KOLMA and IHDA Indoor Type Cable Current Transformers. Catalogue. Catalogue KOLMA 1 GB Medium Voltage. ABB Transmit KKOLMA 1 GB

Similar documents
Medium Voltage. KOFD Indoor Type Current Transformers Cast Resin Insulated. Catalogue. 12, 13.8, 17.5, 24 and 36 kv KOFD 1 GB

Cable current transformers for indoor applications. Product overview. Cable current transformers. for indoor applications.

Current accuracy class. Sensor principles

Air-insulated switchgear UniGear type ZS1

MEDIUM VOLTAGE PRODUCT. TJC 4 Indoor voltage transformers

Single-phase CT current transformers Cat. Nos :

Resin Impregnated Paper Bushing, Oil to SF 6. , Type GSBK

11kV Compact Switchgear. tec - range. Minimum to Zero SF6 Insulation Gas. Outec Controls

Technical information

1ZSC AAA en, Rev. 6. Resin impregnated paper bushing, oil to SF 6., type GSBK Technical guide

EMPAC Metal enclosed capacitor bank for wind applications

CP Automatic capacitor bank

PowerIT Indoor Voltage Transformer Fuses, WBP. Outdoor Voltage Transformer Fuses, BRT. Catalogue 1YMB en. Industrial IT.

1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide

Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide

Indoor instrument transformers Current transformers Voltage transformers

AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR

1ZSE en, Rev. 7. Transformer bushings, type GOB Technical guide

MV Air Insulated Switchgear TAP17. Technical Data TGOOD

MEDIUM VOLTAGE PRODUCT. KECA 80 D85 Current Sensor Instructions for installation, use and maintenance

Combined instrument transformers

Medium voltage products. KEVCD A combined current and voltage sensor Instructions for installation, use and maintenance

Key features. DESIGNS: - Conservator type - Hermetically sealed

BHARAT HEAVY ELECTRICALS LIMITED, JHANSI

Transformer bushings, type GOH. Technical guide

KECA 80 C85 Current Sensor Instructions for installation, use and maintenance

Zero-phase current transformer for F-MPC application. Notification of geometry change in EW Series

MEDIUM VOLTAGE PRODUCT. KECA 250 B1 Current Sensor Instructions for installation, use and maintenance

1ZSE en, Rev. 9. Transformer bushings, type GOB Technical guide

1ZSE en, Rev. 3. Wall bushings, type GSA-AA Technical guide

1ZSE EN, REV. 7. Oil SF 6. bushings type GOEK Technical guide

1ZSE EN, REV. 4. Wall bushings type GSA-AA Technical guide

Fuse switch disconnectors

TECHNICAL SPECIFICATIONS OF PCC PANEL

COMPACT SUBSTATION GUIDE

AFTER GAZETTING (WORKING DOCUMENT FOR A 3 YEAR PERIOD) DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED

DURESCA Busbar system. For indoor and outdoor applications, type DE / type DG DURESCA

PHOENIX CONTACT

CURRENT TRANSFORMER MODEL N. SS BAND SECURES BRACKET (view of screw clamp band omitted for clarity) 0.25 x 0.50 SLOT (2 PLACES)

MEDIUM VOLTAGE PRODUCT. KECA 80 C85 Current Sensor Instructions for installation, use and maintenance

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE

Compact Gas Insulated Switchgear (GIS) up to 145kV 126kV,145kV Compact Gas Insulated Switchgear (GIS)

INTRODUCTION. The plug-in connection on the cables and lightning arrestors, allows for easy installation and replacement.

