CP-9301 CP Application. Features. Applicable Literature. Electronic Actuator Drives General Instructions

Similar documents
CP-8301-xxx Series. Application. Features. Applicable Literature. 1 to 15 Vdc Input Electronic Actuator Drive General Instructions

CP (Vdc) CP (Milliamp) CP (Slidewire)

MA-5200 Series MA-5300 Series

MP-5400 Series. Application. Features. Applicable Literature. Electronic Positive Positioning Hydraulic Actuator General Instructions

CP-8551 & CP Application. Features. Applicable Literature. Electronic to Pneumatic Transducers General Instructions

CP CP

MF4E MF4E

MP-5200 Series. Application. Features. Applicable Literature. Electronic Hydraulic Actuator General Instructions

MS Application. Features. Proportional Valve Actuator General Instructions

MAx-305 & MAx-318 Series MAx-405 Through MAx-419 Series Two-Position Actuators

SLC-811X Series. Single Loop Proportional Temperature Controller General Instructions APPLICATION SPECIFICATIONS

THC-2, THC-3, THCR-4, THCR-5. Enthalpy Control. General Instructions APPLICATION SPECIFICATIONS. ACCESSORIES None

MF-22xx3. Application. Features. Floating Valve Actuator General Instructions

AV-430. Application. Features. Applicable Literature. Valve Linkage for Pneumatic Actuators General Instructions

AM-751, AM-752, AM-753, AM-754, AM-755. Applications. Applicable Literature

TS , -850 Series TS , -850 Series TS-57031, TS

453X Series. Application. Features. Two-Position Damper Actuator General Instructions

SPECIFICATIONS ATTENTION OPERATION DESCRIPTION

AV-497. Application. Features. Valve Linkage for MK-6811 and MK-6911 General Instructions

AV-401. Application. Features. Applicable Literature. Pneumatic Actuator Valve Linkage Kit General Instructions

AV-611. Application. Applicable Literature. Schneider Electric DuraDrive Globe Valve Linkage General Instructions

T500 Series. Applications. Features. Applicable Literature. Non-Digital, On/Off Thermostat General Instructions

MS40-717X Series. Application. Features. DuraDrive Series Spring Return Proportional Actuators General Instructions

MX4X-6XXX Series MX4X-7XXX Series. Selection Guide. Applications. DuraDrive Series Actuators and Accessories

MA40-704X Series MA41-707X Series MA41-715X Series

MF Series MS Series

TS Series TS Series

Non-Spring Return EconoDrive Floating Actuator

MK-6600 Series, MK-6800 Series, and MK-6911

AK Application. Features. Applicable Literature. Positive Positioner Pneumatic Relay General Instructions

VA, VF, and VS Series Direct Mounted Globe Valve Assemblies. Application. Features

MC-351, 421, 431, MC-4311

MA/F/S 4D-xxxx-xxx Two Position, Floating and Proportional Series SmartX Actuators Rotary Overshaft Actuators

Instruction Manual for Barber-Colman Series EA Electric High Torque Actuators

2211 Series. Application. Features. One-Pipe Pneumatic Room Thermostats General Instructions SPECIFICATIONS

Application. Features

Selection Guide. Vx-2x13-5xx-9-xx Series Vx-2x13-8xx-9-xx Series VB-2x xx Series. Schneider Electric Ball Valve Assemblies

MS Series MS Series MS Series

MS41-634X Series. Features. SmartX Actuators Non-Spring Return Proportional General Instructions

TSMN-90xxx Series TSMN TSMN TSMN Electronic Room Temperature Sensor General Instructions

TAC DuraDrive Product Guide Direct Coupled Actuators

MF Series MF Series MF Series

TK-6024, TK-6124, TK-8024, TK-8124

M100F Incremental Motor Actuator R81F Interface Board

IMP-5400 Series. Application. Features. Applicable Literature. Electronic Positive Positioning. Hyciraulic Actuator General Instructions SIEBE

MAx1-720x Two Position Series MFx Floating Series MSx Proportional Series

MX4X-6XXX-20X Series MX4X-7XXX-20X Series

VB-8000 Series VB-9313 Series. Selection Guide. Applications. Applicable Literature. Selection Guide Contents. Valve and Actuator Selection Procedure

