Standard Duty Que - Temp Desuperheater Model: 33 / 43

Similar documents
YARWAY NARVIK MODEL 33/43 STANDARD DUTY QUE-TEMP DESUPERHEATER

Heavy Duty Que - Temp Desuperheater Model: 13 / 23

Standard Duty A.T.S.A. - Temp Desuperheater Model 24 / 34

Standard Duty SLN - Temp Desuperheater Model: 50 / 60

NARVIK-YARWAY. Heavy Duty A.T. - Temp Desuperheater Model: 18/54 and 28/64

YARWAY NARVIK STANDARD DUTY A.T.-TEMP DESUPERHEATER MODEL 38/48

YARWAY NARVIK MODEL 60/70 STANDARD DUTY SLN-TEMP DESUPERHEATER

Yarway Narvik Desuperheater Model 18/54 and 28/64 Heavy Duty

Standard Duty A.T.-Temp Desuperheater for cryogenic processes

Yarway Narvik Ven-Temp Desuperheater Model 25

Yarway Narvik Model 37 and 47 Cryogenic injector

LESLIE DESUPERHEATERS SIZES 1/2" 16" ANSI Class 150 to 2500

TempLowHT Steam Desuperheater Model: 59/69/79

YARWAY NARVIK VEN-TEMP DESUPERHEATER MODEL 25

YARWAY NARVIK MODEL 88 SPID SMALL PIPE INLINE DESUPERHEATER

Yarway Que - Temp Desuperheater Standard-/heavy Duty Installation and maintenance Instructions

Fisher DMA, DMA/AF, and DMA/AF HTC Mechanically Atomized Desuperheaters

Desuperheaters Fixed Nozzle, Minicooler Design and Variable Nozzle

Fisher DFA Variable Geometry Desuperheater

VELOCITY CONTROL TECHNOLOGY DESUPERHEATERS

Series DK Type DKV and DKM

VAD Variable Area Desuperheaters

FLOW TEK VALVES & CONTROL S INC

NARVIK-YARWAY. High Pressure Level Gauges, Model: 17

Series TD. Type TDL Type TDM. Automatic Recirculation Valve for pump protection

SEMPELL TURBINE BYPASS VALVE MODEL 115 CHP

Standard Duty A.T.-Temp Desuperheater for cryogenic processes Installation and Maintenance Instructions

Injection Desuperheater

SERIES MULTIPLE NOZZLE DESUPERHEATERS

Fisher DFA Variable Geometry Desuperheater

Series DK. Type DKV. Desuperheaters to control the Temperature of Superheated Steam (or Gas)

MNSD-V MULTIPLE NOZZLE SPRAY DESUPERHEATER BULLETIN 1144 APRIL 2004

DRAG VLN Turbine Bypass Valve for Hot Reheat Bypass Applications

DESUPERHEATER (SERIES 800)

Installation and Maintenance Instructions

MNSD-V MULTIPLE NOZZLE SPRAY DESUPERHEATER BULLETIN 1144 SEPTEMBER 2001

SERIES DESUPERHEATERS

PRESSURE REDUCING AND DESUPERHEATING STATIONS SERIES

Designed to provide maximum service life with minimum maintenance.

Series TD. Type TDL Type TDM. Automatic Recirculation Valve for pump protection

Installation and Maintenance Instructions

Aeroflow SCV Steam Control Steam Conditioning Turbine Bypass Valve

CROSBY STYLE JB PRESSURE RELIEF VALVE

5. Combustion of liquid fuels. 5.1 Atomization of fuel

MNSD-V & MNSD-U. Multiple Nozzle Spray Desuperheater

Yarway TempLow Steam Desuperheater Installation and Maintenance Instructions

High Pressure Turbine Bypass Valve HBSE

For Applications Demanding Precision and Efficiency, FloMax Nozzles Outperform All Others

