Installation Manual for DC Injection Brake Units

Similar documents
SDS Enclosed Star-Delta Starter User Guide

Open Chassis Star-Delta Starter User Guide

KD LV Motor Protection Relay

Direct On Line (DOL) Motor Starter. Direct Online Motor Starter

2.1 Warnings & Agency Approvals Electrical Connections - Specifications Standard Wiring Configurations...2 4

CI-tronic Soft Start Motor Controller Type MCI 25B with Brake

Crompton Controls. This is. Installation and Maintenance Instructions. S10 & Smooth-BRAKE DC Injection Brake Modules. Tel: +44 (0)

MAGNETIC MOTOR STARTERS

RVS-AX Instruction Manual

SHORT-STOP. Electronic Motor Brake Type G. Instructions and Setup Manual

CI-TI Contactors and Motor Starters Type CI 6-50

ADS7 AC Contactor Starters

CI-TI Contactors and motor starters Types CI 61 - CI 98

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW

Power Electronics. Motor brake relay GA 9031 ministop

CI-Tronic Soft start motor controller MCI 3, MCI 15, MCI 25, MCI 30 I-O, MCI 40-3D and MCI 50-3 I-O

Data sheet. CI-tronic Soft start motor controller Type MCI 3, MCI 15, MCI 25, MCI 30 I-O, MCI 50 I-O 520B1443

FUSERBLOC CD. The universal Fuse Combination Switch FROM 20 TO 1250 A. Industrial Switching & Protection Systems

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2

CTi Automation - Phone: Fax: Web:

HIB Enclosed Inverter User Guide

3.2. Current Limiting Fuses. Contents

RE-PR1-F 1-Phase Din-Rail Mount 1.5, 3 & 6kW

SALDET SALES & SERVICE, INC. CLINTON TOWNSHIP, MICHIGAN

Data sheet. CI-TI TM Contactors and Motor Starters Circuit Breakers CTI B1427

DEEP SEA ELECTRONICS PLC

FUSE: SAFE & RELIABLE

Application example of a motor controlled by MCD100 and protected by a circuit breaker

Commissioning Instructions Inbetriebnahme Anleitung VB 230/ L (LP)

SECTION MOTOR CONTROL

Technical Guide No. 7. Dimensioning of a Drive system

ACS motor protection circuit breakers KT 7 Introduction

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC

Low Voltage Fuses For Motor Protection

Presentation Soft starters 0 Altistart 48 soft start - soft stop units

Softstarters. Softstarters Type SSM Medium voltage ,800V 1

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

1 Phase electronic contactor (SC 1)

EXPERIMENT 2 THREE PHASE INDUCTION MOTOR, PART 1

Question Number: 1. (a)

Approved Standards. Motor Contactor. Main contactor. Accessoires. 21 Motor Contactor J7KN

Motor Starting Solutions Open Type Version, in Kit Form

Series Motor Protection

Low cost, internally bypassed non optimizing soft starter

Combined Motor Start and Braking Device VBMS... Assembly- and Commissioning Instructions

AF series contactors (9 2650)

Technical Section: Miniature Circuit Breakers

DNH INDUSTRIES ***** COMPACT ***** EASY TO INSTALL ***** STATUS INDICATORS ***** DUAL LINE FUSING ***** INSULATED FRONT COVER ***** ADJUSTABLE OUTPUT

LCL FILTERS INSTRUCTIONS MANUAL (M A) (c) CIRCUTOR S.A.

AF series contactors (9 2650)

Types of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are:

Essential equipment for all your requirements

MAKING MODERN LIVING POSSIBLE. Design Guide VLT MCD 100 Soft Starter the single speed drive

PHASE CONVERTERS OPERATING & MAINTENANCE INSTRUCTIONS. MODEL NO: PC40 and PC60. PART Nos:

Paramount HRC Cartridge

Design Guide. VLT Soft Start Controller MCD 100

ELECTRICAL INSTALLER THEORY EXAMINATION 21 June 2014 QUESTION AND ANSWER BOOKLET

AF09... AF30 3-pole Contactors up to 20 HP / 480 VAC

MAKING MODERN LIVING POSSIBLE. Technical brochure. Minicontactors CI 5-

CI-tronic Soft starters for Danfoss commercial compressor applications Type MCI 15C, MCI 25C, MCI 50CM-3 I-O

Electronic Ballast EVG 2000-T

1-3 RAMP AND TORQUE BOOST EXERCISE OBJECTIVE

CI-TI TM Contactors and Motor Starters Contactors CI 6-50

1332 TROUBLESHOOTING GUIDE. Remarks: If this function is not appropriate for the application, it can be eliminated by turning off DSWl, switch 3.

