GE Arc Vault TM Protection System. By Mark Clapper GE Specification Engineer. Introduction. What Variables Contribute To An Arcing fault?

Similar documents
Design Considerations to Enhance Safety and Reliability for Service Entrance Switchboards

Arc-Flash Mitigation Technologies. Dennis Balickie

Arc flash solutions catalogue Australia. Safety solutions - Protecting employees and the enterprise

Arc flash hazard mitigation

6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton

Reducing. with Current. arc flash note 2. points of interest. Why Use Current Limiting Fuses. By mike lang, Principal field engineer

Not all Low Voltage Switchgear is created equal

Electrical Safety and Overcurrent Protection

Not all Low Voltage Switchgear is created equal

Selective Coordination

Mark Lyvers LLC / Cooper Bussmann Arc Flash Script Script to accompany PowerPoint on New 2002 NEC Arc Flash Hazard Marking Requirement

Future Proof Your Arc Flash Assessment

The safest, most reliable Switchgear in the market today

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

Arc Flash Detection and Mitigation

Energized Electrical Work

MITIGATE ARC EFFECTS WITHIN AN E-HOUSE

Chapter 6 Generator-Voltage System

Design considerations for generator set mounted paralleling breakers

Miniature circuit breaker Application guide

Fuses still the best form of overload protection

ZX2 Gas-insulated medium voltage switchgear

ETAP Implementation of Mersen s Medium Voltage Controllable Fuse to Mitigate Arc Flash Incident Energy

MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI

Type 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear

Zone Selective Interlock Module. For GE Circuit Breakers

Instruction and Installation Guide

Electrical Safety CSA Z462 & NB Regulations

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

Brochure. Arc Guard System TVOC-2 A protection device for reliable safety

Two Recent Case Studies in the Mining Industry

CONSIDERATIONS FOR THE APPLICATION OF A MV HIGH SPEED GROUNDING SWITCH FOR ARC FLASH MITIGATION OF LV EQUIPMENT

Guidelines for Modernizing Existing Electrical Switchgear in LV and MV Networks

ABB AG - EPDS. Ultra-Fast Earthing Switch UFES active internal arc protection

Understanding Arc Flash Hazards. White Paper

ARC FLASH MANAGEMENT REVIEW. October 2017

Transformer Protection

Advanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear

Power systems Protection course

School of Electrical and Information Engineering. ELEC High Voltage. University of Sydney. Dr Keith Mitchell. Engineering

Learning Module 6: Medium Voltage Power Circuit Breakers. 101 Basic Series

Overcurrent protection

ECET Distribution System Protection. Overcurrent Protection

Circuit breaker interlocking and operation requirements SIEMENS

MAGNETIC MOTOR STARTERS

HIGH VOLTAGE vs. LOW VOLTAGE: POTENTIAL IN MILITARY SYSTEMS

Ensuring the Safety Of Medical Electronics

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

EE 741 Over-voltage and Overcurrent. Spring 2014

Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections

Safe, fast HV circuit breaker testing with DualGround technology

TERMS AND DEFINITIONS

Close-Open (Short-Circuit) Time Results Interpretation

Breaking new ground. A circuit breaker with the capacity to switch 15 large power plants

Gas-insulated medium-voltage switchgear. For the metal industry. Answers for energy.

4-Day Power System Analysis, Coordination, System Studies

Ultra Fast Earthing Switch UFES retrofit Overview

Selective Coordination Enforcement:

SLOVAK UNIVERSITY OF TECHNOLOGY Faculty of Material Science and Technology in Trnava ELECTRICAL ENGINEERING AND ELECTRONICS.

MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES

Gas-insulated medium-voltage switchgear. For the mining industry. Answers for energy.

