Supplementary Instructions for Mechanical Latch Attachment for Type SJA or SJO Contactor Single or Dual Trip, 360 Amp~re

Similar documents
Instructions for Replacing

CR193 Vacuum Limitamp* Contactors

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

Installation Sheet January, 2016 Supersedes February, 2013

Instructions for A200, A210, A250 size 6, two- or three-pole non-reversing or reversing motor controllers

www. ElectricalPartManuals. com

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet

Module 2 CONTROL SYSTEM COMPONENTS. Lecture - 4 RELAYS

Synchronous Wired and Electronic Movement Manual

Installation Sheet January, 2016 Supersedes June 2013

Electrically Held to Mechanically Latched Contactor

Vacuum Circuit Breaker Type VAD-3

INSTRUCTIONS. seconds. the tween the end of the bearing screw and the. top of the shaft. The moving contact is a small silver hemisphere

Power Circuit Breakers

Programmable Logic Controller. Mat Nor Mohamad

Ampgard medium voltage motor control renewal parts

SERVICE AND REPAIR PARTS NEMA SIZE 3, SINGLE POLE, NORMALLY OPEN, P/N SERIES NEMA SIZE 4, SINGLE POLE, NORMALLY OPEN, P/N SERIES

Cutler-Hammer. Instructions for Potential Transformer and Auxiliary Control Power Disconnecting Means for Use in Ampgard Lineups, 7.2 kv I.B.

SERVICE AND REPAIR PARTS NEMA SIZE 5, SINGLE POLE, NORMALLY OPEN, P/N SERIES NEMA SIZE 5A, SINGLE POLE, NORMALLY OPEN, P/N SERIES

Auxiliary Contact Rating Induction Motor 1750 HP 2250 HP 3000 HP 4500 HP Voltage (Max)

STARTER - HITACHI Isuzu Trooper II DESCRIPTION TESTING STARTER PERFORMANCE TESTS Starters HITACHI. Isuzu

A - Add New Information C - Change Existing Information D - Delete Information. Page 7. Delete the fourth paragraph beginning CAUTION

PALMER MASTER SWITCHES CONT ACTOR TYPE REQUIREMENTS AND ADJUSTING PROCEDURES

RELAYS. Figure Relay construction.

Model 2300DL Installation Guide

INSTRUCTIONS. 1 Schematic. I Device ' I. S8C Switch Operators - Type CS-24. For Operation

1. Take the cover off the relay, taking care to not shake or jar the relay or other relays around it.

TABLE I. AMPGARD EQUIPMENT RATINGS

CA Breaker Instruction Manual

C. Figure 1. CA-16 Front View Figure 2. CA-16 Rear View

U STYLE "TP" TIME RELEASE UNION SWITCH & SIGNAL DIVISION OF WESTINGHOUSE AIR BRAKE CO. INSTALLATION AND MAINTENANCE AUGUST, 1951

Q-04: Replace Brake Shoes/Adjust Brakes

Garden Tractor Clutch

MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES M450

SERVICE AND REPAIR PARTS NEMA SIZE 5, SINGLE POLE, NORMALLY CLOSED, P/N SERIES NEMA SIZE 5A, SINGLE POLE, NORMALLY CLOSED, P/N SERIES

COLLATOR REFERENCE CONTENTS. Copyright 1947, ADJUSTMENTS. FeedHoppers... Feed Knives... FeedKnifeGuides... Card Guides... FeedRolls..-.. rn...

Type CRN-1 Reverse Power Relay 50 and 60 Hertz

IMI vibration switch USER MANUAL INSTALLATION - OPERATION - MAINTENANCE

An Investment in Plant Floor Safety. 802C Safety Cable Pull Switches 802E Hinge Safety Interlock Switches 802F Safety Interlock Switches

Cutler-Hammer. Instructions for Installation, Operation, and Maintenance of the AMPGARD Reduced Voltage Soft Starter

5 Series - Mechanical Latch 2PDT - 4PST, 30 Amps

TYPE KF UNDER-FREQUENCY RELAY A. Figure 1: Type KF Relay for 60 Hertz without Case. (Front & Rear View.) Front View Rear View

#92 DISC BRAKE ADJUSTMENTS # BRAKE MONITOR

www. ElectricalPartManuals. com INSTRUCTIONS INTERLOCKED MOTOR-DRIVEN OPERATING MECHANISM For No-Load Tap Changers DESCRIPTION OPERATION MAINTENANCE

