Tesoro Logistics Northwest Product System GP, LLC Product Quality Control Guidelines

Similar documents
Tesoro Logistics Northwest Terminalling Company LLC Product Quality Control Guidelines

Sweeny to Pasadena Pipeline

Phillips 66 Pipeline LLC. Borger-Denver Pipeline Product Specifications

Phillips Texas Pipeline Company, LTD. Amarillo-Lubbock Pipeline (SAAL) Product Specifications

Phillips 66 Carrier LLC. Borger-Amarillo Pipeline (BAM) Product Specifications

Heartland Pipeline. Heartland Pipeline Company Product Specifications. Effective Date: 10/1/2015

Specifications Of Straight Run Naphtha for Exportation

Cross-Channel Connector Pipeline

ANNEX 2, REFERENCE FUELS

ANNEX 3 REFERENCE FUELS. Parameter Unit Limits (1) Test method Minimum Maximum Research octane number, RON

International Quality Assurance Exchange Program Schedule. Fuel Month Number Type Dispatch Date Closing Date

Specification. Marketing. Distillate, JP-8, High Sulfur (3,000 ppm), Nato Code F-34. Marketing specification All Terminals

REBCO (RUSSIAN EXPORT BLEND CRUDE OIL) SPECIFICATION GOST

SCOPE OF ACCREDITATION TO ISO/IEC 17043:2010. ASTM INTERNATIONAL 100 Barr Harbor Drive West Conshohocken, PA Amy Meacock

Renewable Fuels Association One Massachusetts Ave. NW Suite 820 Washington, DC Telephone: (202) Fax: (202)

Exceeding Expectations

एमआरप एल ग णव नय ण य गश ल उप दन व श:२०१७ MRPL QC LABORATORY

ASTM Aviation (Turbine) Jet Fuel Sample ID: JF1211

CERTIFICATE OF ACCREDITATION

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005

Louis Dreyfus Claypool Holdings, LLC. Biodiesel Production Plant Claypool, Indiana

3. QUALITY ASSURANCE PROGRAM

Standard Test Method for Sulfur in the Analysis Sample of Coal and Coke Using High-Temperature Tube Furnace Combustion

Regional Laboratory, Indian Oil Corporation Limited, Korukkupet Terminal, Kathivakkam High Road, Chennai, Tamil Nadu

BUCKEYE PIPE LINE COMPANY, L.P. BUCKEYE PIPE LINE TRANSPORTATION, LLC LAUREL PIPE LINE COMPANY, L.P. NORCO PIPE LINE COMPANY, LLC

St. Clair County Road Commission Specifications Diesel Fuels

NuStar Pipeline Operating Partnership, L.P.

Biodiesel Fuel Quality

Crude Assay Report. Crude Oil sample marked. Barrow Crude Oil. On Behalf Of. Chevron Australia Pty Ltd. Laboratory Supervisor. Crude Assay Chemist

Supply of Services for Detailed OEB Crude Assay Analysis

Magellan Pipeline Product Specifications

Bengal Pipeline Company Section 3 Product Codes and Specifications (Effective Date [W] May 5, 2014 September 30, 2014 )

Bengal Pipeline Company Section 3 Product Codes and Specifications (Effective Date [W] September 30, 2014 March 13, 2016

NuStar Pipeline Operating Partnership, L.P.

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005

Magellan Pipeline Product Specifications

HQCEC has contracted KBC to obtain an assessment of future market and market pricing. The market study results have been used as the basis of study.

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

3. QUALITY ASSURANCE PROGRAM

Bengal Pipeline Company Section 3 Product Codes and Specifications (Effective Date [W] December 9, 2011 March 1, 2012 )

COLOMBIA. 2. Vehicle categories: 2.1. Categories for application with European limits. M = Passenger vehicle N = Commercial vehicle

PETROLEUM PRODUCTS INSPECTION OPERATIONS MANUAL

Standard Diesel & FCC Additive Technical Analysis on Lubricity

Annex no. 1 of Accreditation Certificate no. LI 333 from

CRC Report No. E-79 COORDINATING RESEARCH COUNCIL, INC MANSELL ROAD SUITE 140 ALPHARETTA, GA 30022

Colonial Pipeline Company Section 3 Product Codes and Specifications Effective Date [W] November 1, 2016 September 24, 2017

On-Line Process Analyzers: Potential Uses and Applications

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005

ASTM D Standard Specification for Biodiesel Fuel (B 100) Blend Stock for Distillate Fuels

FORLINE LTD. Global Energy Solutions Kenneth Pike, Suite 200B Greenville, Delaware, 19807, USA. 19 Kathleen Road, SW11 2JR, London, England

William Piel

Northville Product Services and Colonial Pipeline B5 Soy Test Data and Report February Soy blended low sulfur diesel

