FSD60, FSD60LP COMBINATION FIRE AND SMOKE DAMPER 1 1 /2 HOUR UL555 RATED, UL555S LEAKAGE CLASS 1

Similar documents
FSD36, FSD36LP COMBINATION FIRE AND SMOKE DAMPER

FSD60, FSD60LP CoMBINAtIoN FIRe AND SMoKe DAMPeR

FSD36, FSD36LP COMBINATION FIRE AND SMOKE DAMPER 1 1 /2 HOUR UL555 RATED, UL555S LEAKAGE CLASS 2

Model SMD-302M. Modulating Smoke Damper. Application. Steel Airfoil Blades UL 555S Leakage Class II. Ratings. Size Limitations.

Model SMD-301. Smoke Damper Steel Airfoil Blades UL 555S Leakage Class I. Application. Ratings. Size Limitations. Features

Model SSFSD-211. Combination Fire Smoke Damper 304 Stainless Steel 3V Blades UL 555S Leakage Class I UL Hour Fire Resistance Rating

Model FSD-331. Combination Fire Smoke Dampers. Application. Ratings. Features

Model FSD-331 Combination Fire Smoke Dampers

Model FSD-211. Application. Combination Fire Smoke Damper Steel 3V Blades UL 555S Leakage Class I UL /2 Hour Fire Resistance Rating.

Model FSD-211. Combination FIRE SMOKE DAMPERS Steel 3-V Blades UL 555S Leakage Class I UL Hour Fire Resistance Rating

SMD-201. Application. Smoke Dampers Steel 3V Blades UL 555S Leakage Class I. Ratings. Operational Rating. Size Limitations.

Model CFSD-211. Corridor Ceiling FIRE SMOKE DAMPER Steel 3V Blades UL 555S Leakage Class I

SMD-201M. Application. Modulating Smoke Dampers Steel 3V Blades UL 555S Leakage Class I. Ratings. Operational Rating. Size Limitations.

Model FSD-212. Combination FIRE SMOKE DAMPERS

SD-1250 and SD-1600 Series Smoke Dampers

Model DFD-230 Multi-Blade Fire Damper Steel 3V Blades UL555 3 Hour Fire Resistance Rating

TED50XT EXTREME TEMPERATURE THERMALLY EFFICIENT, INSULATED BLADE DAMPER

Model DFD-150. Dynamic Rated Fire Damper 11/2 Hour Fire Resistance Rating. Application. Ratings. Optional Features

Model SEVCD-33. Low Leakage Airfoil Control Damper. Application and Design. Ratings (See page 3 for specific limitations) Blade Operation

Model DFD-150. Dynamic Rated Fire Damper 11/2 Hour Fire Resistance Rating. Application. Ratings. Optional Features

VCD-23 Low Leakage CONTROL DAMPER

Model VCD-20. Control Damper. Application. 3V Blade. Ratings. Flange Options. Size Limitations. Blade Operation. Features and Options

VCD-23. Low Leakage CONTROL DAMPER

Model VCD-40. Extruded Airfoil Blade Control Damper Narrowline Frame Construction. Application. Ratings. Flange Options.

Model DFD-350. Dynamic Rated Fire Damper 3 Hour Fire Resistance Rating. Application. Ratings. Optional Features

Model VCD-43 Extruded Airfoil Blade Control Damper

FBV-43. Vertical Face & Bypass Control Damper Ultra Low Leakage Aluminum Frame Construction. Application and Design. Size Limitations.

Model VCD-20 3V CONTROL DAMPER

Model VCD-34. Low Leakage Insulated Airfoil CONTROL DAMPER. Ratings (See page 3 for specific limitations) Flange Options.

HCD-135. Industrial Control Damper. Application and Design. Ratings (see page 2 and 3 for specific limitations) Standard Construction.

Model VCD-33. Low Leakage Airfoil CONTROL DAMPER. Flange Options. Blade Operation. Size Limitations

Model VCD-20V. 3V Vertical Control Damper. Application and Design. Ratings (See page 4 for specific limitations) Flange Options.

Baked Enamel, Epoxy, Hi Pro Polyester, Industrial Epoxy, Kynar/Hylar (70%) Permatector. Single or Reverse Flange 8 x 6 (203 x 178)

Fire Dampers Catalogue

VCD-23. Flange Options. Size Limitations

Model VCD-18. Ratings. Blade Operation. Size Limitations. Features & Options

Model FDD Dynamic Curtain Fire Damper 1-½ or 3 Hour, UL555 Listed

Model FD-350. Static Rated Fire Dampers 3 Hour Fire Resistance Rating. Application. Ratings. Construction Standard Optional.