AV-608 Linkage Adapter Kit

VB-9323 Series. Application. Features. Applicable Literature. 2-1/2" to 6" 125 Lb. Flanged Three-Way Diverting Valves General Instructions

Series EA High Torque Actuators with Integrated Controller

MA40-704X Series, MA4X-707X Series, MA4X-715X Series DuraDrive Series Spring Return Two-Position Actuators General Instructions

Invensys Energy Solutions 1354 Clifford Avenue (Zip 61111) P.O. Box 2940 Loves Park, IL United States of America

NETSIAN TECHNOLOGY VALVE SCHEDULE

VB-9313 Series. Application. Features. Applicable Literature

Powermite 599 MT Series SSC Electronic Valve Actuator, 24 Vac Proportional Control

Damper Actuator Installation

Powermite 599 MT Series SSC Electronic Valve Actuator, 24 Vac Proportional Control

M9106-AGx-2N0x Series Electric Non-spring Return Actuators

AV-602. Application. Globe Valve Linkage General Instructions

Installation Instructions

Installation Instructions

M9216 Series Electric Spring Return Actuators

MF /MS Series

DuraDrive MF /MS Series Non-spring Return Rotary Electronic Damper Actuators 24 Vac Three-position/Modulating

T158 Series. Application. Digital, Three-Wire Floating/On-Off Thermostat/Controller General Instructions. Features

VA-4233-GGx Series Electric Valve Actuators

Q7130A, Q7230A, Q7330A Modutrol IV Interface Modules

VA-640GSX024P. Overview. Applications. Features & Benefits. Datasheet. Large Globe Valve Actuators

VA-7450 Series. Electric Valve Actuators

Versatile and Powerful

System 350 S350P Proportional Plus Integral Temperature Stage Module

TAC TM Butterfly Valve Assemblies

OpenAir Electronic Damper Actuators GLB Series Enhanced Non-spring Return Rotary

How to Select the RE Industrial Actuator Part Number

DA-053 Series. Overview. Applications. Features & Benefits. Datasheet. 53lb-in (6 Nm), Non-Spring Return Damper Actuators

Minimum 27 in-lb torque

Series 71, 72, and 76 Modutrol IV Motors

ComfortPoint Programmable Lon, VAV/Unitary Controllers

Technical Instructions Flowrite 599 Series SKD6xU Electronic Valve Actuators 24 Vac Proportional Control Description Features Application

OpenAir Electric Damper Actuator GDE/GLB Series Non-spring Return, 24 Vac Floating Control, Rotary

GMX24-SR. Proportional Control, Non-Spring Return, Direct Coupled, 24V, for 2 to 10 VDC and 4 to 20 ma

D-70, D-140, D-210, and D-280 Series Electric Non-Spring Return Actuators

SAX Electronic Valve Actuator

M9203-xxx-2(Z) Series Electric Spring-Return Actuators

Flowrite EA 599 Series SKB/C/D 62UA Series Electronic Valve Actuator 24 Vac Proportional Control Advanced Features

OpenAir Electric Damper Actuator GDE/GLB Series Non-spring Return Rotary 24 Vac 3-position Control

LMCB24-SR LMCB24-SR-T. applications. Dimensions (All numbers in brackets are in millimeters.) 1/4 to 3/4 [6 to 20] 5/16 to 3/4 [8 to 26] 1.

Minimum 18 in-lb Torque. Applications. TF Series At A Glance. TF Series Spring Return Direct Coupled Actuator. For damper areas up to 4.

12 Series Linear Actuators. Operation & Maintenance Manual, Analog Positioner Installation

ELECTRIC ACTUATOR HVAC/BAC ELECTRIC IOM. E024, EO25, E026, EO29 & E030 Installation Operation and Maintenance Instructions TABLE OF CONTENTS

GM Series Direct Coupled Actuator

LF Series Spring Return Direct Coupled Actuator

ELECTRIC ACTUATOR 94OE IOM. E024, EO25, E026, EO29 & E030 Installation Operation and Maintenance Instructions TABLE OF CONTENTS

Flowrite EA 599 Series SKB/C/D 62UA Series Electronic Valve Actuator 24 Vac Proportional Control Advanced Features