Fuel Management for Federal Agencies

Guidance on Changes to ASTM D1655 and Def Stan to Increase Allowable FAME Limits to 50 mg/kg

CHEVRON PHILLIPS CHEMICAL PIPELINE COMPANY LLC PETROCHEMICAL PRODUCTS (AS DEFINED HEREIN)

Product Specifications

Smoke Point Significance and Use

3. QUALITY ASSURANCE PROGRAM

Colonial Pipeline Company Section 3 Product Codes and Specifications ([C] Proposed Effective Date [W] January 20, 2014 May 5, 2014 )

एमआरप एल ग णव नय ण य गश ल वष 2019 क लए प उ!प द# क लए भ रत य म नक QC LABORATORY INDIAN STANDARD FOR PETROLEUM PRODUCTS SPECIFICATION FOR YEAR 2019

Ethanol and the Economics of Octane The Superior Solution

SECTION 916 (Pages ) is deleted and the following substituted: SECTION 916 BITUMINOUS MATERIALS

एमआरप एल ग णव नय ण य गश ल आई.एस एस.उप दन व श:२०१ MRPL QC LABORATORY IS PRODUCTS SPECIFICATION:2018. Page 1 of 17

CHEVRON PHILLIPS CHEMICAL PIPELINE COMPANY LLC PETROCHEMICAL PRODUCTS (AS DEFINED HEREIN)

The Importance of Biodiesel Meeting the ASTM D6751 Standard. Barbara E Goodrich Manager, Engine Fluids John Deere Power Systems 6 February 2008

Jet fuel control: Specification test methodology

Softening point by Ring & Ball. Density and relative density of liquids by Hubbart pycnometer

SCOPE OF ACCREDITATION

Table of Contents. Copyright and Trademarks 5. Copyright 5 Revision 5 Disclaimer of Liability 5 Copy and Use Restrictions 5.

Ceiba Crude (31.44 API, Sul WT%)

PERFORMANCE SPECIFICATION CALIBRATING FLUIDS, AIRCRAFT FUEL SYSTEM COMPONENTS

PRICE LIST 2017/2018

Alberta Innovates - Technology Futures ~ Fuels & Lubricants

SELLING GTL SOME OBSERVATIONS ON THE MARKETING OF GTL PRODUCTS

Warter Fuels JSC Aviation Gasoline AVGAS 100LL Edition VIII

EAST AFRICAN STANDARD. Automotive gasoline (premium motor spirit) Specification EAST AFRICAN COMMUNITY. HS (regular); HS

एमआरप एल ग णव नय ण य गश ल आई.एस एस.उप दन व श:२०१ MRPL QC LABORATORY IS PRODUCTS SPECIFICATION:2018. Page 1 of 16

Oregon Department of Transportation Standard Specifications For Asphalt Materials 2004

Draft Indian Standard SYN GAS/ AMMONIA TURBO COMPRESSOR LUBRICATING OILS SPECIFICATION

BQ-9000 Quality Management System. Producer Requirements

Annex to the Accreditation Certificate D-PL according to DIN EN ISO/IEC 17025:2005

OIL PT. Scheme Description. Oils and Fuels Analysis Proficiency Testing Scheme

COMMODITY TESTING SUMMARY TABLE 6

DRS 366 RWANDA STANDARD. Fuel additives Guidelines for inspection. First edition mm-dd. Reference number DRS 366: 2017

On-Line NIR Analysis for Blending

CLICK TO EDIT MASTER TITLE STYLE

SHELLSOL D60. Shell Chemicals. Data Sheet. Lemont, IL Cotton Valley, LA. Product Name

Oil & Gas. From exploration to distribution. Week 3 V19 Refining Processes (Part 1) Jean-Luc Monsavoir. W3V19 - Refining Processes1 p.

PETROLEUM LABORATORY TESTING AND OPERATIONS

Phillips 66 Pipeline LLC. Blue Pipeline Natural Gas Liquids Specifications

National Oil Corporation Libyan Petroleum Institute. Crude oil assay Sarir crude oil

Passengers Capacity USA LCV - Class 1 - LCV - Class LCV - Type 1 - LCV - Type Load Adjusted Mass (kg) MV - Class 1 - -

IC Chapter 2. Inspection, Sale, and Delivery of Petroleum Products

10 S Naphtha - Isomerized Not Diluent Minimum RVP of S Naphtha Mix Not Diluent Minimum RVP of 4.5

ISBN SANS 342:2006 Edition 4 SOUTH AFRICAN NATIONAL STANDARD Automotive diesel fuel Published by Standards South Africa 1 dr lategan roa

SOUTH AFRICAN NATIONAL STANDARD

6. Lone Star NGL Mont Belvieu LP E/P Mix November 16, Lone Star NGL Mont Belvieu LP Refinery Grade Butane November 29, 2012

