VdS-Guidelines for water extinguishing systems. VdS en. Sprinkler Pumps. Requirements and test methods. VdS en : (03)

Similar documents
European Fire Pump Listing

GRUNDFOS DATA BOOKLET. Fire CRFF. Grundfos fire systems. VdS-approved CR pumps for fire systems 50 Hz

GRUNDFOS DATA BOOKLET. Fire NKF. Grundfos fire systems. Fire pump sets with electrically and diesel-powered pumps according to DBI 251/CEA4001

Side channel pumps PN 16 SOH - SOHB. Self-priming centrifugal pumps. Technical description

Data sheet: Wilo-Multivert MVI 205 (3~400 V, EPDM, PN 16)

Data sheet: Wilo-Multivert MVI 805 (3~400 V, EPDM, PN 16)

Data sheet: Wilo-Multivert MVI 404 (1~230 V, EPDM, PN 16)

ISO 1217 INTERNATIONAL STANDARD. Displacement compressors Acceptance tests. Compresseurs volumétriques Essais de réception. Fourth edition

PTB GLV. Vertical Centrifugal Pump

Norm-Centrifugal Pumps PN 10

ISO INTERNATIONAL STANDARD. Seal-less rotodynamic pumps Class II Specification

PRE-RELEASE VERSION (FDIS)

Operating Instructions

MTB /183 A-F-A-BQQV 400D-2 11kW

INTERNATIONAL STANDARD

XFLO XS SERIES. Single Stage Double Suction Split Casing Centrifugal Pump

Contents. Identification

ISO 2320 INTERNATIONAL STANDARD. Prevailing torque type steel nuts Mechanical and performance properties

ISO INTERNATIONAL STANDARD

franklinwater.com 50 Hz VR SERIES Vertical Multi-Stage Pumps

Data sheet. Etaline GN /3002 G11 Version no.: 1 Inline pump. Operating data. Design. Clean water. Efficiency 61.6 % 20.0 C.

CR3-6 A-FGJ-A-E-HQQE 1x220/240 50HZ

CR1-3 A-FGJ-A-E-HQQE 1x220/240 50HZ

VARIABLE SPEED WATER BOOSTER SETS WITH MULTISTAGE VERTICAL ELECTRIC PUMPS FLOW RATES UP TO 400 m 3 /h. 50 Hz GHV30 GHV40 SERIES

2018 High Performance Check Valves for liquid and gaseous media

Close-coupled pumps Series ES04

ISO INTERNATIONAL STANDARD. Rolling bearings Sleeve type linear ball bearings Boundary dimensions and tolerances

Company name: BKB Building Solutions Created by: Michael Chlopek Phone: Date: 13/03/2017

Data sheet. Etaline GN /1852 G10 Version no.: 1 Inline pump. Operating data. Design. Requested developed head m

3D SERIES. EBARA PUMPS EUROPE S.p.A. CENTRIFUGAL PUMPS. Page

Understanding BS 1363 Amendment No.4

50 Hz PX CHANNEL 1. Performance curves. data refered to : W ater, pure [100%] ; 20 C; 0,9983kg/ dm³; 1,001mm²/ s. Tolerances acc.

Data sheet. Page: 1 / 5 ETN GG A 11GA201502B. Operating data. Design. Requested developed head m. Efficiency 74.

High-pressure pumps Series HP45

LPCD. EBARA PUMPS EUROPE S.p.A. CENTRIFUGAL PUMPS. Page

Lowara. Centrifugal Electric Pumps Manufactured in AISI 316 Stainless Steel in Compliance with EN 733. SH Series. 60 Hz

7 The revised IS 8034:2002 and revised STI be implemented w.e.f. 1 Feb 2005.

ISO INTERNATIONAL STANDARD

Side channel pumps PN 16 SOH - SOHB - SOHM. Self-priming centrifugal pumps. Technical description

Data sheet. Customer item no.: Communication dated: Number: ES Doc. no.: Item no.: 100 Quantity: 1 Date: 19/03/2015 Page: 1 / 6

ISO INTERNATIONAL STANDARD. Lubricants, industrial oils and related products (Class L) Family X (Greases) Specification

