Effective May 2017 Supersedes January 2003 (S )

Similar documents
This Kit Is for Use with Types RE, RVE, WE, WVE, VWE, VWVE27, and VWVE38 Reclosers.

COOPER POWER SERIES. Pad-mounted Switchgear MN285019EN. Effective March 2017 Supersedes February 2007 (S )

COOPER POWER SERIES. Testing a motor capacitor on a voltage regulator procedure instructions. Voltage Regulators MN225064EN

COOPER POWER SERIES. KA662R tank-lifting windlass assembly and installation instructions. Recloser Mountings MN280071EN

COOPER POWER SERIES. Dielectric grease application to recloser cable instructions. Reclosers MN280070EN

Effective November 2016 Supersedes September 1998 (S )

COOPER POWER SERIES. Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions. Fusing Equipment MN132014EN

COOPER POWER SERIES. KA1169R Closing Coil Transfer-Switch Accessory Operation. Reclosers MN280069EN

Effective June 2016 New Issue

COOPER POWER SERIES. Types 4H single-phase and 6H three-phase vacuum interrupter conversion kits. Reclosers MN280014EN

COOPER POWER SERIES. High-voltage primary bushings installation instructions. OEM Equipment MN800008EN

COOPER POWER SERIES. QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit A26 installation instructions

COOPER POWER SERIES. KA146W5 single pole-mounting hanger; KA146W2 tank lifting windlass assembly and installation instructions. Reclosers MN280039EN

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

COOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

Effective May 2017 Supersedes December 2004 (S )

COOPER POWER SERIES. Edison Modular Fuse (EMF) Installation Instructions. Fusing Equipment MN132031EN

COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. S.T.A.R. Hot line voltage indicator installation instructions. Fault Indicators MN320011EN. Indicator boot.

COOPER POWER SERIES. S.T.A.R. type LVR faulted circuit indicator installation instructions. Fault Indicators MN320005EN

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

Effective March 2015 Supersedes S August 2012

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

High-voltage primary bushings installation instructions

COOPER POWER SERIES. ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions. Fusing Equipment MN132017EN

COOPER POWER SERIES. Mercury switch to microswitch retrofit kit KA349WE installation instructions. Reclosers MN280022EN

COOPER POWER SERIES. RTE EL-BAY-O-NET FUSE Re-Fusing Instructions. Fusing Equipment MN132024EN

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

COOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN

Type NR oil switch installation and operation instructions

COOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S )

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN

Effective November 2016 Supersedes February 2012 (S )

COOPER POWER SERIES. KA716L7001 adjustable control valve kit for Types L, E, 4E, V4E, and V4L reclosers installation and adjustment instructions

COOPER POWER SERIES. Electronic control battery testing, charging, and replacement instructions. Reclosers MN280074EN

COOPER POWER SERIES. Quick Connect Assembly (QCA) Retrofit Kit, General Electric Installation Instructions. Voltage Regulators MN225075EN

S Voltage Regulators GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage. Standards

COOPER POWER SERIES. Surge arrester interchangeable fuse cutout combination installation instructions. Surge Arresters MN235004EN

COOPER POWER SERIES. Types D and DV recloser installation instructions. Reclosers MN280030EN

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

COOPER POWER SERIES. Types VWE, VWVE27, VWVE38X, WE, WVE27, and WVE38X; threephase electronically controlled; installation and operation instructions

S Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage.

S Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage

COOPER POWER SERIES. Fused loadbreak elbow connector installation instructions. Loadbreak Apparatus Connectors MN650014EN

COOPER POWER SERIES. Manually-Operated M-Force Switch Installation and Operation Instructions. Switches and Disconnects MN008003EN

S Voltage Regulators GENERAL. PRODUCT INFORMATION Introduction. Contents. Acceptance and Initial Inspection. Handling and Storage.