F O R M. Installation and Maintenance Manual for FCR Equipped Motors and Gearmotors. 9055E Revised October 2015

INSTRUCTIONS. GEI-38974A Supersedes GEI INSTANTANEOUS CURRENT RELAY TYPE PJC2OA GENERALS ELECTRIC

INSTRUCTION MANUAL HIGH-VOLTAGE VACUUM CONTACTORS MOTOR& TRANSFORMER APPLICATION. May, 2001 TOSHIBA CORPORATION SOCIAL INFRASTRUCTURE SYSTEM COMPANY

Fuse contactor drawer CVX for PIX Switchgear (12kV)

Installation Instructions For Motor Control Center (MCC) Units

Page 2 DS LOW VOLTAGE POWER CIRCUIT BREAKERS Digitrip Trip Unit Inside Wiring Guide Outside Wiring Guide Shutter Drawout Unit Position Indicator Escut

One- Touch Installation Instructions

ProTrip Conversion Kits. For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION. DEH Installation Instructions

Model 2300JL Installation Guide

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers

Type SOQ Negative Sequence Time Overcurrent Relay

ACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS

ABB. Type CRQ Directional Negative Sequence Relay for Ground Protection B 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION CAUTION

Cutler-Hammer. AMPGARD MV Motor Control Vacuum Break SJ Series II II. Renewal Parts. r II li I. Pages. Contents. Effective: March 2000 Page 1

INSTRUCTIONS. S&c Circuit-Switchers - Mark v Grounding Switches - 70,000 Amperes Momentary Outdoor Transmission I INTRODUCTION INSTRUCTION SHEET 7 1 1

Using new Magnetically Actuated Vacuum Interrupter technology for safe and reliable medium voltage circuit breaker switching in mines

Installation and Service Instructions for Self Adjust Brakes 81,000 Series

Limit Switches. Reference Information. Proper Application of Limit Switches General Information. Definition of Limit Switch Terms.

Z-Gate Universal Shifter

GE CONSUMER & INDUSTRIAL

P. Sub 4 184A404. Sub 3 876A220

Installation and Service Instructions for Self Adjust Brakes 82,000 Series

Ch 4 Motor Control Devices

MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES MV600

Installation Instructions

www. ElectricalPartManuals. com INSTRUCTIONS TYPE CO CONTACT MAKING AMMETER INSTALLATION OPERATION MAINTENANCE I.. L APPLICATION

Specifications D3C, D4C AND D5C SERIES III TRACTORS POWER TRAIN. Steering Brake Group Pedal Steer (Standard)

I-BFV.KIT Butterfly Valve Gear Operator Replacement

AUTOTRANSFORMER-TYPE STARTERS ALLEN-BRADLEY COMPANY REPLACEMENT PARTS AND PROCEDURES

***Be sure that the loaded trailer weight does not exceed 24,000 lbs. or the vertical load rating does not exceed 6000 lbs.

Series A Construction

./#0#. 1"&." 1994 ELECTRICAL Suzuki of America Corp. - Starters. Swift

70 Series 8700 End Mount Three Phase Brake Instructions IP43 (NEMA 2) Housing

L. Photo. Figure 2: Types CA-16 Relay (rear view) Photo. Figure 1: Types CA-16 Relay (front view)

Installation Instructions Z-Gate Shifter

PT-150 PLUG-IN THERMAL RELAY WITH SNAP-ACTION BACK CONTACT *****************

COM Overcurrent Relay

AL625 & AL625HD INSTALLATION & OWNER S MANUAL

Fuse contactor drawer CVX for PIX-M Switchgear (7.2kV)

POWER BREAK Circuit Breakers

Two-way cable interlock kit for Magnum fixed circuit breakers

www. ElectricalPartManuals. com Instructions for Low-Voltage Power Circuit Breakers Types DS-206, DS-416 and DS-532 Westinghouse Electric Corporation

BBC. Renewal Parts. I-T-E Low-Voltage Power Circuit Breakers

ELECTRICAL. Contents - Wiring Diagrams

Installation and Service Instructions for 87,000 Series Manual Adjust Brakes (rev. B)