Rate B standard. Rate A Rate A option. max +260 C/ min -40 C

Every component precisely matched

AN ISO 9001:2008 CERTIFIED COMPANY. Safety Valve

DVG/AF Variable Geometry Desuperheater

STEAM CONDITIONING VALVES TECHNICAL BULLETIN HORA POWER TECHNOLOGY

EXTRACTION CHECK VALVES TYPE C09.6

A MEMBER OF THE ARCA FLOW GROUP

Direct Contact Desuperheaters

Specially designed low-maintenance control valves for a wide range of applications in water circulation

Purpose & Advantages. The ARTES desuperheater can be actuated by means of electric, pneumatic or hydraulic drives.

94D / 94F / 94M / 96M

RAIMONDI. High pressure forged globe valves to guarantee the pressure envelope integrity on harsh services.

MA-III & MA-IIIU MECHANICAL ATOMIZING DESUPERHEATER

SAMSON 3281 & Steam Converting Valves SMART IN FLOW CONTROL

IBV Series C-LF2 Carbon Steel Inverted Bucket Vertical Steam Trap

Pressure Reducing and Desuperheating Valves

Direct Contact Desuperheaters

Fisher TBX Steam Conditioning Valve

Steam-Conditioning Valve

Series MRK and MRM For nominal pressures up to 640 bar /class 4500 Automatic Recirculation Valve for pump protection

YARWAY HIGH PRESSURE GLOBE VALVE

R o L. BUTTERFLY VALVE of carbon steel with welded ends 313 -series BLUE LINE. Description

STEAM TURBINE BY-PASS AND STEAM CONDITIONING VALVE

10000 SERIES. Steam Desuperheater With Spray Nozzles

STEAM EXTRACTION / COLD REHEAD ACTUATED CHECK VALVES

Hollow Cone Spray Nozzles Series

BUTTERFLY VALVE WAFER TYPE of carbon steel 311 ( ) series

Please note this is a condensed catalog. For a complete version, contact Velan directly.

CHEMICAL INJECTION PASSIVATING COATING STERILIZING FOGGING HUMIDIFYING MISTING COATING MOISTURIZING GAS COOLING LUBRICATING

DAM. Engineering GREAT Solutions. Steam Desuperheater

High Pressure Bypass System Type SOV acc. to TRD 421

YARWAY THROTTLING VALVES HY-DROP MODEL 5817/ 5827

DAM-B. Engineering GREAT Solutions. Steam attemperator

General Stem-Guided Control Valves

JUMO flowtrans DP R. Meter run R01 and orifice plate R02. Applications. Brief description. Special features. Customer benefits.

Full cone nozzles.

Desuperheater FCD VLENTB /11. Experience In Motion

Si Engineering GREAT Solutions. Steam Safety Valves to PED and DIN/EN standards

General Stem-Guided Control Valves

Turbine Bypass. Systems

Control Ball Valve Type W

Controls the destructive forces inherent in high pressure drop service through rapid energy dissipation.


APPLICATIONS IN PALM OIL MILL - CONTROL VALVE - DESUPERHEATER -PRDS -FLOWMETER -GAUGES

This innovation places FluoroSeal Plug Valves at the leading edge of technology in the industrial valve market.

Si 6303 / Si 6304 / Si 6305

Yarway Hy-Drop Throttling valve

Series MRM/MRK For nominal pressures up to 640 bar /4500 lbs Automatic Recirculation Valve for pump protection

ATOMIZATION OF LIQUID FUELS COMBUSTION AND FUELS

Mounting and Operating Instructions EB 5894 EN. Electric control valves with jet pump. Flanged version of valve with jet pump

Series Direct contact, metal-to-metal seating, make the globe valve ideal for most shut-off applications. Features

Edward. Equiwedge Forged Gate Valvee. Experience In Motion

Transcription:

Model: 33 / 43 Narvik-Yarway covers requirements for desuperheaters, pneumatic actuators, strainers with a wide range of models, sizes and materials to satisfy all the specifications of the power-pulp & paper industry and process gas applications Features Fabricated construction Variable nozzle type Wide range of Kv (Cv) capacities available Special nozzle combinations available Pressure class and connections: - ASME B16.34 class 150 to 1500 - EN 1092-1 class PN 25 to 250 - Buttweld connections to ASME B16.25 or DIN 2559 Materials: - ASTM SA 105 / SA 106 Gr.B or P250GH / P235 GH TC2 - ASTM SA 182 F11 / SA 335 P11 or 1.7335 - Other materials upon request Technical data Size : Steam 3 (DN 80) Water 1-1 1/2 (DN 25-40) Steam 4 (DN 100) Water 1 1/2-2 -3 (DN 40-50-80) General application Cooling of process steam or gas, Boiler superheater, Boiler reheater, Turbine bleed steam and Pressure reducing valve www.tyco.com/flowcontrol Tyco reserves the right to change the content without notice NRVSB-0061-EN-1112

Standard Duty Que - Temp Desuperheater Mode: 33/ 43 Water inlet flange is available to various standards. Model 33: 1-1 1/2 (DN 25-40) Model 43: 1 1/2-2 -3 (DN 40-50-80) Version circular-welded for class 600 (PN 100) up to and including class 1500 (PN 250) Steam flange is available to various standards. Model 33: 3 (DN 80) Model 43: 4 (DN 100) Fabricated body available in various materials. Construction in accordance with ASME B16.34 and EN 12516. CE-marking, if required. Version tack-welded for class 150 (PN 25/40) and class 300 (PN 64) Body extension pipe in various lengths, depending upon the installation requirements. Lower body with extension of more than 40 (1.0 mtr.) are provided with additional stem guiding. High performance spray nozzles give fine atomization of injection water. Fig. 1 Fig. 2 Tyco reserves the right to change the content without notice page 2

Mode: 33/ 43 The Narvik-Yarway Que - Temp Desuperheater is specifically developed for use on low-/medium pressure steam applications. Its fabricated construction makes it easy adaptable to meet various boiler codes and material specifications. The unit can also be used as a liquid into gas injector for which high grade alloy such as stainless steel is often used. The nozzle components are identical to those used in A.T. - Temp Desuperheater. More than 3800 units of both Heavy - and Standard Duty A.T. - Temp Desuperheaters are in service today. Applications Narvik-Yarway Que - Temp Desuperheaters are used for temperature control of: boiler superheaters - boiler reheaters - turbine bleed steam - pressure reducing valve outlet steam - process steam and process gasses. For system comparison, please see the relevant brochure. Superior spray nozzle Narvik-Yarway has incorporated the latest technology in the spray nozzle design. The high quality surface finish minimizes frictional losses, thereby ensuring that the total water to steam Δp is available for atomization of the water (see Fig. 3). The nozzle consists of two components A) the orifices and B) the nozzle body. Each nozzle is served by individual feed holes in the cylinder wall. Water enters the chamber behind the orifice plate through these openings. The relatively large volume of this chamber ensures that water is proportioned evenly through each orifice. The Δp across this orifice plate results in an increase in the fluid velocity. The water is subsequently rotated in the nozzle chamber before being emitted through the central hole. The combination of splitting the feed flow, increasing velocity and rotating effect, ensures that the water is injected into the system in a fine symmetrical hollow cone spray. The nozzles are assembled with the spray cylinder and sealed by a vacuum brazing process. This maintains the integrity of these components even under the most extreme conditions. Material compatibility of spray cylinder is well proven in hot/cold service conditions, as typically found in steam attemperators. This enables reliable operation over an extended period. Surfaces are finely machined to reduce frictional losses and internal contours are so designed as to optimize water swirl action, ensuring uniform and consistent droplet size. Minimum Δp available from the Que - Temp Desuperheater inlet flange to steam pressure must be: Nozzles A through Dx : 1 bar Nozzles E through K : 2 bar A B A B Fig. 3 Tyco reserves the right to change the contents without notice page 3