A. Submit manufacturer's literature and technical data before starting work.

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

The Evolution of Arc Fault Circuit Interruption

GE CONSUMER & INDUSTRIAL

www. ElectricalPartManuals. com Section 13 Switchgear Low Voltage

Illinois State University. Electrical Safety Procedure

Design Standards NEMA

Boric Acid Fuse Links

Zone Selective Interlocking

Application of Sepam Relays for Arc Flash Hazard Reduction at Low Voltage Switchgear

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 2

Guideline for Parallel Grid Exit Point Connection 28/10/2010

Cost Benefit Analysis of Faster Transmission System Protection Systems

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Switchgear Arrangement, Torque Requirements, Insulation Systems & Maintenance Intervals. Mike Schmaderer

Medium Voltage Metal-Enclosed Switches

FUSE: SAFE & RELIABLE

RBA Catalog Numbers and Information

Medium Voltage Metal-Enclosed Switches

White Paper. Ground Fault Application Guide. WL Low Voltage Power Circuit Breakers

A Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Steve Summers Region Sales Manager

Grounding Of Standby & Emergency Power Systems

MOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E.

Electrical Workplace Safety

NFPA 70E Standard for Electrical Safety Requirements for Employee Workplaces. Table Hazard Risk Category Classification

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

WEAPONX CIRCUIT COMPRESSION

Safety Working with LV Drives

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

ACHIEVING MAXIMUM BENEFITS WITH A FUSE PROTECTED MOTOR CONTROL CENTER

Learning Module 5: Fundamentals of Circuit Breakers. 101 Basic Series

Hazards SAFETY CORNER. of Establishing an. Work Condition

Specification for 70mm pole pitch Air circuit breaker up to 1600 A

Exhaust System Bypass Valves and Exhaust Valve Bypass Controller

Transcription:

By Mark Clapper GE Specification Engineer Introduction To address the increasing concerns and standards around arcing faults, GE challenged our Global Research Center to develop a new, active method of detecting & removing an arcing fault. The goal was to develop a technology that would, in simple terms, reduce the potential for injury and equipment damage. The result is an innovative product called the Arc Vault TM Protection System. This article will outline some basic arc flash mitigation techniques, and culminate with a description of the new GE technology. It should be noted from the onset that this technology is currently in the prototype phase and that the discussion covers applications of 480V and below. variables are and the corresponding incident energy calculations that help categorize them. A complete discussion on arc flash calculations can be found in IEEE 1584 Guide for Performing Arc Flash Hazard Calculations. [1] What Variables Contribute To An Arcing fault? There are many items that can initiate an arcing fault. Rather than focusing on what the ignition sources can be, the system factors associated with how we quantify the arcing fault will be considered. With the benefit of this information, mitigation techniques can be outlined and categorized. Figure 1 illustrates some of the basic parameters that factor into an incident energy calculation that in turn leads to the Hazard Risk Category labeling. Let s start with the basic question of why is the industry concerned with arcing faults? If the reader is unfamiliar with arcing faults, please refer to the newsletter article titled Arc Flash Basics before continuing. Arcing faults Why the Industry Concern? Simply put, the affects may result in serious injury, death, equipment damage, and downtime. Unlike the bolted fault, an arcing fault uses ionized air as the conductor. The cause of the fault normally burns away during the initial flash and the arc is sustained by the establishment of a highly conductive, intensely hot plasma arc. The intense heat vaporizes conductors/ barriers and superheats the surrounding air resulting in an explosive volume-metric increase within the space. The consequence is an intense pressure wave, deafening sound, blinding light, toxic gases, molten metal and shrapnel. This is often referred to as the arc blast. Unless action is taken to either quickly remove the fault or redirect the arc blast, the brunt of these items will impact people, equipment or both. The magnitude of the arcing fault is only 43-57% of a bolted fault, so traditional overcurrent protection may not detect and clear the fault before the full impact of the arc develops and causes damage or injury. To gain a better understanding of how to deal with an arcing fault, let s consider what the contributing Figure 1 Incident Energy Calculation Clearly, there are many variables that factor into the incident energy calculation. Some are specific to equipment types while others are tied to system parameters or maintenance practices. Each variable plays a particular role in how we categorize the arc flash hazard and each is briefly touched upon below: Voltage The ability to sustain the arc. Arcing faults are generally limited to systems where the bus voltage is greater than 120V. Available bolted fault current - The punch behind the arc fault magnitude. Recall that the magnitude of an arcing fault is approximately 43-57% of the bolted fault value. This implies that systems with significant bolted fault currents will have elevated arcing current levels. The reverse is also true; lower bolted fault levels will lead to lower arcing fault energies. Items such as system impedance, transformer sizing, utility, motor, and generator contributions establish the available fault current. Arc clearing time - This includes detection & protective device operating time. It is tied to the operating characteristics of a specific protective Page 1 / 5

