Company Switch Installation Instructions and User Manual

Similar documents
Instruction Bulletin NF Panelboard Dual Sub-Feed Circuit Breaker Adapter Kit Installation onto an NF Panelboard Class 1670

Quick Connection Panel (QCP) Installation Guide

AUTOMATIC DUST COLLECTION FOR SMALL SHOPS INSTRUCTIONS GG500C MOTOR CONTACTOR WITH THERMAL PROTECTION 220VAC COIL

Instruction Bulletin Dual Sub-Feed Circuit Breaker and Adapter Kit Installation onto an NQ Panelboard Class 1640

Q-Frame Main Circuit Breaker (225 A Maximum) and Adapter Kit Installation onto an NQ Panelboard Class 1640

Installing Power Components

AUTOMATIC DUST COLLECTION FOR SMALL SHOPS INSTRUCTIONS GG500B MOTOR CONTACTOR WITH THERMAL PROTECTION 115VAC COIL

INSTRUCTIONS. Power Panel. Installation Instructions

INSTALLATION MANUAL. Melink Corporation (513) Revision

Installation and Construction Notes for EVSE4

Raritan PX. Power Cord Installation Guide. Safety Guidelines. Safety Instructions

Dry Contact Closure Interface

Installation Instructions For Motor Control Center (MCC) Units

CAT-1 Series 3. Installation Guide. The Valley Group, Inc. 871 Ethan Allen Hwy. Suite 104 Ridgefield, CT 06877

H- or J-Frame Main Circuit Breaker and Adapter Kit Installation onto an NQ Panelboard Class 1640

PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide

EPLX and D2LX lighting panelboards Installation & maintenance information IF 1813 APPLICATION D2LX/EPLX IF SHEET TABLE OF CONTENTS WEIGHTS

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

The Ultimate Smart Grid Solution INSTRUCTION MANUAL

Stevens Type A/F Encoder. For Stand-Alone Encoder Part # AND Encoder Attachment Part # INSTRUCTION 90044

Mirror Solutions Bevel & Pivot Models Installation Instructions INSTALLATION INSTRUCTIONS. Figure 1

For Use with Model(s):all electric models

The Ultimate Smart Grid Solution INSTRUCTION MANUAL

Florham Park, NJ USA Call (ASCO) for sales or service

920 Remote Control Switches

WARNING. Important Notice

Electric Range installation manual

A B C D E F. Tools Required (supplied by others)

3ATS & 3NTS J-design 600 A 3ADTS & 3NDTS A Transfer Switches. Installation Manual. Installation A DANGER. Table of Contents WARNING

8300 Series Installation Guidelines

AquaLumin III - Nicheless Light Installation Guide IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS

Florham Park, NJ USA Call (ASCO) for sales or service

5300 Series Installation Guidelines

Eaton Corp. - Marina Power and Lighting, Inc. General Specifications for Lighthouse Power Pedestal

Quick Connection Cabinet (QCC)

High Frequency SineWave Guardian TM

Instruction Bulletin. Jockey Pump Controller

An Investment in Plant Floor Safety. 802C Safety Cable Pull Switches 802E Hinge Safety Interlock Switches 802F Safety Interlock Switches

INSTALLATIONINSTRUCTIONS FREESTANDINGELECTRICRANGE WITH DOUBLEOVENS

JEEVES. JEEVES Installation Manual. Installation Manual The Easiest Do-It-Yourself Dumbwaiter on the Market

Wiring the FRC Control System

Sivoia QS Wireless Drapery Lite System

IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS

INSTALLATION INSTRUCTIONS. Solid-State Series !! NOTE!! Covers the following models: Refer to INSERT for additional information

Switches & Motor Controls

Trus<T>Lift 750 Installation and Operation Manual. Copyright 2013

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING

Eaton Corp. - Marina Power and Lighting, Inc. General Specifications for Hatteras Light Pedestals

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

ANZI Transfer Switch and Generator Wiring Installation Addendum

Installation and Operation Guide. Tundra HD 2500 Power Inverter. for the. Webasto BlueCool Truck System

Installation Manual. For. Hi-Speed Alumavator / Platinum Vertical Boat Lifts

Network Zone System Part Numbers: Z23N-***** Z23R-****

Cellwatch Electrical Installation

Optimal Series. Automatic Transfer Switch. Installation and User Manual for the OPT2225 Automatic Transfer Switch. Full Version