Inductive voltage transformers

Inductive voltage transformers

Voltage Rated operating voltage [kv] Rated power frequency withstand voltage [kv] Rated lightning impulse withstand voltage [kv]

Extensible Unit - VCE2a

1. Table of Contents T-LINE. Page. 1. Table for contents Description Current transformers type HF Product Overview 4

Zinc Oxide Surge Arrester EXLIM R

Cast resin transformers

M-RING 24. SF6 Insulated Ring Main Unit Metal-Enclosed (LSC2A)

24kV Medium Voltage Switchgear Metal-Enclosed (LSC2A)

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin

B kv Gas-insulated Substations

Innovac SVS/08 - SVS/ kv modular switchgear

Cable current transformers

Inductive voltage transformers

Combined instrument transformers

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

UniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions

Current transformers. Current transformers

DPX moulded case circuit breakers

Zinc Oxide Surge Arrester PEXLIM Q

HIGH VOLTAGE LABORATORY INSTYTUT ENERGETYKI

energy management systems Current Transformers

CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards

Kuhlman Electric Corporation. Engineered Designs Instrument Transformers

Current transformers. Outdoor operation SF 6 -gas insulated. JGF ( ) kv

Index. Manual Motor Starters 1. Auxiliary Contact Blocks 1. Trip Alarm Auxiliary 1. Switch. Shunt Release 1. Under-voltage Release 2.

Medium-Voltage Switchgear and Switches

TGK Prefabricated Substation Technical Data

Instrument Transformer Reference. Meter and Relay Applications for the Electrical Industry

Metal Clad Switchgears

Benefits, typical uses

Unitole UP kv Primary substations Motor control centres

SWITCHCRAFT. Switchcraft Europe GmbH SWITCHCRAFT

Fault management for grid automation Advanced fault location solution

Product Specification

Switchgear Type 8BT1, up to 24 kv, air-insulated. Medium Voltage Switchgear Catalog HA 26.

Metal Clad VCBs ~ Mk1

Inductive voltage transformers

Inductive voltage transformers

Multi-purpose percentage restraint differential protection

Basic Series Accessories Low Voltage Current Transformer Class 1

Medium Voltage Products. KEVA 24 B20; KEVA 24 B21 Voltage Sensors Instructions for installation, use and maintenance

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear

Inductive voltage transformers

ENYSTAR Load Centers up to 250 A

with Vacuum Circuit Breaker HAF

Descriptive bulletin. ReliaGear ND ANSI narrow frame metal-clad switchgear

Valid for you. medium voltage switchgear

I B D Q I B D Q O I B D Q O

MESG 12 / 17.5 / 24 / 36 KV

Outdoor load disconnectors DRIBO Flc GB. three-pole design rated voltage 25 and 38.5 kv rated current 630 A

YOUR KEY ENERGY EFFICIENCY PARTNER CAST RESIN DRY-TYPE TRANSFORMERS

SABRE VRN2a ENGINEERING BRILLIANT SOLUTIONS

Applications. Distribution transformers up to 2000 kva High-voltage motors up to 3 MW Capacitors up to1200 kvar MV voltage transformers Cable feeders

SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin

KYN28A-12 (GZS1) A.C METALCLAD REMOVABLE SWITCHGEAR FOR INDOOR USE CHINATCS

Transcription:

Catalogue KOLMA and IHDA Indoor Type Cable Current Transformers Catalogue KOLMA 1 GB 99-05 Medium Voltage ABB Transmit 1 KKOLMA 1 GB

KOLMA and IHDA Indoor Type Cable Current Transformers Index Description... 3 Technical data and ordering information Cable Current Transformers type KOLMA... 4 How to select the correct residual current transformers... 4 Technical data... 4 Installation... 5 Number of turns and terminal markings... 5 Current rations and rated burdens for accuracy class 10 P 10. 6 Ordering data... 6 Current transformers type IHDA... 7 Selection table... 7 Technical data... 7 Special current transformers KOKM and KOKU... 10 Accessories Ordering data... 11 Overall dimensions KOLMA, KOLA... 12 IHDA... 14 2 ABB Transmit KOLMA 1 GB

KOLMA and IHDA Indoor Type Cable Current Transformers 881125 Description Transformers, KOLMA_ and KOLA_ are suitable for the measurement of the sum of three-phase currents in a 3-phase cable. Under normal operating conditions this sum is zero. In the event of an earth-fault the sum of the currents is equal to the earthfault current and a corresponding current flows in the secondary. IHDA 05 current transformers are suitable for measuring of phase currents in low voltage switchgear. An uninsulated busbar or low voltage cable serves as the primary conductor. These transformers are used together with static earth-fault relays. The cable current transformers can generally be used when measuring the residual current e.g. to prewarn of, or locate an earth-fault. ABB Transmit 3 KKOLMA 1 GB