device for a given level of arcing current. Reducing clearing time is critical to reducing the impacts of arcing fault. Conductor gap distance. Defines the distance between conductors that an arc must cross. Varies by equipment type and manufacturer, but is fixed for a specific piece of equipment. Working distance. The distance from a potential arc source to a worker s face and chest. Typically assumed to be 18. Items such as remote monitoring and racking can be implemented to remove the operator from the flash zone to for routine maintenance tasks. System configuration. Solidly grounded, resistance grounded, etc. This category also takes into consideration whether the arc environment is enclosed or open. Given a basic understanding of what variables contribute to an incident energy calculation, the next logical question is to ask what the engineer can do to reduce this energy or exposure to it? Since energy is a function of current, voltage and time, there are several strategies that can be explored: Reducing the available fault current Reducing the arcing time Transferring the energy into a less damaging form or place quicker than it could otherwise be interrupted. This is the basis of the GE Arc Vault TM Protection System The paragraphs that follow will highlight several of these strategies. Methods of Limiting Incident Energy and The Exposure to Arcing Faults Over the years, different methods to limit arc flash exposure and incident energy have been introduced and can be divided into two general categories; active and passive. Passive mitigation is defined to be an equipment option or type that either contains and re-directs the arc blast or helps to eliminate the potential of a flash event (i.e. insulated main bus). This type of mitigation does not require any actions or settings by an operator to implement. On the opposite end of the spectrum is active mitigation. Active mitigation takes a pro-active approach to reducing both incident energy and the exposure to arcing faults through the active use of technology, design and maintenance practices. The simplest example of active mitigation is to not approach or work on live electrical equipment. Figure 2 contains a list of passive and active items. Passive Reduce exposure with equipment options Insulated/ isolated bus IR scanning windows Closed door drawout of breakers Side section barriers Hinged vs. bolted doors Heaters Reduce exposure with equipment types Arc resistant structures Others? Active Technology to reduce arcing time & incident energy Arc Vault TM ZSI of instantaneous Crow bar Bus differential (87B) Maint settings (RELT) Current limiting devices Design practices to reduce arcing time & incident energy Consider fault currents Transformer sizes Grounding Single or double ended Reduce exposure via maintenance practices Follow NFPA 70E No live maintenance Remote switching Remote racking Remote monitoring Remove contaminants Training & labeling Use of proper PPE Figure 2 Arc Flash Mitigation Techniques One clear distinction between the passive and active methods is that the passive method does nothing in the way of detecting or removing an arcing fault. It is focused solely on containing the arc blast or eliminating a potential starting point for an arc flash via equipment options. One should not employ passive techniques without thinking through items such as thermal scanning. Equipment options like insulated main bus and isolated phase bus are good preventative measures, however they present an issue to performing thermal scans of items other than load connections. The active methods seek to attack on both fronts; incident energy reduction and reduced exposure. The newest technology on the active side is the GE Arc Vault TM Protection System. To highlight the application of thearc Vault TM, the following Page 2 / 5

