(by authors Jouko Niiranen, Slavomir Seman, Jari-Pekka Matsinen, Reijo Virtanen, and Antti Vilhunen)

Similar documents
Wind Turbine Grid Integration Challenge

Full-Scale Medium-Voltage Converters for Wind Power Generators up to 7 MVA

ABB low voltage wind turbine converters Reliable technology for wind power

ABB Wind Power Solution

CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM

Research on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC

IMPROVEMENT IN DOUBLY FED INDUCTON GENERATOR UNDER FAULT USING INDUCTOR

Journal of American Science 2015;11(11) Integration of wind Power Plant on Electrical grid based on PSS/E

FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE

Testing Renewable Power Plants on High-Voltage-Ride-Through Capability

Study of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank

Doubly fed electric machine

Wind Power Plants with VSC Based STATCOM in PSCAD/EMTDC Environment

Design and Hardware Implementation of a Supervisory Controller for a Wind Power Turbine

EPE97 OPTIMIZED DESIGN OF VARIABLE-SPEED DRIVES BASED ON NUMERICAL SIMULATION

Generators for the age of variable power generation

J.-J.Simond*, A.Sapin**, B.Kawkabani*, D.Schafer***, M.Tu Xuan*, B.Willy***

Grid Code Testing of Wind Turbines by VSC-based Test Equipment

Enhancement of Transient Stability Using Fault Current Limiter and Thyristor Controlled Braking Resistor

Power System Stability Analysis on System Connected to Wind Power Generation with Solid State Fault Current Limiter

Integration of Large Wind Farms into Electric Grids

Simulation and Analysis of a DFIG Wind Energy Conversion System with Genetic Fuzzy Controller

ABB low voltage wind turbine converters Reliable technology for wind power

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET)

Statcom Operation for Wind Power Generator with Improved Transient Stability

Anupam *1, Prof. S.U Kulkarni 2 1 ABSTRACT I. INTRODUCTION II. MODELLING OF WIND SPEED

Fuzzy based STATCOM Controller for Grid connected wind Farms with Fixed Speed Induction Generators

LOW VOLTAGE WIND CONVERTERS. ABB wind turbine converters ACS880, 800 kw to 8 MW

Wind Farm Evaluation and Control

Grid Integration Issues for Large Scale Wind Power Plants (WPPs)

Comparative Analysis of Integrating WECS with PMSG and DFIG Models connected to Power Grid Pertaining to Different Faults

ASSESSING BEHAVOIR OF THE OUTER CROWBAR PROTECTION WITH THE DFIG DURING GRID FAULT

CONTROL AND PERFORMANCE OF A DOUBLY-FED INDUCTION MACHINE FOR WIND TURBINE SYSTEMS

Implementation of FC-TCR for Reactive Power Control

Workshop on Grid Integration of Variable Renewable Energy: Part 1

Analysis of Low Voltage Ride through Capability of FSIG Based Wind Farm Using STATCOM

Modular Standardized Electrical and Control Solutions for Fast Track Projects

Combined Input Voltage and Slip Power Control of low power Wind-Driven WoundRotor Induction Generators

ENHANCEMENT OF ROTOR ANGLE STABILITY OF POWER SYSTEM BY CONTROLLING RSC OF DFIG

Modeling Of DFIG and Improving the LVRT Capability Of System Using Crowbar And Battery Energy Storage System

/12/$ IEEE. M. Bashir M.Sc student, Student Member, IEEE Ferdowsi University of Mashhad Mashhad, Iran

Dynamic Performance Of DFIG Based WECS Under Different Voltage Sag

COMPARISON BETWEEN ISOLATED AND GRID CONNECTED DFIG WIND TURBINE

Regenerative Utility Simulator for Grid-Tied Inverters

Control Strategy for DFIG Wind Turbine to Enhance LVRT under Various Faults

Digital Twin Validation for Distributed Resource Converters and Assets

Facility Employing Standard Converters for Testing DFIG Wind Generators up to 30kW

Effect of crowbar resistance on fault ride through capability of doubly fed induction generator

Performance of Low Power Wind-Driven Wound Rotor Induction Generators using Matlab

Simulated Switching Transients in the External Grid of Walney Offshore Wind Farm

DIgSILENT GridCode. DIgSILENT REP Meeting September Gomaringen (Germany)

Performance Analysis of 3-Ø Self-Excited Induction Generator with Rectifier Load

Transforming the US Electric Grid

Abstract. Benefits and challenges of a grid coupled wound rotor synchronous generator in a wind turbine application