KFE10010-E. Reclosers. Contents. Type KFVE and KFVME (27kV) Bus Bar Kit KRK710-1 Installation Instructions. Cooper Power Systems

COOPER POWER SERIES. Instructions for oil-filled, single-phase overhead distribution transformers. Distribution Transformers MN201003EN

S Fault Indicators. S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions. Contents INSTALLATION PROCEDURES

COOPER POWER SERIES. Metal-enclosed capacitor banks installation instructions. Power Capacitors MN230010EN

COOPER POWER SERIES. Metal-enclosed, pad-mounted capacitor banks installation instructions. Power Capacitors MN230009EN

3-way multi-family drawout cable interlock kit - type 32 - RF

Figure 1. Kearney Type HX cutout.

Installation Instructions for Interlocking Trip Indicator with Remote Reset for Magnum Low Voltage Circuit Breakers

Factory Authorized Mechanism Enhancement (FAME)

Installation and removal instructions for Series NRX RF fixed breaker three-way Type 32 cable interlock kit

Two-way cable interlock kit for Magnum fixed circuit breakers

Reprogramming guide. Power Defense ICCB. Instructional Leaflet IL EN WARNING WARNING. Instructions apply to:

Removal/installation instructions for Series NRX (IZMX) drawout levering (racking) mechanism

Two-way cable interlock kit for Magnum drawout circuit breakers

CCP2-FLR1-21_ flange-rod operating mechanism

Effective May 2017 Supersedes October 2002 (S )

Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version

COOPER POWER SERIES. Externally fused block banks installation instructions. Capacitors MN230004EN

COOPER POWER SERIES. VFI tester operating instructions. Underground Distribution Switchgear MN285001EN

Installation Instructions for R-Frame G-Series (RG) 310+ Trip Unit

COOPER POWER SERIES. Type VSA12, VSA12B, VSA16, VSA20, and VSA20A operation and installation instructions. Reclosers MN280063EN

ELB ELB

Installation Instructions For Motor Control Center (MCC) Units

O & M Manual for the EATON Generator Ready Loadcenter

TVSS Installation for RLCM/CHGENLC, RLCU, and CHGEN ATSs

Instruction Booklet IB E. Contents

CM52 Network Protector with Arc Flash Reduction Module

Installation Instructions for KPS and KPH Circuit Breakers and Molded Case Switches

www. ElectricalPartManuals. com Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers

Effective October 2016 Supersedes January 2014 (S )

Digitrip Retrofit System for General Electric AKR/AKRU-6D/7D-30S Series Breakers

Type DTU De-energized Tap Changer Application, Installation & Selection Guide. IL A Instruction Leaflet Page 1 September, 2003

Flush Mount AIN ALPHA Meters. General. Hardware Kit

Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers

S Voltage Regulators. Contents. QD3 Quik-Drive Voltage Regulator Tap-Changer Manual. Figure 1B. QD3 Tap-changer. Figure 1A. QD3 Tap-changer.

COOPER POWER SERIES. Type VSO maintenance instructions. Reclosers MN280066EN. Effective October 2017 Supersedes August 1986 (S )

Advanced Test Equipment Rentals ATEC (2832)

Hubbell has a policy of continuous product improvement. Please visit hubbellpowersystems.com to confirm current design specifications.

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

Digitrip Retrofit System for Allis-Chalmers LA-600 F Electrically Operated Fused Breakers

II DISTRIBUTION & SUBSTATION TYPE C

Digitrip Retrofit System for BBC LKD 8 Breakers

Effective June 2017 Supersedes June 1984 (S ) Applicable to serial numbers and above.

Type 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear

S Contents. Applicable to Serial Numbers A101 and above or beginning with CP57.

Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker

www. ElectricalPartManuals. com Digitrip Retrofit System for BBC LKD 8 Breakers IL 33-LK8-2

COOPER POWER SERIES. Type VSA12, VSA16 and VSA20/800 maintenance instructions. Reclosers MN280064EN

Instructions for using Functional Test Kit on Digitrip 520 and 1150 family of Power Circuit Breaker Trip Units and Series G and FD MCCB Trip Units

Transcription:

Reclosers MN280068EN Effective May 2017 Supersedes January 2003 (S280-80-13) CT field modification kit KA906R1 installation and testing instructions COOPER POWER This kit is for use with types RE, RVE, WE, WVE, VWE, VWVE27, and VWVE38 reclosers. Not for use with type RE reclosers serial number 101 through 399 or type WE reclosers serial number 101 through 299. SERIES Bushing assembly Hex nut Lead Flat washer Lockwasher Hex nut Bushing clamps 3/8-16 x 2 1/4 hex head capscrew Split clamping ring Lower bushing gasket

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation s ( Eaton ) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or other-wise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice. INSTALLATION AND TESTING INSTRUCTIONS MN280068EN May 2017 i

Contents DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY... I SAFETY FOR LIFE... III SAFETY INFORMATION... III Safety instructions... iii PRODUCT INFORMATION.... 1 Introduction...1 Read this manual first...1 Additional information...1 Acceptance and initial inspection...1 Handling and storage...1 Quality standards................................................................................1 Description...1 INSTALLATION PROCEDURE.... 2 TESTING CURRENT TRANSFORMERS... 4 Continuity check...4 Ratio test for sensing CT s...4 Polarity test for sensing CT s...5 CT insulation withstand test...5 SURGE SUPPRESSORS (LOW-VOLTAGE CLOSING COILS ONLY)... 5 ii INSTALLATION AND TESTING INSTRUCTIONS MN280068EN May 2017

! SAFETY FOR LIFE Safety for life Eaton meets or exceeds all applicable industry standards relating to product safety in its Cooper Power series products. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing, and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high voltage lines and equipment, and support our Safety For Life mission.! SAFETY FOR LIFE Safety information The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians who are familiar with this equipment should install, operate, and service it. A competent technician has these qualifications: Is thoroughly familiar with these instructions. Is trained in industry-accepted high and low-voltage safe operating practices and procedures. Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. Is trained in the care and use of protective equipment such as arc flash clothing, safety glasses, face shield, hard hat, rubber gloves, clampstick, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Hazard Statement Definitions This manual may contain four types of hazard statements: DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only. Safety instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. DANGER Hazardous voltage. Contact with hazardous voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around high- and low-voltage lines and equipment. G103.3 WARNING Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. G101.0 WARNING This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury and equipment damage. G102.1 WARNING Power distribution and transmission equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install or maintain power distribution and transmission equipment can result in death, severe personal injury, and equipment damage. G122.3 INSTALLATION AND TESTING INSTRUCTIONS MN280068EN May 2017 iii