VCD-43V. Vertical Airfoil Blade Control Damper. Application and Design. Ratings. Size Limitations. Features and Options: Pressure:

Fire, Smoke, and Combination Fire Smoke Dampers

AMD-33. Air Measuring Station with VCD-33 Control Damper. Application and Design. Features & Control Options

Fusible Link (replaceable) Horizontal Mount

AMD-33 Air Measuring Station with VCD-33 Control Damper

B. Fabricate in accordance with ASHRAE handbooks and SMACNA duct manuals. A. Submit in accordance with Division-1 and Section

Smoke Dampers. Installation Instructions

SP Standard Profile. In Duct or Flanged to Duct Install Types OPPOSED ACTION PARALLEL ACTION. Extended Rear Flange Install Type

SMOKE DAMPERS SMOKE DAMPERS SMOKE DAMPERS

HCD-230 Industrial Control Damper

Life Safety Dampers. Fire Combination Fire Smoke Smoke Ceiling Radiation

Nobody delivers dampers and louvers faster!

Introduction to Johnson Controls Dampers

3900 Dr. Greaves Rd. Kansas City, MO (816) FAX (816) ABD-SEA-E

Control Dampers and Fire Dampers. Volume 1 - March Insulated Control Dampers. Non-Insulated Control Dampers. Framing. Accessories.

CONTROL DAMPERS. Model Model 1370CB. Model 1380CB. Model 1390CB B7

FIBERGLASS DAMPERS FOR ODOR CONTROL AND CORROSIVE HVAC SYSTEMS

Insulated Control Damper. 12 x 7 (305 x 178) 8 x 7 (203 x 178)

AMD-42V Air Measuring Station with VCD-42V Control Damper

AMD-42 Air Measuring Station with VCD-42 Control Damper

Fusible Link (replaceable) Horizontal Mount

CFSD Series. Product Description

Insulated Control Damper. 1/2 in. (13mm) 1/2 in. (13mm) 12 x 12 (305 x 305) 8 x 12 (203 x in. W x 120 in. H (3658mm x 3048mm) 5 in.

CONTROL DAMPERS. Models 1810 & Model Model Model 1370

Thermal Isolation Break. Frame Type Channel Quick Connect Single or Reverse Flange Blade Action Parallel Opposed Parallel Opposed Parallel Opposed

DAMPERS FOR COMMERCIAL & INDUSTRIAL APPLICATIONS IN HEATING, VENTILATING & AIR CONDITIONING

HVAC Control & Balancing Dampers

AMCA MEMBER. American Warming and Ventilating. A Mestek Company. Quality Air Control Dampers

Air Measuring Products AMD AMS IAQ

FIBERGLASS ROUND CONTROL DAMPERS. Model K-RD INTRODUCTION M.K. PLASTICS PROVIDES FOUR DAMPER MODELS K-RD SUGGESTED SPECIFICATION

SMOKE DAMPER - CLASS F MODEL BMSD

Insulated Control Damper. 1/2 in. (13mm) 1/2 in. (13mm) 12 x 12 (305 x 305) 8 x 12 (203 x 305) 5 in. (127mm) Parallel

MULTI-BLADE FIRE DAMPERS

CURTAIN TYPE FIRE DAMPER

AMD-42-TD. Thermal Dispersion Air Measuring Station with VCD-42 Control Damper. Application and Design. Ratings. Features and Control Options

CONTROL & BACKDRAFT DAMPERS. Nailor. Industries Inc.

COMBINATION FIRE/SMOKE DAMPER - CLASS F MODEL BMFSD (3 HR) / MODEL BEMFSD (1½ HR)

Thermal Isolation. Break

Air Quality Solutions

VD-1600 Series Volume Control Dampers

Model FD Static Curtain Fire Damper 1-½ or 3 Hour, UL555 Listed

Motorized Fire Dampers

MULTI-BLADE FIRE DAMPERS

ZONE DAMPERS. Form No. PDS DAMP.0.3

Installation, Operation and Maintenance Manual

AD-1250 Airflow Measuring Station

ARROW INDUSTRIAL PRODUCTS

Life Safety Dampers - International. Fire Combination Fire Smoke Smoke Ceiling Radiation

BD-1600 Balancing/Zone Control Damper

WD-300 Series. Backdraft Damper Vertical Mount - Horizontal Airflow. Application and Design. Ratings. Frame Styles. Size Limitations.

