COOPER POWER SERIES. High-voltage primary bushings installation instructions. OEM Equipment MN800008EN

Similar documents
High-voltage primary bushings installation instructions

COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN

COOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

Effective March 2015 Supersedes S August 2012

COOPER POWER SERIES. Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions. Fusing Equipment MN132014EN

Effective June 2016 New Issue

Effective November 2016 Supersedes September 1998 (S )

COOPER POWER SERIES. QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit A26 installation instructions

COOPER POWER SERIES. Testing a motor capacitor on a voltage regulator procedure instructions. Voltage Regulators MN225064EN

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. Edison Modular Fuse (EMF) Installation Instructions. Fusing Equipment MN132031EN

COOPER POWER SERIES. ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions. Fusing Equipment MN132017EN

COOPER POWER SERIES. RTE EL-BAY-O-NET FUSE Re-Fusing Instructions. Fusing Equipment MN132024EN

COOPER POWER SERIES. S.T.A.R. Hot line voltage indicator installation instructions. Fault Indicators MN320011EN. Indicator boot.

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

COOPER POWER SERIES. KA1169R Closing Coil Transfer-Switch Accessory Operation. Reclosers MN280069EN

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

COOPER POWER SERIES. KA662R tank-lifting windlass assembly and installation instructions. Recloser Mountings MN280071EN

COOPER POWER SERIES. Pad-mounted Switchgear MN285019EN. Effective March 2017 Supersedes February 2007 (S )

COOPER POWER SERIES. S.T.A.R. type LVR faulted circuit indicator installation instructions. Fault Indicators MN320005EN

COOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN

Effective November 2016 Supersedes February 2012 (S )

COOPER POWER SERIES. Dielectric grease application to recloser cable instructions. Reclosers MN280070EN

COOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S )

Type NR oil switch installation and operation instructions

Effective May 2017 Supersedes January 2003 (S )

COOPER POWER SERIES. KA146W5 single pole-mounting hanger; KA146W2 tank lifting windlass assembly and installation instructions. Reclosers MN280039EN

COOPER POWER SERIES. Types 4H single-phase and 6H three-phase vacuum interrupter conversion kits. Reclosers MN280014EN

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

COOPER POWER SERIES. KA716L7001 adjustable control valve kit for Types L, E, 4E, V4E, and V4L reclosers installation and adjustment instructions

Effective May 2017 Supersedes December 2004 (S )

COOPER POWER SERIES. Surge arrester interchangeable fuse cutout combination installation instructions. Surge Arresters MN235004EN

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN

COOPER POWER SERIES. Electronic control battery testing, charging, and replacement instructions. Reclosers MN280074EN

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

COOPER POWER SERIES. Quick Connect Assembly (QCA) Retrofit Kit, General Electric Installation Instructions. Voltage Regulators MN225075EN

COOPER POWER SERIES. Mercury switch to microswitch retrofit kit KA349WE installation instructions. Reclosers MN280022EN

S Voltage Regulators GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage. Standards

COOPER POWER SERIES. Fused loadbreak elbow connector installation instructions. Loadbreak Apparatus Connectors MN650014EN

COOPER POWER SERIES. Manually-Operated M-Force Switch Installation and Operation Instructions. Switches and Disconnects MN008003EN

COOPER POWER SERIES. Types D and DV recloser installation instructions. Reclosers MN280030EN

This Kit Is for Use with Types RE, RVE, WE, WVE, VWE, VWVE27, and VWVE38 Reclosers.

S Fault Indicators. S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions. Contents INSTALLATION PROCEDURES

COOPER POWER SERIES. Instructions for oil-filled, single-phase overhead distribution transformers. Distribution Transformers MN201003EN

A 1.2 kv class externally removable secondary bushing

S Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage.

COOPER POWER SERIES. Metal-enclosed capacitor banks installation instructions. Power Capacitors MN230010EN

S Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage

COOPER POWER SERIES. Metal-enclosed, pad-mounted capacitor banks installation instructions. Power Capacitors MN230009EN

S Voltage Regulators GENERAL. PRODUCT INFORMATION Introduction. Contents. Acceptance and Initial Inspection. Handling and Storage.

Eaton s Cooper Power Systems

Two-position sidewall (horizontal) and cover (vertical) mounted loadbreak switches

Factory Authorized Mechanism Enhancement (FAME)

Figure 1. Kearney Type HX cutout.