Electric Modulating Actuator Installation, Operation & Maintenance Manual

Powermite 599 MT Series SSC Electronic Valve Actuator, 24 Vac Floating Control

Electric Actuator Instructions

D24-53 Series Electric Non-Spring Return Actuators 53 lb in Models (6 N m)

Minimum 27 in-lb Torque

Transcription:

CP-90 CP-90 Electronic Drives General Instructions Application The CP-90 and CP-90 electronic actuator drives process a variable input signal from a controller to provide proportional control of an electric gear train actuator. The CP-90 is preset at the factory for voltage input. The CP-90 is factory preset for current input and has additional wiring for connection to an override switch, for those applications requiring an external override of the input signal. These drives are equipped with built-in jumpers and adjustable potentiometers, so that the type of input signal, deadband, input span, and start point may be reset in the field when necessary. Features Mounts directly onto Schneider Electric proportional, electric, gear train actuators. Power is supplied directly from the actuator. May be used with all gear train actuator voltages and frequencies. Jumpers for selecting either voltage or current input, as well as % or 5% deadband. Adjustable span and start point potentiometers. Applicable Literature Environmental Controls Cross-Reference Guide, F-68 Rnvironmental Controls Reference Manual, F-68 Environmental Controls Application Manual, F-5 Pneumatic Products Catalog, F-78 MP-XX Series, MP-4XX Series, MP-XXX Series, and MP-4XXX Series Reversible and Proportional Electric s General Instructions, F-5479 MC-9000, MF-9000, and MP-9000 High Torque, Oil-Submerged s General Instructions, F- Printed in U.S.A. 4-0 Copyright 00 Schneider Electric All Rights Reserved. F-656-

SPECIFICATIONS Mounting: Directly to an actuator. The drive may be mounted on either the left or right side of the actuator, in a conduit opening adjacent to the low voltage wiring compartment. Case: Injection molded plastic with stamped aluminum cover. Inputs Voltage and Current Input: Refer to Table- and Adjustments Section. Input Span Adjustment: Refer to Table- and Adjustments Section. Start Point Adjustment: Refer to Table- and Adjustments Section. Input Impedance: Voltage Input, Greater than 0,000 ohms. Current Input, 50 ohms. Power Supply: Power shall be supplied directly from the shading coil windings provided on the shaded pole reversible motor of the gear train actuator (less than 0 Vac). Outputs Connections: Color-coded leads with crimped screw terminal connectors. Purge override (input signal override) leads are color-coded pigtails. Shading Coil Triac Output:. A RMS. Deadband: Refer to Table- and Adjustments Section. Environment Ambient Temperature Limits: Shipping & Storage, -40 to 60 F (-40 to 7 C). Operating, -40 to 6 F (-40 to 58 C). Humidity: 5 to 95% relative humidity, non-condensing. Locations: NEMA Type 4; IEC IP56. Agency Listings UL Listed: UL 87 (File #E949 Category Temperature Indicating and Regulating Equipment). Certified for use in Canada by Underwriters Laboratories. European Community: EMC Directive 89/6/EEC. Table- Model Chart. Part Number CP-90 CP-90 Input Signal Override Not Available Available (Use is Optional) Factory Presets Input Deadband Signal Voltage (6 to 9 Vdc) % of Current (4 to 0 madc) Input Span Start Point Input Span Jumper Settings Input Signal 6 Vdc Vdc Voltage or 4 madc 6 madc Current Potentiometer Adjustment Ranges Deadband Input Span Start Point % or 5% of Input Span.0 to 6.5 Vdc or 8 to 6 madc 0 to 0 Vdc or to 6 madc Table- Typical s. Power Torque Stroke Spring Internal Series Vac (60 Hz) Amp Lb-in. N-m Degrees Return Transformer a MP--500 4. 50 5.6 80 No MP-6 4.5 50 5.6 80 CW No MP-7 4.5 50 5.6 80 CCW No MP-8 4.5 0 4.9 80 No MP-97 4 4.0 800 90. 80 No MP-50-500 0 0.5 50 5.6 80 Yes MP-465 0 0.5 50 5.6 80 CW Yes MP-475 0 0.5 50 5.6 80 CCW Yes a Units with a - suffix, e.g. MP-XXXX-XXX--X, include a built-in transformer (used for Schneider Electric Microtherm or with AE-504) with secondary leads wired externally to terminals 7 (Blue, Vac) and 8 (Red, 4 Vac) of the actuator. Caution: When using the CP-90 or CP-90 with actuators containing an internal transformer, disconnect and tape off the red and blue leads before installing and powering the device. Failure to do so can result in damage to the actuator drive. Note: Models prior to - suffix had transformer wired directly to potentiometer. To disconnect the transformer, remove the back plate of the actuator, then disconnect and tape the transformer leads. Copyright 00 Schneider Electric All Rights Reserved. F-656-