Model 33 / 43 Codes and standards The Que - Temp Desuperheater is designed and manufactured to meet a wide variety of international codes and standards. Certified acceptance documents are available upon request. If special codes or standards are required by your local authority, then we would be pleased to discuss them. Multiple nozzle heads The Que - Temp Desuperheater may be equipped with a variety of spray heads. The uniform body threading accepts spray cylinder heads with a wide range of Kv (Cv) values. Standard configurations are with either 6 or 9 equally sized spray nozzles but combinations are available. This feature enables the Que - Temp Desuperheater to be customized to specific system requirements. Consult Narvik-Yarway or your local representative for details. Size Que - Temp standard capacity range 6A Cv = 0.075 Kv = 0.064 9A Cv = 0.112 Kv = 0.097 6B Cv = 0.158 Kv = 0.136 9B Cv = 0.238 Kv = 0.205 16 6C Cv = 0.300 Kv = 0.259 9C Cv = 0.451 Kv = 0.389 6D Cv = 0.586 Kv = 0.505 9D Cv = 0.879 Kv = 0.757 6Dx Cv = 1.160 Kv = 1.000 9Dx Cv = 1.740 Kv = 1.500 6E Cv = 1.900 Kv = 1.639 9E Cv = 2.853 Kv = 2.455 6F Cv = 2.839 Kv = 2.448 9F Cv = 4.259 Kv = 3.672 25 6G Cv = 6.032 Kv = 5.200 9G Cv = 9.048 Kv = 7.800 6H Cv = 9.396 Kv = 8.100 9H Cv = 14.094 Kv = 12.150 6K Cv = 13.488 Kv = 11.628 9K Cv = 20.232 Kv = 17.442 Flow capacity limitations are: - Model 33 with a maximum water flow capacity of 50 m 3 /hr in continuous service - Model 43 with a maximum water flow capacity of 100 m 3 /hr in continuous service Definition S.G. Kv = Q ΔP Q = m 3 /hr S.G. = kg/dm 3 Δp = bar hw Gw h1 Gst h2 Gst + Gw Fig. 4 Sizing formula Every desuperheating station is a mixing point where there is a heat and mass balance. The universal formula is: Gw = Gst ( h1-h2 ) : ( h2-hw ) This formula enables calculation of the quantity of water required to lower the inlet steam temperature to the setpoint temperature of the outlet steam. In which: Gw Gst h1 h2 hw = Injection water mass = Inlet steam mass = Enthalpy of the inlet steam = Enthalpy of the outlet steam = Enthalpy of the injection water Tyco reserves the right to change the contents without notice page 4

Model 33 / 43 Important system parameters Apart from the spray quality of the atomizer (primary atomization) there are other system parameters which influence the desuperheater stations performance. These are: Inlet steam velocity At high steam velocities, water droplets are easily disintegrated. This factor contributes to the overall atomization quality (secondary atomization). The minimum acceptable steam velocity varies as a function of the nozzle size and pipe diameter. In case of doubt, consult Narvik-Yarway. Water to steam ratio This ratio is determined by dividing Gw by Gst. For system steam pressures below 15 bar, this ratio should not exceed 5% for the normal operating conditions. Systems operating between 15 and 25 bar can have a ratio of up to 10%. For higher pressure duties, consult Narvik-Yarway. Distance to sensor The distance from the injection point to the temperature sensor should be 12 to 15 meters. Systems operating at pressures above 25 bar can have significantly less run to the sensor, consult Narvik- Yarway. Required straight pipe run The distance from injection point to the first pipe bend is also a function of steam pressure, temperature and nozzle size. Experience has shown that in systems up to 25 bar, 4 to 6 meters, is an acceptable distance. Ordering / sizing data Steam desuperheaters are selected specifically against application data. For optimal sizing, the following comprehensive data should always be supplied. Steam data Inlet pressure bar Inlet temperature C Outlet temperature C setpoint Steam flow max. t / hr Steam flow normal t / hr Steam flow min. t / hr It is essential not to over specify the required turndown ratio i.e.: Steam flow max. Steam flow min. Otherwise this will necessitate selection of special nozzle heads which are non - stock items. Standard stock consists of nozzles with 6 or 9 equally sized atomizers having turndown ratio approx. 4:1 on the water flow control. Experience shows that the majority of applications fall within this range. Water data Water pressure bar Water temperature C General Pipe size mm Pipe schedule Required water flange position (9) (12) (3) (6) Water flange positions Steam line Steam flow Fig. 5 FP9 Spraywater must be injected in the direction of the steam flow. Flange bolt holes will straddle with main pipe centerline. Narvik-Yarway always recommends a strainer with a mesh size of approx. 100 μ (400 μ on request) in the water supply line to protect the Que - Temp Desuperheater from clogging. Tyco reserves the right to change the contents without notice page 5

