY 1001 62002 [6] M.Kapetanovic, "High voltage circuit breakers", a book, Faculty of Electrotechnical Engineering, Sarajevo, 2011 [7] R.Ostojic, J. Levi, Use of micro-ohm meter as a power source for DRM testing on dead tank Circuit Breakers, presented at the Doble Client Conf., Boston, MA, 2013. [8] M. Landry, A. Mercier, G. Ouellet, C. Rajotte, J. Caron, M. Roy, F. Brikci, A new measurement method of the dynamic contact resistance of HV circuit breakers IEEE PES Transmission and Distribution Conference and Exhibition, Dallas, USA, p. 1002-1009, 21-24 May 2006. As the injected current is increased from 100 A to 200 A, the graph is far smoother and the main contact separation can be easily identified, as shown in Fig. 2.3. In view of these results, it is recommended to apply an injected current of at least 200 A when performing DRM tests at the rated contact speed on the 145 kv SF6 circuit breakers. 5