Technical Data Sheets

Similar documents
Technical Data Sheets

Technical Data Sheet. Uninterruptible Power Supply. Digital Energy. imagination at work

Technical Data Sheets

Technical Data Sheets

Technical Data Sheets

Technical Data Sheets

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Technical Data Sheets

Technical Data Sheets

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Technical data sheets

gimagination at work Technical data sheet Uninterruptible Power Supply LP Series 6 & 10 kva GE Digital Energy

Technical data sheet VH UL. Digital Energy Uninterruptible Power Supply. GE Digital Energy Power Quality

Technical data sheets

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

TECHNICAL DATA SHEET B8031 FXS kva 3Ph(In) 1Ph(Out)

TECHNICAL DATA SHEET B8033FXS kva 3Ph(In) 3Ph(Out)

POWER kva

POWER kva

POWER kva Nominal output power (Cos φ0,8) kva Nominal output power (Cos φ1,0) kw >88 Efficiency (AC AC)

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

TLE Series UPS 400/500 kw With eboost Technology

EFFEKTA Power Supplies

TLE Series UPS 160/200/225/250 kw with eboost Technology

TLE Series UPS 750/1000 kw With eboost Technology

PowerValue 11/31 T kva

Eaton 93PS 8-40kW UPS Technical Specification Manufacturer s declaration in accordance with IEC

PowerScale kva Technical Specifications

TECHNICAL DATA SHEET INFINITY kva 3Ph(in) 3Ph(out)

TECHNICAL DATA SHEET KVA UPS Systemss

PowerScale TECHNICAL SPECIFICATIONS

ConceptpowerTM Modular kVA

POWERTRONIX QUASAR 5-40 KVA

SitePro UPS 400Vac / CE. GE Consumer & Industrial August 2004

Industrial PFC UPS System

DELPHYS GP. Green Power 2.0 range 160 to 1000 kva/kw

TECHNICAL SPECIFICATIONS

1.1 GENERAL CHARACTERISTICS

Master DIALOG INDUSTRY RANGE

SmartOnline SUT Series 3-Phase 208/120V 220/127V 20kVA 20kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option

TELECOM- MUNICATIONS DEVICES INDUSTRIAL EMERGENCY DEVICES. (Servers Farms, ISP/ASP/POP)

D Series: UPS UPTO - 300KVA - Three / Three Phase

SmartOnline SUT Series 3-Phase 208/120V 220/127V 30kVA 30kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option

UPS. MODULAR from 10 to 60kVA THE GLOBAL SPECIALIST IN ELECTRAL AND DIGITAL BUILDING INFRASTRUCTURES

60 to 160 kva.

TELECOM- MUNICATIONS DEVICES INDUSTRIAL EMERGENCY DEVICES. (Servers Farms, ISP/ASP/POP)

10 20KVA 3Ph/1Ph KVA 3Ph / 3Ph

SmartOnline SUT Series 3-Phase 208/120V 220/127V 40kVA 40kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option

UPS Sentry HPS. power supply sources - isolation transformers and generators over less sophisticated power systems.

POWER+ CLASSIC 20/30 KVA, 3X208 VAC WITH INTERNAL BATTERIES. GAMATRONIC, A SolarEdge Division

POWER+ CLASSIC 20/30 KVA, 3X208 VAC WITH INTERNAL BATTERIES. GAMATRONIC, A SolarEdge Division

Master Plus kva

APC Smart-UPS. GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply

Master Plus kva

Technical Specifications. Sentinel PRO 700 VA up to 3000 VA 1000 VA ER-2200 VA ER-3300 VA ER

KEOR HP. THREE-PHASE UPS from 100 to 800 kva GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

SmartOnline SVTX Series 3-Phase 380/400/415V 20kVA 18kW On-Line Double-Conversion UPS, Tower, Extended Run, SNMP Option

KEOR HP. THREE-PHASE UPS from 100 to 800 kva GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

EMERGENCY ELECTRO- MEDICAL INDUSTRIAL PLCS DEVICES. (Lights/Alarms)

MKN-DSP SERIES - THREE PHASE

Power+ CLASSIC. 20/30 kva, 3x208 Vac

Power Safety. Protect 8. Industrial UPS. Protect 8.31 Single Phase output 10 kva 120 kva. Protect 8.33 Three Phase output 10 kva 120 kva

un I Jet ИБП ABB Conceptpower DPA 500 ( квт) - технические спецификации. Юниджет

UPS Multi Sentry 10-20kVA

PowerWAVE EL. Technical Specification. (Single phase 500 VA 30 kva. Three phase kva)

tel: Enhanced Power Services Limited Industrial PLCs Electro Medical Devices

MODULYS RM GP. Rack-mounted modular UPS system. Green Power 2.0 range up to 4 x 25 kw