CR3-2 A-FGJ-A-E-HQQE 3x230/400 50HZ

CR5-26 A-FGJ-A-E-HQQE 3x400D 50HZ

Butterfly valve Series K

MTB /158 A-F-A-BQQV 400D-2 5,5kW

RS Multi-Stage, Ring Section Pumps

GRUNDFOS DATA BOOKLET. Fire NKF. Grundfos fire systems. Fire systems with electrically powered (50 Hz) pumps approved by VdS

CR3-13 A-A-A-E-HQQE 1x220/240 50HZ

CR1-9 A-A-A-E-HQQE 1x220/240 50HZ

CR1S-6 A-A-A-E-HQQE 1x220/240 50HZ

INTERNATIONAL STANDARD

3D SERIES. EBARA PUMPS EUROPE S.p.A. CENTRIFUGAL PUMPS. Page

Part 5: Generating sets

SF6. EBARA PUMPS EUROPE S.p.A. SUBMERSIBLE PUMPS. Page - CONTENTS 100

Model 133 Models 134 & 135 AURORA 130 SERIES SINGLE STAGE TURBINE TYPE PUMPS

General Catalog. A New Vision for Quality Pumps. General Catalog

DEUTSCHE NORM DIN 8077

EBARA LPC 4-POLIGA CENTRIFUGALA PUMPAR

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

MODEL INFORMATION CANNED MOTOR PUMP TYPE CAM HERMETIC

High-pressure pumps Series HP49

Hydraulic fluid power Dimensions and requirements of quick-action couplings

ISO 2941 INTERNATIONAL STANDARD. Hydraulic fluid power Filter elements Verification of collapse/burst pressure rating

- CONSTRUCTIONS 300 SECTIONAL VIEW DRAWING 300 SECTIONAL VIEW TABLE 301 QUANTITY FOR MODEL 302 INTERMEDIATE CASING WITH BEARING POSITION 303

CR15-10 A-F-A-E-HQQE 11kW 3x400D 50Hz

الهيئة السعىدية للمىاصفبت والمقبييس والجىدة Saudi Standards, Metrology and Quality Org (SASO)

CR5-6 A-FGJ-A-E-HQQE 3x230/400 50HZ

Page - CONSTRUCTIONS 300 SECTIONAL VIEW 300 MECHANICAL SEAL DIMENSIONS AND WEIGHT 400 PUMP 400

M-18 Controllable-Pitch Propeller

GIS/ GISO Series End Suction Pumps TECHNICAL BULLETIN

ISO 4409 INTERNATIONAL STANDARD. Hydraulic fluid power Positivedisplacement

CR3-19 A-FGJ-A-E-HQQE 3x230/400 50HZ

Pressure Relief Valve DB12 CE

Page - CONSTRUCTIONS 300 SECTIONAL VIEW DRAWING 300 SECTIONAL VIEW TABLE DIMENSIONS AND WEIGHT 400 PUMP DRAWING 400 DIMENSION PUMP TABLE 401

Part 11: Wheelchairs. Test dummies

INTERNATIONAL STANDARD

E-15 Uninterruptible Power Systems (UPS)

UNIT TAG: TYPE OF SERVICE: SUBMITTED BY: APPROVED BY: ORDER NO.: CME3-7 A-S-I-E-AVBE. Pump Data

TECHNICAL DELIVERY SPECIFICATION II Technical Equipment Instructions. TA05 Lubricating Technology

NB80-160/161 A-F2-A-BQQE

LPC. EBARA PUMPS EUROPE S.p.A. CENTRIFUGAL PUMPS. Page

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

ISO 5700 INTERNATIONAL STANDARD

Volute Casing Centrifugal Pumps in In-line Design with Magnetic Drive. Series CNI-M

SIL Inline Single Stage Centrifugal Pumps

INTERNATIONAL STANDARD

Series MRK and MRM For nominal pressures up to 640 bar /class 4500 Automatic Recirculation Valve for pump protection

Lowara. Centrifugal electric pumps made of AISI 316 stainless steel in compliance with EN 733. SH Series. 50 Hz

Metallic materials Rockwell hardness test. Part 2: Verification and calibration of testing machines and indenters

MMD 4 Poles. EBARA PUMPS EUROPE S.p.A. CENTRIFUGAL PUMPS. Page

This document is a preview generated by EVS

EU RO Mutual Recognition Technical Requirements

TYPE PC Propeller Condensate Pumps

CR10-01 A-A-A-E-HQQE 1x220/ HZ

CM5-5 A-R-A-E-AVBE C-A-A-N

Mounting and Operating Instructions EB 8097 EN. Type and Type Pneumatic Control Valves

