Installation Instructions: ACCENT HIGH OUTPUT SYSTEM

Similar documents
Installation Instructions: ACCENT SYSTEM

Installation Instructions: HYPERION R-Lite SYSTEM

SloanLED THINLED. Constant Current. Installation Guide

WARNING. Tools: 1. Wire Strippers 2. Screw Driver or Rivet Gun 3. Tape Measure 4. Drill. Components: AWG (0.82mm) Wire-UL Approved

PDX and PX Retrofit Series

Installation Instructions: Eco Linear High Bay

Tetra minimax. LED Lighting System. BEFORE YOU BEGIN Read these instructions completely and carefully. Installation Guide

The Gallery System DIRECTIONS. Components of the System

Installation Instructions: External-Driver SEP T8 LED Tube Lamp

Installation Instructions: Memory-Dimmable SEP T8 Tube Lamps

G2.1 RETROFIT LED LIGHTING

LumaFilm Light Emitter Installation Instructions

GENUINE PARTS INSTALLATION INSTRUCTIONS

SunLink PV System Disconnect with Arc Fault Detection Installation and Operations Manual


Assembly Instructions Retrofitting

VITALink Taped Splice Pigtail Crimp

WARNING/AVERTISSEMENT. Coupez l alimentation électrique à la boîte de fusibles ou au disjoncteur avant servicing or installing product.

Anthony LED Lighting System Retrofit Installation Instructions For Models 101X and 101A

Technical Installation Manual

SCION xd INTERIOR LIGHTING UPGRADE Preparation

Installation Instructions: Read these instructions in its entirety before performing any installation work.

Installation Instructions: Read these instructions in its entirety before performing any installation work.

LM79 LM80 L70:5+ YEARS

E E VDC COOLEDGE TILE INTERIOR INSTALLATION INSTRUCTIONS. Caution: Observe precautions for handling electrostatic sensitive devices.

HPNLS-HO. Installation Manual

Optimax Pro Retrofit Instructions

SECTION 300 OVERHEAD SERVICE

Installation Instructions Studio Makeup Station

ThermoLite 40W Solar Panel Installation Instructions

GENUINE PARTS INSTALLATION INSTRUCTIONS

2 4 L R I G I D L E D L E D S I M U L AT E D N E O N I N S TA L L AT I O N G U I D E MANUAL FOR 48 SYSTEM ADVANCE POWER SUPPLY ONLY!

Universal Retrofit System Installation Instructions Revised:

GENUINE PARTS INSTALLATION INSTRUCTIONS

ULTRA PERFORMANCE LED TUBE INSTALLATION INSTRUCTIONS

LED Recessed Troffer Retrofit Kit

Strip Fixture URS Light Bar Retrofit Installation Instructions Revised:

INSTALLATION INSTRUCTIONS TRAILER HITCH MAIN HARNESS KIT

Installation Manual. CS9300 Professional Series Landscape Lighting System

IP65 COOLEDGE TILE EXTERIOR R2 INSTALLATION MANUAL. Exterior TILE Jumper Cable. Exterior Cutout TILE. Cable Clamp. T-Cable.

Electric Vehicle Charging Station

GENUINE PARTS INSTALLATION INSTRUCTIONS

Generator Fire Safety: Generator assemblies should be located outside the building.

STREET WRAP INSTALLATION GUIDE

MONORAIL KITS INSTALLATION INSTRUCTIONS PENDANTS

poollux Power plx-pw60 & plx-pw100

LED LINEAR INSTALLATION GUIDE RED 20L VER /13/

Model LA 4400 Time Delay OFF Controller

ALL PURPOSE CNC/HEAVY DUTY

10 Commercial, Industrial, Agricultural Services

331-SV. User Manual THREE PHASE DUPLEX LIFT STATION CONTROL PANEL WITH STATIONVIEW CONTROLLER. Ashland, OH

* * APPLICABLE MODELS: 2014 > Mazda 3

BAL3000 BAL3000. Fluorescent Emergency Ballast Lumens. Specification Sheet. Emergency Ballast 1/19/2012. Project: Catalog#: Approved by:

3 year warranty. (1) Treo Micro fiberglass, gunite fitting, 3/4 PVC. FLED-TM-W-PK10 (10) Treo Micros (WHITE) 80 NEW! Treo Micro fitting adapter

Model LA 4100 Time Delay OFF Controller

GENUINE PARTS INSTALLATION INSTRUCTIONS

Lumination TM LED Luminaire LUR Series

INSTRUCTIONS. Power Panel. Installation Instructions

LED LINEAR AMBER 20L INSTALLATION GUIDE /01/16 VER. 1.0 CERTIFIED SAFETY US CA

SAVE THESE INSTRUCTIONS!!