50 Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO)

install o IIVIPORTANT - Savethese -&WARNING - -&WARNING - This appliance must -&WARNING - Before beginning the Mode_s PB970, PB975

INSTALLATION MANUAL ELECTRIC DOUBLE OVEN RANGE

Raychem CSJA Safety Instructions. Safety Instructions. Customer Service. Kit Contents. Installation Instructions

HD 7700 Setup & Operator Manual

SPECIAL SPECIFICATION 1788 Surveillance Cabinet

dans un panneau de distribution NQ Instruction Bulletin Boletín de instrucciones Directives d'utilisation

IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS

Installation Instructions for Load Management Kit A051C329

Operator s Manual Series ATS Automatic Transfer Switches 600 through 1200 amps

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

ELB ELB

MODEL ELC-12/40-CVM-D BATTERY CHARGER

CON EDISON EQUIPMENT

Installation Manual. E-design A Transfer Switches A

VA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING

PART B BRAND SPECIFIC MANUAL

Wiring the 2015 FRC Control System

MODEL ELC-12/60-D BATTERY CHARGER

Operator s Manual Series ADTS Automatic Delayed Transition Transfer Switches, amps

SPECIAL SPECIFICATION 6894 Communication Cabinet

User Manual JS-ICON. 624 ARCH Dimmer Rack. JOHNSON SYSTEMS INC. Spring

Installation Manual. For. Alumavator / Platinum Boathouse Lifts

A B C D E F. b.tools Required (supplied by others) 3/16" Drill Bit 3/8" Wrench Phillips Head Screwdriver

Preparation Advanced Preparations: Be familiar with the controls of the range hood by reading through Range Hood Operations, Page 12. Place the range

Checker Unload Checkstand Installation Instructions

Midnite Kid Basic Solar Charging Kit

Wiring the 2016 FRC Control System

Troubleshooting Title of Bulletin guide for single phase GFCIs Manual machines

Sunwize Power Ready Express Quick Start

Installation Instructions Z-Gate Shifter

Symmetra PX with Maintenance Bypass

Eaton Corp. - Marina Power and Lighting, Inc. General Specifications for Lighthouse-SS Power Pedestals

Procharger Stage II Intercooled Supercharger System (11-14 GT)

INSPECTION REQUIREMENTS: PHOTOVOLTAIC (PV) RESIDENTIAL

Installation Instructions Pro Stick Shifter

Installation Instructions Studio Makeup Station

Acme Conduit Entry. String Combiner/Pass-Through. FOR PHOTOVOLTAIC INSTALLATION Installation Manual

Lokar Cable Operated Sensor Kit Installation Instructions

Installation Instructions

Installation Instructions

Explosion Proof Receptacle - Integral Circuit Breaker - Class 2 Division 1-30 Amp 480VAC

W-VACiMB FIXED SECONDARY TERMINAL BLOCK OEM CONVERSION TYPE #2 RING-TYPE TERMINAL BLOCK

Your Global Flow Control Partner. Series 70 24V On/Off Electric Actuator Operation and Maintenance Manual

Transcription:

Lex Products Corporation 15 Progress Drive Shelton, CT 06484 203.363.3738 203.363.3742 Fax Lex West 11847 Sheldon Street Sun Valley, CA 91352 818.768.4474 818.768.4040 Fax www.lexproducts.com info@lexproducts.com 800.643.4460 US Patent No. 7,136,278 B2 (U.S.A. and Canada) PowerGATE Switches & Panels Installation Instructions and User Manual LP-CS-001 Rev001

Table of Contents Introduction...3 Step 1: Installing the...4 Step 2: Tools Needed...5 Step 3: Mounting the Unit...6 Step 4: Wiring the Unit...7 Step 5: Isolating Chassis Ground (If applicable)...8 Step 6: Pre- Power Up Check List...9 Step 7: Powering Up...9 7.1: Troubleshooting...10 Step 8: Operation & Use...11 Step 9: Making Lug Connections...12 Step 10: Making Cam Connections...12 Notes... 13 2 LEX User Guide

Introduction The Lex PowerGATE has been specifically designed for safe power access and has been put to use in such places as: Theaters Conventions Centers Studios Theme Parks Recreational Facilities Manual Notes Photographs shown throughout this manual are of the 400A NEMA Type 1 but are representative of the 100A and 200A Type 1 and 100A, 200A and 400A Type 3R as well. 203-363-3738 www.lexproducts.com 3

