Installation and Operation Manual Back-UPS BX1100CI-CN

Similar documents
Installation and Operation Manual Back-UPS BX800CI-ZA/BX1100CI-ZA

Installation and Operation Back-UPS BX550CI-CN

User Manual Back-UPS BX650CI-MS 230 Vac with AVR

Installation and Operation Manual Back-UPS BR800/1100CI-IN

Installation and Operation Manual Back-UPS BR1000-CH

User Manual Back-UPS BC500-RS, BC650-RS 650 VA 230 V

Back-UPS 650 VA 230 V with AVR (BX650CI-ZA)

User Manual Easy UPS BV Series 500VA, 650VA, 800VA, 1000VA Safety and General Information

Installation and Operation Smart-UPS SUA500PDR

Back-UPS CS Back-UPS CS 350

Back-UPS ES APC Back-UPS ES, 6 outlet 350VA, 120V, without auto shutdown software

3000VA 120/208/230VAC

User Manual. NetGuard IMPORTANT. PSD 650/1200/1600 Line Interactive UPS Uninterruptible Power Supply System. UPS Monitoring Software

User Manual. English. APC Smart-UPS. 750/1000/1500 VA 100/120/230 Vac 2U Rack-Mount Uninterruptible Power Supply

User Manual Back-UPS BE425M/425M-LM, BN450M/450M-CA

Installation Guide Smart-UPS On-Line SRT1000/1500 UXI-NCLI, SRT1000/1500 UXI-LI, Tower/Rack-Mount

Power Inverter. User s Manual. Diamond Series CPD1200EILCD

Operation Manual. Smart-UPS C. Uninterruptible Power Supply 1000/1500/2000/3000 VA. 120/230 Vac. Tower. su0813a

User Manual. Smart-UPS. Uninterruptible Power Supply 750/1000 VA. 100/120/230 Vac. Rack Mount 1U

800VA/ 1000VA/ 1200VA/ 1500VA 2200VA/ 3000VA USER S MANUAL

User Manual. Smart-UPS. Uninterruptible Power Supply. 1000/1500 VA 100/120/230 Vac. 750XL/1000XL VA 120/230 Vac. Tower

Operation Manual. English. APC Smart-UPS VA 3U Rack and Stack Uninterruptible Power Supply 230 Vac , Revision 1 12/00

Installation Guide Smart-UPS On-Line SRT1000/SRT1500 XLA Tower/Rack-Mount

Solar Hybrid Power Generating System CPS1200EOH12SC CPS2200EOH24SC CPS3000EOH24SC. User s Manual K01-C

Uninterruptible Power System

Installation and Operation

SUA1000I-IN / SUA1500I-IN 230 VAC

User s Manual. English. APC Smart-UPS RT. 3000/5000 VA VAC 3U Tower/Rack Mount Uninterruptible Power Supply

Installation Guide Smart-UPS X 2000/2200/3000 XL Tower/Rack-Mount 4U

APC Smart-UPS RT UX. User s Manual. Models SURT1000UXI and SURT2000UXI 220/230/240 Tower/Rack Mount Uninterruptible Power Supply.

APC Smart-UPS 2200/3000 VA 230 VAC. Uninterruptible Power Supply

UTILITY INPUT MAINS OUTLET

Allen-Bradley. User Manual for 3000/5000 VA UPS. Tower/Rack-Mount 3U Uninterruptible Power Supply

Installation and Operation

Broadband PowerShield. CP27U Models. User Manual

Operation Manual. Smart-UPS. Uninterruptible Power Supply. Rack-Mount 1U. 1200/1500 VA 100/120/230 Vac

Allen-Bradley. User Manual for 8000/10000 VA UPS. Tower/Rack-Mount 6U Uninterruptible Power Supply

Installation Guide. Marine Filter SURT023M SURT024M

User Manual. English. APC Smart-UPS. 7500/10000 VA VAC 6U Tower/Rack Mount Uninterruptible Power Supply B 02/2004

BRAVER UPS. (Uninterruptible Power System) User s Manual

USER MANUAL. Blazer Vista 1000/1400/2000. Uninterruptible Power System

Operation Manual. Smart-UPS. Uninterruptible Power Supply. 750/1000/1500/2200/3000 VA Tower 100/120/230 Vac. 500 VA Tower 100 Vac

