DANGER. Instruction Bulletin WARNING. Shunt Trip Kit for Manual DS/DSL Circuit Breakers POWER ZONE III Low Voltage Switchgear Class 6035 INTRODUCTION

Similar documents
Q-Frame Main Circuit Breaker (225 A Maximum) and Adapter Kit Installation onto an NQ Panelboard Class 1640

Instruction Bulletin NF Panelboard Dual Sub-Feed Circuit Breaker Adapter Kit Installation onto an NF Panelboard Class 1670

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Instruction Bulletin Dual Sub-Feed Circuit Breaker and Adapter Kit Installation onto an NQ Panelboard Class 1640

Instruction Bulletin. DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Class 6035

H- or J-Frame Main Circuit Breaker and Adapter Kit Installation onto an NQ Panelboard Class 1640

ibusway for Data Center

Electrically Held to Mechanically Latched Contactor

Position Switch Kits Accessory Kits for EntelliGuard* Retrofill Circuit Breakers

Dead Tank Outdoor Vacuum Circuit Breaker, Type VOX

Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers

Instructions for Field Retrofit of a Model 98 Temperature Controller in place of a Model 85 Temperature Controller

dans un panneau de distribution NQ Instruction Bulletin Boletín de instrucciones Directives d'utilisation

Digitrip Retrofit System for Allis-Chalmers G-25 Breakers

Digitrip Retrofit System for Allis-Chalmers LA-600 F Electrically Operated Fused Breakers

Test Cabinet (Inspection Box) Instructions. for Testing Accessories on Manually and Electrically Operated EntelliGuard G Low Voltage Circuit Breakers

Installation Instructions for Interlocking Trip Indicator with Remote Reset for Magnum Low Voltage Circuit Breakers

Vacuum Circuit Breaker Type VAD-3

www. ElectricalPartManuals. com Digitrip Retrofit System for Allis-Chalmers LA-4000 F Fused Breakers IL 33-A1K-1 WARNING

Digitrip Retrofit System for General Electric AKR/AKRU-6D/7D-30S Series Breakers

Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker

Freedom egen System End-of- Line Functional Checklist

Galaxy Receiving and Unpacking 09/

Two-way cable interlock kit for Magnum fixed circuit breakers

www. ElectricalPartManuals. com Digitrip Retrofit System for BBC LKD 8 Breakers IL 33-LK8-2

S&C Type FVR Substation Circuit Breaker

a WARNING Allen-Bradley Parts K-Frame Circuit Breaker Instruction Leaflet for Alarm Switch and Alarm /Auxiliary Switch Combination Bul.

MASTERCLAD Metal-Clad Indoor Switchgear

OPERATION MANUAL, POWER MODULE-CHARGER SYSTEM. Man Occup. Machine Occup. Cycle Time Setup Time Batch Qty. Equipment Manufacturer Qty

Series A Construction

Feeder Circuit Breaker Units Secure Support Pan and Change Door Latch

SecoVac * Ground & Test Device

Q and M-Frame Circuit Breakers Instruciton Leaflet for Alarm Switch and Auxiliary Switch Combinaiton

Digitrip Retrofit System for Siemens-Allis RLX-1600 Breakers

www. ElectricalPartManuals. com

505 Size 5 Series A Construction

SM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety

ProTrip Conversion Kits. For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION. DEH Installation Instructions

www. ElectricalPartManuals. com Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers

User manual W-VACi. W-VACi 12 / 17.5 / 24 kv IEC Vacuum Circuit Breakers

Universal Splice Tray Installation Instructions

Vacuum Circuit Breakers (Vehicle)

IL131029EN. Instructions for the 15kV VCP-W 25-63kA Simple Manual Ground and Test Device

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

www. ElectricalPartManuals. com Digitrip Retrofit System for the Westinghouse DA-50 IL 33-DAC-2 WARNING

Page 2 DS LOW VOLTAGE POWER CIRCUIT BREAKERS Digitrip Trip Unit Inside Wiring Guide Outside Wiring Guide Shutter Drawout Unit Position Indicator Escut

Digitrip Retrofit System for the General Electric AKR 6D/7D-30/50 and AKRT 6D/7D-50 Series Breakers

Instruction Booklet IB E. Contents

Removal/installation instructions for Series NRX (IZMX) drawout levering (racking) mechanism

Altivar 61/71 Adjustable Speed Drives Plastic Kits and Power Terminal Kit

Installation and Service Instructions for Self Adjust Brakes 81,000 Series

PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide

Cutler-Hammer I.L. 29C160G WARNING NOTICE 1-0 INTRODUCTION. General Information

Circuit breaker interlocking and operation requirements SIEMENS

EntelliGuard Power Circuit Breaker Accessories. Network Interlock for Ampere Circuit Breakers. Introduction. Operation

Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version

Simple Electrically Operated Ground & Test Device For use in Type VCP-W Switchgear rated up to 15kV, 25 and 40kA UPPER TERMINAL SET VERSION

Cutler-Hammer. Instructions for Potential Transformer and Auxiliary Control Power Disconnecting Means for Use in Ampgard Lineups, 7.2 kv I.B.

Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9928C

Specification Guide. for RMVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

Type 38-3AH3 38 kv vacuum circuit breaker instruction manual. Installation operation maintenance E50001-F710-A238-V1-4A00. Answers for energy.

RIGID ENTRY BOOT INSTALLATION GUIDE

Galaxy 300 Battery Breaker Kit G3HTBKIT1

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.

Galaxy VM. Battery Breaker Box Installation 09/

Vacuum Circuit Breakers (Vehicle)

INSTALLATION GUIDE AND USER MANUAL

CCP2-FLR1-21_ flange-rod operating mechanism

T- VACR Fixed (up to 40kA) T-VAC Draw out (up to 40kA)

Type 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear

38 kv Type VCPW-HD Simple Electrical Ground & Test Device (SEG&TD) lower terminal instruction booklet

Service Bulletin No. 3089

Installation and Service Instructions for 87,000 & 87,100 Series Self-Adjust Brakes (rev. B)

TSS Tool Stand. Installation and Operation Manual. Document #:

Enclosure for AMP1 Series Energy Meters with Swing Panel Kit

Installation Instructions For Motor Control Center (MCC) Units

Replacing a Gun RTD. Instruction Sheet P/N B. 1. Introduction. Using this Instruction Sheet

Installation and Service Instructions for 87,000 & 87,100 Series Self-Adjust Brakes (rev. B)

Digitrip Retrofit System for BBC LKD 8 Breakers

Magnum breaker remote racking device (MRR1000)

VD4 Installation and service instructions kv A ka

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING

Programmer Disconnect Accessory Manual for Retrofil CB

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.

Installation and removal instructions for Series NRX RF fixed breaker three-way Type 32 cable interlock kit

FOR PRICES ON DSII and DSLII BREAKERS, REFER TO PRICE LIST PL.22B.01.P.E

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

Instruction Bulletin. Hand-held Test Kit. for Micrologic Series 2.0 and Above Trip Units and Compact NS Circuit Breakers Equipped with STR Trip Units

PROCEDURE FOR EVALUATION OF THE INTEGRITY OF THE FIXED PARTS

3-way multi-family drawout cable interlock kit - type 32 - RF

INSTRUCTIONS. Power Panel. Installation Instructions

Installation Instructions for Type SM Safety Handle Mechanism for L-Frame Series C Circuit Breakers and Molded Case Switches

The Power Systems Industry Experts. Installation Instructions. PT100 Stationary Generator Monitoring System

MASTERCLAD. Metalclad Indoor Switchgear 27 kv with Type VR Vacuum Circuit Breakers Class Instruction Bulletin. Retain for future use.

Galaxy VX Battery Breaker Trip Board (GVXBBTB) and Battery Breaker Capacitor Board (GVXBBCB)

SX-16 Nightsun Searchlight Safety and Service Bulletin # SL

ABB ADVAC TM. INSTALLATION/MAINTENANCE INSTRUCTIONS Medium Voltage Vacuum Power Circuit Breakers and Auxiliary Devices

EnergyCell FLA Series. Owner s Manual

INSTALLATION GUIDE AND USER MANUAL

S&C Vista Underground Distribution Switchgear

Transcription:

Instruction Bulletin Bulletin No. 44027-017-01 Middletown, OH USA Class 6035 INTRODUCTION This bulletin contains instructions for adding a shunt trip assembly to a manual DS/DSL circuit breaker and modifying the POWER ZONE III switchgear to accept a shunt trip circuit. Perform all steps as described to ensure safe installation and proper operation. If problems are experienced during installation, contact Square D Field Services Division at (800) 634-2003. PRECAUTIONS! DANGER HAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION This equipment must be installed and serviced only by qualified electrical personnel (OSHA 1910.331-335). Turn off all power supplying this equipment before working on or inside equipment. Always use a properly rated voltage sensing device to confirm all power is off. Circuit breaker contacts must be open and all springs discharged before performing maintenance work. Replace all devices, doors, and covers before turning on power to this equipment. Failure to observe these precautions will result in death, serious injury, or electric shock. HAZARD OF FALLING EQUIPMENT WARNING Never walk, stand, or work under a suspended load. Never walk, stand, or work under a circuit breaker resting on extended cradle arms. Failure to observe these precautions can result in death, serious injury, or equipment damage. 1997 Square D All Rights Reserved 1