TABLE OF CONTENT

Page - CONSTRUCTIONS 300 SECTIONAL VIEW 300 MECHANICAL SEAL DIMENSIONS AND WEIGHT 400 PUMP 400

INTERNATIONAL STANDARD

Greater Cairo Foundries. Concentric Rubber Lined Butterfly Valves

Transcription:

VdS-Guidelines for water extinguishing systems VdS 2100-07en Sprinkler Pumps Requirements and test methods VdS 2100-07en : 2013-05 (03)

Publisher: VdS Schadenverhütung GmbH Publishing house: VdS Schadenverhütung GmbH Amsterdamer Str. 172-174 50735 Köln, Germany Phone: +49 221 77 66 0; Fax: + 49 221 77 66 341 Copyright by VdS Schadenverhütung GmbH. All rights reserved.

VdS 2100-07 : 2013-05 (03) Sprinkler Pumps VdS-Guidelines for water extinguishing systems Sprinkler Pumps Requirements and test methods CONTENT Declaration of non-binding status... 4 1 Scope... 4 2 Normative references... 4 3 Definitions... 5 4 Requirements... 5 4.1 Marking... 5 4.2 Technical documentation... 6 4.3 Connections... 7 4.4 Resistance to pressure... 7 4.5 Design requirements... 7 4.6 H(Q) characteristic curve, delivery flow and delivery head... 8 4.8 Drive power and torque... 8 5 Tests... 9 5.1 Test conditions... 9 5.2 Type testing... 9 5.3 Other tests... 10 6 Additional provisions for the approval procedure... 10 6.1 Pump casing pressure tests by the manufacturer... 10 6.2 Pumps with not-tested impeller diameters in approved impeller range... 11 6.3 Pumps with not-tested speed in approved speed range... 11 Annex A 12 Annex A.1 Example of a name plate... 12 Annex A.2 Example for the H(Q) charts of the characteristic curves... 13 3

Sprinkler Pumps VdS 2100-07 : 2013-05 (03) Declaration of non-binding status These VdS-Guidelines for water extinguishing systems, Sprinkler Pumps, VdS 2100-07en, are binding only if their application has been agreed on an individual basis. 1 Scope These guidelines specify requirements and test methods for fire pumps (traditionally called sprinkler pumps) for use in extinguishing systems according to e.g. VdS CEA 4001, VdS 2109 and VdS 2108 fest. Moreover, these guidelines define regulations for the approval procedure of sprinkler pumps applicable in addition to the procedure guidelines VdS 2344 and VdS 2841. These guidelines are applicable to centrifugal pumps of the following types: above ground pumps, submersible motor pumps and vertical shaft turbine pumps. The use of submersible motor pumps at water temperatures exceeding 25 C is not regarded. Note: The delivery head is limited inherent to the design. Therefore it is assumed that the rated pressure does not exceed 80 bar. For other pump constructions, these guidelines can serve as a guide. In each such case it has to be assessed whether additional tests and/or measures are necessary. 2 Normative references These guidelines incorporate, by dated or undated references, provisions from other publications (e.g. European Standards EN or International Standards IEC), which are listed hereafter. For dated references, subsequent amendments to or revisions of any of these publications apply to these guidelines only when incorporated in them by amendment or revision. For undated references the latest edition of the publication referred to applies. VdS CEA 4001 Guidelines for sprinkler systems Planning and installation VdS 2109 Guidelines for water spray systems Planning and installation VdS 2108 Guidelines for foam extinguishing systems Planning and installation DIN EN ISO 9906 : 2002-08 Rotodynamic pumps. Hydraulic performance acceptance test. Grades 1 and 2 (ISO 9906:1999); German version EN ISO 9906:1999 EN 12723 ISO 7-1 EN ISO 228-1 EN 1092 Liquid pumps General terms for pumps and installations Definitions, quantities, letter symbols and units Pipe threads where pressure-tight joints are made on the threads Part 1: Dimensions, tolerances and designation Pipe threads where pressure-tight joints are not made on the threads Part 1: Dimensions, tolerances and designation Flanges and their joints Circular flanges for pipes, valves, fittings and accessories, PN designated 4