Table- Typical s. (Continued) Series Power Torque Stroke Vac (60 Hz) Amp Lb-in. N-m Degrees MP-48 0 0.5 0 4.9 90 Yes MP-485 0 0.5 0 4.9 80 Yes MP-495 0 0.95 450 50.8 80 Yes MP-9750 0 0.9 800 90. 80 Yes MP-465 40 0.5 50 5.6 80 CW Yes MP-485 40 0.5 0 4.9 80 Yes a Units with a - suffix, e.g. MP-XXXX-XXX--X, include a built-in transformer (used for Schneider Electric Microtherm or with AE-504) with secondary leads wired externally to terminals 7 (Blue, Vac) and 8 (Red, 4 Vac) of the actuator. Caution: When using the CP-90 or CP-90 with actuators containing an internal transformer, disconnect and tape off the red and blue leads before installing and powering the device. Failure to do so can result in damage to the actuator drive. Note: Models prior to - suffix had transformer wired directly to potentiometer. To disconnect the transformer, remove the back plate of the actuator, then disconnect and tape the transformer leads. ACCESSORIES None Tools See tools listed in Requirements section. TYPICAL APPLICATIONS (wiring diagrams) Spring Return Internal Transformer a Refer to Figure- for a service application wiring diagram showing the connections between a CP-90 or CP-90 drive and an MP-XX, MP-4XX, MP-XX, or MP-97XX series actuator. Figure-, Figure-, and Figure-4 diagram the connection of multiple actuators. CP-90 or CP-90 Drive Yellow Blue Violet/White Violet Brown/White Brown Brown/Black Red/Black Blue/Black Yellow/Black Green/Yellow Caution: Before installing the actuator drive onto actuators equipped with an internal transformer, the red and blue leads must be disconnected from actuator terminals 7 and 8, and taped off. Failure to do so will result in damage to the actuator drive. As diagrammed, increasing input causes CW actuator rotation. All references to the direction of rotation are determined by facing the actuator output shaft. The wires to terminals 7 and 8, and and, may be reversed for CCW rotation with an increasing input signal. 4 MP-XXXX-XXX-X- models are equipped with an external green jumper from terminal X to the terminal block mounting screw (ground). If the application requires it, this jumper may be removed for isolation purposes. 5 4 Vac models are equipped with a jumper from terminal G to the case ground screw. 6 The green/yellow wire must be installed under the terminal block mounting screw. 7 Shield must be grounded to the terminal block mounting screw. 6 Terminals 7 4 8 X 4 6 7 L (H) L (G) MP-XX, MP-4XX, MP-XX, or MP-97XX Series Wire Nuts Drive Input Common Purge Input (Override Input) Purge + (Override +) 00 Ohm Slidewire Limit Switches Shading Windings Field Winding 5 7 To Controller Purge Override (Input Signal Override) 8 From Power Source 8 Purge override (input signal override) is available on CP-90 only. A dry contact closure from the override input (violet/white) lead to the blue lead of the actuator drive forces the actuator to drive to the end of travel, independent of the input signal conditions. Connecting the violet/white and violet leads together forces the actuator to drive to the opposite (high input signal) end of travel, independent of input signal conditions. Figure- Service Application Wiring Diagram. F-656- Copyright 00 Schneider Electric All Rights Reserved.

