Extract-air grille with ATK plenum box

Square supply diffuser

LØV-R. Orion-Opus. Square supply diffuser

a partner to rely on

VAV controller. TROX Auranor Norge AS. Telephone Fax

Rectangular inlet air diffuser

Ceiling swirl diffusers

Apartment ventilation

Apartment ventilation

DFB - Conical Ceiling Diffuser. Halton DFB. Conical Ceiling Diffuser

Ceiling swirl diffusers

TCM - Conical Ceiling Diffuser. Halton TCM. Conical Ceiling Diffuser

Chilled beam for ceiling installation

Type VDL FOR HIGH ROOMS, WITH ADJUSTABLE AIR CONTROL BLADES. Homepage > Products > Air Diffusers > Swirl diffusers > Type VDL

DFA - Conical Ceiling Diffuser. Halton DFA. Conical Ceiling Diffuser

THB - Perforated Ceiling Diffuser. Halton THB. Perforated Ceiling Diffuser

Ceiling swirl diffusers

Ceiling diffusers. Type VDR. For large temperature differences in heating mode, high penetration of air, with adjustable air control blades

Ceiling swirl diffusers with perforated face plate

DCS - Ceiling Diffuser. Halton DCS. Ceiling Diffuser

Accessories. Balancing plenum PRI For balancing & equalising the airflow and attenuating the duct noise

Circular Silencer. Rigid and flexible construction Type CA CB CF CS. TROX GmbH Telephone +49/28 45/ Telefax +49/28 45/

VAV terminal units. Type TVM. For dual duct systems PD TVM 1

Ventilation grilles for installation into walls, sills or rectangular

Type DCS FOR HORIZONTAL SWIRLING SUPPLY AIR DISCHARGE CREATING HIGH INDUCTION LEVELS, WITH FIXED AIR CONTROL BLADES

Ventilation grilles for installation into walls, sills or rectangular

Front panel Perforated galvanised steel Stainless steel AISI 316 as option Casing Galvanised steel Stainless steel AISI 316 as option

WGA Long throw nozzle grille

TBV - Terminal Unit. Halton TBV. Terminal Unit

C O L M A N. Air Distribution LINEAR SLOT DIFFUSERS CD SERIES SERIES

PURELINE18 PARTICULARLY SLIM DIFFUSER FACE, AVAILABLE IN NUMEROUS VARIANTS FOR MANY DIFFERENT INSTALLATION SITUATIONS

CAV controllers. Type RN. For the precise control of constant volume flow rates PD RN 1

Accessories. Front vane panel Coupling sleeve with gasket Galvanised steel Gasket of rubber compound

TRB - Conical Ceiling Diffuser. Halton TRB. Conical Ceiling Diffuser

DKR - Multi-nozzle Ceiling Diffuser. Halton DKR. Multi-nozzle Ceiling Diffuser

LINEAR BAR GRILLES T SERIES. Quality and e!ciency without compromise

Slot diffusers for ceiling installation

Ventilation grilles for installation into walls, sills or rectangular

CAV controllers. Type EN. For the precise control of normal and high constant volume flows. 01/2017 DE/en PD EN 1

Ventilation grilles for installation into walls, sills or rectangular

CAV controllers. Type EN-Ex. For the precise control of normal and high constant volume flows in potentially explosive atmospheres (ATEX)

C O L M A N. Air Distribution LINEAR BAR GRILLES T SERIES SERIES

DRUM SLOT DIFFUSER TYPE: RT350

Lint separator FLARE

CAV controllers. Type VFL. Volume flow limiter for insertion into ducting K

KLIMA Active Chilled Beams

Compact Grille Model KG

Slot diffusers, Round duct diffusers. IMP Klima

SDV Vane Swirl Diffusers

DKS - Multi-nozzle Ceiling Diffuser. Halton DKS. Multi-nozzle Ceiling Diffuser

Homepage > Products > Chilled Beams and Multi Service Chilled Beams > Active Chilled Beams > SMART BEAM > Type SMART BEAM SMART BEAM

COLIBRI Ceiling QUICK FACTS. Square ceiling diffuser with discs for supply air

WDD/WSD - Grille. Halton WDD/WSD. Universal Grille

PELICANTM. Wall. Rectangular perforated wall air diffusers for supply air. Quick guide

AHF - Exhaust Grille. Halton AHF. Exhaust Grille

Ceiling swirl diffusers with perforated face plate

CONSTANTFLOW Volume Flow Controllers

GDD - Supply Grille. Halton GDD. Supply Grille

Adjustable Curved Vane Diffusers. Vanes are parallel to the width dimension Vanes are parallel to the height dimension

Linear Slot Diffusers Model Slot 20 and Model Slot 25

Circular silencers. Type CA. For the reduction of noise in circular ducts, galvanised sheet steel construction. 02/2017 DE/en PD CA 1

ceiling swirl diffuser DQJ

Halton Rex 600 RE6 - Adaptable active chilled beam

C O L M A N. Air Distribution LINEAR SLOT DIFFUSERS CE SERIES SERIES

Plenum boxes. About Lindab. Comfort and Design. Product overview / symbols. Theory. Ceiling diffusers. Ceiling diffusers - visible.