Proposal for E75 reference fuel specifications for Type 6 test (emissions at low temperatures)

E/ECE/324/Rev.2/Add.119/Amend.1 E/ECE/TRANS/505/Rev.2/Add.119/Amend.1

Transcription:

Tesoro Logistics Northwest Product System GP, LLC Product Quality Control Guidelines For All Products Bound for NWPS Storage Effective 11/01/2015

PRODUCT QUALITY CONTROL Scope It is Tesoro s NWPS (Northwest Product System) intent to meet or exceed the Product Quality requirements of its customers. To be able to achieve this end, NWPS has implemented a product quality-control procedure for product shipped to NWPS terminals. Complete product specifications that all shippers will be required to meet are shown in Attachment 1. Certificate of Analysis C of A Process Tesoro NWPS shall require a C of A (Certificate of Analysis) from each Refinery and/or Refinery Laboratory at least One (1) Hour prior to the Batch entering the pipeline for all products received into NWPS. Tesoro NWPS will receive the C of A via the LGSTC (Tesoro Logistics) C of A process which requires this document for every batch shipped on the Pipeline. For Denatured Ethanol receipts into NWPS Terminals a C of A must accompany the bill of lading. 1. Shipper Nominates Barrels 2. Scheduler prepares Monthly Plan and issues Batch Number 3. Shipper prepares product for shipment and prepares C of A 4. Shipper adds Tesoro Batch Number to C of A 5. At least One (1) Hour prior to shipment, C of A sent to Control Center and Salt Lake Pump Station (SLPS) a. No C of A, SLPS calls Control Center and Control Center calls Shipper b. C of A arrives, move to Item 6 c. No C of A, Control Center notifies Shipper that they are in Violation of C of A Process and pipeline will take no responsibility if the product is not in Specification at the Receiving Terminal d. Product is tested at SLPS to verify Product is on Specification. If the Product is Off Specification, the Receiving Terminal (or Terminals) and the Shipper will be notified that the Product is Off Specification and will require an Action Plan to correct the situation 6. Control Center and SLPS compare C of A with Product Specifications 7. C of A meets Specifications 8. Control Center informs SLPS Operator Product is ready to receive and informs Receiving Terminal the Product ETA 9. Batch ships normally 10. SLPS Operator files C of A on Shared Drive Product Quality Methods Tesoro NWPS will obtain the same samples as described in the next section and will test for key properties with field analyzers to confirm the correct product was shipped and delivered. Please note that for all Ultra Low Sulfur Diesel Fuels (ULSD) we will test 100% of all product received for sulfur content. Tesoro NWPS s quality assurance program is composed of three main components, namely: Sampling Procedures Testing Procedures Action Plans 11/1/2015 Page 2 Quality Control Guidelines

Product Tank Inspection PRODUCT QUALITY CONTROL When a tank is taken out of service, inspection for cleanliness shall be undertaken and thorough cleaning carried out if indicated by inspection results. If the inspection reveals Microbial growth or buildup of sediment exceeding approximately 1/5 of the tank bottom surface, cleaning of the tank shall be undertaken. Prompt inspections shall be carried out if there are indications that fuel quality downstream of the tank is unsatisfactory (e.g. short filter life, sediment in finished product, discolored water drainage or slimy deposits per API 1640 Section 6.5). Inspection for internal mechanical condition shall be carried out in accordance with local regulatory requirements or per API 653. Sampling Procedures Retention: All terminal receipt samples will be retained for 30 days after exhaustion of the Batch unless otherwise notified. Tank Sampling Tanks will be sampled after each batch receipt or at least Weekly using API 1640 and/or EI 1595 Guidelines. Ethanol Receipts from trucks will be randomly sampled and tested. Tank Composite Samples are to be collected and tested on a bi-weekly basis. ULSD receipts are to be to isolated tanks and a composite sample is to be collected and tested before the tank is to be opened to the Truck Loading Rack. Marine Vessels (Barges) Each barge compartment will be sampled and visually checked, the samples will be composited for each shipped and product grade, prior to discharge, using API 1640 and/or EI 1595 Guidelines. Microbiological Testing Testing for Microbiological contamination shall be carried out for each product tank for all products. Samples may be collected from tank bottoms or water draws. If unable to collect water from the bottom of the tank via the tank water draw, other means of obtaining water samples (i.e. Bacon Bomb Samples) should be used. Microbiological Growth Testing shall be conducted at a minimum of every Six Months. More frequent testing should occur when appropriate samples indicate Microbiological activity or when downstream Microbiological Growth is reported. New Product Acceptance (Pipelines) Contact: Contact the Quality Assurance Department; Dennis Burchell Measurement & QC Specialist Tesoro Logistics Dennis.R.Burchell@tsocorp.com 801-606-2150 Office 713-775-1198 Mobile Product: Provide Description of product requesting to be shipped on the Pipeline System or Systems. Specifications: Provide ASTM Specifications for the product requesting to be shipped on the Pipeline System or Systems. C of A: Provide a Laboratory Certificate of Analysis to be reviewed by the Quality Assurance Department. 11/1/2015 Page 3 Quality Control Guidelines