ThermoLite 110W-330W Solar Panel Installation Instructions

LightRider. Instructions for Power Link Helmet Light. Helmet Vertical Midline

COOLEDGE TILE EXTERIOR INSTALLATION INSTRUCTIONS FIT-2. Caution: Observe precautions for handling electrostatic sensitive devices.

Model LA 4300 Time Delay OFF Controller

Installation Manual CS9300-LED. Professional Series Landscape Lighting System

OPTIMAX RADIANT FIELD RETROFIT INSTRUCTIONS

GENUINE PARTS INSTALLATION INSTRUCTIONS

CONTENTS. This Product is Certified by CANADIAN STANDARDS ASSOCIATION and Bears the Mark:

* * APPLICABLE MODELS: 2014 > Mazda 6

ChargePoint Gateway Installation Instructions

JBS-100-A, A6 SINGLE ENTRY POWER CONNECTION WITH JUNCTION BOX INSTALLATION INSTRUCTIONS

LED Flat Panel Installation Instructions For 1 x4, 2 x2, and 2 x4 LED Flat Panels (FP Series)

Do not work on the system or connect or disconnect cables during periods of lightning activity. Statement 1001

UNPACK AND IDENTIFY THE FOLLOWING PARTS.

* * APPLICABLE MODELS: 2017 > CX-5

INSTALLATION INSTRUCTIONS. Solid-State Series !! NOTE!! Covers the following models: Refer to INSERT for additional information

SLIMFLEX LED Tape Lighting

Replacing the Gear Drive Motor Assembly and GFCI Module for Operation with the Chain Drive Motor Assembly

GENUINE PARTS INSTALLATION INSTRUCTIONS

INSTALLATION GUIDE AND USER MANUAL

Parts and Accessories Installation Instructions

METERING REQUIREMENTS

Compressor Duty Motor - 1 HP. Model 40132

ONE TOUCH CONTROL BOX

LEXUS RC 350/RC-F ILLUMINATED DOOR SILLS Preparation

GENUINE PARTS INSTALLATION INSTRUCTIONS

Installation Instructions for SINGLE COLOR 24V LINEAR LED NEON

* * APPLICABLE MODELS: 2016 > CX-3

Installation and Service Manual

UL AND CODE COMPLIANCE

DEFENDER SERIES. 5 Gallon, Double Walled, Field Replaceable Spill Container Model Series INSTALLATION, OPERATION, & MAINTENANCE

Temporarily Approved Solar Photovoltaic System Electrical Schematics

Albeo TM LED Luminaire Heavy Industrial High Bay Lighting (ABR1-Series)

RibbonFlex Pro LED Accent Lighting White LED Tape Light. Welcome to RibbonFlex Pro LED Tape Lighting. Notes:

Enclosure for AMP1 Series Energy Meters with Swing Panel Kit

R. STAHL Schaltgeräte GmbH Geschäftsbereich Leuchten Nordstraße Weimar, Germany

Model Description Vac. Max rating Pedestal Only: 36 Utility Pedestal W/O Disconnect General Duty Series:

Customer Requirements Downtown Secondary Network Service

Chapter 8 Interior Wiring and Lighting

M-150S Series 12-Volt Fuel Pump M-150S-B100-MU Manual Nozzle & M-150S-B100-AU Automatic Nozzle Owner s Manual

Transcription:

Installation Instructions: ACCENT HIGH OUTPUT SYSTEM READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS WILL VOID YOUR WARRANTY! INSTALLATION TIPS Read this entire installation manual. Power Connectors: The 12 MODULE rule: keep the runs to 12 MODULES or under and the power connection can be made ANYWHERE on the strip. The 24 MODULE rule: for runs that are 13 to 24 MODULES the power connection must be made in the MIDDLE of the strip. Properly clean and prep the surface area that the strip will be applied to. For secondary low-voltage wiring use 10AWG or 12AWG Class 2 rated wire only. Using higher than 12AWG wire will result in increased voltage drop. Do Not Use Wire Nuts for connecting power connectors to secondary low-voltage wiring. Use wire nuts to insulate only the ends of the low-voltage wires. RETROFITTING OF UL LISTED SIGNS E230263 / 7BA6 E230262 Copyright 2016 Revolution Lighting. All rights reserved. IN066_01_20160829 Page 1 of 15

The main power to any existing system must be disconnected prior to the installation. The Accent system is intended to be used for new lighting systems or as a retrofit for existing ne-on, fluorescent or any combination thereof. When installing retrofit systems please refer to the existing products manufacturer for proper removal guidelines. All existing system components must be removed before installation of the Accent system. All removed material must be properly disposed of to meet your federal, state and local regulations. Install in accordance with the NEC and Local Electrical Codes. The Retrofit Kit System is to be installed in Listed Signs only. Hardware Screws IDC connectors Wire nuts Class 2 low-voltage wire Tools Scissors Drill Screwdriver Pliers Optional Support Clamps Silicone New Install 1. Surface must be free of dust, dirt and grease. Use non-oil based solvent (409, alcohol) to clean the surface. Area must be dry before application. The Accent strip bonds to all non-porous surfaces. Note: For porous surfaces use Accent support clamps which can be purchased from Lumificient. Note: Application temperature range: 32 F to 100 F (0 C to 38 C). Note: It is recommended to test one or more areas before installation for acceptable color and illumination. 2. Determine the linear footage required for each area to be illuminated. Do not precut LED strips. Group runs into equal load groups not to exceed the maximum footage allowed for the power supply you are using. The power supply should be located within 25-ft of the LED strip. Please contact Lumificient if the power supplies need to be located more than 25-ft away from the runs. Note: Accent comes in 12.5-ft and 25-ft sections, so before beginning your application it is recommended that you review your plans and layout longer runs first. Please follow layout diagrams and if needed consult with a Lumificient representative. By doing this you will maximize the strip and limit the need for added components. 3. Expose approximately 6 inches of the adhesive backing. Note: Do not touch adhesive tape with greasy or wet hands! Copyright 2016 Revolution Lighting. All rights reserved. IN066_01_20160829 Page 2 of 15

4. Adhere the Accent strip inch by inch to surface. Note: It may take some time for the adhesive to bond to the surface (24-48 hours). In case of poor adhesion of the strip you may use the plastic support clamps or silicone to secure strip to surface. ( Attachment 2) 5. To make a curve, bend the Accent flexible conductor strip between the sockets pinching excess strip between thumb and forefinger together. After pinching adhere corner of the turn by firmly pushing down with your forefinger. Note: Do not put support clamps over any bends in the strip ( Attachment 2). 6. To trim Accent strip to desired length, cut strip with scissors directly between sockets. Note: Do not make cuts near any socket. Do not use wire cutters or utility knives to trim the strip. Doing so may cause permanent damage to the strip! Installing Power Connector (Dry or Damp Locations Only) The power connector must be connected in the middle of the strip. Note: Do not exceed the maximum loads for what the different power supplies are capable of driving. See power supply tables for minimum and maximum loads. For better power distribution, group runs into equal load groups. 1. Unplug the LED module from the socket. To remove the LED module, place thumb and forefinger on side edges of LED module and pull directly upwards until LED module is released from the socket. 2. With thumb and forefinger at base of the connector and aligned parallel with the strip, place connector pins into socket and lightly push down on top of connector with forefinger until the connection is secure. 3. Plug in previously unplugged LED module to the top of the power connector. Note: Do not tug on connector leads. 4. Secure the connector with the connector holder and secure the connector cable with a 1/4 wire clamp ( Attachment 1). Copyright 2016 Revolution Lighting. All rights reserved. IN066_01_20160829 Page 3 of 15