Bulletin No. 44027-017-01 INSTALLATION Removing the Circuit Breaker Mounting the Shunt Trip To remove the circuit breaker: 1. Open all load devices on the circuit and open the circuit breaker. NOTE: When opening or closing the circuit breaker, refer to job requirements for operating key and electrical interlocks. 2. Disconnect the control power (internal and external). 3. Once the circuit breaker has been opened, rack it out to the disconnect position. 4. Pull out the cradle arms and withdraw the circuit breaker from the cell. 5. Remove the circuit breaker from the cradle arms by using the proper circuit breaker lifting devices. Refer to instruction bulletin 6035-1 for circuit breaker removal and installation procedures. 6. Place the circuit breaker on a secure, flat, level surface that can support a minimum of 450 lbs (205 kg). To mount the shunt trip: 1. Remove the screws on the circuit breaker face plate (Figure 1) and take the face plate off. Screws Screws Figure 1: Location of faceplate screws 2 1997 Square D All Rights Reserved

Bulletin No. 44027-017-01 2. Locate the mounting holes in the left side circuit breaker frame. See Figure 2. Mounting Holes Figure 2: Location of mounting holes 3. Mount the shunt trip assembly (Figure 3) to the circuit breaker frame using the supplied screws. Shunt Trip Assembly Figure 3: Position of shunt trip 1997 Square D All Rights Reserved 3

Bulletin No. 44027-017-01 Mounting the Auxiliary Switch The auxiliary switch mounts on top of the circuit breaker. Facing the unit front and looking down on the unit top, the auxiliary switch mounts on the lower right as shown in Figure 4. If the circuit breaker is already equipped with an auxiliary switch, proceed to the next section, Mounting the Moving Contact Frame. Auxiliary Switch Figure 4: Position of the auxiliary switch To mount the auxiliary switch: 1. Remove the auxiliary switch cover. See Figure 5. 2. Insert the linkage arm through the square hole on top of the circuit breaker. 3. Attach the auxiliary switch to the top of the circuit breaker using the supplied screws. 4. Attach the linkage arm to the pin located on the lever of the pole shaft. Secure the linkage to the pin using the x-ring provided. See Figure 6. Cover Linkage Arm Figure 5: Removing the auxiliary switch cover 4 1997 Square D All Rights Reserved

Bulletin No. 44027-017-01 X-Ring Location Figure 6: Auxiliary switch linkage arm Mounting the Moving Contact Frame Refer to Figure 7 to determine if the circuit breaker is already equipped with a moving secondary contact frame. If so equipped, proceed to the next section, Mounting the Moving Contacts. Moving Contact Frame Figure 7: contact frame If the circuit breaker is not equipped with a moving secondary contact frame, mount one as follows: 1997 Square D All Rights Reserved 5

Bulletin No. 44027-017-01 1. Remove the wiring tray on the left side of the circuit breaker frame. See Figure 8. Wiring Tray Figure 8: Wiring tray Mounting the Moving Contacts 2. Mount the moving secondary contact frame with the supplied hardware as shown in Figure 7. 3. Replace the wiring tray on the left side of the circuit breaker frame. Ensure that wiring is not pinched between the wiring tray and the side of the circuit breaker. Refer to Figure 9 to determine if the moving secondary contact block is present. If so, proceed to the next section, Wiring the Shunt Trip and Auxiliary Switch. If the moving secondary contact block is not present, use the hardware provided to mount it to the circuit breaker in the upper left hand position (when viewed from the front of the circuit breaker). Refer to Figures 9 and 12. NOTE: The moving secondary contact block may break if hardware is overtightened. Moving Contact Block Figure 9: Moving secondary contact block 6 1997 Square D All Rights Reserved

Bulletin No. 44027-017-01 Wiring the Shunt Trip and Auxiliary Switch 1. Using the wire provided, wire the shunt trip, auxiliary switch, and moving secondary fingers according to Figure 10. 5 6 Disconnect Fingers 5 Auxiliary Switch no. 1 1 2 3 4 5 6 7 8 Upper Left 2 4 6 8 10 12 14 17 18 20 a 1 3 b 5 a b 7 9 a 11 b 13 a 15 b 16 a 19 b 68 6 SH TR 68 Figure 10: Wiring diagram for circuit breaker (front view of circuit breaker) NOTE: If contacts 1 and 2 are being used, connect wires to any a contact on the auxiliary switch. The a contacts are open when the circuit breaker is open. 2. Secure all wires with the cable ties included in the kit. Route wires from the moving secondary contacts along the left side of the circuit breaker (when viewed from the front). Place these wires into the wire tray on the side of the circuit breaker to secure them. Wires routed to the auxiliary switch should be routed behind the trip unit mounting bracket. 3. Mount the moving secondary contact cover using the supplied hardware as shown in Figures 11 and 12. NOTE: Glass polyester contact cover may break if hardware is overtightened. Moving Contact Cover Figure 11: Moving secondary contact cover Moving Contact Cover Moving Contact Block Lock Washer Moving Contact Frame Figure 12: Moving secondary contact block and cover 1997 Square D All Rights Reserved 7