Step 1: Installing the WARNING: RISK OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. Refer to NFPA 70E. This equipment must only be installed and serviced by a licensed electrician. Turn off all power supplying this equipment before installing, working on or inside equipment. Lockout/tagouts are recommended. Always use a properly rated voltage sensing device to confirm that power is off. Replace all devices, doors and covers before energizing this equipment. FAILURE TO FOLLOW THESE INSTRUCTIONS WILL RESULT IN DEATH OR SERIOUS INJURY. External Layout: A: Main switch, B: Phase indicator C: Connection chamber access door D: Mounting ears, (2) located on the bottom and (2) located on the top of the unit. A B C D 4 LEX User Guide

External Layout: F: Shunt trip interlock G: Internal light H: Lug output connector access door I: Cam type output connectors F H I G Step 2: Tools Needed Lineman s pliers Utility knife Set of screwdrivers Wrenches to connect the conduit into the unit 3/8 Allen key for making lug connections A hole saw or hole punch for providing an access hole in the cabinet for the conduit connection An insulation stripping tool, and cutter to provide square cut ends of the cables. 203-363-3738 www.lexproducts.com 5

Step 3: Mounting the Unit Remove upper panel to expose main switch connections, and to make the unit easier to mount. Determine where you wish to install the unit and make sure that the mounting surface will support the full weight of the plus connected 4/0 cables. Mounting ears are provided on positions 1 & 2 on the top and 3 & 4 on the bottom (see below). The mounting hole pattern dimensions are: Horizontal Vertical CS400 14.00 45.22 CS200 & CS100 14.00 37.00: The minimum clearance (free space) from bottom of unit to nearest flat surface needs to be no less than 24 to allow for cable with cam connections. A mounting height of 44 AFF to the bottom of the panel is recommended. Hold unit into place and level, then mark the mounting hole locations, drill and temporarily mount the unit. While unit is mounted, locate the desired conduit location. Remove the unit and cut conduit hole. Ensure that the main switch is covered during this operation to make sure that metal filings do not enter it. IMPORTANT Bend radius requirements dictate that the conduit for incoming power may only enter the cabinet from the top of the cabinet. Conduit entry from the sides or back of the cabinet is not permitted. NOTE 1:The completed conduit when connected to the box must be a minimum of at least one inch from any of the top edges for proper clearance. Remount the unit permanently and attach and tighten conduit. Mounting tab locations and conduit placement: NOTE 1 2 1 1" Min. from all edges. 3 4 6 LEX User Guide

Step 4: Wiring the Unit The Lex PowerGATE comes in three amperage types, 100A, 200A and 400A. The recommended input (contractor direct wire) wire gage for these units is as follows: 100A: #2AWG minimum 200A: 4/0 AWG minimum 400A: 500 kcmil minimum With the conduit in place, make sure main source of power is off or isolated and pull the power cables through into the unit. Follow the chart provided below for strip length and torque required to secure cables to binding lugs. Do not nick any strands while stripping cable. Cable ends need to be cut square. Circuit Breaker Wire Gauge Range Torque (lb.-in.) Strip Length 100A 350 kcmil - 6 AWG 275 1-1/8 200A 350 kcmil - 6 AWG 275 1-1/8 400A Ground & Neutral Lugs 500 kcmil - 250 kcmil 250 kcmil - 3/0 kcmil 350 kcmil - 6 AWG 380 275 See table behind Chamber Access Door 1-1/8 1-1/8 NOTE: Fine stranded wire MUST be sleeved with copper shim stock before inserting into lugs or strands may interfere with threads of wire binding screw resulting in false torque indication. Wire Installation Strip the cable to the length indicated in the table above. To install, start with the ground,then the neutral, then the phases. Place the appropriate cables into the lugs and and torque the screw to the torque indicated in the table above using a 3/8 Allen wrench. NOTE:The use of 600 kcmil cable will require different lugs and/or reducers. These are not supplied by Lex Products but are readily available from most electrical suppliers. Neutral Ground Blue (Phase C) Red (Phase B) Black (Phase A) 203-363-3738 www.lexproducts.com 7