B CW POWER RELAY

HANDLING MECHANICAL INSTALLATION

FULL VOLTAGE STARTERS z SIZE 8 SERIES B CONSTRUCTION

Horizontal Circuit Switchers

70 Series 8700 End Mount Three Phase Brake Instructions IP56 (NEMA 4) Housing

ARCHITECTURAL CONTROL SYSTEMS, INCORPORATED ST. LOUIS, MISSOURI

Electrical Equipment - Course SWITCHGEAR: PART 2 CONTROL CENTRES. (b) the electrical protection and other safety

SEW Brakes. Service and Maintenance

McCANNA Actuation Systems B

ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065

MGM Brakes Service Manual

Transcription:

Supplementary nstructions for Mechanical Latch Attachment for Type SJA or SJO Contactor Single or Dual Trip, 36 Ampre. L. 16 2-35A Fig. 1 Type SJO with Latch Attachment APPLCATON trip the latch arm - when energized - by pushing the ra:tch arm down (below the armature), allowing the cont11ctor armature to move into the open-contacts position. The latch arm has a rller-bearing cam )ll'heel on the end 'that engages the armature so that.. friction is minimizec; and the trip action is fast. The contactor coil and trip solenoid coils are ntermittently rated and will burn-out if energized contin; uously, there are many possible operating schemes and diagrams, and the installer should check the oper. ation of the latch against the specified diagram for. the specific application. 1.t s recommended that the coils be automatically de-energized by auxiliary contacts on the contactor itself, without depending on supplemen tary relays elsewpere.. The latch sensitivity is adjustable. f unlatching occurs accidentally from vibration or impact, the sensitivity. should be decreased. f either unlatch solenoid fails to trip the latch when rated solenoid voltage is.applied, then the sensitivity should be increased. Refer to the. seotiofr on MANTENANCE. '.. ',1-: '-... ' TABLE - COL NRUSH DATA.Coll Function Rating VoltAmperes Close contactor 11-12 VAC 13 Close contactor 22-24 VAC. 14 Close contactor 125 VDC 15 Close contactor 25 VDC 16 Open contactor AC 225. Open ontactor 24 voe 6 Open contactor 4896 voe 19 Open contactor 125 VD.C 3 Open contadtor 23 VDC 265 ' '; NSTALLATON This industrial type control is designed to be installed, operated, and maintained by adequately trained ;per' sonnel, with adequate supervision. These instructions do not cover all details, variations, ;or combinations, of the equipment, ts storage, delivery, '>installation, checkout, safe operation, dr maintenance. Care must. be exercised to, comply with local, st'ate, and national regulations, as well as safety practices, for this, class of equipment. WARNNG: ALL. WORK ON THS.. CoNT:ACTOR SHOULD BE DONE. WTH THE. MAN DSCO.NNECT DEVCE OPEN. AS WTH ANY CONJACrOR OF'THS VOLTAGE CLASS, THERE S DANER OF ELECTRO CUT ON AND/OR SEVERE. BURNS, MAKE CERTAN THAT POWER S OFF'..

MECHANCAL LATCH FOR 36A SJ l.l. t6-2 35A HOLE N LATCH MOUNTNG FOR TWO SLOTTED HOLES (BOTH S DES) ". NOTE: LATCH ARM SHOWN UN-LATCHED 1(2") 5259C56 Fig. 2 Mechanical Latch Assembly Figure 2 shows a latch assembly before it is mounted on a contactor. The enlarged detail shown in Figure 3 shows the relationship betwee.n the cam roller on the end of the latch arm and a notch in the lower left corner of the contactor armature. When the latch is installed, it appears as shown in the lower portion of Figure 3. Latch sensitivity can be understood by studying the inset of Figure 3, which is a magnified detail view showing the lower left corner of the armature and the cam roller. The cam roller travels between positions (U) and (L) through a 6112'' radius arc around the latch shaft. This is the radius of the latch arm. n the unlatched (open) contactor position, the cam roller is in position (U). t cannot travel upward to position (L) even though the latch spring is pushing the latch arm upward because latch edge (F) of the armature stops it. However, when the contactor operating coil is energized, the armature rotates toward the magnet and latch edge (F) travels across the cam roller easily. As latch edge (E) passes the centerline of the cam roller, the' roller starts moving upward, driven by the latch spring. By the time the armature reaches the magnet, the cam roller passes completely by latohcedge (E) into position (L), and the contactor is latched closed. The cam roller cannot trave;j to the top of the notch in the armature because the latc.h arm stops against the latch adjustment bolt. The further into the notch the cam roller penetrates, the, less sensitive the latch becomes. There will always be some "backlash" clearance between the contactor armature and magnet in order to provide free motion. This only needs to be a few thousandths of an inch; so for practical purposes, the contactor is held "fully" closed. When either or both trip solenoids are momentarily energized, their armatures. push the latch arm downward against its spring; As the centerline of the cam roller passes below latch edge (E) of the armature, the contactor armature will snap to the fully open position; i.e. the contactor is open. f the latch has been de-sensitized with an adjustment that allows the cam roller to travel high into the armature notch when latched, the trip solenoids have an increased resistance to their push. n a poorl adjusted latch, this may prevent tripping at 8% of trip soleoid voltage, in which case the latch must be made more sensitive. 2