PRODUCT QUALITY CONTROL Quantity: Provide the initial quantity requesting to be shipped on the Pipeline System or Systems. MOC: A Management Of Change document will be generated and approved by the Quality Assurance Department and Management before the new product can be received. Batch No: After MOC approval, a Batch Number will be issued by the Scheduling Department and the Control Center will determine and advise the shipper when the product can be shipped through the Pipeline System or Systems. CofA Process Shipper Control Center SL Station & Receiving Terminals Shipper Nominates barrels CofA received prior to shipment? No Contact Shipper at least two hours prior to shipment to request CofA Scheduler prepares monthly plan & issues batch numbers Control Center compares CofA with Spec Can shipper provide CofA prior to scheduled start time? Shipper prepares product for shipment and prepares CofA Shipper adds Tesoro Batch Number to CofA Control Center sends CofA to SL Operator and to Destination Terminal CofA meets specs? No No Contact Shipper to notify that product cannot go into fungible storage, and Shipper is responsible to find storage for batch Product is tested upon receipt into the pipeline and results documented Does product pass initial testing? 24hrs prior to shipment, Shipper emails CofA to Control Center Batch ships normally Control Center shares CofA with SL Operator, with Boise, Burley & Pocatello Control Center stores CofA on shared drive Receive CofA from Shipper before allowing product into fungible storage Notify destination Terminal; work with Shipper to find acceptable destination for batch Phase 11/1/2015 Page 4 Quality Control Guidelines

Testing Procedures PRODUCT QUALITY CONTROL Marine Vessels (Barges) Upon Arrival at Pasco All testing is performed on a blended compartment composite sample for each product grade, before discharging to shore tankage (see Attachment 3 for Process to Evaluate Field Testing Results): ULSD Other Diesels Gasoline Ethanol Jet Visual Visual Visual Visual Clear and Bright API Gravity API Gravity API Gravity API Gravity API Gravity Flash Flash Octane Acidity Color Sulfur RVP Water Content Flash Point (TCC) Microseparometer (MSEP) Terminals This testing is performed on each pipeline / barge batch after it is received into a tank and/or on a composite sample from the receiving line at NWPS Terminals. ULSD product tank samples and/or spot samples are to be tested for sulfur immediately after they are obtained. The following tests will be performed (see Attachment 3 for Process to Evaluate Field Testing Results): ULSD Other Diesels Gasoline Ethanol (By Truck) Jet* Visual Visual Visual Visual Clear and Bright API Gravity API Gravity API Gravity API Gravity API Gravity Flash Flash Octane Acidity Color Sulfur RVP Ethanol content (quarterly GC)* Flash Point (TCC) Conductivity Water content Distillation + Conductivity Existent Gum+* Water Reaction+* Microseparometer (MSEP) JFTOT+* Note *: Note +: Run by outside laboratory at Boise or by Pasco Terminal Laboratory. Not run on Jet batches continuing on to Spokane. FULL TESTING A Full Test will be performed when a fungible storage tank is off-spec or when it can be reasonably assumed that there are problems with product quality. This testing includes all tests shown on the ASTM specification through a non- NWPS affiliated testing lab. 11/1/2015 Page 5 Quality Control Guidelines

PRODUCT QUALITY CONTROL Test Records FULL TESTING CONFIRMATION TESTING Action Plans Situations 1. Product found, as a result of our quality assurance testing, not meeting the NWPS Specifications, in a barge compartment, or a NWPS tank. Results of full testing from each Supplier and by an outside laboratory will be filed in a binder by Shipper and by product. Records will be kept for five years after testing. The records will be kept at each terminal office. Each time a confirmation test is performed, the results will be recorded. A separate log will be kept at each station. The results will be reviewed periodically to assure that quality control measures are adequate to protect product integrity and provide the desired product oversight. Information obtained by tank testing will be shared upon request, but only with participating shippers. Additionally, any shipper may sample any tank for analysis at any time. Action plans and MOCs are in place to deal with upsets or other conditions which may occur from time to time that are out of the ordinary. These processes describe the actions that will be taken when such an event occurs. Actions In a barge compartment Pasco Operations will notify the terminal and shipper of the incident and assume the lead role to resolve the problem. In NWPS Tank - NWPS personnel will: Isolate the product and Stop Sales. Notify all affected parties of the problem. Work with responsible Party to: Correct the product or remove it from the facility. Determine the cause of the problem. Review plans to prevent future occurrences Responsible Party will be responsible for all costs associated with the incident. These costs may include, but not be limited to: Trucking Product Down-grading (redesignation) Tank Cleaning Testing Pipeline Down-time Tank Storage Barge Demurrage 11/1/2015 Page 6 Quality Control Guidelines