Model: 33 / 43 Table 1 - Standard materials Fig. 6 Item Name Material Equivalent 1 + 2 Spray Nozzle assembly AISI 410 * 1.4006 * 5 Fastener ring SA182 F11 1.7335 8 Mounting part SA105 P250GH SA182 F11 1.7335 9 Body pipe SA106 Gr.B P235GH TC2 SA335 P11 1.7335 10 Water flange SA105 P250GH SA182 F11 1.7335 19 Name plate SS SS 24 Steam flange SA105 P250GH SA182 F11 1.7335 33 Reducer A234 Gr. WP B P235GH TC2 Gr. WP11 1.7335 * Welded sprayhead: material is simular to body material with AISI 410 nozzles. 33 10 Notes Other materials are available upon request. Certification: Que - Temp Desuperheater is approved by authorized authorities to comply with the requirements of ASME B16.34 and EN 12516. All data subject to changes. 19 24 Materials and data of units supplied, may deviate from this brochure. Please consult order documents in case of doubt. Recommended spares (in case of welded sprayhead, no spares available) 9 8 5 1 2 Detail A Detail A Tyco reserves the right to change the contents without notice page 6

Model: 33 / 43 Fig. 7 Table 2 - Dimensions (in mm) Water flange Table 3 C Model 33 Model 43 Qmax = 50 m 3 /hr Qmax = 100 m 3 /hr Standard length for steam line sizes up to 12 (DN 300) A A through Dx 380 399 E through K 399 B A through Dx 436 476 E through K 476 Option: standard length for steam line sizes 14 (DN 350) and higher A A through Dx 580 599 E through K 599 B A through Dx 636 676 E through K 676 C upon request upon request L Depending on size and pressure Depending on size and pressure class min. 150 class min. 200 M min. 66,0 80,0 N 60,3 x 11,1 73,3 x 14,0 P 64,0 78,0 Steam flange Table 3 Note L Dimensions may be subject to change without prior notification. Narvik- Yarway will provide a certified dimensional drawing upon request. M Table 3 - Flange connections Model 33 Model 43 N A B Qmax = 50 m 3 /hr Qmax = 100 m 3 /hr Steam flange 3 class 150 4 class 150 class 300 class 300 class 600 class 600 class 900 class 900 class 1500 class 1500 DN 80 - PN 25/40 DN 100 - PN 25/40 PN 64 PN 64 PN 100 PN 100 PN 160 PN 160 PN 250 PN 250 Tack-weld or Circular-weld P Water flange 1-1 1/2 1 1/2-2 - 3 DN 25-40 DN 40-50 - 80 Pressure classes as per Pressure classes as per water data requirements water data requirements Nozzles Minimum steam pipe size For nozzles A-B-C-D-Dx: 6 (DN 150) For nozzles E-F-G-H-K: 8 (DN 200) Tyco reserves the right to change the contents without notice page 7