MODULYS RM GP. Rack-mounted modular UPS system Green Power 2.0 range up to 4 x 25 kw

POWER+ PREMIUM CBS. BS-EN Emergency electrical installations Electric power systems Emergency lighting Escape lighting

Marketing Management Team of Europe

kVA. Liebert NX. Enterprise-Scale UPS Protection For Medium And Large Data Centers

Multi DIALOG MDM/MDT. MDM 10-20kVA single/single-phase and three/single-phase MDT 10-80kVA three/three-phase NETWORK RANGE

Technical Specification SENTINEL PRO

SUPREME kva three-phase/single-phase 10-80kVA three-phase/three-phase

Three Phase UPS Systems Range: 10 to 500kVA

DC POWER SUPPLY SYSTEMS

LanPro 11 U. Product Description. GE Digital Energy. Uninterruptible Power Supply. LanPro UPS. Technology for the Digital World.

AME. Rectifier - Battery charger. Industrial applications: Key features:

SUPREME kva three-phase/single-phase 10-80kVA three-phase/three-phase

SR series. on-line

n Lower energy costs and carbon footprint n Cooler operation extends internal component life n High input power factor of 0.99

Liebert. FP 50Z kva

Green Power 2.0 MASTERYS GP

CENTAURI ENERGY SERVER TECHNICAL DATA kw POWER

TECHNICAL SPECIFICATIONS FOR. 3/5/6/8/10 kva Single phase in/out Single or parallel UNINTERRUPTIBLE POWER SUPPLY SYSTEMS

MEGALINE UPS MODULAR SINGLE-PHASE from 1250 to VA

PowerWave 33 Efficient power protection for today s IT and process-related work environments

n Lower energy costs and carbon footprint n Cooler operation extends internal component life n High input power factor of 0.99

Master MPS kva kva 3:1 3:3 VFI TYPE

Master MPS kva kva 3:1 3:3 VFI TYPE

SmartOnline S3MX Series 3-Phase 380/400/415V 60kVA 54kW On-Line Double-Conversion UPS

MASTERYS IP+ 10 to 80 kva

Liebert Hipulse E The High-ECO-Availability UPS. AC Power Systems

INDUSTRIAL PROCESSES TELECOM- MUNICATIONS DEVICES EMERGENCY DEVICES INDUSTRIAL

MODULAR THREE-PHASE AND SINGLE-PHASE UPS SYSTEM

UPS UNINTERRUPTIBLE POWER SUPPLY GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

Transcription:

Digit al Energy T M L P Seri es Di gi ta l Energy TM LP Series Digita l Energ y T M L P Se rie s GE Consumer & Industrial Power Protection Technical Data Sheets Digital Energy Uninterruptible Power Supply LP 33 Series / 40 60 80 100 120 kva 400 Vac CE Series 1 Date of issue: 01.11.2007 LPS33_040_UPS_GE_01 LPS33_060-080_UPS_GE_01 LPS33_100-120_UPS_GE_01 GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91 / 850 51 44 www.gedigitalenergy.com GE imagination at work

GENERAL DATA Topology VFI-SS-111, double conversion Nominal output apparent power at PF=0.6...0.8 lag. kva 40 60 80 100 120 Nominal output effective power at PF=0.8 lag. kw 32 48 64 80 96 Overall efficiency at 100% load in VFI mode % 92.8 93.3 92.8 92.8 92.8 Overall efficiency at 100% load in ECO mode % 99 98.8 99 98.8 98.8 Heat dissipation at 100% load in VFI mode, PF=0.8 lag. and charged battery kw 2.48 3.45 4.97 6.21 7.45 Cooling air (25 C 30 C) m 3 /h 725 1010 1450 1815 2175 Audible noise level db(a) 64 67 67 70 70 Battery type Valve regulated lead-acid (VRLA) Operating temperature range UPS: 0 C 40 C Storage temperature range -25 C +55 C Relative humidity Max. 95% (non-condensing) Max. altitude without power derating Power derating (according to IEC 62040-3) 1000m 1500m: -5% / 2000m: -9% / 2500m: -14% / 3000m: -18% Protection degree IP 20 (IEC 60529) s EN 50091 / IEC 62040, CE marking EMC EN 50091-2 / IEC 62040-2 Class A Electrostatic discharge immunity 4kV contact / 8kV air discharge Internal protection All live parts shrouded Transport Cabinet suitable for handling by forklift Colour RAL 9003 (white) Installation Can be positioned against a wall and floor fixed Service access Front access only External cable connections Bottom Cooling Forced front to top by internal blower Paralleling (RPA version) Up to 4 units parallelable for redundancy or capacity in RPA configuration (optional) RECTIFIER Rectifier bridge Three phase - Active IGBT Rectifier input voltage Nominal: 3 x 380V / 400V / 415V + N Rectifier accepted ph-ph voltage range: 320V 460V Input frequency 50/60Hz +/-10% (45 66 Hz) Input power factor 0.98 lag. Input current THD Active IGBT Rectifier: <9% Active IGBT Rectifier - Clean Input Module: <4.5% (<3.5% @ 75% load) Output voltage tolerance +/- 1% Battery ripple current <200 ma (pk-pk) Battery charging characteristic IU (DIN 41773), T compensated floating voltage Battery charging current limit Programmable Input power data kva 40 60 80 100 120 Input power at inverter nominal load, PF=0.8 lag. and charged battery kw 34.5 51.5 69 86 103.2 Max. input power at inverter nominal load and max. battery recharge current (programmable) kw 43.1 60.1 77.6 94.6 111.8 Max. battery charging current (programmable) A 15 15 15 15 15 Modifications reserved Page 2/5