Air diffuser system Model AUDIX -AW

For installation into ductwork

THL - Conical Ceiling Diffuser. Halton THL. Conical Ceiling Diffuser

VAV Terminal Units SDS

Nozzle diffuser DYRH / Supply air unit DYRB (=DYRH+ATTD)

CAV controllers. Type RN-Ex. For the precise control of constant volume flows in potentially explosive atmospheres (ATEX) PD RN-Ex 1

Variable Air Volume Dampers

CCE - Adaptable active chilled beam for exposed installation. Halton CCE. Adaptable active chilled beam for exposed installation

Type ISH FOR INDUSTRIAL ZONES WITHOUT AIR POLLUTING PROCESSES

Type VSD35. Nominal length up to 1500 mm: one spigot

Wall air diffusers with discs for supply air and flush mounting. Quick guide COLIBRI WALL

Ventiduct nozzle ducts

Ventiduct nozzle ducts

HIGH CAPACITY LINEAR SLOT DUFFUSERS

Swegon PACIFIC. Integrated climate beam QUICK FACTS KEY FIGURES

CAV controllers Type RN

MULTIDIRECTIONAL DIFFUSERS WITH EXTRACTABLE CONES

PELICAN Ceiling HF. Square extract air diffuser QUICK FACTS

VAV terminal units. Type TVZ. For supply air systems with demanding acoustic requirements PD TVZ 1

C O L M A N. Air Distribution JET DIFFUSERS DCJ SERIES DCJ SERIES

LINEAR SLOT DIFFUSERS

CornerAir. CornerAir. Active chilled beam

VAV terminal units. Type TVA. For extract air systems with demanding acoustic requi rements K

CAV controllers. Type VFL. Volume flow limiter for insertion into ducting PD VFL 1

C O L M A N. Air Distribution SWIRL DIFFUSERS DWT SERIES DWT SERIES

AIRODYNE CATALOGUE VOLUME CONTROL TAMPERS CONSTRUCTION / MATERIALS

FALCON Ceiling. Circular ceiling air diffuser for supply air QUICK FACTS

DAC - Conical Diffuser. Halton DAC. Conical diffuser

Swegon PACIFIC. Integrated climate beam

DCV-CF DCV-CF. DCV-CF Pressure control with airflow measuring CFL Version B03. Pressure controlwith airflow measuring. Product description

C O L M A N. Air Distribution PERFORATED FACE DIFFUSERS P SERIES SERIES

Long Throw Nozzle WDA

ACCESSORIES FOR DUCT FANS

Circular silencers. Type CS. For the reduction of noise in circular ducts, aluminium construction PD CS 1. 02/2017 DE/en

Regulation and shut-off damper SPB and SPC

Transcription:

Quick Selection Catalogue Version 6.1 1

WHAT DO YOU USE THE QUICK SELECTION CATALOGUE TO? The quick selection catalogue is designed to provide opportunity to quick and easy find the appropriate products for a given case. Once you have found an actual product and dimension, you may find additional details for engineering in the product's own data sheet. All the data sheets is available at www.trox.no. There are also separate dimensioning programs for chilled beams and sound attenuators. WHAT DOES THE TABLES IN THE QUICK SELEC- TION CATALOGUE SAY? Quick selection tables indicate maximum airflow that the productscan handle under normal conditions and requirements.for each dimension is given the airflowsinvolving specified sound power levels. where the productshave an damper installed the airflows is given at 30 or50 Pa total pressure loss over the device. When it comes to valves, it is important to note thatthe sound pressure level in the room normally is lower than indicatedsound power level. Previously, it was customary to state sound pressure levelsat the valve placed in a room with 4 db attenuationin all frequencies. db(a)- value in such a room is 4 dblower than the sound power level. To estimate resultantsound pressure level in various room types and with different numbers, the program "Aurakustikk" can be used. 2