MECHANCAL LATCH FOR 36A SJ LL. 162 35A SDE VEW RCJNT VEW SPACNG WASHERS 5259C57 Fig. 3 Mechanical Latch nstalled CHECK-OUT, MECHANCAL Refer to the nstruction Leaflet relating to the electrically-held contactor l.l. 16-2-32 or l.l. 16-2-33. Make sure all power circuits are de-energized and/or isolated. The contactor can be checked in its enclosure or outside. f the starter is a new factory assembly it is probably easiest to test the contactor as nstalled. Any mechanical nterlocks must be checked as nstalled, to make certain that safety interlocks function properly. f the contactor is checked in ts enclosure, make certain that the contactor coil is electrically isolated, to prevent feedback into a control transformer that could be hazardous. With an extension cord and a separate power source of correct voltage, connect power to the coil of the contactor. Operate appropriate pushbuttons to close. f the contactor does not close fully, refer to MANTENANCE. The contactor should automatically latch and stay closed. Make sure that the coil clearing contact automatically removes control circuit voltage after the contact s closed, to prevent coil burnout. While the contactor is closed, observe the overtravel gap between the pivot plates on the crossbar and the underside of the lower bottle nut on each pole. This overtravel gap should be no less than.7 nch when the contactor s new. f less, refer to MANTENANCE. Note: When a contactor is latched, it has a small amount of "backlash" to nsure freedom of motion. The armature is not sealed againstthe magnet as n an electrically-held contactor. Therefore, the full.75 inch overtravel specified for an electrically-held contactor cannot be achieved. While the contactor is closed, operate the manual trip arm: to assure that the unlatch mechanism functions. 3

MECHANCAL LATCH FOR 36A SJ 1.L. 16 2 35A Effective 1/86 Supersedes 16-2-35 (11/83) Westinghouse Electric Corporation Control Division Asheville, N.C., U.S.A. 28813 Printed n USA