Cable Current Transformers type KOLMA Technical data and ordering information How to select the correct residual current transformers The transformer for an earth-fault relay is selected according to dimension of the window, and construction of the transformer. For types KOLMA 06 A1, and KOLMA 06 D1, the number of turns used in the secondary winding is selected according to the relay setting value, and the earth-fault current or the required current ratio. In addition correct functioning of the earthfault protection relays for KOLMA 06 A1 and KOLMA 06 D1 is easy to test by means of the test winding (terminals P1x - P2x) of the transformer. The test winding is rated for 6 A max. continuous current. Table 1. Selection of residual current transformers Type Window diam. Construction Weight mm kg KOLMA 06 A1 90 Ring core, multi-tap secondary 7.0 KOLMA 06 A2 58 Ring core 2.9 KOLMA 06 B2 100 Ring core 5.4 KOLMA 06 D1 180 Ring core, multi-cap secondary 11.5 KOLMA 06 D2 180 Ring core 11.4 KOLA 06 B2 100 Split ring core 6.0 KOLA 06 D2 180 Split ring core 11.0 Technical data The primary winding of indoor type cable current transformers is either a cable or a busbar, which is insulated for the application voltage. The secondary winding and ring shaped iron core is cast in resin which has good electrical and mechanical properties. 881123 Cable current transformers, types KOLMA_ Rated voltage 0.72 kv (1) Insulation test voltage 50 Hz 1 min 3 kv (IEC 185) Frequency 50 Hz (60 Hz) Rated thermal current 1.2 x I pn Short-time withstand current I th 1 s 60 x I pn (2) Peak withstnad current I dyn 2.5 x I th Secondary terminals For 6 mm 2 conductor Operating temperature range 5...+40 o C (1) The insulation level of the primary conductor determines the maximum operating voltage. (2) KOLA 06 B2 is type tested for 10 ka 3 s. 4 ABB Transmit KOLMA 1 GB

Cable Current Transformers type KOLMA Technical data and ordering information Installation The KOLMA-types must be installed before the cables and cable terminations are connected. INST With the KOLA 06 B2 and KOLA 06 D2 -types, the ring core can be opened and thus the transformer can be installed eventhough the cable is already connected. The two halves of the ring core are tightened together with four screws which also guide the halves to the correct position. The secondary winding is distributed over both halves of the core. The two sections of the winding are connected together with two connecting pieces. Cable current transformers are fastened either by means of the fixing base or by the nuts cast into the transformer frame. When installing the transformer, the effect of the current in the metal armour or in the protective conductor must be eliminated. In case the metal armour or the protective conductor is drawn through the transformer, the earthing conductor must be drawn back through the transformer for earthing. The earthing conductor between the cable termination box and the transformer, must not be connected to conductive structures, and the metal cable termination box must be insulated from the supporting structures. On a multi-ratio transformer the unconnected secondary winding terminals and test winding must not be short circuited. Number of turns and terminal markings KOLMA 06 A1 KOLMA 06 D1 KOLMA 06 A2 KOLMA 06 B2 KOLMA 06 D2 KOLA 06 B2 KOLA 06 D2 KOLMA ABB Transmit 5 KKOLMA 1 GB