Contents Main group Product Page Exhaust valves USI 4 Inter 5 LØV-A 6-7 KSO 8 LVS 9 ESNU 10 UPK 11-15 Orion-ATV 16-18 RIA-SA 19 Grilles and transfer units RIA 20 OVA 21 LOV 22 VSR 23 TOG-R 24 Supply air diffusers and plenum boxes Pegasus Comfort 25-27 Opus-4/5 28 Pegasus 29-31 Orion LØV with Sirius Comfort 32-33 Orion Opus with Sirius Comfort 34-35 Orion PTV with Sirius Comfort 36-37 TLH 38 LØV-R 39-40 TLG/LØV 41-42 Tellus-LØV 43 Tellus-Opus 44 Tellus-LØV VAV 45-46 Tellus-Opus VAV 47-48 TLK 49-50 TUB 51 TIH and TIR 52-53 DKW 54 RFD 55-56 Orion-LØV 57-58 Orion-Opus 59-60 Orion-PTV 61-62 JBV 63-64 Orion-LØV-Sirius 65-66 Orion-Opus-Sirius 67-68 Orion-PTV-Sirius 69-70 Siv-inn comfort and industry Siv-inn 1 71 Siv-inn 2000 72 Siv-inn Inlaid 73 Siv-inn school 74 Siv-inn 2 75-76 Siv-inn T/V 77 Siv-inn PP and PK 78 Siv-inn Aula 79-80 Dampers and VAV DRS/DRS-T 81-82 EPS 83 Rego-T 84 Iris 85 Leo 86-88 TSK 89 Sound attenuators LEV 90 LKR 91 LKK 92 LKL 93 Access doors and duct systems ILP and ILS 94 KSA 95 Chilled beams Svalbard-H 96-97 Svalbard-I 98-100 Svalbard-F 101-102 DID-614 103-104 Automation VIP-X 105 EasyLink 106 3

USI The USI extract air terminal is intended for open installation. It is suitable for high air flow rates, and can thus be used as a central extraction unit in large rooms ideal in combination with VAV. The valve is available with and without integrated sound attenuator. DIMENSIONS AND WEIGHT, USI Dim. D A Weight[kg]¹ Weight[kg]² 200 199 320 4,0 11,7 250 249 365 4,4 13,0 315 314 435 5,4 15,7 400 398 528 6,8 19,5 500 498 620 8,5 25,5 Table 2: 1 without sound attenuator, 2 with sound attenuator The device is made of galvanised steel, and comes in RAL 9003 - gloss 30. Other colours are available on request. QUICK SELECTION USI [m³/h] Dim 25dB(A) 30dB(A) 35dB(A) 200 396 490 605 250 662 796 954 315 896 1087 1318 400 1786 2124 2525 500 2228 2804 3528 Table 1: The table shows air flow rates at given sound power levels. ORDER CODE, USI USI - 315 / L / 0-0 Fig. 1 Dimension: Ø200 - Ø500 L = Design with sound attenuation SL = Special finish SM = Special material USI-315 / L / 0-0 USI dim. Ø315, with sound attenuation 4

Inter Inter is used to simplify the installation of valves in lightweight ceilings (mineral wool). Inter is produced in galvanised steel. INSTALLATION Cut a groove in the ceiling plate (1) D1 + 5 mm, using the end-piece of the Inter as a template. Install the Inter (2) in the ceiling plate (1) by using 3 self-drilling screws inside the Inter to attach the mounting frame for the valve (3). Then fit the valve in the mounting frame. Finally, install the assembled ceiling plate in a modular ceiling system. Use of connection nipple (4) or bend between Inter and Spiro duct (5) is recommended. ORDER CODE, Inter Inter - 160 Product Dimension Ø100 - Ø200 Inter-160 Inter dimension Ø160. DIMENSIONS AND WEIGHT, INTER Dim. D1 H1 H2 Weight [kg] 100 100 12 100 0,30 125 125 12 100 0,35 160 160 12 100 0,45 200 200 12 100 0,60 Table 1. Fig. 2 MAINTENANCE No specific maintenance requirements ENVIRONMENT Enquiries regarding product declaration can be directed to our sales team, or information can be found at our website: www.trox.no Fig. 1 5