Installation of Power Connector Attachment 1 DO NOT exceed the maximum run lengths allowed per power connector. manage or move cable wires without connector holder installed. Doing so may permanently damage the connector. Installation of Support Clamp DO NOT Drive the screw through the strip. Put the clamp over strip bends. Doing so may cause a short circuit and permanently damage the system! Attachment 2 Copyright 2016 Revolution Lighting. All rights reserved. IN066_01_20160829 Page 4 of 15

HRLA-24 Power Supply Installation All secondary wiring must comply with Article 725 of the 2002 National Electrical Code (NEC). Class 3 or PLTC wire can be used as a substitution of Class 2 wire. Please refer to NEC 725.61 Cable Substitution Hierarchy. HRLA-24 1. Group runs into equal load groups not to exceed the maximum load as listed in the Power Supply Loading Guidelines ( Table 1). The power supply should be placed within 25-ft of the LED strip. Should you be required to locate the power supply further away please consult with your Lumificient representative. 2. Place the power unit in the middle of the selected load group as shown in the schematic drawing in attachment 3. Run a pair of Class 2 rated wires the length of the selected load group ( Attachment 3). Note: Longer runs of 12AWG secondary wiring will decrease maximum allowable linear footage. Note: Using higher than 12AWG wire will result in increased voltage drop. 3. Connect power connector leads to Class 2 rated wires (parallel electrical connection) by using tap and run IDC connectors. Note: Do not use wire nuts for connecting power connectors to Class 2 rated wires! 4. Use wire nuts to insulate ONLY the ENDS of the Class 2 wires. Secure Class 2 rated wires on the wall with wire clamps. Note: All free hanging wire must closely follow the building structure and must be supported by wire clamps every 4.5-ft and at least 1-ft from the power unit. 5. Connect secondary/output wires from the HRLA-24 power unit to Class 2 rated wires by using tap and run IDC connectors ( Attachment 3). Important: For Maximum load requirements per power unit see Power Supply Loading Guidelines ( Table 1). Note: Do not connect power supply outputs in series or parallel! 6. Secure power unit inside of electrical enclosure. Note: For wet locations, HRLA-24 power unit must be installed in NEMA 3R enclosure. Exit point of low-voltage wiring must be secured against water entry into the box (rain tight bushing, cord grip etc.). Note: For dry or damp locations, HRLA-24 power unit must be installed in NEMA 1 rated enclosure OR inside of all metallic enclosure. Copyright 2016 Revolution Lighting. All rights reserved. IN066_01_20160829 Page 5 of 15

7. Connect the power unit to 120VAC junction box. Note: It is required to use UL rated metallic or nonmetallic conduit between the junction box and the power supply enclosure. Caution: Have a licensed electrician connect primary. Note: High voltage primary wiring, including wiring within 120VAC junction box, should comply with any applicable grounding and bonding requirements in Article 600 of the 2005 National Electrical Code (NEC). Verify if disconnect switch is present. National Electrical Code (NEC) requires a disconnect switch. If disconnect switch is not present, it must be installed between the main breaker and the first power unit. 8. Test the runs by turning the main power on. Note: Do not touch any metal parts while testing. Please refer to the Typical Layouts document for examples of installations. Table 1: Power Supply Loading Guidelines HRLA-24 Accent H/O Power Supply Outputs Output Voltage Minimum Linear Footage Per Terminal 2 MOD/FT HRLA-24 1 8.0VAC nom. No minimum 3 MOD/FT HRLA-24 1 8.0VAC nom. No minimum 4 MOD/FT HRLA-24 1 8.0VAC nom. No minimum Maximum Total Linear Footage/ 7 linear feet/ 14 5 linear feet/ 15 3 linear feet/ 12 Attachment 3 Copyright 2016 Revolution Lighting. All rights reserved. IN066_01_20160829 Page 6 of 15