Voltage Input from Controller + _ Yellow (OP) Blue (COM) Yellow (OP) Blue (COM) Yellow (OP) Blue (COM) To Additional s drives configured for voltage input. The maximum number of actuators that may be connected to one controller is limited by the amount of current the controller can supply. Figure- Typical Control Wiring for Multiple s with Drives Configured for Voltage Input. Current Input from Controller + _ Yellow (+) Blue (-) CP-90 drives configured for current input. This diagram shows a typical installation consisting of two actuators connected in series. When configured for current input, the maximum number of actuators that may be connected to one controller is limited by the amount of voltage the controller can supply. CP-90 actuator drives are available with a purge override (input override) feature. Use of this override feature is optional. Blue (-) Purge Override (Input Signal Override) Yellow (+) Blue (-) Purge Input (Override Input) Purge + (Override +) CP-90 Figure- Typical Control Wiring for Two s with Drives Configured for Current Input. 4 Copyright 00 Schneider Electric All Rights Reserved. F-656-

Current Input from Controller + _ Yellow (+) Blue (-) CP-90 drives configured for current input. Each actuator requires 5 Vdc at 0 ma, at full scale. When configured for current input, the maximum number of actuators which may be connected in series is limited by the output voltage the controller can supply. CP-90 actuator drives are available with a purge override (input override) feature. Use of this override feature is optional. Yellow (+) Blue (-) Purge Override (Input Signal Override) Yellow (+) Blue (-) Purge Input (Override Input) Purge + (Override +) CP-90 CP-90 Purge Input (Override Input) Purge Override (Input Signal Override) Purge + (Override +) INSTALLATION Figure-4 Typical Control Wiring for Three or More s with Drives Configured for Current Input. Inspection Requirements Inspect the package for damage. If damaged, notify the appropriate carrier immediately. If undamaged, open the package and inspect the device for obvious damage. Return damaged products. Tools (not provided): Appropriate screwdriver Slip joint pliers Digital Volt-ohm Meter (DVM) Suitable voltage signal source (for voltage start point and input span adjustment) Milliamp meter Suitable current signal source (for current start point and input span adjustment) Training: Installer must be a qualified, experienced technician Other accessories as required to install the actuator Wiring diagrams Warning: Electrical shock hazard! Disconnect power before installation to prevent electrical shock or equipment damage. Make all connections in accordance with the electrical wiring diagram and in accordance with national and local electrical codes. Use copper conductors that are suitable for 05 C. Caution: Do not exceed the ratings of the device(s). Static charges produce voltages high enough to damage the electronic components. Follow static electricity precautions when installing or servicing the device(s). Avoid locations where excessive oil, dust, moisture, corrosive fumes or vibration, or an explosive atmosphere is present. F-656- Copyright 00 Schneider Electric All Rights Reserved. 5

Mounting The drive may be mounted on either the left or right side of the actuator, in a conduit opening adjacent to the low voltage wiring compartment. Mount the drive onto an actuator as follows:. Remove the cover from the actuator, to expose its power wiring compartment and low voltage wiring compartment. Note that each side of the actuator casing features two /" knockouts which provide access to these two compartments.. Determine on which side of the actuator the drive is to be mounted (Figure-5, Figure-6, and Figure-0). Remove the knockout on that side, adjacent to the low voltage wiring compartment.. Temporarily remove the locknut from the drive. Verify that the O-ring (Figure-6 and Figure-0) is fully seated on the drive s casing, and insert the drive s /" conduit connector into the opening from which the knockout was removed. Drive Drive Left-Side Mounting Right-Side Mounting Figure-5 Mounting Position of Drive on. 4. Secure the drive to the actuator with the locknut removed in step. Refer to Figure-6. 5. Connect the drive to the actuator according to the instructions in the Wiring section. 5 To Controller + _ 5 From Power Source Low Voltage Wiring Compartment Drive Input Common Ground L (H) L (G) 6 Case Ground Screw L (H) 5 L (G) 6 8 x 7 4 Power Wiring Compartment Barrier Drive Purge Override (Input Signal Override) 4 5 Purge Input (Override Input) Purge + (Override +) Top view. Shield Right-side mounting is shown. Shield Alternate left-side mounting. 4 Purge override (input signal override) is available with CP-90 only. 5 Make all connections in accordance with the electrical wiring diagram and in accordance with national and local electrical codes. Use copper conductors that are suitable for 05 C. 6 The terminals marked L and L on 0 and 40 Vac actuators are marked H and G on 4 Vac actuators. O-Ring Terminal Block Mounting Screw Locknut (Ground) 7 7 Ground the following at the terminal block mounting screw: the shield wire; the drive's green/yellow ground wire; and the jumper wire from terminal X (MP-XXXX-XXX-X- models). Figure-6 /Drive Wiring and Mounting Arrangement. 6 Copyright 00 Schneider Electric All Rights Reserved. F-656-