Table 1. Serial number break for reclosers with type a sensing CTS Recloser Below serial number RXE 5831 RVE 5894 WE 11199 WVE 3695 VWE 7199 VWVE27 7208 VWVE38 1204 All VSA reclosers are equipped with Type A Sensing CTs. All VSML reclosers are equipped with Type A Sensing CTs. All VSA12, VSA12B, VSA16, VSA20, VSA20A, and VSA20B reclosers are equipped with Type B Sensing CTs. All VWVE38X and VWE38X reclosers are equipped with Type B Sensing CTs. Table 2. CT field modification kit contents Item no. QTY. Description Part number 1 1 Label KP2560R 2 6 Bushing gasket KA1193R 3 2 Varistor assembly * KA1240R 4 3 1000:1 current transformer KA86RE3 5 1 3 wire assembly * KA260ME268 6 1 4 wire assembly * KA260ME269 7 1 7 wire assembly * KA260ME270 8 1 Terminal strip * KP2101A3 9 1 Head gasket KP2103A8 10 6 Spacer KP3009A212 11 2 Rd. hd. screw, #6-32 x 3/4 * K721515106075A 12 2 Elastic stop nut, #6-32 * KP2020A6 13 6 Shrink tube KA2137-13 14 6 Rd. head screw 1/4-20 x 2 K721515125200A 15 1 Label KP1373ME 16 2 Terminal * KP2010A38 * Items used when kit is installed on a recloser that is equipped with the low-voltage closing accessory. Product information Introduction Service Information MN280068EN provides installation and testing instructions for the CT Field Modification Kit. Read this manual first Read and understand the contents of this manual and follow all locally approved procedures and safety practices before installing or operating this equipment. Refer to the applicable maintenance manual for additional service and repair procedures. S280-40-3, Type RE, Three-Phase Maintenance Instructions S280-40-4, Type WE, Three-Phase Maintenance Instructions S280-40-5, Types RVE and WVE, Three-Phase Maintenance Instructions MN280061EN, Types VWE, VWVE27, and VWVE38X Maintenance Instructions Additional information These instructions cannot cover all details or variations in the equipment, procedures, or process described, nor provide directions for meeting every possible contingency during installation, operation, or maintenance. For additional information, contact your Eaton representative. Acceptance and initial inspection This product is completely assembled, tested, and inspected at the factory. It is in good condition when accepted by the carrier for shipment. Upon receipt, inspect the carton for signs of damage. Unpack the control and inspect it thoroughly for damage incurred during shipment. If damage is discovered, file a claim with the carr ier immediately. Handling and storage Be careful during handling and storage of this equipment to minimize the possibility of damage. Quality standards ISO 9001-Certified Quality Management System. Description The Type B sensing current transformers supplied in this kit are used to update Type RE or WE family reclosers for use with an Eaton Cooper Power series microprocessor electronic control. Reclosers manufactured prior to June 1989 are equipped with Type A bushing current transformers (CT s). These reclosers were designed for use with Form 2, Form 3, and Form 3A controls. Eaton Cooper Power series microprocessor-based controls, Form 4A, Form 4C, Form 5, and Form 6, have the ability to generate event records and/or oscillographs during a fault. These controls should be used with Type B sensing CT s. Type B sensing CT s may also be used with Form 2, Form 3, and Form 3A controls. The terminal board and varistors, included in this kit, are only used on reclosers equipped with the low-voltage closing accessory. The varistors provide additional surge protection for units equipped with low-voltage closing. 1 INSTALLATION AND TESTING INSTRUCTIONS MN280068EN May 2017

Installation procedure IMPORTANT Type R and W family reclosers interfaced with Type 3/3A controls featuring Low-Current Ground Fault Trip capability do not have 100 ohm resistors that normally shunt the recloser sensing current transformers. Consequently, high voltage from the current transformers can be present at the recloser/ control interface when the recloser is under load. Do not disconnect control from recloser unless recloser is de-energized or, if equipped with in-line Low-Current Ground Fault Tripping Accessory KA1009ME/ KA1009ME2 (located between control and recloser), placing Low-Current Ground Fault Tripping Accessory KA1009ME/ KA1009ME2 into the NORMAL position and disconnecting the interface cable at the control. If shunt resistors are not present, contact your Eaton representative for additional information before proceeding with the installation of this kit. WARNING Hazardous voltage. De-energize the switchgear before installing this kit. Follow all locally approved safety practices and procedures when working around high voltage lines and equipment. Failure to comply can result in contact with high voltage, which will cause death or severe personal injury. T232.3 WARNING Falling equipment. Use the lifting lugs provided and follow all locally approved safety practices when lifting and mounting the equipment. Lift the unit smoothly and do not allow the unit to shift. Improper lifting can result in severe personal injury, death, and/or equipment damage. G106.3 CAUTION Equipment damage. Refer to the specific switchgear unit maintenance manual for tanking/untanking procedures and related instructions. Failure to follow these instructions could result in equipment damage or personal injury. T238.0 IMPORTANT Remove the recloser from service and transport it to a clean suitably equipped service center prior to installing the kit. Refer to the appropriate service information instruction manual for the step-by-step procedures to remove the recloser from service. Refer to the Product Information section of this manual for specific service manual information. 1. Bypass, trip, de-energize, and remove the recloser from service using all locally approved safety practices. 2. Untank recloser and position head assembly in a suitable service stand as described in recloser maintenance manual. Refer to the Read This Manual First section of this manual. 3. Remove lower bushing nuts and leads. Bushing assembly Lead Hex nut Bushing clamps Figure 1. Bushing removal Hex nut Flat washer Lockwasher 3/8-16 x 2 1/4 hex head capscrew Split clamping ring Lower bushing gasket 4. If bushings are equipped with corona shields, loosen clamps and slide corona shields from bushings, see Figure 1. 5. Remove bushing clamps and carefully remove bushings. Discard lower bushing gaskets. 6. Remove original head gasket and discard. Install new gasket, using a permanent, flexible adhesive (such as Pliobond 20 Industrial Adhesive) to retain. Current transformer CT lead Shunt resistor Figure 2. Cutting CT leads INSTALLATION AND TESTING INSTRUCTIONS MN280068EN May 2017 2