paragraphs will contrast the Arc Vault TM vs. the passive, arc resistant structure. The remaining items are listed for reference and will not be covered in detail LV Metal Enclosed Switchgear Typical LV Metal Enclosed Switchgear is designed and tested to withstand the mechanical forces associated with bolted faults (non arcing). It is not constructed to contain and re-direct the arc blast away from the operator. The standard construction must be able to withstand (carry) the bolted fault current from the line side of the main breaker through the load terminations on the feeders and is short circuit tested to ensure compliance with the applicable ANSI standards. During a short circuit interruption, there may be some out gassing of arc by-products from the breaker, but not to the violent extent of the arcing fault. An arc resistant line of LV switchgear is also designed to withstand and interrupt a bolted fault, however it provides a level of protection to arcing faults that is not incorporated in the standard design. Arc resistant structures have been around for 30 plus years and can trace their roots back to IEC standards. In North America, this type of structure is tested & categorized to ANSI C37.20.7, refer to figure 3. The word arc resistant implies that no arc fault emissions/blast will occur in the areas described by each category. For example, with a properly installed Type 1 design, an operator could approach the front of a switchgear lineup and not be exposed to the arc blast if an arcing fault were to occur. If the operator were standing to the side of this design, the same protection would not be provided. ANSI Type Type 1 Comments arc resistant construction applies to The front only. Figure 3 Arc Resistant Structure Categories To function properly, arc resistant structures have several distinguishing characteristics not found in traditional gear. Reinforced construction is used to withstand & contain the pressure wave. Front & rear doors, section barriers, etc may be reinforced and gasketed depending on the ANSI type. Exhaust chambers are employed within the structure to safely re-direct the arcing fault by products away from the operator and toward the vent flaps. Vent flaps that open due to increased pressure vent the arc blast. Typically out the top. Figures 4 illustrates the re-direction and venting of the arcing fault. Figure 4 Illustration of Arc Resistant Venting Considerations Arc Resistant Structures The arc resistant structure does an excellent job of protecting the operator from an arc flash event, however it is not a panacea. As noted earlier, this passive technique seeks only to contain the arc blast, but nothing to reduce incident energy or remove the arcing fault, which can result in substantial equipment damage and downtime. Like all products, the application of arc resistant structures requires consideration and awareness of items that are specific to the construction. Several items are listed below for consideration. Type 1C Type 2 Type 2C The front, as well as between compartments of the same or adjacent cells. The front, back and sides of the enclosure. The front, back, sides as well as between compartments of the same or adjacent cells. E quipment Damage / Downtime What type of downtime will the owner experience for an arcing fault? It is reasonable to expect some structural damage that will require repair as a result of the arc blast. Bus, doors, barriers are likely candidates for repair. Are there other mitigations methods that can provide operator protection and help reduce equipment damage at the same time? Page 3 / 5