Installation and Operation

APC Smart-UPS RT UXI/UXICH

MM-AVR UPS Series User s Manual

Installation Guide Smart-UPS 1200/1500 VA 100/120/230 Vac Rack-Mount 1U

Uninterruptible Power System

POWERSTAR INC. Operations / Maintenance Manual Model: PS VA Tower UPS

Broadband PowerShield. External Battery Pack 20 Ah 12 V Battery. User Manual

Smart-UPS RT External Battery Pack Stack/Rack-Mount 6U

User Manual. Digital Energy Uninterruptible Power Supply ML Series UPS VA. GE Digital Energy Power Quality. GE imagination at work

User Manual Digital Energy Uninterruptible Power Supply ML Series UPS VA GE Digital Energy Power Quality

User Manual Easy UPS On-Line SRV Series 1000VA, 2000VA, 3000VA

CONTENTS 1. INTRODUCTION SAFTY INSTRUCTION CABLE CONNECTION SYSTEM DESCRIPTION INVERTER OPERATION...

Installation and Operation Manual Smart-UPS Tower 220/230/240 Vac SRC1000ICCIND; SRC1000UXIND

User Manual Easy UPS On-Line SRVS Series Rack-Mount 1000VA, 2000VA, 3000VA

Safety and General Information

Start UP Guide. Symmetra LX Tower Rack-Mount. UPS Models 200 V, 4-8 kva 208/240 V, 4-8 kva 220/230/240 V, 4-8 kva

USER S MANUAL CONTENTS. Uninterruptible Power Supply 1. INTRODUCTION SAFTY INSTRUCTION SYSTEM DESCRIPTION... 4

Uninterruptible Power System

BroadBand PowerShield. 20 AHr Battery. User Manual

Smart-UPS RC External Battery Pack Tower/Rack-Mount 4U

w w w.apc.com Home Appliance & Lighting UPS HI800SQ Installation Guide and User s Manual

Operation Manual. Smart-UPS Uninterruptible Power Supply. 1000/1500/2200/3000 VA 220 Vac. Rack-Mount 2U

Operation Manual. Smart-UPS Uninterruptible Power Supply. Rack-Mount 2U. 750/1000/1500 VA 120/230 Vac VA 120 Vac. 100/120/208/230 Vac

02/15/01. Powerware User s Guide VA.

On Line UPS. LUC 1000E / LUC 2000E / LUC 3000E User Manual

USER MANUAL. PowerMust 1400/2000 LCD. Uninterruptible Power System

POWER TROLLEY 8 INSTRUCTION MANUAL POWER TROLLEY 8. Model: SINE Instruction Manual for: Self-Contained Sinewave Mobile Power Backup System

Uninterruptible Power Supply

Uninterruptible Power System

LINE INTERACTIVE LONG BACKUP TIME UPS EN-1000 / EN-2000 USER S MANUAL

Installation and Operation

Operation Manual. Smart-UPS Uninterruptible Power Supply. 750/1000/1500/2200/3000 VA 100/120/230 Vac. 500 VA 100 Vac. Tower

Power Inverter. Model BI800T and BI800F. w w w.apc.com. Installation Guide and User s Manual

Electrical Installation

Installation and Operation

CONTENTS 1. INTRODUCTION SAFTY INSTRUCTION CABLE CONNECTION SYSTEM DESCRIPTION OPERATION... 9

Installation and Operation

User Manual V1.1 OptiFlex 1100 / OptiFlex 2000

Match 19" GE Digital Energy. Uninterruptible Power Supply VA. Technology for the Digital World. Match 19" UPS.

POWERWARE User s Guide VA.

400 Watt Backup Power System Owner s Manual

General Precautions. Personnel Precautions

PR1000ELCD / PR1500ELCD User s Manual

Operation Manual. Smart-UPS. Uninterruptible Power Supply VA Short-depth Rack-Mount with Lithium-ion batteries. 120 Vac

USER MANUAL. IPS home inverters with UPS function. IPS home inverter manual

USER MANUAL. Power GUARD UPS. Uninterruptible Power System

Operation Manual. Smart-UPS. Uninterruptible Power Supply. 750/1000/1500 VA Short-depth Rack-Mount with Lithium-ion batteries.