PRODUCT QUALITY CONTROL Oversight Program for Sub-Octane Gasoline This oversight program will have an initial phase for sub-octane entering into the Tesoro Logistics Pipe Line systems for the purpose of collecting baseline data on the octane values for each shipper. After that period there will be an on- going PQ sampling and testing program for Pipeline and NWPS tankage to verify that sub-octane will meet the minimum posted octane requirement for ethanol blended gasoline. Batches Entering Tesoro Logistics Pipeline Beginning on July 15th, 2015 Tesoro Logistics Pipe Line has agreed to draw 3 samples from each shipper for each grade of Sub-Octane product entering the pipeline at the Salt Lake Pump Station. The following tests will be run on these samples: 1) The octane value (R+M/2) will be determined using ASTM D2700 or D2699 on the as-is sample. 2) The octane value (R+M/2) will be determined after blending with ethanol to a 9:1 gasoline to ethanol ratio, 10% ethanol by volume. If all testing shows that minimum posted octane is reached for the ethanol blended samples, sampling and testing of in-coming sub-octane product for each shipper will convert to quarterly verification testing. Northwest Product System Tankage Beginning July 15th, 2015 and continuing on a monthly basis thereafter, a one gallon tank sample will be drawn for each sub-octane grade at Pasco, Boise, and Pocatello and tested as follows: 1.) The octane value (R+M/2) will be determined using ASTM D2700 or D2699 on the as-is sample. 2.) The octane value (R+M/2) will be determined after blending with ethanol to a 9:1 gasoline to ethanol ratio, 10% ethanol by volume. All test results will be blinded and made available to Position Holders upon request 11/1/2015 Page 7 Quality Control Guidelines

Tesoro Logistics Northwest Product System LLC ATTACHMENT 1 PRODUCT SPECIFICATIONS Effective November 1, 2015 Replaces July 15, 2013 Version

Tesoro Northwest Product System Product Codes Tesoro Description Octane Destination Logistics Product Code R1 Regular Unleaded Sub-Octane Gasoline 81.3 Burley/Pocatello (pre Ethanol) R4 Regular Unleaded Sub-Octane Gasoline 84.0 Boise/Pasco (pre Ethanol) R5 Regular Unleaded Gasoline 85.0 M9 Midgrade Unleaded Gasoline 89.0 P0 Premium Unleaded Sub-Octane Gasoline 90.0 Pasco (pre Ethanol) P1 Premium Unleaded Gasoline 91.0 P2 Premium Unleaded Gasoline 92.0 P8 Premium Unleaded Sub-Octane Gasoline 88.0 Boise/Burley/ Pocatello (pre Ethanol) 1D15 #1D 15 ppm sulfur motor All vehicle diesel fuel 2D15 #2D 15 ppm sulfur motor All vehicle diesel fuel LM500 #2D 500 ppm sulfur motor vehicle Diesel fuel B5-#2D 15 ppm sulfur motor vehicle diesel fuel Pasco Terminal Rack Sales Only Denatured Ethanol Boise / Pasco JP8 Military Jet Fuel JET Commercial Jet Fuel Boise / Pasco Effective 11/1/2015 Page 2 Product Specifications

Tesoro Northwest Product System Origin Product Specification Denatured Ethanol ETOH Must Meet ASTM D 4806-13a Product Property ASTM Test Method Specifications Minimum Note Appearance Bright & Clear - Appearance Visibly free of suspended or precipitated contaminants Ethanol, volume % D 5501 92.1 Methanol, volume % 0.5 Solvent-washed gum, D 381 5.0 mg/100 ml Water content, volume %, E 203 or 1.0 E 1064 Denaturant content, volume %, 1.96 4.76 Inorganic Chloride content, mass Mod. D512 40 ppm (mg/l) Method C Copper content, mg/kg Mod. D 1688, 0.1 Test Method A Acidity (as acetic acid D 1613 0.007 (56) CH3COOH), mass % (mg/l), phe D 6423 6.5 9.0 Sulfur, ppm (wt./wt). D 2622, 30 D 3120 D 5453 D 7039 Sulfate, mass ppm D 7318 D 7319 D 7328 4 Effective 11/1/2015 Page 3 Product Specifications