Series HCD Airfoil Control Damper

AMD-23-TD. Thermal Dispersion Air Measuring Station with VCD-23 Control Damper. Application. Ratings. Features and Options

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION DUCTWORK ACCESSORIES

Installation, Operation and Maintenance Manual

CONTROL DAMPERS GENERAL PRODUCT OVERVIEW MODELS 1010 & 1020 LOW LEAKAGE CONTROL DAMPER VEE GROOVE BLADE MODELS 1012 & 1022 STANDARD CONTROL DAMPER

AIR DUCT ACCESSORIES

ID-141x 12-Gauge Hat Channel Industrial Damper

LLOYD INDUSTRIES INC.

The IAQ50 Air Damper/Monitor Installation and Maintenance Manual

AMCA International. Guide for Commissioning and Periodic Performance Testing of Fire, Smoke and Other Life Safety Related Dampers

SECTION DUCTWORK ACCESSORIES

FOR USE IN SOLUTION AIR HANDLING UNITS

Transcription:

3900 Dr. Greaves Rd. Kansas City, MO 64030 (816) 761-7476 FX (816) 765-8955 FSD60, FSD60LP COMINTION FIRE ND SMOKE DMPER 1 1 /2 HOUR UL555 RTED, UL555S LEKGE CLSS 1 PPLICTION Ruskin FSD60 Series ultra low leakage combination fire and smoke dampers provide point-of-origin fire and smoke containment. The FSD60 includes high strength one-piece airfoil blades to ensure the lowest resistance to airflow and is rated up to 4000 fpm (20.3 m/s) and 8 in. wg (2 kpa). Ruskin FSD60LP ultra low leakage, low profile, and low pressure drop combination fire and smoke damper is provided with an integral sleeve/frame design. ll FSD60 Series dampers may be installed vertically in walls or horizontally in masonry floors and are rated for airflow and leakage in either direction. STNDRD CONSTRUCTION Description FSD60 FSD60LP Frame lades earings Jamb Seal lade Seal Linkage 5"x16gage(127x1.6) galvanized, single piece, hat-shaped channel, structurally superior to 13 (2.3) gage channel frame. One-piece airfoil, 6" (152) wide and 16 (1.6) gage galvanized steel equivalent thickness. lades are approximately 6" (152) on center. Stainless steel sleeve type, pressed into frame. Stainless steel, flexible metal compression type. Silicone edge type for smoke seal to 450 F (232 C) and galvanized steel for flame seal to 1900 F (1038 C) mechanically fastened to the blade edge. Concealed in frame. Integral sleeve and frame 20 (1.0) gage galvanized single piece. One-piece low profile aerodynamic shape, 20 gage (1.0) galvanized. Stainless steel sleeve type, pressed into frame. Stainless steel, flexible metal compression type. Stainless steel, flexible metal compression type. DMPER SIZES Sizes indicated below are for ratings of 2000 FPM (10.2 m/s) and 4 in. w.g. (1 kpa). MINIMUM SIZE FSD60LP - 6"w x 6"h (152 x 152) FSD60-8"w x 6"h (203 x 152) MXIMUM SIZE FSD60LP Single Section Vertical or Horizontal 36"w x 14"h (914 x 356) FSD60 Single Section Vertical 32"w x 48"h (813 x 1219) Single Section Horizontal 30"w x 48"h (762 x 1219) FSD60 Multiple Section Vertical 120"w x 96"h (3048 x 2438) Multiple Section Horizontal Electric ctuator 120"w x 96"h (3048 x 2438) Pneumatic ctuators 144 w x 96 h (3658 x 2438) CONTROLLED CLOSURE DEVICE (HET-CTUTED) EFL (Electric Fuse Link) - 165 F (74 C) standard. 212 F (100 C), 250 F (121 C), 350 F (177 C) available. PFL (Pneumatic Fuse Link) - 165 F (74 C) standard. 212 F (100 C), 285 F (141 C) available. NOTES 1. Dampers are furnished approximately 1 /4" (6) smaller than given opening dimensions. 2. Dimensions shown in parentheses ( ) indicate millimeters. N/ Height MXIMUM OPERTIONL RTINGS Description FSD60 FSD60LP UL555S Leakage Rating Class I Class I UL555 Hourly Rating 1 1 /2 Hour 1 1 /2 Hour Maximum Velocity 4000 FPM (20.3 m/s) 2000 FPM (10.2 m/s) Maximum Pressure 8in.wg (2 kpa) 4in.wg (1 kpa) Temperature 350 F (177 C) 350 F (177 C) OPTIONS FM pprovals as Specification Tested Product. DTS (Damper Test Switch) test switch for cycle testing. TS150 FireStat for reopenable operation in dynamic smoke management systems. DSDF/DSDN Duct Smoke Detector (Flow rated or No-Flow). SP100 Switch Package to allow remote indication of damper blade position. MCP control panels for test purposes or smoke management systems. Factory s of various lengths and gages to ensure field compliance with UL installation requirements. FST ngle factory supplied for labor saving angle one-side installation. Other angles of various sizes and gages also available for oneside or two-side installation. UL CLSSIFIED UL555 Listing R5531 FSD60 Model FSD60 series meets the requirements for smoke dampers established by: National Fire Protection ssociation NFP Standards 80, 90, 92, 92 and 101 ICC International uilding Codes CSFM California State Fire Marshal Listing (#3235-0245:0126) New York City (S Listing #176-82-SM) Spec FSD60-211/Replaces FSD60-909 LL STTED SPECIFICTIONS RE SUJECT TO CHNGE WITHOUT NOTICE OR OLIGTION. Ruskin 2011