USER MANUAL MPS 1-5KW SERIES

User Manual Smart-UPS On-Line SRC1KI-IN, SRC1KUXI

Uninterruptible Power System. Line Interactive Network Protection Pure Sine Wave Output UPS. Rack Mount Models 1000VA/ 1500VA/ 2000VA/ 3000VA

Sola/Hevi-Duty S3K Series Mini-Tower UPS

Installation and Operation

CP900EPFCLCD User s Manual K

Smart-UPS RC External Battery Pack Tower/Rack-Mount 4U

Installation and Operations Manual

USER S MANUAL ENDURE 500VA ENDURE 750VA ENDURE 1000VA ENDURE 2000VA

Liebert PSA VA. Installer/User Guide

Transcription:

Installation and Operation Manual Back-UPS BX1100CI-CN Safety and General Information This unit is intended for indoor use only. Do not operate this unit in direct sunlight, in contact with fluids, or where there is excessive dust or humidity. Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation. The battery typically lasts for two to five years. Environmental factors impact battery life. Elevated ambient temperatures, poor quality AC power, and frequent short duration discharges will shorten battery life. Connect the Back-UPS power cable directly into a wall outlet. Do not use surge protectors or extension cords. Connect the Battery Connect the battery connector prior to using the UPS. Pull the battery connector handle down. Then push the connector into the UPS. The battery charges fully during the first 10 hours while the Back-UPS is operating on AC power. Do not expect full runtime capability during the initial charge period. There are no serviceable parts in the Back-UPS. Do not attempt to open or repair the Back-UPS as this will void the warranty. The battery in this unit is not replaceable. Contact APC through the Web site www.apc.com, for customer support.

Installation Connect the Equipment Battery Connector Connect the battery, refer to Connect the Battery on page 1. Battery Backup + Surge Protection outlets AC Power Cable Circuit breaker These outlets provide battery backup power to connected equipment for a limited period of time during power outages and voltage fluctuations. The Battery Backup + Surge Protection outlets provide battery power to connected equipment only when the Back- UPS is turned on. Connect critical equipment such as a computer, computer monitor, modem or other data sensitive devices to these outlets. Do not connect aquarium equipment, laser printers, paper shredders, sump pumps, or fans to these outlets as the modified sine wave output of the Back-UPS may cause these devices to experience a decrease in performance. Do not connect surge protectors or extension cords to these outlets. Connect the Back-UPS to AC power. Use to reset the system after an overload condition has occurred causing the circuit breaker to trip. Battery Backup + Surge Protection bu043c bu224b Operation Turn On the Back-UPS Press the POWER ON/OFF button located on the front of the Back-UPS. The On Line LED will illuminate green and a single short beep will be audible to indicate that the Back-UPS is providing protection for connected equipment. 2 Back-UPS BX1100CI-CN Installation and Operation

Status Indicators Status LED Indicator Audible Indicator On Power On The Back-UPS is supplying AC power to connected equipment. On Battery The Back-UPS is supplying battery power to battery backup outlets. Low Battery warning The Back-UPS is supplying battery power to the battery backup outlets and the battery is near a total discharge state. Replace Battery The battery is disconnected. The battery needs to be charged or replaced. Overload Shutdown While operating on battery power an overload condition has occurred in one or more of the battery backup outlets. Sleep Mode While operating on battery power the battery is completely discharged. The Back-UPS will awaken once AC power is restored. Overload Alarm The equipment connected to the Back-UPS is drawing more power than the voltage rating allows. The On Line LED illuminates green. The On Line LED illuminates green. The LED is not illuminated during the beeps. The On Line LED flashes green. The Battery LED flashes red. Battery and On Line LEDs flash alternately. None Back-UPS beeps 4 times every 30 seconds. The Back-UPS emits rapid beeping. (once every second) Constant tone N/A Audible Indicator Terminates The beeping stops when AC power is restored or the Back-UPS is turned off. The beeping stops when AC power is restored or the Back-UPS is turned off. The Back-UPS is turned off. None Constant tone The Back-UPS is turned off. None The Battery LED illuminates red. The Back-UPS beeps once every four seconds. Constant tone AC power is restored AC power is not restored within 32 seconds The Back-UPS is turned off Alarm stops when nonessential equipment is disconnected from the Battery Backup outlets. Back-UPS BX1100CI-CN Installation and Operation 3