VdS 2100-07 : 2013-05 (03) Sprinkler Pumps 3 Definitions For the use of these guidelines the following definitions apply: Allowable pressure: Pressure specified by the manufacturer at which the component may be used. On the basis of this value the test pressures are calculated and the tests are conducted. Note: This pressure specification limits the pressure of the medium to be pumped for all operating conditions of the sprinkler pump and must take into account the simultaneous occurrence of the highest possible delivery head at zero flow or the maximum delivery head respectively, the permitted exceedance of the rotational speed of the engine and the highest possible inlet pressure. NPSH (net positive suction head): (see EN 12723). NPSHR (net positive suction head required): (see EN 12723) The minimum (NPSH) at the pump inlet connection required to give rated or operating performance at the specified conditions. Pump-H-Q-curve (also known as pump head capacity curve or characteristic curve): The relationship between the total head of the pump and the flow rate at given operating/rated conditions of speed and liquid. Stable pump H-Q-curve: A pump H-Q-curve where the maximum head and shut-off head are coincidental and the total head declines continuously with increasing rate of flow. Q zul : Permissible delivery flow (reference value for the use in extinguishing system according to VdS-Guidelines). Wear ring (Spaltring): Wear ring made of metal between pump casing and impeller, either fixed in the casing (cover) and/or fixed in the impeller. Seal ring (Spaltringdichtung): Sealing ring of multistage pumps with impeller and impeller casings made of formed stainless steel sheet. 4 Requirements 4.1 Marking Sprinkler pumps shall be marked by the manufacturer with the details according to 4.1.1 and 4.1.2. In the case of submersible motor pumps a duplicate of the name plate shall be provided for attachment to the switch cabinet. This marking on the pump shall be non-detachable, non-flammable and permanent. It should be well legible. Adhesive foil or similar measures are not acceptable. 4.1.1 The name plate shall bear the following information: Manufacturer s name or trademark; location of the company headquarters Model designation Serial number/year of manufacture "VdS or VdS-Logo, and VdS Approval number Permissible delivery flow Q zul in [l/min] Delivery head H in [m] at permissible delivery flow Rated speed nn in [1/min], at which the pump is driven. This value shall not exceed 3600 1/min. Required motor output PM in [kw] as per section 4.8 5

Sprinkler Pumps VdS 2100-07 : 2013-05 (03) Diameter of the impeller mounted in [mm]; In the case of angled blade ends, the largest and smallest impeller diameters are to be indicated (e.g. 280/270 mm) Maximum starting current in [A] (if necessary; see 4.8.1) 4.1.2 The pump shall be provided with the following markings and information: Direction of rotation This information needs not to be present on submersible motor pumps. Maximum allowable pressure in [bar] Abbreviation identifying the alloy from which the pump casing was manufactured (e.g. JL 1040) Note: This information need not to be present on the name plate. 4.2 Technical documentation The manufacturer shall provide the following documents: General drawings together with parts list and material specifications of the following major parts, if existent: pump casing with pressure cover, pump shaft, shaft protection sleeves, impeller/impellers, impeller mounting components (impeller nut, locking plate or washer and key), wear rings (if existent). List with the following information: Pump type, e.g. above ground centrifugal pump, with indication of the number of stages (one figure or range) Allowable pressure in [bar] according to clause 4.4 Casing material and breaking elongation of the casing material according to clause 4.5.2 Material of the single parts according to clause 4.5.2 Standard of connections according to clause 4.3 Minimum bypass flow in [l/min] or [m³/h] according to clause 4.7.4 Maximum starting torque and torque at maximum power consumption (as graphic presentation or as table of values) Charts for characteristic curves The operating manual to be supplied with every pump Image/drawing of the name plate The following data shall appear in the charts of the characteristic curves: Model designation VdS Approval number with or without VdS-Logo Delivery flow in [l/min] and [m 3 /h] Delivery head in [m] and guaranteed delivery head design tolerance for the whole delivery flow range Note: Maximum permitted tolerances in the range 50% to 100% of the permissible delivery flow are in case of double-sided tolerance ± 5% and in case of single-sided positive tolerance +6%. Outside of this range, tolerances up to ± 6% or +7% respectively are permitted. Permissible delivery flow Q zul in [l/min] or [m³/h], at least as marking on the curve(s) in the approved impeller range, with wording Zulassungsgrenze ( Rated Capacity ). Required power in [kw] If applicable, maximum current load in [A] (see 4.8.1) NPSHR in [m] Rated speed in [1/min] 6