BATTERY Battery type Valve regulated lead-acid (VRLA) Number of 12V blocks, 6 cells/block 40, placed in external cabinets Float voltage at 20 C 2 x 273 VDC Min. discharge voltage (programmable) 1.65V / cell Recharge time 6 8 hours Automatic and manual battery test Common battery in parallel system Up to 4 units Battery power data kva 40 60 80 100 120 DC power at full load and PF=0.8 lag. kw 34 51 68 85.1 102.2 DC power at full typical computer load (PF=0.66 lag.) kw 28 42.1 56.2 70.2 84.3 Matching battery cabinets See optional features on page 3 INVERTER Nominal output power at PF=0.6... 0.8 lag. 40 60 80-100 - 120 kva Nominal output voltage (on site programmable) 3 x 380V / 400V / 415V + N Inverter bridge IGBT technology Output waveform Sine wave Output voltage tolerance: - static... +/- 1% - dynamic (at load step 0 100 0%)... +/- 1% - dynamic (at load step 0 50 0%)... +/- 0.5% - recovery time to +/-1%... <3 ms - output voltage THD for 100% linear load... <1% - output voltage THD for 100% non-linear load (EN 50091) <2.5% Output voltage tolerance at 100% unbalanced load (Ph-N) +/- 3% Output frequency 50/60 Hz (selectable) Output frequency tolerance: - free-running... +/- 0.1% - with mains synchronisation adjustable to... +/- 4% Phase displacement: - at 100% balanced load... 120 : +/- 1% - at 100% unbalanced load... 120 : +/- 2% Overload capability (at PF=0.8) 125% - 10 minutes, 150% - 1 minute Short-circuit characteristic Electronic short-circuit protection, current limit to 2.2 times In for 100 ms MTCB clearance capability (selectivity) 20% In within 5-10 ms (with MTCB class C) Crest factor >3:1 BYPASS Input connection Primary components Voltage limits for inverter/bypass load transfers Overload on bypass - Common input (Rectifier & Bypass) - Dual input (optional) - Static switch (SCR) on bypass - Electromechanic contactors (backfeed protection) on bypass and inverter - 2 manual switches for maintenance bypass +/- 10% (adjustable) 200% for 5 minutes 40 kva: 35 times In for 10 ms, non repetitive 60-80 kva: 45 times In for 10 ms, non repetitive INTERFACING Potential free contacts Serial channel RS232 (on Delta 9 pin connector) EPO (Emergency Power Off) Extended Customer Interface Card (optional) Note: all indicated values are typical. Variations may be found from one unit to another. - 4-28 user settable signals - Genset-On contact - 6 potential free alarm contacts - 1 auxiliary contact Modifications reserved Page 3/5