CT support Current transformer Spacer Shunt resistor Figure 3. CT removal 7. Cut the leads from the original current transformers approximately 4 from the shunt resistor. See Figure 2. 8. Remove screws and hardware that secure CT supports; note the routing of the CT leads as the transformers are being removed. Discard original current transformers, and spacers. Save shunt resistor and mounting screw for reuse. See Figure 3. 9. Place new CT s into position, with the polarity mark toward the head casting, as shown in Figure 4. Position the leads so they are oriented similarly to the leads of the CT removed. 10. Strip the stub ends of the shunt resistor leads. 11. Install the new spacers and CT support. Secure with new 1/4-20 x 2 machine screws and the previously removed washers. Re-attach the shunt resistor assembly. See Figure 3. 12. Cut the CT leads to leave a stub approximately 3 long. Strip the ends, slide the shrink tube over the wire, splice, and solder the leads together. Remove any sharp edges or burrs. See Figure 5. Current transformer Polarity mark CT support Figure 4. CT installation Shrink tubing Figure 6. Securing shrink tubing Figure 5. Splicing CT leads 13. Slide shrink tubing over splice and apply heat to secure, see Figure 6. 14. Tuck wires toward head casting. 15. Check the split aluminum clamping rings on each bushing. Clamping rings can be reused if in good condition, replace if damaged. NNote: The clamping rings cushion and distribute the pressure between the ceramic and the clamps. DO NOT OMIT. 3 INSTALLATION AND TESTING INSTRUCTIONS MN280068EN May 2017

16. Install bushing assemblies with the new lower bushing gaskets provided. Position each bushing with the stud end of the terminal pointing outward. NNote: If corona shields were installed on the bushings, slide them onto the bushings as they are being installed. 17. Position clamping rings with the split centered between two clamping bolts. 18. Reassemble the bushing clamps to head casting. Tighten the bolts evenly, a little at a time, to a torque of 10-15 ft-lbs. NNote: The clamping forces must be applied gradually and equally in rotation to each bolt, to provide evenly distributed gasket sealing pressure. 19. Reconnect leads to each bushing rod. 20. If the bushings are equipped with corona shields, slide shield assemblies into position and secure clamps. 21. Install labels on sleet hood. See Figure 7. NOTICE RECLOSER IS EQUIPPED WITH TYPE B SENSING CT'S. RECLOSER DOES NOT HAVE A BATTERY CHARGER. A B C 2 1 RATIO-TEST CIRCUIT A K G H J L Control cable receptacle socket Current sensing transformers Recloser contacts in closed position Battery charger CT (accessory) A B C Test leads connecting phases in series K G H Test leads connecting J bushings at secondaries in parallel L RATIO-TEST CIRCUIT B Figure 7. Type B sensing CT label Testing current transformers The current sensing transformers are mounted on the source side bushings underneath the head casting. The battery charger CT power source (if applicable) is mounted on the load side center bushing. Refer to Figure 8 for these tests. Continuity check 1. Connect an ohmmeter, in turn, to pin sockets K and G, K and H, and K and J to check the continuity of the three current sensing transformers. The meter should read approximately 3 ohms, the DC resistance of each winding. 2. Connect the ohmmeter to pin sockets K and L to check the continuity of the battery charger CT winding, if used. The meter should read approximately 1000 ohms. A zero ohms reading indicates the 0.2 mfd capacitor may be short circuited. Readings deviating more than ± 20% from 1000 ohms indicates a damaged resistor or transformer winding. Figure 8. Testing current transformers Ratio test for sensing CT s CAUTION Hazardous voltage. Open CT secondaries can generate high voltages. Contact with CT pins of the disconnected cable can cause electric shock and may result in personal injury. Open recloser contacts and open disconnect switches before disconnecting control cable. T204.3 1. Connect all three phases of the recloser in series as shown in Figure 8 and close the recloser contacts with the manual closing tool. 2. Connect a 100 ampere ac test current to test points 1 and 2. 3. Energize the 100 ampere test source. 4. Using a 0-500 milliammeter check the current output across socket pins K-G, K-H, and K-J (Figure 8, Ratio-Test Circuit A). The output of each CT should measure 100 ma ±10%. INSTALLATION AND TESTING INSTRUCTIONS MN280068EN May 2017 4