FSD60 MC LICENSED IR PERFORMNCE DT Ruskin Company certifies that the FSD60 shown hereon is licensed to bear the MC Seal. The ratings shown are based on tests and procedures performed in accordance with MC Publication 511 and comply with the requirements of the MC Certified Ratings Program. The MC Certified Ratings Seal applies to air performance for the FSD60. The FSD60LP pressure drop depicted on the chart below is preliminary data only. MC Certified testing pending. To determine the MC Licensed air performance: Locate the applicable feet per minute face velocity on the bottom of the velocity vs. pressure drop chart below. Move up the chart to the most appropriate size damper line. From the intersection point, move left to determine the pressure drop on the left side of the chart. For other damper sizes refer to ir Performance Data For ll Fire and Smoke Dampers spec sheet. VELOCITY vs. PRESSURE DROP PRESSURE DROP (INCHES W.G.) 12 x 12 FSD60LP FCE VELOCITY FEET/MINUTE MC Fig. 5.3

EXTENDED OPERTIONL RTINGS (FSD60 ONLY) The UL555 and UL555S Test Standards require all fire smoke dampers to prove closure or operation against heated air flow velocities of at least 2,000 feet per minute (10.2 m/s) and 4 inches of water (1 kpa) and minimum operating temperature of 250 F. ll Ruskin fire smoke dampers in all sizes meet the minimum requirements. In addition Ruskin FSD60 dampers exceed those minimum requirements. Ruskin FSD60 dampers exceed these minimum requirements in many cases. MODEL 2,000 FPM Fail Close Operation SIZE STTIC PRESSURE TEMPERTURE INSTLLTION FSD60 120 x 96 4 w.g. 350 Vertical FSD60 144 x 96 4 w.g. 350 Horizontal FSD60LP 36 x 14 4 w.g. 350 Vertical or Horizontal 3,000 FPM Fail Close Operation 64 x 72 FSD60 120 x 36 4 w.g. 250 Vertical 32 x 96 60 x 72 FSD60 120 x 36 4 w.g. 250 Horizontal 30 x 96 64 x 64 FSD60 120 x 32 4 w.g. 350 Vertical 32 x 96 60 x 64 FSD60 120 x 32 4 w.g. 350 Horizontal 30 x 96 FSD60 120 x 96 6 w.g. 250 Vertical FSD60 144 x 96 6 w.g. 250 Horizontal 4,000 FPM Fail Close Operation 48 x 48 Vertical FSD60 96 x 24 8 w.g. 250 or 24 x 96 Horizontal CTUTOR REQUIREMENTS * UL555S requires that all smoke dampers have factory mounted actuators in order to bear the UL label. Fire smoke dampers larger than single section may require multiple actuators. See Smoke Damper Multiple Section Detail spec sheet for details. Ruskin s smoke dampers are UL555S labeled with either electric or pneumatic actuators mounted internal (in air stream) or external (out of air stream). Fire smoke dampers utilizing multiple actuators must have all actuators field wired to a common point for simultaneous closure. ll field wiring shall be in accordance with applicable codes, ordinances and regulations. FSD60LP SLEEVE DIMENSIONL DT The drawing shows the standard position of the FSD60LP when installed. The mounting location provides enough space for the actuators, controls (FST) retaining angles and duct connections. The minimum sleeve length is 20 (508). Consult Ruskin for shorter sleeve lengths. NOTES 1. The entire frame is not required to be installed within the wall. The center line of the closed blade, should be contained within the wall. 2. See basic UL installation instructions for complete installation requirements. 20 (508) or 24 (610) Wall Depth 10 1 /2 (267) Min. 12 (305) Max.