DIESEL ASTM D975-14a Test ASTM Specification Difference from Certificate of Analysis CONTROL CHECK (PIPELINE) Visual Appearance D4176 D2709 & D1500 API Gravity D4052 Flash Point D93a Microsep D7224 Sulfur D5453 & D7039 Conductivity D2624 & D2654 Clear & Bright Water 0.05/Sediment 0.50 30.0-42.0 (876-816) Min 126 º F Min 80 15 PPM 25 Ps/M ±0.5 (If outside tolerance email Dennis) ±5º F (If outside tolerance email Dennis) Minimum (Head and Comp, all batches) REFINERY C OF A (CERTIFICATE OF ANALYSIS, ASTM D975) (additional) Distillation 90% EP (FBP) Residue Vol% Loss Vol% D86 D86 D86 D86 539º F / 640 º F 698 º F 2.0 2.0 Min / Max Viscosity D445 1.3 / 4.1 Min / Max Ash D482 0.01 Aromatics D1319 25 volume % Copper Strip D130 #3 Corrosion at 122º F Cetane D4737a & D976-80 #40.0 Minimum Lubricity Haze Thermal Stability D6079 D4176 D6468 520 2 80 Minimum Lubricity D6079 520 SUMMER / WINTER BLENDS Cloud Point D2500 Oct 1 to Feb 28: +6 Mar 1 to Mar 31: +24 Sep 1 to Sep 30: +24 Apr 1 to Aug 31: +32 Refining/Terminal Tests (not specs) Additional Testing: Filterability Cold Filter Plugging Point Rams bottom Carbon 2Residue D4539 D6371 D524 0.35 Effective 11/1/2015 Page 4 Product Specifications

GASOLINE ASTM D4814 14b Test ASTM Specification Difference from Certificate of Analysis CONTROL CHECK (PIPELINE) Visual Appearance D4176 API Gravity D4052 Octane D2700 & D2699 RVP D5191 NOTE: Each Shipping Agent is responsible to pass random testing at random Service Stations (Minimum 85.0, 87.0, and 91.0 Octanes). Clear & Bright Water and Sediment Minimum 60.0 (739) 80.0, 84.0, & 88.0 Mar 16 to Sep 15: 9.0 Sep 16 to Sep 30: 10.0 Mar 1 to Mar 15: 11.5 Oct 1 to Oct 30: 11.5 Feb 16 to Feb 28: 13.5 Nov 1 to Nov 30: 13.5 Dec 1 to Feb 15: 15.0 ±0.5 (If outside tolerance email Dennis) Minimum NOTE: REFINERY C OF A (CERTIFICATE OF ANALYSIS, ASTM D4814) (additional) Distillation (ºF) D86 10% Max 140 Distillation (ºF) D86 50% Max 240 Distillation (ºF) D86 90% Max 365 Distillation (ºF) D86 FBP Max 437 Distillation (ºF) D86 Residue Vol % Max 2 Distillation (ºF) D86 Drivability Index (Refer to RVP Section Pg. 7) Copper Strip Corrosion Oxidation Sulfur Benzene (Wt. %) V/L Ratio Corrosion, Silver Strip Gums Oxygenates Hydrocarbon Type D130 D525 D3227, D2622, & D5453 D3606 D4814 & D5188 D7671 D381 D4815 D1319 #1b 240 80 4.9 Dec 1 to Feb 15: 105 Feb 16 to Feb 28: 116 Nov 1 to Nov 30: 116 Mar 1 to Mar 15: 122 Oct 1 to Oct 30: 122 Mar 16 to Sept 15: 129 1 5 Report Report Minimum Minimum Minimum Minimum Minimum Minimum Effective 11/1/2015 Page 5 Product Specifications