Contactor Types CI 61-98

Sentry Technical. Miniature Circuit Breakers (MCBs) Standards and approvals. Description. Technical specification

Functions provided by measuring relays in railway equipment

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES

NRBM Series. Between main circuit terminals: 2,000V AC, 1 minute Between main circuit and auxiliary contact: 2,000V AC, 1 minute

DRAFT 1400HP 1000HP 100HP. Reduced Voltage Solid State Starters. Softstarters SOFT. PF Controller PCS Controller PDS Controller V 1...

This manual is to be given to the end user. Optional RFI filter. Drive. Stop. Thermal protection device. Start / Reset +DC.

REVISED ATM72 Auto Transfer Module

Mini Contactors CI 4-

Synergy EN product information

SOLSTART Instruction Manual

Contactor Catalogue. According to CE, IEC 947, EN Pole & 4 Pole Contactors 4kW - 160kW Thermal Overload

Bussmann series NH catalogue. Leadership in circuit protection

Miniature circuit breaker Application guide

Application of AC Dahlander Three-Phase Induction Motor AEL-ACDHA

INSTALLATION INSTRUCTIONS FOR SYMCOM'S MODEL 777-HVR-SP ELECTRONIC OVERLOAD RELAY

High-Efficiency AR Series. RK Series /0.72 /Geared. CRK Series. RBK Series. CMK Series. 2-Phase Stepping Motors A-278.

TeSys contactors. Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current Ie. to be wired in series

Starting Torque Limiter Type TCI (Soft Start)

Industrial contactors CTX-1

DFE. Fairford low cost, internally bypassed non-optimizing Soft Starter

Starters. Overview. Siemens caters with following types of starters to agricultural and industrial sector.

SECTION MOTORS AND VARIABLE FREQUENCY DRIVES

Chapter 8. Understanding the rules detailed in the National Electrical Code is critical to the proper installation of motor control circuits.

Starting Combinations

Starting of Induction Motors

Application of AC Three-Phase Induction Motor of Squirrel Cage AEL-ACINA

Miniature & Moulded Case

Braking Devices BR 230/ Assembly- and Commissioning Instructions

Principles of iers (intelligent

IQS and IQSL Range. Electrical Data Single-Phase Power Supplies. Keeping the World Flowing

Mechanical Operating Instructions

LA Motor Protection. A South African Company to be Proud of

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM

WARRANTY INFORMATION...

Components for EEx e Panels

Transcription:

Power Drive Services INJ Series DC brake modules PDS 11-30-100A Page 1 of 17 Issue 15

Contents. 1. Safety. 2. Installation. 3. Setting Up. 4. Wiring Diagrams. 5. Specifications. 6. Selection. 7. Timing Diagram. 8. Physical Dimensions. Power Drive Services Unit 1 Victoria Street Ind. Est. Victoria Street Leigh Greater Manchester WN7 5SE UK Tel. 01942 260 206 Email www.inverter.co.uk/contact.htm Web www.inverter.co.uk Date, April 2012 PDS 11-30-100A Page 2 of 17 Issue 15

1. Safety. Modification of any machine may require a safety risk assessment. As a result of the risk assessment additional safety systems or interlocks may be required. Safety relays are available if required. Please contact us if you require help with a risk assessment or any other safety equipment. Read this manual fully before installation. The assembly is an electrical system and must be installed by a competent person. Ensure all authorised persons are aware of the dangers and safe working practices. 1.1. Safety Electrical. The voltage at some of the terminals is high enough to endanger life. The terminals have only protection against accidental contact. The module must be installed in a panel to which unauthorised access is denied. Semiconductor fuses should be fitted to protect only the brake module. Upstream circuit breakers must be provided to protect the wiring. The wiring should conform to the latest IEE regulations, or local regulations whichever are more stringent. 1.2. Safety Mechanical. Rotating and moving machinery can cause injury or endanger life. Only a competent person should modify the operation of any machine. Consideration must be taken of any potential hazards. These may be couplings: threaded couplings which may unscrew if the motor is stopped, couplings fixed by shear-pins would need to be checked to see if these can withstand the stopping torque, friction couplings would need to be checked to see if these withstand the torque. The machine mountings must be checked to see if they can withstand the forces during stopping. 2. Installation. The brake module is installed downstream of the machine isolator and any motor overload relay. The module will require an auxiliary contactor of its own in most starter circuits. Please refer to the typical installation diagrams at the back of this manual. A cursory view of the diagrams will show that the brake significantly alters the starter circuit 2.1. Earth Connection. The brake assembly must have an earth connection. The earth cable cross section should be as big as the cable used for the power wiring. PDS 11-30-100A Page 3 of 17 Issue 15