HRLA-PSSQ Power Supply Installation All secondary wiring must comply with Article 725 of the 2002 National Electrical Code (NEC). Class 3 or PLTC wire can be used as a substitution of Class 2 wire. Please refer to NEC 725.61 Cable Substitution Hierarchy. HRLA-PSSQ 1. Group runs into equal load groups not to exceed the maximum load as listed in the Power Supply Loading Guidelines ( Table 2). The power supply should be placed within 25-ft of the LED strip. Should you be required to locate the power supply further away please consult with your Lumificient representative. 2. Place the power unit in the middle of the selected load group as shown in the schematic drawing in attachment 4. Run a pair of Class 2 rated wires the length of the selected load group ( Attachment 4). Note: Longer runs of 12AWG secondary wiring will decrease maximum allowable linear footage. Note: Using higher than 12AWG wire will result in increased voltage drop. 3. Connect power connector leads to Class 2 rated wires (parallel electrical connection) by using tap and run IDC connectors. Note: Do not use wire nuts for connecting power connectors to Class 2 rated wires! 4. Use wire nuts to insulate ONLY the ENDS of the Class 2 wires. Secure Class 2 rated wires on the wall with wire clamps. Note: All free hanging wire must closely follow the building structure and must be supported by wire clamps every 4.5-ft and at least 1-ft from the power unit. 5. Connect secondary/output wires from the HRLA-PSSQ power unit to Class 2 rated wires by using tap and run IDC connectors ( Attachment 4). Important: For Minimum and Maximum load requirements per power unit see Power Supply Loading Guidelines ( Table 2). Note: Do not connect outputs in series or parallel! 6. Secure power unit on the wall with three screws. Note: For wet locations, HRLA-PSSQ power unit must be installed in NEMA 3R enclosure. Exit point of low-voltage wiring must be secured against water entry into the box (rain tight bushing, cord grip etc.). Copyright 2016 Revolution Lighting. All rights reserved. IN066_01_20160829 Page 7 of 15

7. Connect the power unit to 120VAC junction box. Note: HRLA-PSSQ is equipped to accept 120VAC, 230VAC OR 240VAC ( see Attachment 5 for wiring diagram). Caution: Have a licensed electrician connect primary. Proper connection is as follows: a) For 120VAC: Hot to Black & Yellow; Neutral/Common to Orange & White; DO NOT Connect BROWN and insulate end separately; Green: Ground. b) For 230VAC: Hot to BROWN; Neutral/Common to Orange; White & Yellow connected and insulate ends; DO NOT Connect BLACK and insulate end separately; Green: Ground. c) For 240VAC: Hot to BLACK; Neutral/Common to Orange; White & Yellow connected and insulate ends; DO NOT Connect BROWN and insulate end separately; Green: Ground. Note: It is required to use UL rated metallic or nonmetallic conduit between the junction box and the power supply enclosure. Note: High voltage primary wiring, including wiring within 120VAC junction box, should comply with any applicable grounding and bonding requirements in Article 600 of the 2005 National Electrical Code (NEC). Verify if disconnect switch is present. National Electrical Code (NEC) requires a disconnect switch. If disconnect switch is not present, it must be installed between the main breaker and the first power unit. 8. Test the runs by turning the main power on. Note: Do not touch any metal parts while testing. Please refer to the Typical Layouts document for examples of installations. Table 2: Power Supply Loading Guidelines HRLA-PSSQ Accent H/O Power Supply Outputs Output Voltage 2 MOD/FT HRLA-PSSQ 1 8.0VAC nom. 3 MOD/FT HRLA-PSSQ 1 8.0VAC nom. 4 MOD/FT HRLA-PSSQ 1 8.0VAC nom. Minimum Linear Footage/ 3 linear feet/ 6 2 linear feet/ 6 1.5 linear feet/ 6 Maximum Total Linear Footage/ 12 linear feet/ 24 8 linear feet/ 24 6 linear feet/ 24 Attachment 4 Copyright 2016 Revolution Lighting. All rights reserved. IN066_01_20160829 Page 8 of 15

Attachment 5 Copyright 2016 Revolution Lighting. All rights reserved. IN066_01_20160829 Page 9 of 15