JET A ASTM D1655 Test ASTM Specification Difference from Certificate of Analysis CONTROL CHECK (PIPELINE) Visual Condition/Appearance - Visual API Gravity Flash Point Conductivity Microsep Conductivity D4860 D4176, D6045 D1298, D4052 D-39A D3948 D2624 D7224 D2624 & D2654 Clear & Bright Water White/Pale Straw 37.0-51.0 (840-775) Min 108 º F Only on Comp. Max 10 Ps/M Min 85 10 Ps/M ±0.7 (If outside tolerance email Dennis) ±5º F (If outside tolerance email Dennis) (Head and Comp all batches) RECERTIFICATION TESTS (additional) Existent Gum D381, IP540 Max 7 Mg/100ml test is negative Water reaction D1094 Max 1B interface rating Water reaction D1094 Max 2 separation rating Conductivity D2624 Less Than 10 ps/m Color Saybolt D156 Min +12 Manufacturing spec JFTOT pressure drop JFTOT deposit code D3241 D3241 Max 25 mmhg Max 3 Distillation 10% point D86, D2887 Max 400º F ±5º F Distillation end point D86, D2887 Max 572º F ±5º F Distillation residue D86, D2887 Max 1.5 volume % Distillation loss D86, D2887 Max 1.5 volume % REFINERY C OF A (CERTIFICATE OF ANALYSIS, ASTM D1655) (additional) Freeze Point D5972 (D2386) Max 40º C ±2º C Acid No. D3242 Max 0.10 Mg KOH/g Aromatics D1319 Max 25 volume % Copper Strip Corrosion D130 Max 1b at 212º F Mercaptan Sulfur D3227 Max 0.003 mass % Naphthalenes D1840 Max 3.0 volume % Net Heat of Combustion D3338, D4529, D4809 Min 18,400 btu/lb Smoke Point D1322 Min 18.0 mm Sulfur, Mercaptan D3227 Max 0.003 mass % mass% Sulfur, total mass% D4294 Max 0.1500 mass % Viscosity D445 kin. at -20º C Max 8.0 cst Refining/Terminal Tests (not specs) Filter membrane gravimetric D2276, D5452 Max 1.0 mg/gal Filter membrane color D3830 Max 2 (dry) Water content Max 15 ppm To truck rack or pipeline to airport Effective 11/1/2015 Page 6 Product Specifications

Ship Dates TESORO NORTHWEST PRODUCT SYSTEM Product Specification Gasoline RVP/Volatility Schedule Class at P/L origin Boise & Pocatello Terminals Pasco Terminal Class at Terminal Class at P/L origin Class at Terminal Jan 1 15 E-5 E-5 E 5 E 5 Jan 16 31 E-5 E-5 E 5 E 5 Feb 1 15 E-5 E-5 E 5 E 5 Feb 16 28 D-4 E-5 D 4 E-5 Mar 1 15 C-3 D-4 A-4 D-4 Mar 16 31 A-4 D-4 A 4 A 4 Apr 1 15 A-3 D-4 A 4 A 4 Apr 16 30 A-3 A-3 A 4 A 4 May 1 15 A-3 A-3 A 4 A 4 May 16 31 A-2 A-3 A-3 A 4 June 1 15 A-2 A-2 A-3 A-3 June 16 30 A-2 A-2 A 2 A 3 July 1 15 A-2 A-2 A 2 A 2 July 16 31 A-2 A-2 A 2 A 2 Aug 1 15 A-2 A-2 A 2 A 2 Aug 16 31 A-2 A-2 A 2 A 2 Sept 1 15 A-2 A-2 A 2 A 2 Sept 16 30 B-2 B-2 C-3 C 3* Oct 1 15 C-3 C-3 D-4 D 4* Oct 16 31 C-3 C-3 D-4 D 4* Nov 1 15 D-4 D-4 D 4 D-4 Nov 16 30 D-4 D-4 D 4 D-4 Dec 1 15 E-5 E-5 E 5 E 5 Dec 16 31 E-5 E-5 E 5 E 5 LGSTCmaintains the right to specify the RVP of any gasoline it receives into its systems in order to meet RVP requirements at NWPS terminals. Refers to Class designation as specified in ASTMD 4814 * Pasco Gasolines not to be delivered into Southern Idaho during these periods. Class RVP Max. psi 10% Dist. Pt. F Max Gasoline RVP / Volatility Requirements Vapor Pressure and Distillation Class Requirements 50% Dist. Pt. F Min 50% Dist. Pt. F Max 90% Dist. Pt. F Max Dist. End Pt. F Max Dist. Resid ue Vol. % DI Max * Class Vapor Lock Class T V/L F Min AA 7.8 158 170 250 374 437 2 1250 1 129 A 9.0 158 170 250 374 437 2 1250 2 122 B 10.0 149 170 245 374 437 2 1240 3 116 C 11.5 140 170 240 365 437 2 1230 4 116 D 13.5 131 170 235 365 437 2 1220 5 105 E 15.0 122 170 230 365 437 2 1200 Note *: Driveability Index is calculated as follows: Driveability Index (DI) = 1.5 T10 + 3.0 T50 + 1.0 T90 + 2.4 F (1.33 C) X Ethanol Volume % (ethanol factor is zero for products delivered without ethanol). Note: Product received at NWPS Terminals must not contain MTBE. Effective 11/1/2015 Page 7 Product Specifications

Tesoro Northwest Product System ATTACHMENT 3 PROCESS TO EVALUATE FIELD TESTING RESULTS 11/1/2015 Page 2 PROCESS TO EVALUATE FIELD TESTING RESULTS

Tesoro Northwest Product System Process To Evaluate Field Testing Results Compare Sample result to Tesoro NWPS Spec Is result within NWPS Spec + tolerance? No Retest and average both sets of results Document result and accept product Is Average within NWPS Spec + tolerance? No Notify Isolate Destination product Terminal; work and work with with Shipper to find Shipper acceptable to resolve problem destination for 11/1/2015 Page 3 PROCESS TO EVALUATE FIELD TESTING RESULTS