LØV-A LØV-A is a circular exhaust valve for ceiling mounting. It is suitable for installation in fixed ceilings. LØV-A features a removable front panel with perforation. Both the valve front and the ceiling plate are in a steel design. The valve body is in aluminium and is fitted with an EPDM rubber gasket at the connection collar. All internal and external valve elements are in a RAL 9003 - gloss 30 finish. Other colours are available on request. LØV-A QUICK SELECTION [m³/h] Dim. 25 db(a) 30 db(a) 35 db(a) 40 db(a) 125 184 230 288 360 160 259 328 425 540 200 475 594 738 918 250 720 882 1080 1296 315 828 1026 1242 1620 Table 1: The table shows air flow rates at given sound power levels. ORDER CODE, LØV-A (LOEV-A) DIMENSIONS AND WEIGHT, LØV-A Cut-out dimensions: ØG+5 Dim. A B C G E F I Weight valve [kg] 125 322 124 230 282 65 115 75 0,9 160 420 159 320 380 70 120 80 1,5 200 460 199 350 420 70 120 80 1,9 250 570 249 470 530 70 120 80 2,7 315 570 314 470 530 70 120 80 2,7 Table 2 G C B A = Standard exhaust pattern LØV-A-160-0 SL = Special finish F E 11 A LOEV-A-160-0 Explantation: LOEV-A, dimension Ø160 Dimension: Ø100 Ø315 Fig. 1 ORDER CODE, Luna Luna-0-0-125-160 UI = Outlet installed, low profile design I = Insulated Dimension outlet: Ø100 Ø315 (Diffuser connection) Dimension inlet: Ø100 Ø315 (Duct connection) Luna-0-0-125-160 Explantation: Luna plenum box with duct connection dim. Ø125 and diffuser connection dim. Ø160 6

LØV-A with Luna plenum box The Luna plenum box is recommended for improved sound attenuation, and works as an adjustment and measurement unit. Luna is a rectangular box with a removable damper providing access to the connecting duct. The damper can be secured in any position required. Luna plenum box features a damper and measuring outlet for commissioning. The box is lined with sound absorber in polyester, and is available in the same dimension or one scale up between inlet and outlet (see table 4). Can be supplied with external condensation insulation. A low-profile version [UI] is also available, and for this design a reduction in capacity of approx. 20% will apply. The distance between valve and box can be increased by up to 35 cm without extending the wire and measuring tube. Luna is supplied in a galvanised finish, and with all four internal walls lined with sound absorber in polyester. The connection collar is fitted with EPDM rubber gasket. DIMENSIONS AND WEIGHT, Luna Dim. D DA B H H1 H2 L L1 L2 Weight Luna [kg] 100-125 99 127 220 122 260 138 325 295 133 2,3 125-125 124 127 250 147 285 138 360 335 150 2,4 125-160 124 162 250 147 290 143 360 335 150 2,9 160-160 159 162 340 182 325 143 400 390 170 4,1 160-200 159 202 340 182 325 143 400 390 170 4,2 200-200 199 202 380 222 365 143 452 460 198 5,7 200-250 199 252 380 222 365 143 452 460 198 5,7 250-250 249 252 390 272 415 143 515 535 228 7,4 250-315 249 317 390 272 415 143 515 535 228 7,4 315-315 314 317 500 337 480 143 600 655 255 11 Table 4 QUICK SELECTION LØV-A Luna [m³/h] Dim. Dim. 25 db(a) 30 db(a) 35 db(a) 40 db(a) 125 100-125 65 115 187-125-125 112 162 216-160 125-160 90 144 234-160-160 187 259 353-200 160-200 173 241 346 500 200-200 299 418 540-250 200-250 234 342 475-250-250 407 522 688 871 315 250-315 425 558 713 936 315-315 684 871 1076 - Table 3: The table shows air flow rates at given sound power levels and 50 Pa total pressure loss. Fig. 2 ORDER CODE, LØV-A (LOEV-A) with Luna LØV-A-L-0 A = Standard exhaust pattern SL = Special finish L = Luna UI = Outlet installed, low profile design I = Insulated L-0-0-125-160 Dimension outlet: Ø100 Ø315 (Diffuser connection) Dimension inlet: Ø100 Ø315 (Duct connection) LOEV-A-L-0-0-125-160-0 Explantation: LOEV-A exhaust diffuser and Luna plenum box duct connection dim. Ø125 and outlet/diffuser connection dim. Ø160. 7