CCP2-FLR1-21_ flange-rod operating mechanism

100 A externally operated one-, twoand three-phase tap-changer switch

ELB ELB

25 kv class fused loadbreak elbow connector

Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version

Two-way cable interlock kit for Magnum fixed circuit breakers

COOPER POWER SERIES. Externally fused block banks installation instructions. Capacitors MN230004EN

600 A 15 kv class T-OP II deadbreak connector

COOPER POWER SERIES. Types VWE, VWVE27, VWVE38X, WE, WVE27, and WVE38X; threephase electronically controlled; installation and operation instructions

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal

Installation and removal instructions for Series NRX RF fixed breaker three-way Type 32 cable interlock kit

Reprogramming guide. Power Defense ICCB. Instructional Leaflet IL EN WARNING WARNING. Instructions apply to:

200 A 25 kv and 28 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

3-way multi-family drawout cable interlock kit - type 32 - RF

Removal/installation instructions for Series NRX (IZMX) drawout levering (racking) mechanism

Two-way cable interlock kit for Magnum drawout circuit breakers

600 A 25 kv class BT-TAP deadbreak connector

200 A 25 and 28 kv class POSI-BREAK loadbreak elbow connector with optional integral jacket seal-canadian Edition

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

COOPER POWER SERIES. RVAC Fluid-insulated Vacuum Switchgear; Installation, Operation, and Maintenance Instructions. Switchgear MN285005EN

600 A 15 and 25 kv class deadbreak accessories, tools, and replacement parts

200 A and 600 A, 15, 25, and 35 kv junction bars for separable connectors

Instruction Booklet IB E. Contents

COOPER POWER SERIES. Type MOST Fluid-Insulated Switchgear; Installation, Operation, and Maintenance Instructions

Installation Instructions for Interlocking Trip Indicator with Remote Reset for Magnum Low Voltage Circuit Breakers

600 A 35 kv class BT-TAP deadbreak connector

KFE10010-E. Reclosers. Contents. Type KFVE and KFVME (27kV) Bus Bar Kit KRK710-1 Installation Instructions. Cooper Power Systems

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

Low voltage bushings for pad-mounted distribution transformers Technical information guide

ELB ES. Product Installation Instructions

Technical specifications for 10 ka, heavy-duty class 1, 3 kv and 3.33 kv VariSTAR MOV disks

600 A 28 kv class Cleer loadbreak connector system

Effective October 2016 Supersedes January 2014 (S )

Technical specifications for 10 ka, heavy-duty class 1, 4.5 kv and 5 kv VariSTAR MOV disks

Edison modular fuse, vault application products

38 kv Bay-O-Net Cartridge and Fuse Assemblies Certified Test Report

Installation Instructions for KPS and KPH Circuit Breakers and Molded Case Switches

600 A 15 and 25 kv class Cleer grounding elbow

5/15/27 kv, 25/31.5/50/63 ka Manual Ground & Test Devices Installation, Operations and Maintenance Manual

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

Type DTU De-energized Tap Changer Application, Installation & Selection Guide. IL A Instruction Leaflet Page 1 September, 2003

Transcription:

OEM Equipment MN800008EN Effective February 2016 Supersedes S800-35-2 November 2013 COOPER POWER High-voltage primary bushings installation instructions SERIES

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation s ( Eaton ) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice. ii HIGH-VOLTAGE PRIMARY BUSHINGS INSTALLATION INSTRUCTIONS MN800008EN February 2016

Contents SAFETY INFORMATION Safety information...iv PRODUCT INFORMATION Introduction...1 Acceptance and initial inspection...1 Handling and storage...1 Standards...1 INSTALLATION INSTRUCTIONS Electrical ratings...2 Mounting requirements...2 Dielectric clearances...3 Torque requirements...3 HIGH-VOLTAGE PRIMARY BUSHINGS INSTALLATION INSTRUCTIONS MN800008EN February 2016 iii

! SAFETY FOR LIFE Safety for life! SAFETY FOR LIFE Eaton meets or exceeds all applicable industry standards relating to product safety in its Cooper Power series products. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing, and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high voltage lines and equipment, and support our Safety For Life mission. Safety information The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians who are familiar with this equipment should install, operate, and service it. A competent technician has these qualifications: Is thoroughly familiar with these instructions. Is trained in industry-accepted high and low-voltage safe operating practices and procedures. Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. Is trained in the care and use of protective equipment such as arc flash clothing, safety glasses, face shield, hard hat, rubber gloves, clampstick, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Hazard Statement Definitions This manual may contain four types of hazard statements: DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only. Safety instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. DANGER Hazardous voltage. Contact with hazardous voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around highand low-voltage lines and equipment. G103.3 Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. G101.0 This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury and equipment damage. G102.1 Power distribution and transmission equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install or maintain power distribution and transmission equipment can result in death, severe personal injury, and equipment damage. G122.3 iv HIGH-VOLTAGE PRIMARY BUSHINGS INSTALLATION INSTRUCTIONS MN800008EN February 2016