WIRING Power Wiring Input Wiring The power for the drive is supplied directly from the shading coil windings of the gear train actuator onto which the drive is mounted. Refer to Figure-7 or Figure-8 for an installation wiring diagram. Power wiring instructions for the gear train actuator may be found in MP-XX Series, MP-4XX Series, MP-XXX Series, and MP-4XXX Series Reversible and Proportional Electric s General Instructions, F-5479, or in MC-9000, MF-9000, and MP-9000 High Torque, Oil-Submerged s General Instructions, F-. The drive s two input leads, which must be connected to the controller, are color-coded blue (common) and yellow (drive input). Refer to Figure-7 if the drive is configured for voltage input (factory preset for CP-90), and to Figure-8 when the input jumper is positioned for current input (factory preset for CP-90). The connections to the low voltage wiring compartment may be per Class circuit requirements. Use 8 to gage, two-conductor (CP-90) or four-conductor (CP-90), shielded cable for runs of up to 000 ft. (05 m) between the controller and the actuator. Use larger-sized leads for longer runs. Caution: Before installing the CP-90 or CP-90 onto actuators equipped with an internal transformer, disconnect the red and blue leads from actuator terminals 7 and 8, and tape off. Failure to do so will result in damage to the actuator drive. Ground the shielding on the signal leads at one end only, using the actuator s terminal block mounting screw. Grounding the shielding at both ends could create a potential difference in the shielding, which may affect the signal carried by the leads. Yellow / Black Blue / Black 6 Red / Black Brown Violet/White Purge Input (Override Input) Violet Purge + (Override +) Yellow + Yellow (OP) Purge Override (Input Signal Override) Blue Blue (COM) Blue Terminal Block Mounting Screw (Ground) 4 4 5 6 7 8 L Brown / White 6 Brown / Black Green/Yellow 8 Shield Wire CP-90 or CP-90 Drive 7 Typical Controllers TP-80 CP-80 Red + _ 7 X L Typical Power Supply ASP-800 Series 5 Case Ground Screw AC Supply Caution: Before installing the CP-90 or CP-90 onto actuators equipped with an internal transformer, disconnect the red and blue leads from actuator terminals 7 and 8, and tape off. Failure to do so will result in damage to the actuator drive. The L and L terminals are marked H and G on 4Vac actuators. Purge override (input signal override) is available on CP-90 only. A dry contact closure from the purge (override) input lead (violet/white) to the blue lead of the actuator drive forces the actuator to drive to the end of travel, independent of the input signal conditions. Connecting the violet/white and violet leads together forces the actuator to drive to the opposite (high input signal) end of travel, independent of input signal conditions. If the purge override (input signal override) function is not used, be sure to tape off the violet/white and violet leads. 4 MP-XXXX-XXX-X- models are equipped with an external green jumper from terminal X to the terminal block mounting screw (ground). If the application requires it, this jumper may be removed for isolation purposes. 5 4 Vac models are equipped with a jumper from terminal G to the case ground screw. 6 As diagrammed, increasing input causes CW actuator rotation. For CCW rotation with an increasing input signal, reverse blue/black and red/black leads, and reverse brown/black and brown/white leads. All references to the direction of rotation are determined by facing the actuator output shaft. 7 Supplied by customer. 8 Ground the shield wire and the drive's green/yellow ground wire at the actuator's terminal block mounting screw. Figure-7 Installation Wiring Diagram for Voltage Inputs. F-656- Copyright 00 Schneider Electric All Rights Reserved. 7