Cable current transformers type KOLMA Current rations and rated burdens Technical data and ordering information Table 2. Current ratios and rated burdens for accuracy class 10 P 10 Design data. Types KOLMA 06 A1 and KOLMA 06 D1 Current ratio Secondary terminals Burden / VA Type A KOLMA 06 A1 KOLMA 06 D1 50/1 S4 - S5 1.0 0.5 70/1 S3 - S4 2.0 1.0 100/1 S1 - S4 2.5 2.0 150/1 S1 - S5 5.0 4.0 50/5 S1 - S2 1.0 0.5 100/5 S2 - S3 2.5 1.5 150/5 S1 - S3 4.0 3.0 250/5 S4 - S5 7.5 5.0 350/5 S3 - S4 10.0 7.5 500/5 S1 - S4 15 10 600/5 S3 - S5 20 15 750/5 S1 - S5 20 15 Table 3. Current ratios and rated burdens for accuracy class 10 P 10 Design data. Types KOLMA 06 A2, KOLMA 06 B2, KOLMA 06 D2 and KOLA 06 B2 Type Current ratio Secondary terminals Burden A VA 881127 Openable residual current transformers, type KOLA 06 B2 complete with fixing base KOLMA-ZK 1 and terminal cover KOK-ZAX 14. KOLMA 06 A2 100/1 S1 - S2 2.0 KOLMA 06 B2 100/1 S1 - S2 2.5 KOLMA 06 D2 100/1 S1 - S2 2.0 KOLA 06 B2 100/1 S1 - S2 2.0 KOLA 06 D2 100/1 S1 - S2 2.0 Ordering data quantity type Accessores shall be ordered separately. 6 ABB Transmit KOLMA 1 GB

Current transformers type IHDA 05 Technical data and ordering information Current transformer series IHDA 05 for measuring of phase currents IHDA 05 current transformers are suitable for measuring of phase currents in low voltage switchgear. An uninsulated busbar or low voltage cable serves as the primary conductor. Series IHDA 05 current transformers can also be used for measuring the phase current at voltages even higher than 0.72 kv, if the insulation of the high voltage primary conductor fulfils the respective standards for the operating voltage. Selection of current transformers Transformer selection is made according to tables 4 and 5. Ordering On order please mention quantity, type and class. Example: 3 pcs IHDA 05 B1-150/1, class 3 Technical data Rated voltage 0.72 kv (1) Insulation test voltage 50 Hz 1 min 3 kv (IEC 185) Frequency 50 Hz (60 Hz) Rated thermal current 1.2 x I pn Short-time withstand current I th 1 s 60 x I pn (2) Peak withstnad current I dyn 2.5 x I th Secondary terminals For 6 mm 2 conductor Operating temperature range 5...+40 o C (1) The insulation level of the primary conductor determines the maximum operating voltage. ABB Transmit 7 KKOLMA 1 GB

Current transformers type IHDA 05 Technical data and ordering information Table 4. Selection of current transformers. Secondary current I sn = 1 A Rated frequency 50 Hz Performance values according to IEC 185 < < F s = F a = Instrument security factor Accuracy limit factor Type Window Prim. Burden (VA) Weight diam. curr. Class and Fs or Fa IHDA mm A 0.5 Fs 1 Fs 3 Fs 10P Fa kg 05A1 100/1 33 100 1 10 3 5 05A1 150/1 33 150 2 10 5 5 05A1 200/1 33 200 4 5 8 5 05A1 300/1 33 300 3 10 6 5 15 5 0.7 05A1 400/1 33 400 4 5 10 5 10 5 05A1 500/1 33 500 5 5 10 5 10 5 05A1 600/1 33 600 8 5 15 5 15 5 05B1 100/1 33 100 10 10 5 5 05B1 150/1 33 150 7 15 20 5 5 10 05B1 200/1 33 200 10 15 15 10 30 5 5 10 05B1 300/1 33 300 15 10 30 5 60 5 7 10 2.5 05B1 400/1 33 400 20 10 40 5 80 5 10 10 05B1 500/1 33 500 20 10 40 5 80 5 7 10 05B1 600/1 33 600 30 10 60 5 80 5 10 10 05B1 800/1 33 800 60 5 80 5 80 5 7 10 05C1 400/1 58 400 15 10 30 5 60 5 7 10 05C1 500/1 58 500 20 10 40 5 80 5 10 10 2.5 05C1 600/1 58 600 40 5 80 5 80 5 12 10 05C1 800/1 58 800 50 5 80 5 80 5 10 10 05C1 1000/1 58 1000 60 5 80 5 80 5 8 10 05D1 600/1 85 600 30 10 60 5 60 5 10 10 05D1 800/1 85 800 40 10 80 5 100 5 12 10 05D1 1000/1 85 1000 60 5 100 5 120 5 15 10 4.0 05D1 1200/1 85 1200 60 10 100 5 120 5 20 10 05D1 1500/1 85 1500 60 10 120 5 120 5 20 10 05D1 1600/1 85 1600 60 10 120 5 120 5 25 10 05E1 1500/1 117 1500 25 5 40 5 40 5 10 5 3.5 05E1 1600/1 117 1600 30 5 40 5 40 5 12 5 05E1 2000/1 117 2000 50 5 60 5 60 5 15 5 Cable current transformers with one secondary winding, typ IHDA_ 881128 8 ABB Transmit KOLMA 1 GB