Product information All associated apparatus must be de-energized and all voltage sources removed during installation, removal or maintenance. Improper operation, handling, or maintenance can result in death or severe personal injury. CAUTION Use red or blue shipping cap provided to protect bushings from physical damage and contaminants. This shipping cap should not be used for insulating a bushing when energizing the unit. AIR GASKET (SELF CONTAINED GASKET) TANK WALL EPOXY WELL: FLAT GASKET W/7 TAPER Figure 1. 200 A, 15, 25, 28 and 35 kv Bushing Well (shown with removable stud and Tri-Clamp Well.) OIL/SF 6 Introduction Eaton's Cooper Power series high-voltage (primary) bushings are designed for external mounting (and removal) on pad-mounted transformers, filled with transformer oil, Envirotemp FR3 fluid, or an approved equivalent. Modified versions of these bushings are also available for applications with SF 6. They are to be installed inside cubicles. High-voltage (primary) bushings are used for connecting the high-voltage cables outside of the tank to the primary leads on the inside of the tank through the tank wall. AIR GASKET TANK WALL OIL/SF 6 Figure 2. 200 A, Loadbreak, One Piece Bushing, 35 kv. Read this manual first Read and understand the contents of this manual and follow all locally approved procedures and safety practices before installing or operating this equipment. Additional information These instructions cannot cover all details or variations in the equipment, procedures, or process described nor provide directions for meeting every possible contingency during installation, operation, or maintenance. For additional information, contact your representative. AIR GASKET TANK WALL OIL/SF 6 Acceptance and initial inspection Each high-voltage bushing is in good condition when accepted by the carrier for shipment. Upon receipt, inspect the shipping container for signs of damage. Unpack the high-voltage bushing and inspect it thoroughly for damage incurred during shipment. If damage is discovered, file a claim with the carrier immediately. Figure 3. 600 A, Deadbreak, One Piece Bushing, 15, 25 and 35 kv (15/25 kv bushing shown). Handling and storage Be careful during handling and storage of the high-voltage bushing to minimize the possibility of damage. If the highvoltage bushing is to be stored for any length of time prior to installation, provide a clean, dry storage area. Standards ISO 9001 Certified Quality Management System HIGH-VOLTAGE PRIMARY BUSHINGS INSTALLATION INSTRUCTIONS MN800008EN February 2016 1

Installation procedure Table 1. Electrical Ratings Voltage Withstand Maximum Voltage Continuous Impulse Minimum Rating (RMS) kv AC 60 Hz DC Current Withstand Corona Class Description 1 Min RMS 15 Min Rating* kv BIL Voltage P-G P-P 15, 25, & 28 200 A Bushing Well (HTN and epoxy) 40 78 200 A 125 21.5 16.2 35 Tri-Clamp, 200 A Bushing Well 50 103 200 A 150 26 21.1 35 1-Pc, 200 A Loadbreak Bushing 50 103 200 A 150 26 21.1 36.6 15/25 1-Pc, 600 A Deadbreak Bushing 40 78 600/900 A 125 19 15.2 35 1-Pc, 600 A Deadbreak Bushing 50 103 600/900 A 150 26 21.1 35 1-Pc, 600 A Deadbreak Bushing 70 114 600/900 A 200 26 21.1 * 600 A with aluminum components and 900 A with copper components. Mounting requirements Sidewall-mounted with the internal stud end completely immersed under oil or SF 6. All parts should be inspected for damage before using. Clamping studs must be welded around the bushing hole to accommodate either a 3-hole or 4-hole clamp. Install the gasket over the bushing assembly through the tank hole and place the clamp* over the welded tank studs against the bushing flange. Install a plated lock-washer and nut onto each stud and tighten to recommended torque. The Tri-Clamp well should have a plated flatwasher, lock washer and nut. Tighten to recommended torque. Connect internal lead to the internal bushing stud using recommended torque and procedures. See Figure 5. *One-piece molded (Tri-Clamp) bushing well does not require a clamp. Table 2. Tank Hole (Ref. Figure 4) 4-Stud Square Clamp kv Class 15 & 25 15, 25 & 35 35 15, 25 & 35 Description 200 A Bushing Well with a 2.19" 200 A Bushing Well with a 2.50" "A"** Tank Hole Size (Dia.) 2.25" (57 mm) 2.56" (65 mm) 200 A Loadbreak 3Ø 2.75" (70 mm) 2.56" 600 A Deadbreak (65 mm) "B" C-C Stud Spacing 2.75", 3.00", or 3.25" (70, 76, or 83 mm) 2.75", 3.00", or 3.25" (70, 76, or 83 mm) 3.87" (98 mm) 3.43" (87 mm) B A MOUNTING STUDS 120 TYP. 4 STUD 3 STUD Figure 4. Tank mounting hole for 3- and 4-hole stud configuration. A 30TYP. C BOLT CIRCLE DIAMETER 4.7" (120 mm) MIN. DIA. EXTERIOR MOUNTING SURFACE BETWEEN THE DOTTED LINE AND TANK HOLE TO BE FLAT AND CLEAR OF SURFACE OBSTRUCTIONS, SUCH AS WELD SPLATTER. GASKET SPACER NUT TANK WALL HIGH VOLTAGE LEAD AND TERMINAL: No sharp edges or burrs. Should be directed parallel to or away from tank wall. BUS BAR: No sharp edges or corners. Should be directed parallel to or away from tank wall. TIGHTENING NUTS (1 OR 2) Figure 5. High voltage bushing (all, including bushing well) internal lead training. (Bushing shown-35 kv, 600 A deadbreak.) 2 HIGH-VOLTAGE PRIMARY BUSHINGS INSTALLATION INSTRUCTIONS MN800008EN February 2016