Yellow / Black Blue / Black 6 Red / Black Brown Violet/White Purge Input (Override Input) Violet Purge + (Override +) Yellow Drive Input (+) Purge Override (Input Signal Override) Blue Common (-) Terminal Block Mounting Screw (Ground) 4 4 5 6 7 8 L Brown / White 6 Brown / Black Green/Yellow 7 Shield Wire CP-90 or CP-90 Drive 4 to 0 madc Controller Input X L 5 Case Ground Screw AC Supply Caution: Before installing the CP-90 or CP-90 onto actuators equipped with an internal transformer, disconnect the red and blue leads from actuator terminals 7 and 8, and tape off. Failure to do so will result in damage to the actuator drive. The L and L terminals are marked H and G on 4Vac actuators. Purge override (input signal override) is available on CP-90 only. A dry contact closure from the purge (override) input lead (violet/white) to the blue lead of the actuator drive forces the actuator to drive to the end of travel, independent of the input signal conditions. Connecting the violet/white and violet leads together forces the actuator to drive to the opposite (high input signal) end of travel, independent of input signal conditions. If the purge override (input signal override) function is not used, be sure to tape off the violet/white and violet leads. 4 MP-XXXX-XXX-X- models are equipped with an external green jumper from terminal X to the terminal block mounting screw (ground). If the application requires it, this jumper may be removed for isolation purposes. 5 4 Vac models are equipped with a jumper from terminal G to the case ground screw. 6 As diagrammed, increasing input causes CW actuator rotation. For CCW rotation with an increasing input signal, reverse blue/black and red/black leads, and reverse brown/black and brown/white leads. All references to the direction of rotation are determined by facing the actuator output shaft. 7 Ground the shield wire and the drive's green/yellow ground wire at the actuator's terminal block mounting screw. Figure-8 Installation Wiring Diagram for Current Inputs. 8 Copyright 00 Schneider Electric All Rights Reserved. F-656-

ADJUSTMENTS Voltage Input Adjustments The CP-90 and CP-90 actuator drives feature one jumper for selecting voltage or current input, a second jumper for selecting % or 5% deadband, and potentiometers for adjusting the input span and start point. The CP-90 is preset at the factory for voltage input, and the CP-90 is preset for current input (Table-). When necessary, these factory presets may be changed according to the procedures in this section. When a CP-90 has been left at its factory presets, the settings detailed in Table- apply. If a CP-90 requires adjustments to its deadband, startpoint, or input span, or if a CP-90 is to be reconfigured for voltage input, make adjustments according to the following: Caution: Do not apply a current source input to a CP-90 or CP-90 actuator drive that is configured for voltage input (factory setting). Doing so may damage the drive. Static charges produce voltages high enough to damage the electronic components. Follow static electricity precautions when servicing the device(s).. Turn off the controller signal to the drive s input.. Turn off power to the actuator.. Remove the screw that secures the cover to the drive, then remove the cover. This provides access to the start point and input span adjustment potentiometers, as well as the input and deadband jumpers (Figure-9). Start Point Potentiometer Input Span Potentiometer % Deadband (Factory Preset) Voltage Input (CP-90 Factory Preset) 5% Deadband Current Input (CP-90 Factory Preset) Alternate Jumper Settings Figure-9 Input and Deadband Jumpers, and Input Span and Start Point Potentiometers. 4. Disconnect the drive s yellow and blue leads from the controller. 5. When reconfiguring a CP-90 for voltage input, reposition the input jumper to the voltage input setting, as shown in Figure-9. 6. Connect the leads of a suitable voltage signal source (voltage calibrator) to the appropriate drive leads. 7. Connect a DVM to the yellow (drive input) and blue (COM) leads of the drive. 8. Apply power to the actuator, then turn on the voltage signal source. 9. If desired, reset the deadband by repositioning the deadband jumper. 0. Adjust the voltage signal source (voltage calibrator) until the DVM reading equals the desired start point voltage (0 to 0 Vdc).. With the desired start point voltage applied, adjust the start point potentiometer, using a small screwdriver, so that the actuator shaft just reaches the start point. F-656- Copyright 00 Schneider Electric All Rights Reserved. 9