HRLA-96 Power Supply Installation All secondary wiring must comply with Article 725 of the 2002 National Electrical Code (NEC). Class 3 or PLTC wire can be used as a substitution of Class 2 wire. Please refer to NEC 725.61 Cable Substitution Hierarchy. HRLA-96 1. Group runs into equal load groups not to exceed the maximum load as listed in the Power Supply Loading Guidelines ( Table 3). The power supply should be placed within 25-ft of the LED strip. Should you be required to locate the power supply further away please consult with your Lumificient representative. 2. Place the power unit between the two selected load groups as shown in the schematic drawing in the attachment ( Attachment 6). Run a pair of Class 2 rated wires the length of the selected load group ( Attachment 6). Note: Longer runs of 12AWG secondary wiring will decrease maximum allowable linear footage. Note: Using higher than 12AWG wire will result in increased voltage drop. 3. Connect power connector leads to Class 2 rated wires (parallel electrical connection) by using tap and run IDC connectors. Note: Do not use wire nuts for connecting power connectors to Class 2 rated wires! 4. Use wire nuts to insulate ONLY the ENDS of the Class 2 wires. Secure Class 2 rated wires on the wall with wire clamps. Note: All free hanging wire must closely follow the building structure and must be supported by wire clamps every 4.5-ft and at least 1-ft from the power unit. 5. Connect secondary/output wires to power unit terminals 1 and 2 ( Attachment 6). Note: For better power distribution divide load between terminals 1 and 2. Important: For Minimum and maximum load requirements per power unit see Power Supply Loading Guidelines ( Table 3). Note: Do not connect outputs in series or parallel! 6. Secure power unit with four screws. Note: For wet locations, HRLA-96 power unit must be installed in NEMA 3R enclosure. Exit point of low-voltage wiring must be secured against water entry into the box (rain tight bushing, cord grip etc.). Copyright 2016 Revolution Lighting. All rights reserved. IN066_01_20160829 Page 10 of 15

7. Connect the power unit to 120VAC junction box. Caution: Have a licensed electrician connect primary. Note: HRLA-96 is equipped to accept 120VAC OR 240VAC ( see Attachment 7 for wiring diagram). Proper connection is as follows: a) For 120VAC: Hot to Black & Yellow; Neutral/Common to Orange & White; Green: Ground. b) For 240VAC: Hot to Black; Neutral/Common to Orange; White & Yellow connected and insulate ends; Green: Ground. Note: HRLA-96 power unit has a cutout for 1/2 conduit fitting. It is required to use UL rated metallic or nonmetallic conduit between the junction box and the power supply enclosure. Note: High voltage primary wiring, including wiring within 120VAC junction box, should comply with any applicable grounding and bonding requirements in Article 600 of the 2005 National Electrical Code (NEC). Verify if disconnect switch is present. National Electrical Code (NEC) requires a disconnect switch. If disconnect switch is not present, it must be installed between the main breaker and the first power unit. 8. Test the runs by turning the main power on. Note: Do not touch any metal parts while testing. Please refer to the Typical Layouts document for examples of installations. Table 3: Power Supply Loading Guidelines HRLA-96 Accent H/O Power Supply Outputs Output Voltage 2 MOD/FT HRLA-96 2 8.0VAC nom. 3 MOD/FT HRLA-96 2 8.0VAC nom. 4 MOD/FT HRLA-96 2 8.0VAC nom. Minimum Linear Footage/ Per Terminal 5 linear feet/ 10 3.5 linear feet/ 10 2.5 linear feet/ 10 Maximum Linear Footage/ Per Terminal 17 linear feet/ 34 11 linear feet/ 33 8 linear feet/ 32 Maximum TOTAL Linear Footage/ 34 linear feet/ 68 22 linear feet/ 66 16 linear feet/ 64 Attachment 6 Copyright 2016 Revolution Lighting. All rights reserved. IN066_01_20160829 Page 11 of 15

Attachment 7 Copyright 2016 Revolution Lighting. All rights reserved. IN066_01_20160829 Page 12 of 15