KSO KSO is an extract air terminal device for ceiling or wall mounting. KSO features an adjustable centre cone for air flow rate commissioning. Supplied with mounting frame, KKT, for circular duct.. DIMENSIONS AND WEIGHT, KSO Dim. D A weight [kg] 100 134 74 0,3 125 160 85 0,4 160 191 89 0,5 200 241 107 0,7 Table 2 KSO is made of steel, and comes in a RAL 9003 - gloss 30 finish. Other colours are available on request. KKT is fitted with a rubber gasket on the connection collar. Cone position QUICK SELECTION KSO Cone position - s [m³/h] Dim. [mm] 30 db(a) 35 db(a) 40 (db) 100 +5 90 110 135 125 +5 135 165 195 160 +5 185 220 260 200 +15 200 250 275 Table 1: The table shows air flow rates at given sound power levels. Product ORDER CODE, KSO KSO - 160 Dimension Ø100 Ø200 KKT KSO-160 / KKT KSO, dimension Ø160, with KKT mounting frame / KKT = Mounting frame Fig. 1 DIMENSIONS AND WEIGHT, KKT Dim. d D 2 Weight [kg] 100 99 125 0,10 125 124 150 0,12 160 159 185 0,18 200 199 225 0,24 Table 3 Fig. 2 8

LVS LVS is an extract air terminal device for ceiling or wall mounting. LVS features an adjustable centre cone for air flow rate commissioning. Supplied with mounting frame, KKT, for circular duct.. DIMENSIONS AND WEIGHT, LVS Dim. B C D Weight [kg] 100 40 99 132 0,2 125 46 124 162 0,3 160 54 159 205 0,4 200 61 199 245 0,6 Table 2 LVS is made of steel, and comes in a RAL 9003 - gloss 30 finish. Other colours are available on request. KKT is fitted with a rubber gasket on the connection collar. QUICK SELECTION LVS Cone position - s [m³/h] Dim. [mm] 30 db(a) 35 db(a) 40 db(a) 100-5 60 70 80 125-6 90 110 140 160-5 140 170 200 200-10 160 190 240 Table 1. The table shows air flow rates at given sound power levels. Fig. 2 Product ORDER CODE, LVS LVS - 125 Dimension Ø100 Ø200 KKT LVS-125 / KKT LVS, dimension Ø125, with KKT mounting frame. / KKT = Mounting frame DIMENSIONS AND WEIGHT, KKT Dim. d D 2 Weight [kg] 100 99 125 0,10 125 124 150 0,12 160 159 185 0,18 200 199 225 0,24 Table 3 Fig. 1 Fig. 3 9

ESNU ESNU is a circular mesh grille, and can be used as both a supply and extract air unit. ESNU is available in two different designs - with or without decorative flange. ESNU is made of galvanised steel, and units with decorative flange come in a RAL 9003 - gloss 30 finish as standard. Both designs are fitted with rubber gasket. ESNU without flange is available in dim. Ø100 to Ø1000. ESNU with flange is available in dim. Ø100 to Ø630. ORDER CODE, ESNU DIMENSIONS AND WEIGHT, ESNU ESNU Decorative Weight [kg] flange A- Without With Dim. D1 D2 D3 weighting flange flange 100 99 105 180 60 0,05 0,20 125 124 132 205 60 0,08 0,23 160 159 167 243 60 0,20 0,38 200 199 207 282 60 0,25 0,47 250 250 258 315 74 0,30 0,56 315 314 325 420 74 0,45 0,77 400 399 410 530 77 0,70 1,10 500 498 510 630 85 0,90 1,40 630 628 640 760 85 1,40 2,00 800 798 810-75 1,60-1000 998 1010-75 2,00 - Table 1 ESNU - 160 / P / 0 Product Dimension: Ø100 - Ø1000 UL = Flange, galvanised steel finish SL = Flange, special finish. P = ESNU with flange (Dim. Ø100 to Ø630 only) ESNU-160 / P / 0 ESNU, dim. Ø160, with decorative flange, white RAL 9003 - gloss 30 finish Fig. 1 INSTALLATION Can be installed directly in Spiro duct. MAINTENANCE Can be cleaned with a damp cloth or vacuum cleaner as required. ENVIRONMENT Enquiries regarding product declaration can be directed to our sales team, or information can be found at our website: www.trox.no om.no 10