Step 5: Isolating the Chassis Ground If you need to isolate the chassis from ground, proceed as follows: The chassis ground (C.G.) termination is located next to the main ground cable. To isolate this ground: 1) Remove the nut holding the chassis ground lug to the threaded stud. 2) Wrap the chassis ground mounting lug with good grade electrical tape or shrink wrap, if available. 3) Using a plastic wire tie, secure the chassis ground to the main ground cable. 4) Check to make sure that the chassis ground is secure and that it cannot come into contact with any metal surfaces of the cabinet. Chassis Ground 8 LEX User Guide

Step 6: Pre-Power up Check List Before energizing the unit make sure all connections are correct and secure. Make sure there is no debris left over from drilling, and that no tools are left in the cabinet. Replace front panel and fasten securely. Make sure lower panel door is closed and secured. Note that as a safety feature of this device, the power will be tripped off when the door is opened. Step 7: Powering Up Turn the power lever to the ON position. LED s for each phase as well as ground continuity should be lit. 203-363-3738 www.lexproducts.com 9

Step 7.1: Troubleshooting WARNING: RISK OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E. This equipment must only be installed and serviced by qualified electrical personnel. Turn off all power supplying this equipment before working on or inside equipment. Always use a properly rated voltage sensing device to confirm power is off. Replace all devices, doors and covers before turning on power to this equipment. Failure to follow these instructions will result in death or serious injury. If the unit immediately trips off on power up, check to make sure the lower panel door is closed and secured. If any or all LED s do not light, and there is power to the unit, turn main power switch off and check the fuses located to the left of the LED s. If the breaker appears to be tripping too quickly, possibly due to inrush current, contact the Lex Technical Services team for instructions on adjusting the trip delay time. The contact information is on page 12. 10 LEX User Guide

Step 8: Operation and Use The breaker switch has a lockout/tagout feature that can be used to safely secure the switch in the off position. Simply lift the gray tab on the hub of the breaker lever. Once lifted, up to three locks may be attached to the tab, locking the handle in the off position. The external connection wire access is located at the bottom of the unit and the connections are made inside the connection chamber, behind the lockable door. The large holes are provided for cables with Cam-type connectors and the smaller holes are provided for stripped wire connections. The stripped wire lug connector access holes are located on the phenolic panel, and the securing screw lugs are located behind the hinged phenolic door as shown below. Cam-type connectors are provided on the aluminum panel as shown at the left. NOTE: If the power is ON and the door is opened, the shunt trip interlock will trip the breaker OFF. As a good personal safety measure, the breaker should be switched to the OFF position before the door is opened. Phase C - Blue Phase B - Red Phase A - Black Neutral Ground Phase C - Blue Phase B - Red Phase A - Black Neutral Ground 203-363-3738 www.lexproducts.com 11

Step 9: Making Lug Connections Make sure main power source is off. Cut the cable end square and strip the wire 1-1/2. Do not nick any strands. When connecting the cables, always start with the Ground, then the Neutral, and finally the phases. Insert the wire into the lug and torque per the label on the lug cover. Open the connection chamber door. Pull the ground cable through the smaller hole in the bottom of the unit that corresponds with the ground mounting lug. The spring loaded door will help hold the cable in place while the wires are connected and torqued. Start by connecting the ground first, torque to the proper spec. then continue with the neutral and then the three phases. When all the cables are connected, use the wing bolts on the spring loaded cable door to clamp down on the cable, providing strain relief for the lug connections. Be sure to leave a little slack in the cable so that there is no strain on the lug connections. When disconnecting, do it in reverse order, (phases, neutral and lastly the ground cable). Step 10: Making Cam Connections Make sure main power source is off. Open the lower cabinet, then pull the ground cable with the cam connections through the large holes in the bottom of the unit that corresponds with the ground cam connector. Beginning with the ground, push the cam connector up into its receptacle with the screw on the cable cam connector facing you, then rotate the cam counter clockwise until it stops in its locked position. Then do the same for the neutral connections and then the three phases. When disconnecting, do it in reverse order, (phases, neutral and lastly the ground cable). Changing Trip Current to 60A (100A only) You may wish to set the trip point on the breaker to 60A when using lighter cable to feed a audio or other smaller distribution rack. Please contact the Lex Technical Services Team for instructions. Technical Services Team Lex Products is available to help in any way possible. If you have questions, need technical advice or have suggestions regarding this product, please contact us at 800.643.4460 or email us at technical_support@lexproducts.com. 12 LEX User Guide

PowerGATE Switches & Panels