Current transformers type IHDA 05 Technical data and ordering information Table 5. Selection of current transformers. Secondary current I sn = 5 A Rated frequency 50 Hz Performance values according to IEC 185 < < F s = F a = Instrument security factor Accuracy limit factor Type Window Prim. Burden (VA) Weight diam. curr. Class and Fs or Fa IHDA mm A 0.5 Fs 1 Fs 3 Fs 10P Fa kg 05A1 100/5 33 100 1 10 3 5 05A1 150/5 33 150 2 10 5 5 05A1 200/5 33 200 4 5 8 5 05A1 300/5 33 300 3 10 6 10 15 5 0.7 05A1 400/5 33 400 4 5 10 5 10 5 05A1 500/5 33 500 5 5 10 5 10 5 05A1 600/5 33 600 8 5 15 5 15 5 05B1 100/5 33 100 10 5 5 5 05B1 150/5 33 150 7 15 20 5 5 10 05B1 200/5 33 200 10 10 15 10 30 5 5 10 05B1 300/5 33 300 15 10 30 5 60 5 7 10 05B1 400/5 33 400 20 10 40 5 80 5 10 10 2.5 05B1 500/5 33 500 20 10 40 5 80 5 7 10 05B1 600/5 33 600 30 10 60 5 80 5 10 10 05B1 800/5 33 800 60 5 80 5 80 5 7 10 05B1 1000/5 33 1000 60 5 80 5 100 5 10 10 05B1 1200/5 33 1200 60 5 100 5 120 5 12 10 05C1 400/5 58 400 15 10 30 5 60 5 7 10 05C1 500/5 58 500 20 10 40 5 80 5 10 10 05C1 600/5 58 600 40 5 80 5 80 5 12 10 05C1 800/5 58 800 50 5 80 5 80 5 10 10 05C1 1000/5 58 1000 60 5 80 5 80 5 8 10 2.5 05C1 1200/5 58 1200 60 5 80 5 80 5 10 10 05C1-1500/5 58 1500 60 5 80 5 80 5 10 10 05C1-1600/5 58 1600 60 5 80 5 100 5 12 10 05D1 600/5 85 600 30 10 60 5 60 5 10 10 05D1 800/5 85 800 40 10 80 5 100 5 12 10 05D1 1000/5 85 1000 60 5 100 5 120 5 15 10 05D1 1200/5 85 1200 60 10 100 5 120 5 20 10 4.0 05D1 1500/5 85 1500 60 10 120 5 120 5 20 10 05D1 1600/5 85 1600 60 10 120 5 120 5 25 10 05E1 1500/5 117 1500 25 5 40 5 40 5 10 5 05E1 1600/5 117 1600 30 5 40 5 40 5 12 5 05E1 2000/5 117 2000 50 5 60 5 60 5 15 5 05E1 2400/5 117 2400 60 5 60 5 60 5 15 5 3.5 05E1 2500/5 117 2500 60 5 60 5 60 5 15 5 05E1 3000/5 117 3000 60 5 80 5 80 5 20 5 ABB Transmit 9 KKOLMA 1 GB