Tesoro Northwest Product System Field Test Tolerances For Products Max or Min Tolerance Action Gasolines RVP Max 0.3 psi See Flowchart. Octane (R+M)/2 Min 0.6 for >= 88 and 0.7 for < 88 See Flowchart. Appearance Bright & Clear If product appears hazy or contains visible particulate mater, isolate product in a tank to allow it to settle. Contact shipper and CONTROL CENTER. API - Gravity Diesel + or - 0.5 deg. API If off + or 0.5 deg. API, have sample tested for distillation. Notify Dennis. and CONTROL CENTER of possible contamination. Flash + or - 0.5 Deg. F Email Dennis if out of tolerance. Sulfur Max 15 PPM See Flowchart Visual Bright & Clear, No Dye API Gravity + or - 0.5 deg. API Email Dennis if out of tolerance. If product appears hazy or contains visible particulate mater, isolate product in a tank to allow it to settle. If product appears to have dye in it, contact shipper and CONTROL CENTER. Test product for dye. If it has dye, keep product isolated. Conductivity Max 25 ps/m No Tolerance allowed. Must meet Specification. If results do not meet Specification, isolate product, and notify shipper and CONTROL CENTER. MSEP Min 80 No Tolerance allowed. Must meet Specification. If results do not meet Specification, isolate product, and notify shipper and CONTROL CENTER. Ethanol (ASTM D4806) Water Content, Vol % Max 1.0 See Flowchart. Acidity, mass % Max 0.007 See Flowchart Visual API Gravity Jet (Run by Outside Laboratory, except at PASCO) Bright & Clear If product appears hazy or contains visible particulate mater, isolate product in a tank to allow it to settle. 0.5 deg. API See Flowchart. Condition Max 10 Ps/W If results do not meet specification, isolate product, and notify shipper and CONTROL CENTER. API Gravity + or - 0.7 deg. API Must be within test tolerance of the gravity as shipped by Shipper. Weighted Average may be used in tanks with a heel of previous product. If results don't meet this requirement, isolate product, and notify shipper and CONTROL CENTER. Color None No Tolerance allowed. Must meet specification when all tests are averaged. If results do not meet specification, isolate product, and notify shipper and CONTROL CENTER. Flash Point (TCC) + or - 0.5 Deg. If results do not meet specification, isolate product, and notify shipper and CONTROL CENTER. Distillation None No Tolerance allowed. Must meet Specification. If results do not meet Specification, isolate product, and notify shipper and CONTROL CENTER. Freeze Point None No Tolerance allowed. Must meet Specification. If results do not meet Specification, isolate product, and notify shipper and CONTROL CENTER. Conductivity Max 25 ps/m No Tolerance allowed. Must meet Specification. If results do not meet Specification, isolate product, and notify shipper and CONTROL CENTER. MSEP Min 85 No Tolerance allowed. Must meet Specification. If results do not meet Specification, isolate product, and notify shipper and CONTROL CENTER. 11/1/2015 Page 3 PROCESS TO EVALUATE FIELD TESTING RESULTS

Response Procedure Potential DRA Over Injection Over-injection susptected Control Center notifies Terminal Supervisor that a refined product batch with a potential DRA concentration higher than 15ppm has been or may be delivered to their terminal. Isolate product to the extent possible and maintain rack operation Estimate DRA ppm in suspected batch, or if in tankage, in the affected tank Capture the following samples, as appropriate:* An all-level (composite) sample and various tank level samples (as appropriate) from the affected tank(s) A composite sample from the pipeline Notify all affected customers of potential high DRA concentration levels and ETA for lab analysis No Can product be isolated in the terminal? Ship samples via fastest method to: CSPG Attn: Elvira Spesikova 1000 So. Pine Ponca City, OK 74602 Work with customer to determine course of action, whether to suspend or continue liftings. Call CSPF at (580) 767-6278 and let them know: Samples enroute Obtain an expedited analysis if necessary Provide contact name (terminal supervisor) when results are ready Lock out rack liftings of the suspected product at customer s request (if any) pending customer notification and concurrence to continue liftting CSPF communicates lab results Does DRA concentration exceed 15 ppm?* No Notify affected customers of lab results. Were customers notified of potential over-injection? No Does Customer elect to lock out product from rack? With Customer, develop plan to resolve lock out* Release isolated product for rack lifting No Perform NLI Perform LI or NLI * With appropriate support and counsel from Logistics Commodity and Measurement Process Consultant 11/1/2015 Page 4 PROCESS TO EVALUATE FIELD TESTING RESULTS