Transfer Voltage and Sensitivity Settings Automatic Voltage Regulation Automatic Voltage Regulation boosts the AC voltage when it drops below safe levels. This allows the equipment that is connected to the Back-UPS to operate during low voltage conditions. Automatic Voltage Regulation will also regulate high voltage conditions down to a safe level. The Back-UPS will switch to battery power if the AC input voltage level becomes too low or too high for the Automatic Voltage Regulation feature to compensate, or if the AC power is experiencing voltage fluctuations. No-load Shutdown The UPS will shut down to conserve energy if while operating on battery power the UPS detects that connected equipment is using less than 15 W of energy for more than 15 minutes. No-load shutdown can be enabled or disabled through Program mode described below. Voltage Sensitivity Adjustment If the Back-UPS switches to battery power too frequently or too infrequently, adjust the transfer voltage and sensitivity settings: 1. Verify that the Back-UPS battery is connected. Connect the Back-UPS to a wall outlet. The Back-UPS should be turned off. 2. Press and hold the POWER ON/OFF button for 10 seconds. The LEDs will illuminate green and red alternately, to indicate that the Back-UPS is in Program mode. 3. The LEDs will flash either green, red or green and red alternately to indicate the current sensitivity level. The Back-UPS will beep to indicate that No-load Shutdown is enabled. Refer to the table for an explanation of the transfer voltage sensitivity levels. 4. To select LOW sensitivity, press the ON/OFF button until the On Line LED flashes green. 5. To select MEDIUM sensitivity, press the ON/OFF button until the Battery LED flashes red. 6. To select HIGH sensitivity, press the ON/OFF button until the On Line and Battery LEDs flash green and red alternately. 7. To exit Program mode wait for five seconds and both LEDs will extinguish. Program mode is no longer active. LED Flashes Audible Indicator Voltage Sensitivity Setting Input Voltage Range No-load Shutdown Recommended Use Green None Low 150-280 Disabled Use this setting with equipment that is less sensitive to fluctuations in voltage or waveform distortions. Green 4 beeps per second Low 150-280 Enabled Use this setting with equipment that is less sensitive to fluctuations in voltage or waveform distortions. Red None Medium 155-280 Disabled Use this setting for normal operation conditions. Red 4 beeps per second Medium (factory default) 155-280 Enabled Use this setting for normal operation conditions. Green and Red None High 160-280 Disabled Use this setting when connected equipment is sensitive to voltage fluctuations or waveform distortions. Green and Red 4 beeps per second High 160-280 Enabled Use this setting when connected equipment is sensitive to voltage fluctuations or waveform distortions. 4 Back-UPS BX1100CI-CN Installation and Operation

Troubleshooting Problem Possible Cause Corrective Action Back-UPS will not turn on. The Back-UPS is operating on battery power, while connected to AC power. The Back-UPS is not connected to AC power. The circuit breaker has been tripped. The internal battery is not connected. The AC input voltage is out of range. The Back-UPS power cable is not securely connected to the wall outlet. The wall outlet is no longer receiving AC power. The circuit breaker has been tripped. The Back-UPS is performing an automatic self test. The AC input voltage is out of range. The frequency is out of range. The waveform is distorted. Be sure that the Back-UPS is securely connected to an AC outlet. Disconnect nonessential equipment from the Back-UPS. Reset the circuit breaker. Reconnect equipment one item at a time. If the circuit breaker is tripped again, disconnect the device that caused the short circuit. Connect the battery connector. Refer to Connect the Battery on page 1. Adjust the transfer voltage and sensitivity range. Verify that the power cable plug is securely connected to the wall outlet. Verify that the wall outlet is receiving AC power by checking it with another device. No action is necessary. Adjust the transfer voltage and sensitivity range. The Back-UPS does not provide the expected amount of backup time. Battery Backup outlets may be fully or improperly loaded. The battery was recently discharged due to a power outage and has not fully recharged. Disconnect non-essential equipment from the Battery Backup outlets. Charge the battery cartridge for eight hours. The BATTERY and ON LINE LEDs flash alternately. The BATTERY LED is illuminated and the Back-UPS emits a constant tone. The battery has reached the end of its useful life. The battery has reached the end of its useful life. The connected equipment is drawing more power than the Back-UPS can provide. Replace the battery. Replace the battery. Disconnect nonessential equipment from the Battery Backup outlets. Back-UPS BX1100CI-CN Installation and Operation 5