Special current transformers Technical data and ordering information Special current transformers KOKM 06_ and KOKU 06_ 901155 881129 Special indoor type current transformer type KOKM 06 J2. Window size 300 x 500. Examples of some special transformer. Left: KOKM 06 for indoor use. Right: KOKU 06 for outdoor use. We also manufacture current transformers cast in epoxy resin, to meet special demands, both for outdoor and indoor use. Enquires for these special transformers should mention the following data: 1. Quantity 2. Current ratio I pn /I sn (A) 3. Burden (VA) 4. Accuracy class 5. Window dimension (mm) 6. Other limiting data such as instrument security factor, dimensions of transformer, fixing of transformer (fixing base) etc. 7. Indoor or outdoor use Maximum service voltage for these transformers is 0.6 kv. The insulation of the primary conductor determines the highest permissible system voltage. 10 ABB Transmit KOLMA 1 GB

Accessories Ordering data Ordering data for accessories - quantity - type Table 6. Selection of accessories for KOLMA_ and KOLA_ Description of accessory Type Suitable for use together with transformer Fixing base KOLMA-ZK 1 KOLMA 06 A1 Fixing base KOLMA-ZK 1 KOLMA 06 A2 Fixing base KOLMA-ZK 1 KOLMA 06 B2 Fixing base KOLMA-ZK 1 KOLA 06 B2 Fixing base KOLMA-ZK 2 KOLMA 06 D1 Fixing base KOLMA-ZK 2 KOLMA 06 D2 Fixing base KOLMA-ZK 2 KOLA 06 D2 Secondary terminal cover KOK-ZAX 14 KOLMA 06 A2 Secondary terminal cover KOK-ZAX 14 KOLMA 06 B2 Secondary terminal cover KOK-ZAX 14 KOLA 06 B2 Secondary terminal cover KOK-ZAX 14 KOLA 06 D2 Table 7. Selection of accessories for IHDA_ Type Description Suitable for IHDA 05... current transformer KOK-ZAX 12 Fixing base (1) A1 KOK-ZAX 13 Fixing base (1) B1...E1 KOK-ZAX 14 Secondary terminal cover (2) B1...E1 (1) The fixing base shall be fixed to the bottom inserts of the current transformer by means of screws equipped with spring washers which are included in the package. The fixing base can be mounted either in line with the current transformer of transversely. (2) The secondary terminal cover shall be mounted on the secondary terminals of the current transformer. The cover includes a bushing sleeve. There are two alternative holes for the outgoing wiring. The cover is sealable. ABB Transmit 11 KKOLMA 1 GB

KOLMA Overall dimensions KOLMA 06 A1 KOLMA 06 A2, B2 06A2 06A1 Type A B C D KOLMA 06 A2 58 177 196 140 06 B2 100 229 249 195 KOLMA 06 D1, D2 06D1 12 ABB Transmit KOLMA 1 GB

KOLA Overall dimensions KOLA 06 B2 KOLA 06 D2 06D2 06B2 ABB Transmit 13 KKOLMA 1 GB

IHDA Overall dimensions IHDA 05 A1 IHDA 05 B1, C1, D1, E1 IHDA A1 IHDAB1 Type Dims./mm IHDA A B C D 05 B1 150 70 120 33 05 C1 170 80 140 58 05 D1 205 98 175 85 05 E1 225 108 195 117 14 ABB Transmit KOLMA 1 GB

IHDA Overall dimensions Base for IHDA 05 A1 Type KOK-ZAX 12 Base for IHDA 05 B1, C1, D1, E1 Type KOK-ZAX 13 05B1 05A1 ABB Transmit 15 KKOLMA 1 GB

IHDA Overall dimensions Terminal cover for IHDA 05 B1, C1, D1 and E1. Sealable. KOK-ZAX 14 KOKZAX IHDA.TBL Type IHDA 05 B1 05 C1 05 D1 05 E1 Dim. H mm 163 183 218 238 16 ABB Transmit KOLMA 1 GB

ABB Transmit 17 KKOLMA 1 GB

Catalogue KOLMA 1 GB 94-11/97-03 ABB Transmit Oy MV Systems Division Instrument Transformers P.O. Box 613, FIN-65101 Vaasa, Finland Phone +358 10 22 4000 Fax +358 10 22 42616 Ykkös-Offset Oy 3000, 97-03 18 ABB Transmit KOLMA 1 GB