UPK (BxH) APPLIcATION UPK is an air-extract grille for wall mounting. It is available in bespoke dimensions and can thus be adapted to fit various groove dimensions or pre-installed boxes. The UPK features square perforation. It is available with pre-drilled holes and enamelled screws. Grilles exceeding 2 m² are split.e. INSTALLATION Installation principle is shown in fig. 2. MATERIALS AND SURFAcE coating The grill is made in steel, and comes in a RAL 9010 finish. It is fitted with polyurethane moulding. Other materials and colours are available on request. QUIcK SELEcTION In terms of projected WxH for the UPK, duct velocity should not exceed 3 m/s. This is to avoid any noise issues. ORDER code, UPK Product B = Width from and incl. 100, max. 2000 (1000) H = Height from and incl. 100, max. 1000 (2000) (Max. area in total: 2 m² per grille UPK - 800-900 / 0 SL = Special finish Fig. 2: Installation commissioning A separate measurement and adjustment unit for commissioning is recommended. UPK-800-900 / 0 UPK, width: 800 and height: 900 MAINTENANcE The valve can be cleaned by using a damp cloth. DIMENSIONS AND WEIGHT, UPK ENVIRONMENT Enquiries regarding product declaration can be directed to our sales team, or information can be found at our website: www.trox.no Fig. 1 11

UPK grille UPK-R is a rectangular extract-air grille for integrated wall or ceiling installation. UPK-H is suitable for T-profile ceiling systems, 600 x 600. The UPK-R grille features square perforation and a fitted frame for ATK box mounting. UPK-R panel and frame are made of steel, and are delivered in a RAL 9003 - gloss 30 finish. Panel in other materials and/or colours are available on request. QUICK SELECTION UPK-R [m³/h] B x H 30dB(A) 35dB(A) 40dB(A) 200-100 200 245 300 300-100 315 390 455 400-100 395 470 575 500-100 460 575 685 300-150 450 560 675 400-150 520 655 800 500-150 700 885 1060 400-200 790 970 1190 500-200 965 1160 1420 600-200 1090 1315 1620 500-300 1270 1600 1945 600-300 1440 1800 2160 Table 1: The table provides air flow rates at given sound power levels. DIMENSIONS AND WEIGHT, UPK-R UPK-R W x H Weight [kg] 200x100 0,50 300x100 0,55 400x100 0,60 500x100 0,65 300x150 0,70 400x150 0,75 500x150 0,95 400x200 1,00 500x200 1,15 600x200 1,20 500x300 1,50 600x300 1,65 Table 2 Fig. 2, UPK-H B + 35 B H + 35 H + 1 50 10 ORDER CODE, UPK-R UPK-R - 400-200 / 0-0 Fig 3, UPK-R ORDER CODE, UPK-H UPK-H / 0-0 Product B = Width H = Height SL = Special finish SM = Special material Product SL = Special finish SM = Special material UPK-R-400-200 / 0-0 UPK-R extract-air grille. 400 width and 200 hight UPK-H / 0-0 UPK-H extract-air grille for T-profile ceiling system, 600x600. 12 ORDER CODE, ATK Product Connection outlet: B = Rear-entry spigot S = Rear-entry spigot LS = Long-side spigot entry: ATK - S - 250-500 - 150 / 0 SM = Special dimensions Grille attachment dimensions: H = Height B = Width Dimension outlet: Ø125 Ø315 ATK-S-250-500-150/0 ATK extraction box with side-entry spigot and Ø250 outlet, 500 width and 150 height for grille attachment. 3 ORDER CODE, ATK-H Product Anslutning utløp: B = Bakanslutning S = Sideanslutning ATK-H - S - 160 Dimensjon utløp: Ø 160 - Ø400 Eksempel: ATK-H-S-160 Forklaring: ATK-H avtrekkskammer for profilhimling 600x600 med sideanslutning Ø160.