FSD60 SLEEVE DIMENSIONL DT The drawing and corresponding table show the position of the damper when mounted in a factory sleeve. The standard mounting locations provide enough space for the mounting of actuators, controls, installation of retaining angles, and duct connections. The minimum factory sleeve length is 17" (432). Consult Ruskin for shorter sleeve lengths. The standard location of a damper mounted in a factory sleeve ("L" dimension) is shown at right. * L Wall/ Floor 3 (76) Ref. L * Wall/ Floor 3 (76) Ref. *Minimum Formula: = "L" dimension + wall/floor thickness + 3" sleeve nonmotor side NOTE: 1. The entire damper frame is not required to be installed within the wall. The damper blades, when closed should be contained within the wall. 2. See basic UL installation instructions for complete installation requirements. and Over ctuator Side ll dampers with EFL or PFL Over 10" (254) 10" (254) and Electric ctuators Over 21" (533) (see note) 21" (533) and (see note) Over 28" (711) ll dampers with TS150, SP100 or DTS Pneumatic ctuators 331-4827(P) 331-2961(P) 331-3060(P) 28" (711) & Over 32" (813) 32" (813) & Over 40" (1016) 40" (1016) & L 7 1 /8" (181) 10 5 /8" (270) 71/8" (181) 10 5 /8" (270) 7 1 /8" (181) 10 5 /8" (270) 7 1 /8" (181) 10 5 /8" (270) 7 1 /8" (181) 10 5 /8" (270) Note: The 21" (533) dimension becomes 32" (813) when the MS4120, MS8120, GGD221 or FSNF and FSF Series are utilized. FSD60 SERIES SPCE ENVELOPE Combination fire smoke dampers are required by the UL listing to have all actuators and accessories factory mounted, wired and/or piped. The Ruskin standard is for the actuator to be located on the right hand side of the damper (onto a factory installed sleeve or side plate) as viewed from the jackshaft face of the unit. Larger units may require multiple actuators which are located on the right, left and maybe internal mount locations. See the Multiple Section Detail specification sheet for details. Ruskin s fire smoke dampers are not air flow directional, so the dampers may be rotated 180 or turned over as long as the blades are running horizontally in a position to accommodate installation obstructions. The adjacent chart indicates an S and a T dimension for the space envelope that each actuator requires for installation. The S dimension is the side clearance, the T dimension is the top clearance required for the various actuators approved for use with Ruskin fire smoke dampers. T S Ruskin recommends 6 (152) of additional space beyond the S dimension for ease of maintenance. CTUTORS ML, FSLF, H2000 MS4209 FSNF, FSF, MS4120 331-4827 331-2961 331-3060 4" (102) 5" (127) 5" (127) 8" (203) 9" (229) 2" (51) 5" (127) 6" (152) 8" (203) 11" (279) NOTES 1. The dimensions shown in the chart above are for dampers 14" (356) tall. 2. Dampers shorter than 14" (356) tall, increase the "T" dimension by 1" (25) for every 1" (25) the damper is less than 14" (356). 3. Dampers taller than 14" (356) high reduce the "T" dimension by 1" (25) for every 1" (25) the damper height is greater than 14" (356). Example: a) 12 (305) tall damper with a FSLF actuator, T = 2 (52) and S = 4 (102). b) 18 (457) tall damper with a FSNF actuator, T = 1 (25) and S = 5 (127). S T FSD60 INTERNL MOUNT CTUTOR DIMENSION Ruskin model FSD60 has been tested for internal mount actuators and accessories. These applications may be preferred where space is limited on the outside of the damper. Internally mounted actuators do not require the damper to have a factory installed sleeve or side plate. X X CTUTORS Dim and bove Dim and bove X X ML, FSLF, H2000 MS4209 FSNF, FSF, MS4120 331-4827 331-2961 331-3060 10" (154) 12" (305) 16" (406) 16" (406) 20" (508) 10" (154) 12 3 /4" (324) 15" (381) 17" (432) 19" (483) 18" (457) 21" (533) 21" (533) 24" (610) 26" (660) 7 1 /2" (191) 5 1 /2" (533) 7 1 /2" (191) 71/2" (191) 9" (229) (Model FSD60LP not available with internal mount actuators)