3. Setting Up. 3.0. General. The minimum equipment required is a dc clip-on ammeter. Be sure to measure the current in the motor wiring which carries the dc injection current. One of the motor wires does not carry any current during braking. Make sure that the brake can cope with the worst case. The worst is achieved by ensuring that the test is carried out with the maximum moment of inertia (load) coupled to the motor shaft. Remove any friction from the rotating member. A series of test start-stop cycles will be made during setting up. If the installation has been done correctly, be aware that the brake unit should deny re-starting during braking. Also be aware that the duty is limited by the braking current, and the ambient temperature. Too many stop / start cycles in close succession may damage the unit. See the specifications for some idea of permissible duty. The procedure requires the machine to be run up to normal speed, and the brake (stop) applied. During the braking period the current is monitored, and adjusted up to the maximum permitted by the motor, or the brake unit. 3.1. Measuring Current 1. Do not estimate dc current by measuring the ac current. The dc current is much bigger than the ac current. It is ESSENTIAL to use a DC measuring clamp meter. Fit the meter around the V line to the motor. 2. If your clampmeter does NOT have a battery it does NOT measure dc current. 3 If it does have a battery it still may not measure dc current. Check the instruments specifications. PDS 11-30-100A Page 4 of 17 Issue 15

3.2. Current 0-100%. The front panel of the module has a ¾ turn screw adjustment for current. Maximum current is fully clockwise. The current must be measured with a dc meter. The rated current of the unit will be achieved at somewhere below 100% depending on the motor. The supply voltage, and the resistance of the motor limit current. Too much current can damage the brake unit, and it is crucial that the DC current is monitored during adjustment. The braking torque increases with current. Consistent with duty and module rating, the DC current for a DOL starter may be set up to 2 x the motor full load current (flc). Above 2 x flc the braking torque may begin to fall. For a star delta starter the dc current is applied to two windings, and should be limited to 2 x the star current, or 1.15 x the delta current (i.e. full load current). 3.3. Time 1-10s. The front panel of the module has a ¾ turn screw adjustment for time. The duration of the braking can be adjusted between 1 and 10 seconds. The adjustment is logarithmic with 4s at 50%, and 3s at 75%. Maximum time is fully clockwise. (The same as the current control.) 3.4. Procedure. 3.4.1. Initially set the time for about 4 seconds (50%). The time is long enough to allow the current meter to get a good indication, and short enough to keep the duty low during repeated stop / starts. 3.4.2. Set the current adjustment to about 20% and start the machine. Stop the machine and observe the current in a motor line that is carrying the DC injection. It is not necessary to attain full speed before stop is applied. 3.4.3. Adjust the current setting and repeat the stop / start until the desired current is attained. Pay attention to the duty rating of the brake unit during setting up. Allow ½ hour for the unit to cool if setting up has taken longer than the duty rating will allow. 3.4.4. Start the machine, and allow it to get to full speed. Stop the machine and observe the residual speed when the braking has stopped. If the machine is still running, the brake time should be increased. If the machine has stopped, it may be possible to reduce the brake time. It does no harm to have the brake applied for half a second after the machine has reached standstill. The brake is now set for use. 3.5. Alternative Procedure. The previous set-up was dominated by the current setting. In some applications you may wish to stop a little less quickly. Set the brake time first, and then increase the current until standstill is achieved within the desired time as follows 3.5.1. Initially set the current for about 30%. The current is high enough to allow the current meter to get a good indication, and short enough to keep the duty low during repeated stop / starts. 3.5.2. Set the time adjustment to the desired amount and start the machine. Allow the machine to reach full speed and stop the machine. Observe the current in a motor line that is carrying the DC injection. Check that the brake action is sustained over the desired stopping time. 3.4.3. Adjust the current setting and repeat the stop / start until the machine stops within the desired stopping time. The brake is now set for use. PDS 11-30-100A Page 5 of 17 Issue 15