. Determine the finish point of the actuator by adding the desired voltage span to the start point voltage. The finish point is the voltage that causes the actuator to just reach its rotational limit. Adjust the voltage signal source (voltage calibrator) until the DVM reading equals the calculated finish point voltage.. With the finish point voltage applied, adjust the input span potentiometer, using a small screwdriver, so that the actuator shaft just reaches its rotational limit. Note: Occasionally, an adjustment to the input span setting results in a change to the start point setting, due to a small interaction between these two settings. After adjusting the input span potentiometer, ensure that both settings meet requirements by repeating steps 0 through, as necessary. 4. Turn off the voltage input signal to the drive and turn off power to the actuator. Then, reconnect the drive s leads to the controller. 5. Reinstall the cover onto the drive and secure it with the screw removed in step. 6. Reapply power to the actuator, then turn on the controller signal to the drive s voltage input. Current Input Adjustments When a CP-90 has been left at its factory presets, the settings detailed in Table- apply. If a CP-90 requires adjustments to its deadband, startpoint, or input span, or if a CP-90 is to be reconfigured for current input, make adjustments according to the following: Caution: Do not apply a voltage source input to a CP-90 or CP-90 actuator drive that is configured for current input. Doing so may damage the drive. Static charges produce voltages high enough to damage the electronic components. Follow static electricity precautions when servicing the device(s).. Turn off the controller signal to the drive s current input.. Turn off power to the actuator.. Remove the screw that secures the cover to the drive, then remove the cover. This provides access to the start point and input span adjustment potentiometers, as well as the input and deadband jumpers (Figure-9). 4. Disconnect the drive s yellow and blue leads from the controller. 5. When reconfiguring a CP-90 for current input, reposition the input jumper to the current input setting, as shown in Figure-9. 6. Connect a digital ma meter in series with the current signal source (current calibrator) by connecting the meter s red lead to the signal source s + output, and the meter s black lead to the drive s yellow lead. 7. Connect the drive s blue (common [-]) lead to the corresponding lead of a suitable current signal source (current calibrator). 8. Apply power to the actuator, then turn on the current signal source (current calibrator). 9. If desired, reset the deadband by repositioning the deadband jumper. 0. Adjust the current signal source (current calibrator) until the ma meter reading equals the desired start point current ( to 6 madc).. With the desired start point current applied, adjust the start point potentiometer, using a small screwdriver, so that the actuator shaft just reaches the start point.. Determine the finish point of the actuator by adding the desired current span to the start point current. The finish point is the current that causes the actuator to just reach its rotational limit. Adjust the current signal source (current calibrator) until the ma meter reading equals the calculated finish point current.. With the finish point current applied, adjust the input span potentiometer, using a small screwdriver, so that the actuator shaft just reaches its rotational limit. 0 Copyright 00 Schneider Electric All Rights Reserved. F-656-

Note: Occasionally, an adjustment to the input span setting results in a change to the start point setting, due to a small interaction between these two settings. After adjusting the input span potentiometer, ensure that both settings meet requirements by repeating steps 0 through, as necessary. 4. Turn off the current input signal to the drive and turn off power to the actuator. Then, reconnect the drive s leads to the controller. 5. Reinstall the cover onto the drive and secure it with the screw removed in step. 6. Reapply power to the actuator, then turn on the controller signal to the drive s current input. CHECKOUT Positioning with Controller Manual Positioning MAINTENANCE FIELD REPAIR After the entire system has been installed and the actuator has been powered up, the following checks can be made to verify proper system operation. If the sensed media is within the controller s throttling range, the actuator can be positioned by adjusting the controller setpoint up and down. Check for correct operation of the actuator (valve or damper) while it is being stroked. Use a DVM or ma meter to verify the actual signal that is applied. A manual positioning test of the drive may be conducted by performing the start point and input span adjustment procedure. Where the procedure calls for adjustments to be made to the potentiometers, simply verify that the actuator shaft is just reaching the start point or is just reaching its limit, as applicable. The drive requires no maintenance. Regular maintenance of the total system is recommended to assure sustained, optimum performance. None. Replace an inoperative drive with a functional unit. F-656- Copyright 00 Schneider Electric All Rights Reserved.

DIMENSIONAL DATA O-Ring Conduit Locknut /" Conduit Bushing -/4" (57 mm) -/4" (70 mm) -/8" (54 mm) -/8" (9 mm) -/4" (70 mm) Figure-0 Mounting Dimensions of CP-90 and CP-90 Electronic Drives. On October st, 009, TAC became the Buildings business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric, however there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate corporate brand changes. Copyright 00, Schneider Electric All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice. F-656- Schneider Electric 54 Clifford Avenue P.O. Box 940 Loves Park, IL 6-940 www.schneider-electric.com/buildings