ABB central inverters PVS to 2091 kva

ECEN 667 Power System Stability Lecture 19: Load Models

Ukujima Photovoltaic Park 400 MW Stable Integration of a 400MW Photovoltaic Farm into the Japanese Power System Challenges and Chances

Renewables & reliability: How Senvion s wind farms enhance grid stability in Canada

Modelling and Simulation of DFIG with Fault Rid Through Protection

Squirrel cage induction generator based wind farm connected with a single power converter to a HVDC grid. Lluís Trilla PhD student

Products for offshore wind turbines

Modelling and Simulation of DFIG based wind energy system

Konferenz Energieversorgung und Klimawandel

LVRT of DFIG Wind Turbines - Crowbar vs. Stator Current Feedback Solution -

Wind Generation and its Grid Conection

ABB central inverters PVS to 2000 kva

Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood

SINAMICS SM150. 4/2 Overview. 4/2 Benefits. 4/2 Design. 4/6 Function. 4/8 Selection and ordering data. 4/8 Options

Current accuracy class. Sensor principles

Dynamic Reactive Power Control for Wind Power Plants

Connection of Power Generating Modules to DNO Distribution Networks in accordance with EREC G99

Model Predictive Control of Back-to-Back Converter in PMSG Based Wind Energy System

Modeling of Active Crowbar Protection Scheme for Various Types of Fault in Wind Energy Conversion System using DFIG

Generation Capacity Design for a Microgrid for Measurable Power Quality Indexes

Battery Energy Storage System addressing the Power Quality Issue in Grid Connected Wind Energy Conversion System 9/15/2017 1

Transient Stability Improvement of Squirrel Cage Induction Wind Turbine Generator using Plugging Mode

Performance Analysis of Transient Stability on a Power System Network

Experience on Technical Solutions for Grid Integration of Offshore Windfarms

SYSTEM INTEGRATION. Railway and urban transport electrification Energy-efficient and reliable solutions

ABB FACTS Grid connection of Wind Farms

Voltage Sag Mitigation in IEEE 6 Bus System by using STATCOM and UPFC

Islanding of 24-bus IEEE Reliability Test System

Design and Control of Lab-Scale Variable Speed Wind Turbine Simulator using DFIG. Seung-Ho Song, Ji-Hoon Im, Hyeong-Jin Choi, Tae-Hyeong Kim

APPLICATION OF STATCOM FOR STABILITY ENHANCEMENT OF FSIG BASED GRID CONNECTED WIND FARM

FUZZY LOGIC FOR SWITCHING FAULT DETECTION OF INDUCTION MOTOR DRIVE SYSTEM

CHAPTER 5 ACTIVE AND REACTIVE POWER CONTROL OF DOUBLY FED INDUCTION GENERATOR WITH BACK TO BACK CONVERTER USING DIRECT POWER CONTROL

Connection of Power Generating Modules to DNO Distribution Networks in accordance with EREC G99

PUMPED STORAGE - GRID REQUIREMENTS FOR BEHAVIOR OF LARGE MOTOR- GENERATORS AND CONFIRMATION OF COMPLIANCE THROUGH SIMULATION

Low-Voltage Ride-Through Capability Improvement of DFIG-Based Wind Turbines

Reactive power support of smart distribution grids using optimal management of charging parking of PHEV

International Journal of Emerging Technology and Innovative Engineering Volume 2, Issue 4, April 2016 (ISSN: )

Diversifying into Marine Energy. ABB March 2015

Technical Guide No. 7. Dimensioning of a Drive system

6545(Print), ISSN (Online) Volume 4, Issue 2, March April (2013), IAEME & TECHNOLOGY (IJEET)

ABB central inverters PVS to 1000 kw

Development of Novel Connection Control Method for Small Scale Solar - Wind Hybrid Power Plant

Electrical grid stability with high wind energy penetration

COMPARISON OF DIFFERENT METHODS FOR EXCITATION OF SYNCHRONOUS MACHINES

Enabling the power of wind. Competence and expertise for wind power customers

Possibilities of Distributed Generation Simulations Using by MATLAB

Transcription:

Technical Paper: Low voltage ride-through testing of wind turbine converters at ABB helps wind turbines meet the requirements of IEC 61400-21 more quickly (by authors Jouko Niiranen, Slavomir Seman, Jari-Pekka Matsinen, Reijo Virtanen, and Antti Vilhunen) Abstract The testing of low-voltage, ride-through capability of wind turbine converters recently has been standardized in the 2nd edition of IEC 61400-21. Thus, testing of the converters produced in the factory is important to shorten the on-site testing time required for meeting the requirements of IEC 61400-21. ABB recently has built a new test facility for its wind turbine converters that is capable of testing those units with up to a 3 MW continuous power rating. A profile of this test facility, and the results of a factory test of a full-power wind turbine drive, follows below. Introduction In order to study the low voltage ride-through (LVRT) behavior of wind turbines, it is necessary to carry out on-site tests and accurate transient simulation analyses, to understand the impact of the power system disturbances on wind turbines in operation. Based on the knowledge obtained from the type test, it is possible to validate the wind park grid code compliance by simulating the overall wind park behavior during the fault. However, on-site testing requires expensive test equipment and personnel to be present in the often remote location of the wind farm. Because the tests are required to be done on several power levels, a correct wind speed must prevail during each test. This means that often considerable time is spent waiting for winds to be suitable for testing. Further, if some problems emerge and require changes in the hardware or software, it may be necessary to start the tests from the beginning. Naturally, significant cost and test-time reductions can be obtained via proper factory testing -- before going to the on-site tests. In factory tests, the wind is replaced by a speed-controlled motor driving the generator. Thus, several tests at multiple power levels can be done in a short time. Also, repeatability of the tests is much better and, thus, it is much easier to pinpoint reasons to any equipment problems, if they are encountered. Because the average power of the turbines now are in the multi-megawatt range, factory testing equipment has to be dimensioned accordingly. Further, ride-through testing according to the most demanding grid codes [1]-[4] and testing standards should be possible. This means that the test equipment has to be flexible enough to provide a multitude of well-controlled voltage levels during the dip. ABB has had longtime facilities to do extensive LVRT factory testing in the drives laboratory of Helsinki, Finland [5]-[7]. Although it was possible to test the most important properties of the wind turbine converters, the voltage levels available were quite limited and did not allow the turbine transformer to be tested with the converters. Thus, it was decided to build a new LVRT testing facility according the latest edition of the IEC 61400-21 [8] testing standard.

LVRT test facility The IEC 61400-21 specifies the voltage dip generator as a voltage divider; see equation below: WT Z1 Sk, ψk Z2 S Fig.1: Low voltage ride-through test equipment principle [8]. The impedance Z2 emulates the fault impedance. Dip starts when the circuit breaker S is closed, and ends when the breaker opens and clears the fault current. The impedances usually are inductors, because they have lower losses than resistors. Moreover, inductive fault impedance is more demanding -- especially for doubly-fed generators [5]. The impedance Z1 is needed in order to limit the influences of the voltage dip in the supplying grid. In order to be able to select the remaining voltage level during the dip (according the grid code requirements), the impedance values have to be possible to be adjusted accordingly. For ease of operation, remote control is preferred. Thus, inductors with motor-controlled tap changers were designed for the purpose; Fig. 2 illustrates that making a fine resolution of voltage levels down to zero is possible: Fig 2: Inductors of the LVRT tester. Z2 on the left, Z1 on the right.

Both inductors are oil cooled for compact size and air core type in order to avoid saturation. Series inductor Z 1 has a big heat exchanger in order to be able to conduct continuously the rated current of a 3 MW turbine drive. The switchgear was selected from the ABB's medium voltage Uniswitch assortment (see Fig 3). A line diagram of the whole test facility is shown in Fig. 4. Fig. 3: Switchgear of the LVRT test equipment. Fig. 4: Single-line diagram of the LVRT test equipment. EUT = Equipment Under Test.

The equipment normally is connected to Helsinki Energy's 20 kv line. The 110 kv sub-station is located close to the test site and, thus, realistic short-circuit ratio is possible to achieve. In addition to this fixed 50 Hz supply, a variable frequency and voltage supply from a variable speed 8 MVA synchronous machine is possible for turbines with 60 Hz rated frequency. With this machine, it also is possible to test other functions of the turbine, such as frequency support. The equipment can be controlled through a computer-controlled interface (note Fig. 5). It is possible to select three-phase, two-phase or single-phase voltage dips. In addition to the duration of the dip, it is possible to select the exact instant during a voltage cycle when the breaker is closed. Further, it is possible to program a sequence of faults in order to emulate reclosing operations, and faults developing from single-phase earth faults to three-phase shorts. The current, voltage and power measurements are recorded and included in a measurement report automatically. Fig. 5: Computer control interface of the LVRT equipment. The speed of the generator is controlled by a variable speed AC motor drive. The parameters of the speed controller can be adjusted to emulate the dynamics of the pitch control. Thus, realistic speed increase and oscillations can be obtained during and after the dip. LVRT testing of a full-power converter wind turbine drive The first LVRT tests with the new test facility were made with a 2.3 MW full-power converter drive (see Fig. 6). Examples of the recorded zero-voltage, ride-through test waveforms are shown in Figures 7-9. The generator was running at rated power before the dip. When the circuit breaker shorts the medium voltage side of the grid, the turbine starts immediately to supply reactive current. Due to the reactive current and the impedance of the transformer, the voltage on the low-voltage side of the turbine transformer, U LV, does not go to zero. After the breaker clears the short, the reactive current is reduced and active current is ramped up.