3.6. Monitoring Brake Activity. Detecting brake activity can be done in several ways as follows 3.6.1 Observe the current meter. Braking only occurs when current is flowing. The current ceases about 200ms before the brake cycle is ended. 3.6.2 Listen for the brake contactor to drop out. Current ceases about 200ms earlier. 3.6.3 Listen to the sound of the motor. During braking the motor noise may be heard as a low "growl". The harmonic currents in the motor during braking are predominantly 50Hz. The characteristic hum of single phase equipment by comparison is an octave higher. Three phase equipment is higher still, and sounds more pleasant. 3.7. Temperature. On initial setting add some extra time or current in excess of the setting that just stops the machine. Add 10% for example. After initial setting-up check the braking during a normal work period. As the motor heats up during use, the resistance of the windings will rise a little. The machine may come to rest a little later than it did during setting-up PDS 11-30-100A Page 6 of 17 Issue 15

4. Wiring Diagrams. PDS 11-30-100A Page 7 of 17 Issue 15

PDS 11-30-100A Page 8 of 17 Issue 15

PDS 11-30-100A Page 9 of 17 Issue 15

4.1 Protection. The wiring diagrams show C type circuit breakers as the protection for the brake modules. Circuit breakers are convenient, but may not be suitable for the application. If the operating current of the unit is high, and the motor inductance is low you may hear the circuit breaker buzzing when the brake is applied. In these cases a D type breaker may be required. The protection of the unit becomes compromised. Fuses are a better solution, but semiconductor types must be used. Fuses are less convenient because they cannot be reset like a circuit breaker. Fuses often get replaced by the wrong types and rating. 4.2 Fuse Ratings. The fuses should be ar types, semiconductor or ultra rapid. The fuse ratings are the ac rating of the fuse. The voltage rating is the ac voltage of the circuit. The A 2 s ratings given are the total let-through, not the pre arcing. Brake Unit Fuse Rating A A 2 s Maximum 11A 6 0.45 ka 2 s 25A 15 0.45 ka 2 s 50A 32 6 ka 2 s 75A 40 6 ka 2 s 120A 63 80 ka 2 s 220A 100 125 ka 2 s PDS 11-30-100A Page 10 of 17 Issue 15

5. Specifications. 5.1.1. General Function of Terminals. L1.L2. Ac power. D,C. Dc output to motor. 4 Control input, referenced to L1. PE Protective earth. Not required on 25A units. 3 Do not connect. 0,1,2. Isolated changeover contacts energised when braking. Trim. Brake current adjustment, 0-100%. Trim. Brake time adjustment, 1-10s. An external contactor connects the unit to the motor. DC current is generated from the ac supply when an enable signal is given. The unit allows for manual adjustment of the current. The time for which the current is applied is also manually set on the unit. An internal contact set is energised during braking so that the start circuit can be defeated. 5.1.2. Power Input L1, L2. The input current into terminals L1 and L2 varies with the line voltage, the resistance across D and C, and the current setting. The input current ac rms will not exceed ½ the dc output current, and in most cases will not exceed ¼ the dc output current. 5.1.3. Control Input. L1, 4 The control input is the primary of a 2VA transformer. Braking action is triggered by sudden application of voltage on terminal 4. If voltage is applied gradually the brake cycle will not be triggered, and the unit will remain in the timed-out state. For detailed information see the timing diagram in this manual. The voltage at this terminal must be from the same phase as that voltage supplied to terminal L2. 5.1.4. Output D,C. The output voltage is a single phase, phase angle controlled half wave rectified voltage. The maximum output voltage is as follows: V rms on L1, L2 400 230 110 V dc ave. on D, C 90 50 25 The current is not controlled, and is determined solely by the resistance across D and C, and the line voltage. It is crucial that the dc current is monitored during setting up, so that the units are not damaged. Motor resistances vary considerably, and for most applications the current setting will be much less than 100%. 5.1.5. Change-over Contact 0,1,2. An isolated change-over contact is provided on terminals 0, 1 and 2. Terminals 0 and 1 are made when the unit is de-energised or timed out. Terminals 1 and 2 are made when the unit is braking. The contacts have a rated breaking voltage of 250Vac, and a maximum breaking voltage of 440Vac. The rated load is 8A or 2kVA. The contacts are usually used only to operate a single contactor. The power contacts of the contactor are used to connect the brake unit to the motor. Further auxiliary contacts on this contactor are used to lock out any attempts to re-connect the motor whilst braking is in progress. PDS 11-30-100A Page 11 of 17 Issue 15