Bulletin No. 44027-017-01 4. Mount the auxiliary switch cover using the supplied hardware as shown in Figure 13. 5. Replace the circuit breaker face plate with the original screws. Auxiliary Switch Cover Figure 13: Auxiliary switch with cover Mounting the Stationary Fingers Refer to Figure 16 to determine if the stationary secondary mounting plate and fingers are in place. If they are present, go to step 4. If the stationary secondary fingers are not present, proceed as follows to mount them: 1. Determine which is the front side of the stationary secondary mounting plate by referring to Figure 14. Mounting Plate Mounting Holes Mounting Plate Mounting Holes Contact Mounting Holes Figure 14: Stationary secondary mounting plate (front side) 2. Mount the stationary secondary contacts to the mounting plate holes using the hardware provided. Refer to Figure 15. NOTE: If switchgear was manufactured before August 1992, the stationary secondary mounting plate is not needed. Mount stationary secondary contacts directly to the rear cell wall of the switchgear. 8 1997 Square D All Rights Reserved

Bulletin No. 44027-017-01 Figure 15: Stationary secondary mounting plate with contacts mounted 3. Mount the mounting plate in the circuit breaker cell using the hardware provided. Use the mounting holes indicated in Figure 14. Figure 16 depicts a stationary secondary contact properly mounted in a circuit breaker cell. NOTE: Extra screws are required for 34 inch (865 mm) sections. Holes for these screws are indicated by A in Figure 17. Figure 16: Stationary secondary contact mounted in the circuit breaker cell 4. Refer to revised Factory Order drawings included with the kit to wire the stationary secondary fingers and trip circuit. NOTE: Use a proper wire crimping tool when terminating wires. A A Figure 17: Screw holes for 34 inch (865 mm) sections 1997 Square D All Rights Reserved 9

Bulletin No. 44027-017-01 VERIFICATION DANGER HAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION Verify that no tools or installation equipment is left inside the switchgear before turning on power to this equipment. Conduct electrical testing to ensure that no short circuits were created during installation. Replace all devices, doors, and covers before turning on power to this equipment. Failure to observe these precautions will result in death, serious injury, or electric shock. To verify that the shunt trip kit is installed correctly: 1. Install the circuit breaker into the test position only. 2. Manually close the circuit breaker. 3. Restore control power and energize the switchgear. 4. Use the external trip circuit for the shunt trip to verify that it opens the circuit breaker. 5. The circuit breaker can now be installed in the connect position and put back into service. TROUBLESHOOTING! DANGER HAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION This equipment must be installed and serviced only by qualified electrical personnel (OSHA 1910.331-335). Turn off all power supplying this equipment before working on or inside equipment. Always use a properly rated voltage sensing device to confirm all power is off. Circuit breaker contacts must be open and all springs discharged before performing maintenance work. Replace all devices, doors, and covers before turning on power to this equipment. Failure to observe these precautions will result in death, serious injury, or electric shock. WARNING HAZARD OF FALLING EQUIPMENT Never walk, stand, or work under a suspended load. Never walk, stand, or work under a circuit breaker resting on extended cradle arms. Failure to observe these precautions can result in death, serious injury, or equipment damage. If the circuit breaker does not function properly, perform these checks: 1. Verify that the shunt trip assembly and auxiliary switch are properly mounted. 2. Verify that secondary contacts are mounted in the correct positions. 3. Check all wiring. Verify that connections are complete and correct. 4. Check the external trip circuit to verify valid operation. After performing these steps, repeat verification steps 1 5 as described above. 10 1997 Square D All Rights Reserved

Bulletin No. 44027-017-01 1997 Square D All Rights Reserved 11

Bulletin No. 44027-017-01 1997 Square D All Rights Reserved. This document may not be copied in whole or in part, or transferred to any other media without the written permission of Square D. POWER ZONE, Square D, and are Registered Trademarks of Square D Company. Electrical equipment should be serviced only by qualified electrical maintenance personnel. No responsibility is assumed by Square D for any consequences arising out of the use of this material. Square D Company 1500 S. University Blvd. Middletown, OH 45044 USA Bulletin No. 44027-017-01 Printed in USA