VdS 2100-07 : 2013-05 (03) Sprinkler Pumps Impeller diameter in [mm] Minimum water coverage depth in [m] for submersible motor pumps Minimum bypass flow in [l/min], [m³/h] or % of Q zul Nominal diameter of the pump inlet, not applicable to submersible motor pumps Nominal diameter of the pump outlet. Delivery flow, delivery head, power requirements and NPSHR are guaranteed values according to DIN EN ISO 9906, at least grade 2. Note: This means that for all pumps produced the delivery head is within the guaranteed tolerance in the whole delivery flow range; and the required power does not exceed the guaranteed required power; and NPSHR does not exceed the guaranteed NPSHR. 4.3 Connections The inlet and outlet connections should preferably be designed according to EN 1092. Threaded connections shall be designed according to ISO 7-1 or EN ISO 228-1. Sprinkler pumps having leakage water due to the design must be equipped with a connection to drain the leakage water. Further connections due to the design are allowable. 4.4 Resistance to pressure The manufacturer shall specify the allowable pressure (according definition in section 3) of the pump casing. The allowable pressure shall be at least 10 bar. 4.5 Design requirements 4.5.1 In the interest of achieving the shortest possible repair periods, it shall be possible using standard tools only to replace all essential functional components ore subassemblies at the installation site. Parts replaceability shall be guaranteed by the specification of appropriate tolerances. The design of the bearings and shaft seals as well as the play in the rotating parts shall be such as to permit trouble-free operation even after extended periods out of service (maximum 6 months). This requirement is normally fulfilled with the use of proven and tested elements, such as ball-bearings, gland packings, mechanical seals, wear rings (see 4.5.2). If axial choke gaps, necessary by the design, are present at the impeller, then the section of the casing affected is to be fitted with wear rings (see 4.5.2). 4.5.2 The pump casing shall be made of cast steel, ductile cast iron, aluminium bronze, gunmetal, red bronze or another metal with at least equivalent characteristics. The elongation at break of these materials shall be at least 15%. In case the delivery head does not exceed 110 m and the allowable pressure does not exceed 12 bar, then cast iron JL 1040 or at least equivalent material is sufficient. Pump shafts, shaft protection sleeves, impellers, impeller mounting components (impeller nut, locking plate or washer and key) and wear rings shall be made of non-rusting metal with a melting point > 800 C. Seal rings (see also section 3) shall be made of adequate material e.g. designed as flat pastic ring, equal/higher quality as PTFE (Teflon) or elastomer O-ring, equal/higher quality as EPDM, VITON, HNBR. 7

Sprinkler Pumps VdS 2100-07 : 2013-05 (03) 4.5.3 The connection of pumps to motors shall be made separably by a coupling. As to horizontally mounted single-stage above-ground pumps including pumps in Back- Pull-Out-design, the coupling between motor and pump shall be designed in such a way that both can be removed independently, with the pump casing staying in the pipeline during inspection and replacement of parts. 4.6 H(Q) characteristic curve, delivery flow and delivery head 4.6.1 H(Q) characteristic curves (pump choke curves) of sprinkler pumps should be stable (i.e. the delivery head should have its maximum value at zero delivery flow or minimum bypass flow and should decline with increasing delivery flow) and flat. An instability is only allowable as follows. The delivery head at zero delivery flow or minimum bypass flow may be up to 5 % (however no more than 5 m) below the maximum delivery head. 4.6.2 The deviations between the characteristic curve specified by the manufacturer and the values recorded during the test according to 5.2 may be 5% of the maximum delivery head in the flow range from the minimum bypass flow up to 0.5 permissible delivery flow (Q zul ). In the range of 0.5 Q zul until the end of the characteristic curve the values recorded during the test according to 5.2 have to be transferred unchanged (without deviation) into the characteristic curve. 4.6.3 The permissible delivery flow (Q zul ) is determined as delivery flow at 4.5 m NPSHR, in the case of submersible motor pumps and vertical shaft turbine pumps in feed operation at 8.5 m NPSHR. When delivering at 1.2 times the permissible delivery flow, an NPSHR of 5.5 m shall not be exceeded (in the case of submersible motor pumps and vertical shaft turbine pumps in feed operation 9.5 m). The criterion for NPSHR is a 3% drop in the delivery head for the first stage of multi-stage pumps or for single-stage pumps operating at fixed speed and constant delivery flow. 4.6.4 The manufacturer shall specify the minimum bypass flow in order to reduce a possible pump breakdown with closed valve. The minimum bypass flow has to be proved by a test according to 5.2.6. The manufacturer may provide a connection on the pump for the bypass flow. 4.8 Drive power and torque 4.8.1 The power provided by the drive motor shall be sufficient in the whole range of the H(Q) curve. Note: The VdS-Guidelines for planning and installation contain the following requirements for the selection of motors which will be considered during the test of submersible motor pumps where pump and motor are clearly specified. Overload values or values for short time operation which are allowed in the standards for electric or diesel motors shall not be applied. The torque of the drive motors shall be greater as the countertorque exerted by the pump all the way from standstill to rated speed. Maximum pump power requirements are to be taken as the basis for determining the countertorque. As to submersible motor pumps where pump and motor are clearly specified the maximum current drawn during starting has to be stated on the name plate (the current surge in the star-delta changeover phase shall be taken into consideration!). Note: Drive power may be provided by an electric motor with direct coupling. The motor speed may not exceed 3600 1/min (r.p.m.). 4.8.2 In the case of pumps which exhibit an output curve which continues to rise when operating in the overload range, the output of the drive motor shall be such that it is equivalent to not less than delivery flow corresponding to an NPSH value of 15 m. 8