FSD60 DIMENSIONL INFORMTION + 2 (51) Height + 2 (51) See Note FSD60 Style FSD60 Style LO,CO & WO FSD60LP Style LO & CO + 2 (51) 6 (152) +2 (51) See Note FSD60(LP) Style FSD60 Style C and WC FSD60LP Style C Dia. + 2 (51) Dia. + 2 (51) Height Dia. See Note FSD60 Style R, CR and WR FSD60LP Style R & CR FSD60LP Style DUCT TRNSITION CONNECTIONS FSD60 Series dampers may be supplied with Round, Oval and Rectangular duct connections. Style Description Units 6 Tall R Round Non-Sealed (Low Pressure) CR Round Sealed (Medium Pressure) WR Round Welded ( Pressure) C Rectangular Sealed (Low and Medium Pressure) WC Rectangular Welded ( Pressure) LO Oval Non-Sealed (Low Pressure) CO Oval Sealed (Medium Pressure) WO Oval Welded ( Pressure) The square damper size will be 2 (51) larger in width and height than the round, oval or rectangular duct size ordered. MINIMUM and MXIMUM SIZES Round Transitions Minimum 4" (102) diameter Maximum 94" (2388) diameter Rectangular and Oval Transitions Minimum 6"w x 4 h (152 x 102) Maximum 118 w x 94 h (2997 x 2388) in diameter Style Transitions Minimum height 4 (102) style transitions are utilized on units where the damper height is less than 6 (152). Consult Ruskin for other available styles and sizes. Note: For medium pressure units (Styles CR, C and CO) the collar extends 1 1 /2 (38) beyond the sleeve length and for low pressure and high pressure units (Styles R, WR, WC and LO) the collar extends 2 1 /2 (64) beyond the sleeve length. pproximate damper assembly weight: 17 lbs. per sq. ft. for Style assembly

SPECIFICTION Combination fire smoke dampers meeting or exceeding the following specifications shall be furnished and installed at locations shown on plans or as described in schedules. Combination fire smoke dampers shall be produced in an ISO 9001 certified factory and shall be warranted to be free from defects in material and workmanship for a period of 5 years after date of shipment. Dampers shall meet the requirements of NFP80, 90, 92 and 92 and shall have a fire rating of 1 1 /2 hours in accordance with the latest edition of UL555 and shall be classified as Leakage Class I Smoke Dampers in accordance with the latest version of UL555S. Dampers shall be MC Licensed and shall bear the MC certified rating seal for air performance. MC certified testing shall verify pressure drop does not exceed.03 w.g. at a face velocity of 1000 fpm on a 24 x 24 damper. Damper frame (when size permits) shall be constructed using the UniFrame Design Concept (UDC) and shall be minimum 16 gage (1.6) galvanized steel formed into a structural hat channel superior to 13 gage (2.30) channel frame. ssemblies less than 36 (914) wide x 14 (356) high shall be Low Profile (LP) design to maximize the free area of these smaller dampers. LP frame and blade shall be 20 gage (1.0) and shall include an integral sleeve. Damper blades shall be single piece airfoil shaped with 14 (2.0) gage equivalent thickness. lade edge seals shall be inflatable silicone mechanically locked into blade edge. Jamb seals shall be stainless steel compression type. earings shall be stainless steel, permanently lubricated sleeve type turning in an extruded hole in the frame for maximum life. Combination fire smoke dampers and their actuators shall be qualified in accordance with UL555S to an elevated temperature of 250 F (121 C) or 350 F (177 C) depending upon the actuator. ppropriate electric or pneumatic actuators (specifier select one) shall be installed by the damper manufacturer at time of damper fabrication. Electric actuators, factory installed on dampers, shall have been tested for prolonged periods of holding (minimum 1 year) with no evidence of reduced spring return performance. Each damper shall be rated for leakage and airflow in either direction through the damper. In addition to the leakage ratings already specified, the dampers shall be MC licensed for ir Performance. Optional FM pprovals Specification Each combination fire smoke damper shall be listed in Factory Mutual (FM) approvals Specification Tested Product and labeled accordingly. Combination fire smoke dampers shall be Ruskin FSD60 Series. (Consult www.ruskin.com for electronic version of this Quick spec as well as for complete 3-part CSI MasterFormat Specifications) 3900 Dr. Greaves Rd. Kansas City, MO 64030 (816) 761-7476 FX (816) 765-8955 www.ruskin.com Printed on recycled paper using vegetable based inks