NNote: Be sure to allow for the tolerances of meter being used. The resistance of certain type of meters is not negligible. Use as high a scale (lower resistance) as is accurately readable. 5. A 100 ma reading verifies the 1000:1 ratio of the sensing CT s. If the 100 ma is not attained, replace the CT. 6. De-energize the test source. 3. Remove power leads from each side of the closing coil contactor assembly; cut leads to provide sufficient length for attachment to the terminal board. Strip ends of leads and install terminals provided. 4. Connect varistors and leads as shown in Figure 10. 1-3/4 3/16 Polarity test for sensing CT s 1. With the phases still connected in series from the previous test, connect the secondaries of the CT s in parallel by connecting pin socket G to H to J and measure the output between pin sockets K and J as shown in Figure 8 (Ratio-Test Circuit B). 2. Energize the 100 ampere ac test source. A. All three transformers should have the same polarity; the output should measure 300 ma. B. If one transformer has its polarity opposite of the remaining two the output will measure 100 ma. Check to determine which CT is reversed and then correct by rotating that CT 180. 3. De-energize the test source and remove the jumper wires from the receptacle. CT insulation withstand test To check the integrity of the CT wiring, ground the recloser head and apply 500 Vac to receptacle pin K for one minute. Surge suppressors (low-voltage closing coils only) The terminal block and surge suppressors included in this kit are installed on the closing coil contactor of reclosers equipped with the low-voltage closing accessory. To install the suppressor, refer to Figures 9 and 10. 1. Drill two 5/32 holes as shown in Figure 9. 2. Install terminal block onto closing coil contactor; secure with #6 screws and locknuts provided. Top right corner of contactor Drill two holes, 5/32 Figure 9. Drilling for terminal block Attach closing coil power leads to the two outside terminals 7 wire assembly 1-3/8 27/64 3 wire assembly attach to ground Terminal board Varistors 4 wire assembly routed through and under contactor Figure 10. Wiring surge suppression varistors 5 INSTALLATION AND TESTING INSTRUCTIONS MN280068EN May 2017

This page intentionally left blank. INSTALLATION AND TESTING INSTRUCTIONS MN280068EN May 2017 6

This page intentionally left blank. 7 INSTALLATION AND TESTING INSTRUCTIONS MN280068EN May 2017

! SAFETY FOR LIFE Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton s Power Systems Division 2300 Badger Drive Waukesha, WI 53188 United States Eaton.com/cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No. MN280068EN May 2017 KA2048-361 Rev. 04 Eaton is a registered trademark. All trademarks are property of their respective owners. For Eaton s Cooper Power series product information call 1-877-277-4636 or visit: www.eaton.com/cooperpowerseries.