VdS 2100-07 : 2013-05 (03) Sprinkler Pumps Note: An additional output dimensioning for a NPSH value of 16 m can be made on request of the manufacturer. Note: No safety factor is included in the characteristic curve itself. Note: In the VdS-Guidelines for planning and installation it is required, when using pumps with output curve increasing in the overload area, that the motor power has to be increased to 1.2 times the motor power according to the charts of the characteristic curves if the operational pressure at the inlet port equals or exceeds 0.5 bar. 4.8.3 In the case of pumps having a demonstrable peak along the output curve (non overloading curve), a value 1.05 times this peak value is to be used for the determination of the motor power. Note: The safety factor of 5 % is not included in the characteristic curve itself, but in the motor power specification in the charts of the characteristic curves. 4.8.4 The manufacturer shall specify the motor power determined according to 4.8.2 or 4.8.3 whichever applies as "necessary motor power [kw]", rounded up to the next IEC standard motor power* (does not apply to submersible motor pumps), on the charts of the characteristic curves allocated to the individual impeller diameters. In addition there shall be a remark that with the use of an electric motor this motor power has be to rounded up to the next higher power according to IEC standard motor powers. For the marking of the required power on the name plate the following applies: Pumps for electric power: required power according 4.8.2 or 4.8.3 rounded up to the next IEC standard motor power* (does not apply to submersible motor pumps). Pumps for diesel power: required power according 4.8.2 or 4.8.3. * The motor power determined according 4.8.2 or 4.8.3 is rounded first. If the rounded value does not coincide with an IEC standard motor power, the next higher IEC standard motor power must be specified as required power. If the standard motor power contains a decimal place, the rounding of the motor power determined according 4.8.2 or 4.8.3 refers to this decimal place. 5 Tests 5.1 Test conditions The tests are conducted at a temperature of (25 ± 10) C unless specified otherwise for a specific test. The tolerance of all test parameters is ± 5 % unless specified otherwise. 5.2 Type testing 5.2.1 Type testing is conducted with tests by VdS or in presence of VdS at the test facility of the manufacturer or at a test facility accepted by VdS according to DIN EN ISO 9906 at least class 2. 5.2.2 Before testing the details in the documents submitted are checked for compliance with these guidelines and the referenced guidelines and standards. 5.2.3 During the tests the pumps with maximum and minimum impeller diameter and with the impeller diameters in between which are matching the IEC standard motor powers are tested. The measurements required for the test evaluation according to DIN EN ISO 9906 are done at 7 points equally distributed over the delivery range. NPSHR has to be determined in five usefully distributed points between 0.3 Q zul and the maximum delivery flow to be measured. 9