HRLA-277 Power Supply Installation All secondary wiring must comply with Article 725 of the 2002 National Electrical Code (NEC). Class 3 or PLTC wire can be used as a substitution of Class 2 wire. Please refer to NEC 725.61 Cable Substitution Hierarchy. HRLA-277 (277VAC) 1. Group letters into equal load groups not to exceed the maximum load as listed in the Power Supply Loading Guidelines ( Table 4). The power supply should be placed within 25-ft of the LED strip. Should you be required to locate the power supply further away please consult with your Lumificient representative. 2. Place the power unit between the two selected load groups as shown in the schematic drawing in the attachment ( Attachment 8). Run a pair of Class 2 rated wires the length of the selected load group ( Attachment 8). Note: Longer runs of 12AWG secondary wiring will decrease maximum allowable linear footage. Note: Using higher than 12AWG wire will result in increased voltage drop. 3. Connect power connector leads to Class 2 rated wires (parallel electrical connection) by using tap and run IDC connectors. Note: Do not use wire nuts for connecting power connectors to Class 2 rated wires! 4. Use wire nuts to insulate ONLY the ENDS of the Class 2 wires. Secure Class 2 rated wires on the wall with wire clamps. Note: All free hanging wire must closely follow the building structure and must be supported by wire clamps every 4.5-ft and at least 1-ft from the power unit. 5. Connect secondary/output wires to power unit terminals 1 and 2 ( Attachment 8). Note: For better power distribution divide load between terminals 1 and 2. Important: For minimum and maximum load requirements per power unit see Power Supply Loading Guidelines ( Table 4). Note: Do not connect outputs in series or parallel! 6. Secure power unit with four screws. Note: For wet locations, HRLA-277 power unit must be installed in NEMA 3R enclosure. Exit point of low-voltage wiring must be secured against water entry into the box (rain tight bushing, cord grip etc.). Copyright 2016 Revolution Lighting. All rights reserved. IN066_01_20160829 Page 13 of 15

7. Connect the power unit to 120VAC junction box. Caution: Have a licensed electrician connect primary. Note: HRLA-277 power unit has a cutout for 1/2 conduit fitting. It is required to use 1/2 metallic or nonmetallic conduit between the junction box and the power unit. Note: High voltage primary wiring, including wiring within 120VAC junction box, should comply with any applicable grounding and bonding requirements in Article 600 of the 2005 National Electrical Code (NEC). Verify if disconnect switch is present. National Electrical Code (NEC) requires a disconnect switch. If disconnect switch is not present, it must be installed between the main breaker and the first power unit. 8. Test the runs by turning the main power on. Note: Do not touch any metal parts while testing. Please refer to the Typical Layouts document for examples of installations. Table 4: Power Supply Loading Guidelines HRLA-277 Accent H/O Power Supply Outputs Output Voltage 2 MOD/FT HRLA-277 2 8.0VAC nom. 3 MOD/FT HRLA-277 2 8.0VAC nom. 4 MOD/FT HRLA-277 2 8.0VAC nom. Minimum Linear Footage/ Per Terminal 5 linear feet/ 10 3.5 linear feet/ 10 2.5 linear feet/ 10 Maximum Linear Footage/ Per Terminal 17 linear feet/ 34 11 linear feet/ 33 8 linear feet/ 32 Maximum TOTAL Linear Footage/ 34 linear feet/ 68 22 linear feet/ 66 16 linear feet/ 64 Attachment 8 Copyright 2016 Revolution Lighting. All rights reserved. IN066_01_20160829 Page 14 of 15

Troubleshooting Issue All runs are off Some runs are off Some LED s appear dim or intermittent Shadows/ uneven lighting Solution Check circuit breaker and AC input connection. Check power supply output connections and re-settable breakers (if applicable). Check IDC connectors to ensure they are fully connected. Check power lead wire connections on strip and verify connections are secure (see Attachment 1). Measure Accent strip length to ensure the maximum load length has not been exceeded. Properly terminate the supply wire connection(s). Check IDC connectors to ensure they are fully connected. Check power supply output connections and re-settable breakers (if applicable). Check power lead wire connections on strip and verify connections is secure (see Attachment 1). Measure Accent strip length to ensure the maximum load length has not been exceeded. Check IDC connectors to ensure they are fully connected. Check power supply output connections and re-settable breakers (if applicable). Measure Accent strip length to ensure the maximum load length has not been exceeded. Make sure the supply wire has not exceeded the maximum length of 25-ft for remote mounting. Make sure supply wire is not higher than 12AWG. Verify the max load length has not been exceeded and that wire connections and terminations are good. Re-route connecting wire and secure with wire clamps to ensure wire does not cover any of the LEDs. Copyright 2016 Revolution Lighting. All rights reserved. IN066_01_20160829 Page 15 of 15