6. Selection. A simple rule of thumb is that a rotating assembly cannot be stopped any sooner than it can be started. A relatively small motor turning a large mass may take 30 seconds to reach full speed. Similarly the same motor will be unable stop the same mass any sooner. Braking is the reverse of accelerating. A standard squirrel cage motor will decelerate quite gently at first. The braking force increases until it reaches maximum near rest (5% rated speed). At rest the braking torque is minimal. To lock the shaft at rest always requires an auxiliary mechanical brake. Combinations of electrical braking and mechanical are not uncommon, the mechanical system provides shaft locking, whereas the electrical system offers wear free stopping. The following tables list the recommended brake ratings. Remember to account for the line to line voltage, and the starter system which is employed. Please be aware of the intended duty of the application. For higher duties choose the next larger size of unit. 6.1. Fixed Motor Configurations 400V. Fixed configurations occur with DOL and most soft start connected motors. In these applications the three windings in the motor are permanently wired, and only three wires go to the motor. The first column shows the rating of the unit required to brake the motor. The second column is the nominal motor power at 400V line to line. The next column lists a typical motor current for the listed motor power. Model Power kw Imot Arms Brake Adc 400V 3ph DOL INJ-H-11A 1 2 4 1.5 3 6 2.2 4.4 8.8 INJ-H-25A 3 6 12 4 8 16 5.5 11 22 INJ-H-50A 7.5 15 30 11 22 44 INJ-H-75A 15 30 60 18.5 37 74 INJ-H-120A-ASS 22 44 88 30 60 120 INJ-H-220A-ASS 37 74 148 45 90 180 55 110 220 The final column shows the maximum dc current which will achieve the braking. Less current will brake more gently. More current may brake more, but not proportionally more, and in some cases may brake less. PDS 11-30-100A Page 12 of 17 Issue 15

6.2. Star Delta Starter Configurations. 400V. With a star delta starter considerable advantage can be gained if you are able to re-connect the motor in star for the duration of the braking period. The recommended dc brake current is that current flowing in series in two of the windings. When retro-fitting a brake system to an existing starter some thought needs to be given to the modification of the circuit. The typical wiring diagrams earlier in this manual give some guidance. Model Power kw Imot Arms Brake Adc 400V 3ph YD INJ-H-11A 1 2 2.3 1.5 3 3.5 2.2 4.4 5.1 3 6 6.9 4 8 9.2 INJ-H-25A 5.5 11 12.7 7.5 15 17.3 11 22 25.4 INJ-H-50A 15 30 34.7 18.5 37 42.8 22 44 50.9 INJ-H-75A 30 60 69.4 37 74 85.5 INJ-H-120A-ASS 45 90 104 55 110 127 INJ-H-220A-ASS 75 150 173 80 160 185 95 190 220 There will be occasions where the circuit does not lend itself to simple modification. In cases where the windings cannot be connected in star during braking, only one winding will be dc injected. More current is required to achieve the same brake torque. The power ratings and brake types in section 6.1 should be used as a guide for the upper limit of brake current. 6.3. Fixed Motor Configurations. 230V. Fixed configurations occur with direct on line and most soft start connected motors. In these applications the three windings in the motor are permanently wired, and only three wires go to the motor. At lower voltage, the same motor power requires more current. Model Power kw Imot Arms Brake Adc 230V 3ph DOL INJ-L-25A 1 3.5 6.9 1.5 5.2 10.4 2.2 7.6 15.2 3 10.4 20.7 INJ-L-50A 4 13.8 27.6 5.5 19.0 38.0 7.5 25.9 51.8 INJ-L-75A 11 38.0 75.9 INJ-L-120A-ASS 15 51.8 103.5 INJ-L-220A-ASS 18.5 64 128 22 76 152 30 104 208 PDS 11-30-100A Page 13 of 17 Issue 15