Table 3. 3-Stud Triangular Bushing Clamp or One Piece Tri-Clamp Bushing Well kv Class 15 & 25 15, 25, & 35 Description 200 A Bushing Well with a 2.19" All 200 A Bushing Wells with a 2.50" 35 200 A Loadbreak Dielectric clearances "A"** Tank Hole Size (Dia.) 2.25" (57 mm) 2.56" (65 mm) 2.75" (70 mm) "C" Bolt Circle (Dia.) 4.68" (119 mm) 4.68" (119 mm) 4.68" (119 mm) NNote: Recommended Tank Stud Dimension 3/8" - 16 x 1.625" (41 mm). ** "A" Tankhole Size Tolerance is -0.00"/+0.10" (-0/+2.5 mm) Oil level and bushing clearance to other internal components to be suitable for voltage class of equipment and components. Minimum underoil clearances: kv BIL Clearance to Ground or Between Phase 95 1.1" (28 mm) 125 1.5" (38 mm) 150 2.5" (64 mm) 200 3.5" (89 mm) Internal (underoil or SF 6 ) bushing stud Brass nuts are recommended for copper threads and aluminum nuts for aluminum threads. Nuts for internal bushing studs should be tightened as follows: 200 A, 3/8-16 brass nuts 12-15 ft-lbs 600 A, 5/8-11 brass nuts 50-65 ft-lbs 600 A, 5/8-11 aluminum nuts 50-65 ft-lbs Install nut onto the internal bushing stud. Place high voltage lead terminal with crimped ring torque terminal onto the bushing stud against the nut. Place a second nut onto bushing stud and tighten to the recommended torque. An optional locking nut may also be placed on the stud and tightened to the recommended torque. Removable stud bushing well The part number for the removable stud replacement kit is 2639081B01B. For replacement instructions of the removable stud from bushing well/insert, refer to S800-34-2. Grounding of bushing insert It is recommended that, when a bushing well insert is installed into the well, the Insert be grounded by attaching a #14 AWG or equivalent wire between one of the three mounting studs to one of the tabs on the Insert (see MN650015EN). This can be accomplished by wrapping the wire around one of the studs and securing with an additional 3/8" nut. Other options are available. Please contact your Eaton representative for more information. Torque requirements Clamping Flange For 3-hole and 4-hole clamp torque requirements, see Table 4. Molded (one-piece) Tri-Clamp bushing well should be tightened to 70-80 in-ibs torque. NFor Note: SF 6 bushings torque should be held at 50-60 inlbs. Hold clamping flange against the bushing and tighten all nuts by hand against the lockwashers. With a torque wrench, tighten nuts down gradually, alternately in increments until the recommended torque is obtained. On 4-hole stud clamp tighten nuts in a diagonal sequence. Mounting studs should be free of nicks, paint, dirt and weld splatter. They must also be correctly positioned to avoid binding on the clamping flange. Table 4. Torque Requirements-Clamping Flange Torque kv Class Description (in-lbs) 15 & 25 200 A Bushing Well with a 2.19" 40-60 15, 25, & 35 200 A Bushing Well with a 2.50" 40-60 35 200 A Loadbreak 3Ø 40-90 15, 25, & 35 600 A Deadbreak 40-90 HIGH-VOLTAGE PRIMARY BUSHINGS INSTALLATION INSTRUCTIONS MN800008EN February 2016 3

Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com! SAFETY FOR LIFE Eaton s Cooper Power Systems Division 2300 Badger Drive Waukesha, WI 53188 Eaton.com/cooperpowerseries 2016 Eaton All Rights Reserved Printed in USA Publication No. MN800008EN Rev 00 (Replaces S800352 Rev 04) Eaton is a registered trademark. All trademarks are property of their respective owners. For Eaton's Cooper Power series product information call 1-877-277-4636 or visit: www.eaton.com/cooperpowerseries.