UPK grille with ATK box The ATK plenum box is used for improved sound attenuation and commissioning options. This rectangular box is fitted with a removable damper which provides access to the connecting duct. The ATK box features a damper for commissioning. ATK-B, S and LS are equipped with measuring point. The box is insulated with sound absorber in polyester. The ATK box is made in galvanised steel, and is lined with sound absorber in polyester inside. Its connection collar is fitted with an EPDM rubber gasket. ORDER CODE, UPK-R with ATK box UPK-R - 500-150 - K / 0-0 B = Width grille H = Height grille K - S - 250 Produkt: K = ATK box Connection collar: B = Rear-entry spigot S = Side-entry spigot LS = Long-side spigot entry SL = Special finish SM = Special material Dimension outlet: Ø125 - Ø315 UPK-R-500-150-K-S-250/0-0 UPK-R extrac-air grille with frame, 500 widt and 150 height, equipped with ATK box with side-entry spigot dim. Ø250, UPK grille in standard white RAL 9003 - gloss 30 Product ORDER CODE, UPK-H with ATK box K = ATK-H box Connection collar: B = Rear-entry spigot S = Side-entry spigot UPK-H - K / 0-0 K - S - 315 QUICK SELECTION, UPK-H SL = Special finish SM = Special material Dimension outlet: Ø160 - Ø400 UPK-H-K-S-315/0-0 UPK-H extrac-air grille for profile ceiling 600x600, equipped with ATK box with side-entry spigot dim. Ø315, UPK grille in standard white RAL 9003 - gloss 30 finish ATK-H box UPK-H m³/h Dim. Spigot ent. Dim. 25 db(a) 30 db(a) 35 db(a) 160 B 600 x 600 133 169 238 160 S 600 x 600 126 234 353 200 B 600 x 600 209 299 418 200 S 600 x 600 201 324 436 250 B 600 x 600 338 504 648 250 S 600 x 600 346 594 756 315 B 600 x 600 475 774 1415 315 S 600 x 600 810 947 1098 400* B 600 x 600 2430 2970 3618 400* S 600 x 600 2088 2412 2808 Table 3: The table provides air flow rates at given sound power levels and 50 Pa total pressure loss. * = Ø400 is without damper. 4 QUICK SELECTION ATK box UPK-R m³/h Dim. Spigot entl. B x H 25 db(a) 30 db(a) 35 db(a) 125 B 200x100 68 119 180 125 S 200x100 86 133 184 125 LS 200x100 68 119 184 160 B 300x100-126 256 160 S 300x100 126 187 263 160 LS 300x100 130 212 281 160 B 400x100 137 198 295 160 S 400x100 126 205 295 160 LS 400x100 133 202 320 200 B 500x100 252 360 454 200 S 500x100 216 284 392 200 LS 500x100-270 396 200 B 300x150 220 324 432 200 S 300x150 216 317 421 200 LS 300x150 191 306 436 250 B 400x150-414 533 250 S 400x150-436 580 250 LS 400x150 360 493 587 250 B 500x150-468 684 250 S 500x150-436 648 250 LS 500x150-446 655 250 B 400x200-529 738 250 S 400x200 324 450 648 250 LS 400x200 335 446 601 315 B 500x200 468 828 1098 315 S 500x200 461 720 918 315 LS 500x200 454 713 918 315 B 600x200 720 1098 1368 315 S 600x200 720 972 1260 315 LS 600x200 720 900 1260 315 B 500x300 648 900 1098 315 S 500x300-774 1116 315 LS 500x300 468 774 1116 315 B 600x300 846 972 1152 315 S 600x300 648 900 1224 315 LS 600x300 612 774 936 Table 4: The table provides air flow rates at given sound power levels and 50 Pa total pressure loss. 13

UPK grille with ATK box DIMENSIONS AND WEIGHT - ATK, S AND LS ATK Dim. BFxHF D A Weight[kg] 125 200x100 124 180 2,8 160 300x100 159 215 4,3 160 400x100 159 215 5,3 200 500x100 199 305 8,5 200 300x150 199 305 6,5 250 400x150 249 355 9 250 500x150 249 355 10,4 250 400x200 249 355 9,5 315 500x200 314 415 12,7 315 600x200 314 415 14 315 500x300 314 415 12,8 315 600x300 314 415 13,7 Table 5 Fig. 5, ATK-S Fig. 4, ATK-B Fig. 6, ATK-LS 14

UPK-H with ATK box DIMENSIONS AND WEIGHT ATK-H-S/B ATK-H-S/B Dim. D H Weight[kg] 160 159 245 7,8 200 199 285 8,2 250 249 335 8,9 315 314 400 10,1 400 399 485 11,2 Table 6 Fig. 7, ATK-H-S Fig. 8, ATK-H-B 15