6.4. Single Phase Motors. 230V. A single phase machine normally has only two wires going to it, and is for smaller machines with DOL starting. Model Power kw Imot Arms Brake Adc 230V 1ph DOL INJ-L-11A 0.25 3.2 4.8 0.37 3.5 5.2 0.55 4.8 7.2 0.75 6.2 9.3 INJ-L-25A 1.1 8.7 13 1.5 11.8 17.7 INJ-L-50A 2.2 17.5 26.3 3 20.0 30 4 26 39 6.5. Options. 6.5.1 Standard. The standard brake modules have an approximately 1s delay before the brake contactor is energised. The voltage then builds up gradually over a further ½ second. The delay and gradual application is most suitable for situations where the brake is applied every time the motor is stopped. Wear on the machinery and motor is kept to a minimum. 6.5.2 EMR. Any brake unit can be factory configured as an EMR unit. In some situations it is more important to stop the machine, than to save wear. A typical compromise is to employ stop/start buttons for normal duty where the machine freewheels to a stop. A third switch (in the form of a normally closed trip-switch) triggers the brake immediately. The EMR type unit can be supplied as a complete assembly with normal duty stop/start buttons, and a normally closed trip switch input. An existing starter may be used, but the wiring is a little more involved. 6.5.3 Longer Brake Times. Some machine / motor combinations just can t stop immediately, nor can they be stopped within 10s. To this end we can supply a brake with a longer application time. Units with maximum brake times of 30s have been supplied. The next size up module may be required depending on the braking current required. Also be aware that the brake current must not so high that it can damage the motor. Please consult the factory. PDS 11-30-100A Page 14 of 17 Issue 15

6.5 Duty Considerations. INJ-L(H)-25A. The chart right shows the duty rating of the 25A units INJ- H-25A and INJ-L-25A. Amps dc 25 20 3s 2s Operation of the unit at the maximum braking period of 10s is possible at any point to the left of the 10s curve. 15 5s For example a 15Amp 10s braking current can applied 20 times an hour. 10 10s Alternately the braking current can be increased to 25Amps, but only for 5s 20 times an hour. The unit will tolerate four consecutive 10s 25Amp brake cycles, but must be allowed to cool for ½ hour before the cycles may be repeated. 5 0 0 0 INJ-L(H)25A Brakes per Hour 10 20 30 40 50 60 70 Minutes between brakes 6.0 3.0 2.0 1.5 1.2 1 50s Duty % 0 2 4 6 8 10 12 14 16 18 20 INJ-L(H)-50A. Amps dc 50 The chart right shows the duty rating of the 50A units INJ-H-50A and INJ-L-50A. The external heatsink considerably extends the operating range so that current or brake time reduction is required only above 55 stops per hour. 40 30 10s 5s INJ-L(H)-75(120, 220)A ASS. The high current assemblies have substantial heatsinks and the duty cycle is limited to 50% at 10s and rated current. The rating is equivalent to three stops per minute continuously. 20 10 0 INJ-L(H)50A Brakes per Hour 0 10 20 30 40 50 60 70 Minutes between brakes 0 6.0 3.0 2.0 1.5 1.2 1 50s Duty % 0 2 4 6 8 10 12 14 16 18 20 PDS 11-30-100A Page 15 of 17 Issue 15

7. Timing Diagram The following diagram needs little explanation. The time between the application of the brake contactor and the release of the run contactor is governed by the brake relay, and is of the order of 1s. Current is applied 200ms after the brake contactor is energised, and removed 200ms before the brake contactor is released. The brake contactor does not have to break the current, and is conservatively rated at a thermal rating of the braking current. For the EMR option, the brake is applied 50ms after the main contactor is released, and current build up is instantaneous. Depending on the characteristics of the motor, there will be an initial pulse of current. Where the motor stops with a jolt, the initial pulse can be as high as the starting current pulse. Energised Motor Run Contactor (s) 1s Standard 50ms EMR Energised 1 and 2 closed Change-over Contacts 0,1,2 Energised Brake Contactor Braking EMR Braking Standard Motor Current PDS 11-30-100A Page 16 of 17 Issue 15

8. Physical Dimensions, Mount units with heatsink fins running vertically. PDS 11-30-100A Page 17 of 17 Issue 15