Fig. 6: Liquid cooled 2.3 MW full power converter. Fig. 7: Example of a zero-voltage, ride-through test of a 2.3 MW full converter WT drive. RMS voltages and currents on the medium voltage (MV) and low voltage (LV) side of the transformer.

Fig. 8: Per-unit active and reactive currents during a zero voltage ride through test of a 2.3 MW full converter WT drive. Fig. 9: Phase currents in the medium voltage side during a zero-voltage ride-through test of a 2.3 MW full converter WT drive. In Fig. 9, the inrush current of the transformer, due to the heavy saturation, can be seen clearly after voltage recovery. The saturation distorts the low-voltage-side waveform considerably. In spite of this, the virtual Direct Torque Control (DTC) of the grid-side converter is able to control the situation without problems. However, the existence of this kind of phenomena highlights the necessity of full-scale testing of wind turbine drives. Conclusions ABB has built a new test facility capable of conducting low-voltage, ride-through tests for wind turbine drives with rated power up to 3 MW. The testing can be done efficiently due to highly automated test set-up. Thorough factory testing is expected to reduce the required on-site testing time and costs considerably.

References 1. TransmissionCode 2007. Network and System Rules of the German Transmission System Operators. BDEW, 2007 Aug.. [Online]. Available: http://www.bdew.de/bdew.nsf/id/de_transmissioncode_2007_network_and_system_rules_of_thegerman_t ransmission_system_operators/$file/transmissioncode.pdf 2. The grid code. National Grid Electricity Transmission plc. 2006 Jan.. [Online]. Available: http://www.nationalgrid.com/uk/electricity/codes/gridcode/gridcodedocs/ 3. Order No 662-A. Federal Energy Regulatory Commission, [Online]. Available: http://ferc.gov/eventcalendar/files/20051212171744-rm05-4-001.pdf 4. P.O. 12.3, Requisitos de respuesta frente a huecos de tensión de las instalaciones eólicas. Ministerio de Industria, Turismo y Comercio, Spain. [Online]. Available: http://www.ree.es/operacion/pdf/po/po_resol_12.3_respuesta_huecos_eolica.pdf 5. Niiranen, J.: Experiences on voltage dip ride through factory testing of synchronous and doubly fed generator drives. Proc. 11th European Conference on Power Electronics and Applications, EPE 2005, Dresden Germany, 11-14 September 2005. 11 p. 6. Niiranen, J.: About the Active and Reactive Power Measurements in Unsymmetrical Voltage Dip Ride Through Testing. Wind Energy 2008; 11:121-131 7. Seman, S., Niiranen, J., Virtanen, R, Matsinen, J-P.: Low Voltage Ride-Through Analysis of 2 MW DFIG Wind Turbine Grid Code Compliance Validations. Proceedings of IEEE 2008 Power and Energy Society General Meeting - Conversion and Delivery of Electrical Energy in the 21st Century. 20-24 July 2008, Pittsburgh, PA, 6 pages. 8. IEC 61400-21. International standard. Wind turbines Part 21. Measurement and assessment of power quality characteristics of grid connected wind turbines. (2nd edn). IEC Central Office: Geneva, Switzerland, 2008; 58 pp. Reaching the Authors: Address: ABB Oy, Drives, P.O. Box 184, 00381 Helsinki, Finland, Tel: +358 10 22 11. E-mailing the authors: jouko.niiranen@fi.abb.com, slavomir.a.seman@fi.abb.com, jari-pekka.matsinen@fi.abb.com, reijo.virtanen@fi.abb.com, antti.vilhunen@fi.abb.com For more information please contact: ABB Media Relations Ken Graber 262-780-3873 phone 262-785-8501 fax ken.j.graber@us.abb.com