FRONT PANEL CONTROLS, SIGNALS AND ALARMS LCD SCREEN Shows the UPS data system data, events messages and UPS setting. The data is displayed on 4 rows, 20 characters each, allowing the operator to select between English, German, French, Spanish, Italian, Finnish or Polish language. CONTROL PANEL Metering Alarm Menu Electrical parameters, operating statistics and information screens. Events (alarms, messages, commands, handling, etc.) and resets general alarm / buzzer. Settings, LED-test and commands. + Scroll to following screen. - Scroll to previous screen. Enter Confirms the selected command. INDICATION LED S Alarm (red) On: No mains available. Load supply at risk due to: - Battery empty; - Overtemperature; - Overload. Warning (yellow) Blinking: Alarm not jeopardizing load supply. Operation (green) On: LOAD ON INVERTER Blinking: SERVICE REQUIRED OPTIONS BUILT-IN UPS OPTIONS: 1. Customer Interface 2. RPA kit 3. Separate mains input (one for rectifier / one for bypass) 4. Input THDI <4.5% COMMUNICATION: 1. Advanced SNMP Card 2. JUMP software suite 3. IRIS service 4. Modbus RTU Interface OPTIONS IN ADDITIONAL CABINETS: 1. Empty battery cabinets Dimensions (WxDxH): 430x725x1415 430x725x1815 600x725x1815 780x725x1815 1 2 3 4 UPS rating 40 kva 60 kva 80 kva Battery Capacity (High rate battery) BATTERY TABLE Autonomy time Cabinet Weight 22 Ah 8 minutes 360 Kg 33 Ah 12 minutes 500 Kg 33 Ah 9 minutes 520 Kg 50 Ah 12 minutes 775 Kg 66 Ah (2x33Ah) 19 minutes 960 Kg 50 Ah 10 minutes 775 Kg 66 Ah (2x33Ah) 12 minutes 960 Kg LPS33_OPT_Cabinets battery_01 100 kva 66 Ah (2x33Ah) 10 minutes 1010 Kg 120 kva 66 Ah (2x33Ah) 9 minutes 1010 Kg Modifications reserved Page 4/5

TECHNICAL DATA LP 33 Series / 40 kva LP 33 Series / 60-80 kva LP 33 Series / 100-120 kva 600mm 720mm 600mm 1415mm 1815mm 1815mm LPS33_040_UPS dimensions_01 LPS33_060-080_UPS dimensions_01 LPS33_100-120_UPS dimensions_01 UPS rating 40 kva 60 kva 80 kva 100 kva 120 kva UPS weight 220 Kg 275 Kg 300 Kg 370 Kg 375 Kg UPS floor loading 487 Kg/m 2 609 Kg/m 2 665 Kg/m 2 683 Kg/m 2 692 Kg/m 2 UPS packed in carton 235 Kg 295 Kg 320 Kg 395 Kg 400 Kg UPS packed in wooden crate 300 Kg 370 Kg 395 Kg 475 Kg 480 Kg UPS BLOCK DIAGRAM, PROTECTIONS AND CABLE SECTIONS Common input Rectifier & Bypass Separated input Rectifier & Bypass (optional) Protections for mains voltages 3x380/220V, 3x400/230V, 3x415/240V Protections and cable sections Cable sections A, B, C, D, E and K recommended by European s Alternatively, local standards to be respected kva Fuses AgL or equivalent MTCB Cable sections (mm 2 ) F1 F2 F3 F4 A / B /C D E K 40 3 x 63 A 3 x 63 A 3 x 63 A 3 x 80 A 5 x 10 4 x 10 5 x 10 4 x 16 60 3 x 100 A 3 x 100 A 3 x 100 A 3 x 125 A 4 x 25 + 16 4 x 25 4 x 25 + 16 3 x 35 + 25 80 3 x 125 A 3 x 125 A 3 x 125 A 3 x 160 A 4 x 35 + 25 4 x 35 4 x 35 + 25 3 x 50 + 25 100 3 x 160 A 3 x 160 A 3 x 160 A 3 x 200 A 4 x 50 + 25 4 x 50 4 x 50 + 25 3 x 70 + 35 120 3 x 200 A 3 x 200 A 3 x 200 A 3 x 250 A 4 x 70 + 35 4 x 70 4 x 70 + 35 3 x 120 + 70 SEV/ASE cable sections recommended in Switzerland (mm 2 ) kva A / B /C D E K 40 5 x 16 4 x 16 5 x 16 3 x 25 + 16 60 4 x 35 + 25 4 x 35 4 x 35 + 25 3 x 50 + 25 F1, F2, F3, F4, A, B, C, D, E, (K): supplied by customer 80 4 x 50 + 25 4 x 50 4 x 50 + 25 3 x 70 + 35 K: supplied by GE only with battery 100 4 x 70 + 35 4 x 70 4 x 70 + 35 3 x 95 + 50 F4: can be supplied by GE. 120 4 x 95 + 50 4 x 95 4 x 95 + 50 3 x 150 + 95 IMPORTANT NOTE! The UPS is designed for TN System. The input neutral shall be grounded at source and shall never be disconnected. 4 pole breaker shall not be used at the UPS input (see also IEC 60634, IEC 61140, IEC 61557). Modifications reserved Page 5/5