Maintenance/ Approaching Live Equipment The protection afforded by the arc resistant structure can be negated if a door is not properly secured or if the maintenance task requires the operator to open a door or compartment. What are the impacts to operator safety, maintenance practices, etc? parallel-connected containment dome, light sensors and a logic controller. Utility 50/51 51G Trip 52 Installation Considerations Where does the effluent go when it is vented from the structure? Does the room size need to be increased? Does a restricted area need to be developed and labeled? Is placement of the structure limited to certain areas? SWGR MAIN Trip RELAY Cost & Size Impacts What are the cost & size impacts associated with the structure itself? Does the room size need to be increased? MCC1 FDR1 FDR2 MCC2 Activate Containment Dome Existing Equipment The arc resistant structure cannot be retrofit onto existing equipment. The comments above are not meant to disparage the arc resistant design. Rather they are meant to highlight that with all products there are application considerations that must be taken into account. Items such as live maintenance, equipment damage, room size and venting are real concerns that need to be thought through and contrasted against other mitigation techniques. How is the GE Arc Vault TM Different? The GE Arc Vault TM is an active mitigation technique and aspires to the same basic goal as the arc resistant structure; to protect the operator. However it does so in a much different fashion than arc resistant structures. Instead of containing and venting the arc flash effluent, it seeks to limit incident energy via the identification and removal of an arcing fault before it escalates into the signature arc blast and elevated hazard risk categories. The result is a solution that addresses three key areas: Reduction of the arc flash hazard. Improved equipment uptime/ reduced damage. Ability to retrofit existing switchgear The architecture for the absorber is depicted in figure 5 and consists of a current sensor, a Figure 5 - Architecture The current sensor looks for the signature of an arcing fault while the light sensor looks for a simultaneous optical event. The combination of the two is fed into a logic controller which makes the decision on whether to engage the absorber or not. At this point you may be thinking that GE has created a crow bar. Rest assured, we have not, please read on. The Arc Absorber has no moving parts and makes use of a plasma gun and containment chamber. When the logic controller activates the absorber, two simultaneous actions take place. A trip signal is sent to the main breaker and the absorber is activated. When activated, the absorber triggers the plasma gun to break down the dielectric in the air gap within the absorption chamber. The resulting arc creates a lower impedance, phase-to-phase path than the in equipment arcing fault presents to the system. This low impedance path is not a bolted fault and in turn re-directs/ absorbs fault current originally flowing towards the arcing fault within the controlled environment of the containment chamber. The arc within the containment chamber is then safely cooled and vented. The open air or in equipment arc is extinguished as the bus voltage decreases due to the low impedance path within the absorber. The time required to quench the open-air arc is 8ms. The event is brought to conclusion when Page 4 / 5

the main protective device opens and eliminates current flow within the absorption chamber. It is important to note that since this system works at arcing fault current levels, as opposed to bolted fault levels, there is a significant energy reduction. The result is 63% less energy, and considerably less stress on the system, when compared to crowbar type systems. This energy reduction applies to not just the local switchgear, but also to other system components like transformers. The prototype of the Arc Vault TM containment dome is about the size of an 800AF breaker and is rated for applications of 65 ka at 480V. The GE Arc Vault TM protection system will contain an arc fault in less than 8ms with the circuit breaker compartment doors open during operation and maintenance. The incident energy in accordance with IEEE 1584 at 24 from the arc event will be less than 1.2cal/cm 2, which is equivalent to HRC0, for a 480V HRG system with available fault currents up to 100kA. In addition to incident energy/ HRC reduction, eliminating the arcing fault, reducing equipment damage, and eliminating arcing fault effluent. The Arc Vault TM offers the following benefits not found in traditional arc resistant structures: No Effluent Ventilation No need for increased ceiling heights or the creation of restricted areas to avoid potential exposure to redirected effluent. Conclusion There are many techniques that can be employed to help mitigate the damaging effects of arcing faults. This article has introduced the concept of the Arc Vault TM as a feasible alternative to arc resistant structures. The Arc Vault TM can at minimum offer the same or similar Hazard Risk Category (HRC) protection as the arc resistant structure but far exceeds the structure in the areas of equipment protection, uptime, re-use and others. GE presented this concept on the arc absorber to the IEEE Petroleum and Chemical Conference Technical Conference in September of 2009. References [1] IEEE 1584 guide for performing arc flash hazard calculations [2] IEEE C37.20.7: Guide for Testing Medium Voltage Metal Enclosed Switchgear for Internal Arcing Faults. New and retrofit applications The Arc Vault TM can be implemented in new or existing LV switchgear platforms while the arc resistant structure is tied to new installations only. Reuse The Arc Vault TM will be reusable, with minor maintenance or parts replacement, depending on the available fault currents it is applied on. Arc resistant structures will in all likelihood sustain some form of damage and require repair to place it back into service. Maintenance Activities The Arc Vault TM does not depend on doors being closed to provide arc flash protection. Hence the established Hazard Risk Category does not change whether the doors are open or closed. Page 5 / 5