MECHANCAL LATCH FOR 36A SJ Reclose contactor, and trip it electrically using each trip solenoid separately. Check the coil clearing auxiliary contact to make sure that each solenoid s de-emirglzed automatically after operating, to prevent solenqid coil burnout. There should be no voltage between the terminals of each trip solenoid coll after the contactor has been opened. When tripped, te latch should move briskly. f it s sluggish, refe( toimantenance. CAUTON! A latch s somewhat like a mousetrap. Use care to protect fi)1gers in the event of an accidental trip during check-out. CHECK-OUT, ELECTRCAL Refer to,the instructions for the electrically-held contactor. ' MANTENANCE A maintenance program.should be established as soon as the contactor is in talled and put into operation. After the contactor has been inspected a number of times at monthly intervals, and the condition noted, the frequency of inspecfion can be increased or decreased to suit the conditions found, since this will depend upon the severity of the contactor duty: t is a matter of operator judgement. ' Failure To Latch Or Unlatch First, establish that the latch operates freely without mechanical nterference. (The contactor can be operated electrically with an ext.e.nsion cord, as described previously under CHECK-OUT, MECHANCAL. Or it can be operated by hand (1) with a wrench on the end of the contactor shaft, (2) by pushing down on the top rear edge of the contactor crossbar, or (3) in the case of an SJA contactor, by turning the yoke interlock arm on the stub shaft clockwise;) Remove )he lat.ch spring. Block the bottom solenoid open temporarily'with a pencil or oth,e)r shim on top of ts magnet frame. and underneath ts armature. Hold the contaotor in the fully sealed-closed position by hand or electrically, and manually close/open the latch using the trip arm. Th.a latch should move easily. f it does not move freely, 'check the roller end of the latch arm to see if the latch arm rubs against the armature. To eliminate rubbing, loosen the two latch mounting bolts (B) (Figure 3) on the right side and move the right latch bearing plate rearward until the latch arm clears the armature. Re-tighten the mounting bolts. Re-check for free motion. Next, hold the contactor n the fully sealed;closed position, operate the latch with the trip arm, then release the trip arm abruptly. The latch should fall freely into the open position. f it doesn't, the "backlash" clearance is insufficient. To increase the clearance, loosen all five latch mounting bolts (A) and (B) (Figure 3) and tap both the left and right bearing plates rearward a few thousandths of an inch. Re-tighten the five bolts and recheck both the free-fall release and the freedom from rubbing between the latch arm and the armature. Re-install the latch spring. Check the overtravel of the main vacuum nterrupters, since increasing "backlash" decreases overtravel. Overtravel must not be below.2 inch with worn contacts. Remove the blocking shim from the bottom trip solenoid. Check that both solenid armatures move. freely. Failure To Latch After making adjustments as outlined n the previous. section, operate the contactor electrically. f it fails to latc.h: a. Qheck voltage applied to the contactor coil to be sure it is within 8% of coil rating. ' b. Check setting of the L-63 normally'closed coll. clearing auxiliary contact to see if t opens too soon and does not allow the contactor to close.. far' enough to latch. c. Make certain that the late spring is properly i in place. d. Decrease the sensitivity of toe latch by loosening: the lock nut on the latch adjustment and backing- off(unscrewlng) the latch adjustment bolt one-half. turn. Try again, and if latching is not successful, back-off another half-turn, etc. until the latch works. Re-tighten the lock nut. Failure To' Unlatch After making adjustments as outlined in the previous two sections, operate the contactor electrically. f the : trip solenold(s) do not unlatch the mechanism: a. Check voltage applied to the solenoids to be sure it is within 8% of rated voltage. b. Check each solenoid coil for continuity. Replace f burned open. See Table. c. Make certain there is an airgap under each solenoid armature of.12 to.13 inch wh\)n the : latch is latched. f there is no gap, the solenoid armatures cannot move to push the latch arm. d. ncrease the sensitivity of the latch qy loosening: the lock nut on the latch adjustment and tighten- ing (turn bolt clockwise) one-half tum. Try again,: and if unlatching is not successful, turn bolt. another half-turn, etc. until the solenoids unlatch ' dependably. Re-tighten the lock nut. Failure To Remain Latched f nuisance unlatching occurs, de-sensitize the latch adjustment as described under Failure To Latch.. TABLE - Trip Coll ntermittent Rating 115-12 VAC, 48 VDC 23-24 VAC; '96-125 VDC 46-48 VAC, 23 VDC 575-6 VAC 24 VDC REPLACEMENT SOLENODS Trip Solenoid Part No. 5259C46G1 5259C46G2 5259C46G3 5259C46G4 5259C46G5 4

;,", "' ;r;... -s "" iii' ca "' r- c () "' g- " C) ""' "' a "' " s- ::;- () :::.. "' ----- '.. f 1rn r-,-- STD. AMPGARD DOOR CONTACTOR CENTERLNE- l(_i- 1! 1-----r_ ------!_ - - t _l_ i! 1 i...j 2.75 r- L 8. --j ',O STD. AMPGARD DOOR,...- 1! :ff...3 TRAVEL REQ'D. TO TRP. TYPE SJA. [ "-.. i r. ' 4.3 ) TRP TARGET FOR LATCH - 'Od 11±_3:); t)-- r---- ' 14.2 D c s: m (') :::c )> z - 2 r-!i (') :::c 'Tl ::D c.> ) CJ) c.. 5259C59 8.5-12.751-,,1 - J : ' _l L:---1\. L -- 1 ' ] f _!'---. _LU-_ LATCH TRP -J-;-i rlri TAf\GET,.. _. Li! U Li 1-- 8.7 --j. - L TYPE SJO_ +- --.:.c..- b) REQ'D. TO '"' r [Lt:{_!-'-'-' too '-+-- - J r-... ) \;) c.>.. ---