Sprinkler Pumps VdS 2100-07 : 2013-05 (03) The maximum delivery flow to be measured is a result from the values to be determined for the required power in consideration of the addition of 1.0 m to the NPSH value. Note: See section 6.2 for the issue of additional charts of the characteristic curves for deviating impeller diameters. 5.2.4 In case of a range of speeds the pumps with maximum and minimum impeller diameter are tested each with the minimum and maximum speed. Note: See section 6.3 for the issue of additional charts of the characteristic curves for deviating speed. 5.2.5 In case of multi-stage pumps the NPSHR test is done with the minimum number of stages and the Q-H-P test with the maximum number of stages. Note: Approval tests which had been carried out with other numbers of stages before the publication of these Guidelines do not have to be repeated with the numbers of stages required here. 5.2.6The pump shall be run for a minimum of 2 hours with the maximum impeller diameter at maximum allowable continuous speed and the minimum by-pass flow specified by the manufacturer. The pump inlet and outlet temperatures shall be measured throughout the test. The maximum water temperature rise across the pump shall not exceed 10 ºC for the duration of the test. Measure the delivery head, flow rate and power input throughout the test at intervals of not exceeding 15 minutes. All parameters shall be measured in accordance with EN ISO 9906:2000 Grade 2. Using a temperature measuring device with an accuracy of ± 2 C. Temperature measurements shall be made: at the pump suction inlet; and at an outlet measuring section normally located at a distance of two diameters from the pump outlet casing 5.3 Other tests Where special designs, special performance characteristics or new manufacturing methods make it necessary, additional tests will be conducted in agreement with the manufacturer. 6 Additional provisions for the approval procedure 6.1 Pump casing pressure tests by the manufacturer The manufacturer must conduct a pressure test with each pump casing in finished condition or in assembled condition: Test medium: water Test pressure: 1,5 times allowable pressure During and after the test no signs shall be visible for breaks/cracks, or inadmissible plastic deformation. 10

VdS 2100-07 : 2013-05 (03) Sprinkler Pumps 6.2 Pumps with not-tested impeller diameters in approved impeller range The manufacturer is allowed to issue characteristic curves for pumps with not-tested impeller diameters and indicate the pumps as VdS-approved provided that: the impeller diameter is within the approved impeller range. the impeller diameter is not more than 5% bigger or smaller than a tested impeller diameter. the characteristic curves are calculated according DIN EN ISO 9906. 6.3 Pumps with not-tested speed in approved speed range The manufacturer is allowed to issue characteristic curves for pumps with not-tested speed and indicate the pumps as VdS-approved provided that: the speed is within the approved speed range. it is proved that the NPSH-value of the pump can be converted according the formula (see DIN EN ISO 9906): (NPSHR) T = (NPSHR) (n sp /n) x with: (NPSHR) T = corrected NPSHR for the specified speed n sp (NPSHR) = determined NPSHR at measured speed n n sp = specified speed n = measured speed x = conversion exponent according manufacturer specification the conversion of the test data is done according to DIN EN ISO 9906 class 2. If these conditions are fulfilled, charts of the characteristic curves can be issued down to 0.75-fold maximum and up to 1.5-fold minimum tested speed. 11

Sprinkler Pumps VdS 2100-07 : 2013-05 (03) Annex A Annex A.1 Example of a name plate Manufacturer Company logo/ Company site Sprinkler pump Model designation: Serial number: Year of manufacture: Q zul : l/min VdS or VdS- Logo n N : 1/min H: m Impeller diameter: mm P M : kw Casing material: max. starting current*: A * if necessary (see 4.1.1) 12

VdS 2100-07 : 2013-05 (03) Sprinkler Pumps Annex A.2 Example for the H(Q) charts of the characteristic curves Where the intention is to use electrical drive for the pump, drive speeds of 2940 1/min (r.p.m.) and 1470 1/min (r.p.m.) should be used in preparing the charts of the characteristic curves. Where the intention is to use diesel engines for the pump, charts of the characteristic curves for the maximum and the minimum speed shall be prepared. In case of a speed in between, the charts of the characteristic curves shall be prepared for the speed ordered and attached to the sales papers of the sprinkler pump. The speeds selected for the H(Q) curve charts may not deviate by more than 1.5 % from the speed used in nominal operation. Example chart: 13

Sprinkler Pumps VdS 2100-07 : 2013-05 (03) Manufacturer: VdS- Approval number: Impeller diameter: Rated speed n N : Min. bypass flow: Pxxxxxx mm 1/min l/min m³/h % of Q zul Sprinkler pump, model: DN S : No of stages: Date of drawing: DN D : Minimum water coverage depth: m When an electric engine is used, the engine power has to be rounded up to the next higher IEC standard engine power. 14