Specifications Specification BX1100CI-CN Input Voltage 230 Vac Nominal Frequency 50 Hz ±3 Hz, 60 Hz ±3 Hz Input Voltage Range 199 Vac - 251 Vac maximum load capacity 150 Vac - 198 Vac or 252 Vac - 280 Vac -60% maximum load at 25 º C -40% maximum load at 40 º C Output UPS Capacity 1100 VA / 660 W Voltage On Battery 230 Vac rms (step-approximated sinewave) Frequency on Battery 50 Hz ±1 Hz (default), 60 Hz ±1 Hz Transfer Time 8 ms, typical Protection and Filtering AC Surge Protection Full time, 273 Joules AC Input Resettable circuit breaker Battery Battery Type (maintenance-free) Each battery 12 V 7.2 Ahr Average Battery Life 2-5 years depending on the number of discharge cycles and environmental temperature Typical Recharge Time 8 Hours Physical Net Weight 12 kg Dimensions (H x W x D) 21.5 cm x 13 cm x 33.6 cm Operating Temperature 0 o C to 40 o C (32 o F to 104 o F) Storage Temperature -15 o C to 45 o C (5 o F to 113 o F) Operating Relative Humidity 0 to 95% non-condensing Operating Elevation 0 to 3000 m (0 to 10,000 ft) 6 Back-UPS BX1100CI-CN Installation and Operation

Service If the unit requires service, do not return it to the dealer. Follow these steps: 1. Review the Troubleshooting section of the manual to eliminate common problems. 2. If the problem persists, contact APC Customer Support through the Web site, www.apc.com. a. Note the model number and serial number and the date of purchase. The model and serial numbers are located on the rear panel of the unit and are available through the LCD display on select models. b. Call APC Customer Support and a technician will attempt to solve the problem over the phone. If this is not possible, the technician will issue a Returned Material Authorization Number (RMA#). c. If the unit is under warranty, the repairs are free. d. Service procedures and returns may vary internationally. Refer to the APC Web site for country specific instructions. 3. Pack the unit properly to avoid damage in transit. Never use foam beads for packaging. Damage sustained in transit is not covered under warranty. Note: When shipping within the United States, or to the United States always DISCONNECT A UPS BATTERY before shipping in compliance with U.S. Department of Transportation (DOT) and IATA regulations. The internal batteries may remain in the UPS. 4. Write the RMA# provided by Customer Support on the outside of the package. 5. Return the unit by insured, pre-paid carrier to the address provided by Customer Support. APC Customer Support China Internet http://www.apc.com/cn Telephone 400 810 1315 Warranty The standard warranty is two (2) years from the date of purchase. APC standard procedure is to replace the original unit with a factory reconditioned unit. Customers who must have the original unit back due to the assignment of asset tags and set depreciation schedules must declare such a need at first contact with an APC Technical Support representative. APC will ship the replacement unit once the defective unit has been received by the repair department, or cross-ship upon the receipt of a valid credit card number. The customer pays for shipping the unit to APC. APC pays ground freight transportation costs to ship the replacement unit to the customer. Back-UPS BX1100CI-CN Installation and Operation 7

2011 APC by Schneider Electric. APC, the APC logo and Back-UPS are owned by Schneider Electric Industries S.A.S., American Power Conversion Corporation, or their affiliated companies. All other trademarks are property of their respective owners. EN 990-4400B 12/2011