Orion-ATV-T Orion-ATV is a square extract air terminal device for installation in modular ceiling systems. Orion-ATV features a removable front panel with square perforation as standard. Circular pattern can be provided on request. The unit is supplied with top-entry spigot as standard, but is also available with side-entry spigot. Furthermore, the unit is equipped with a TA flange suitable for T-profile ceiling systems, but is also available with alternative flange designs, type: DC, DG, DS and EK (see fig. 3 and under order code). DIMENSIONS AND WEIGHT, Orion-ATV Orion-ATV D Weight valve Dim. [kg] 125 124 3,9 160 159 3,9 200 199 3,9 250 249 3,9 315 314 3,9 400 399 3,9 Table 2 The front panel, ceiling plate and valve body are in a steel design, and the connection collar is fitted with an EPDM rubber gasket. Corner connection points are in plastic, and are fitted with holding magnets. All internal and external valve elements are in a RAL 9003 - gloss 30 finish. Other colours are available on request. QUICK SELECTION [m³/h] Orion-ATV 25 db(a) 30 db(a) 35 db(a) Dim. 125 187 234 299 160 306 392 500 200 504 612 742 250 680 882 1134 315 1080 1285 1526 400 1188 1404 1660 Table 1: The table shows air flow rates at given sound power levels. Fig.1. Orion-ATV with top-entry (T) ORDER CODE, Orion-ATV Orion-ATV - K - TA - T - 160 / 0 SL = Special finish Front-panel pattern: K = Square, standard S = Circular, custom For ceiling types: Dimension: Ø160 - Ø400 TA = A-flange DC = Dampa Clip-In DG = Dg-flange Spigot: : DS = Ds-flange T = Top, standard EK24 = E-flange-T24 EK15 = E-flange-T15 Orion-ATV-K-TA-T-160/0 Orion-ATV extract air terminal device with square front pattern, TA flange for inst. in T-profile ceiling. Standard top-entry spigot, dim. Ø160. ORDER CODE, Luna Luna-0-0-125-160 Fig.2. Orion-ATV with side-entry (S) UI = Outlet installed, low profile I = Insulated Dim. outlet: Ø125 - Ø400 Dim. inlet: Ø125 - Ø315 A-flange Dampa Clip-In Dg-flange DS-flange E-flange 16 Luna-0-0125-160 Luna with inlet Ø125 and outlet Ø160. Fig. 3: Ceiling types T24,T15

Orion-ATV with Luna plenum box The Luna plenum box is recommended for improved sound attenuation, and works as an adjustment and measurement unit. Luna is a rectangular box fitted with a removable damper which provides access to the connecting duct. The damper can be secured in any position required. Luna plenum box features a damper and measuring outlet for commissioning. It is insulated with sound absorber in polyester and is available with one or two dimensional changes between inlet and outlet. Furthermore, the box can be delivered with external condensation insulation. A lowprofile design [UI] is also available, and for this type a reduction in capacity of approx. 20% will apply. The distance between valve and box can be increased by up to 35 cm without extending the wire and measuring tube. Luna is supplied in a galvanised finish, and with all four internal walls lined with sound absorber in polyester. The connection collar is fitted with an EPDM rubber gasket. DIMENSIONS S AND WEIGHT, Luna Dim. D DA B H H1 L L1 L2 Weight Luna [kg] 125-125 124 127 250 147 253 360 335 150 2,4 125-160 124 162 250 147 253 360 335 150 2,9 160-160 159 162 340 182 288 400 390 170 4,1 160-200 159 202 340 182 288 400 390 170 4,2 200-200 199 202 380 222 328 452 460 198 5,7 200-250 199 252 380 222 328 452 460 198 5,7 250-250 249 252 390 272 378 515 535 228 7,4 250-315 249 317 390 272 378 515 535 228 7,4 315-315 314 317 500 337 443 600 655 255 10,7 315-400 314 402 500 337 443 600 645 265 10,7 Table 4 QUICK SELECTION Orion-ATV Luna [m³/h] Dim. Dim. 25 db(a) 30 db(a) 35 db(a) 125 125-125 90 144-160 125-160 79 155-160-160 137 238-200 160-200 162 238 338 200-200 263 346 461 250 200-250 263 367 504 250-250 367 475-315 250-315 310 446 626 315-315 594 842-400 315-400 630 828 1152 Table 3: The table provides air flow rates at given sound power levels and 30 Pa total pressure loss.. Fig. 4 ORDER CODE, Orion-ATV with Luna Orion-ATV - K - TA - T - L / 0 SL = Special finish, valve. Front-panel pattern: K = Square, standard S = Circular, custom For ceiling system: TA = A-flange DC = Dampa Clip-In DG = Dg-flange DS = Ds-flange EK24 = E-flange-T24 EK15 = E-flange-T15 Spigot: T = Topp, standard L - 0-0 - 125-160 S = Side, spesial Produkt: L = Luna UI = Outlet insatalled, low profile I = Insulated Dim. outlet: Ø125 - Ø400 Dim. inlet: Ø125 - Ø315 Orion-ATV-K-TA-T-L-0-0-125-160/0 Orion-ATV extract air terminal device with square front pattern, TA flange for T-profile ceiling. Top-entry spigot as standard. Luna plenum box with inlet dim. Ø125 and outlet/valve dim. Ø160 Valve in standard RAL 9003 - gloss 30 finish. 17

Orion-ATV-S Orion-ATV-S is a square extract air terminal device for installation in modular ceiling systems. Orion-ATV features a removable front panel with square perforation as standard. Circular pattern can be provided on request. The unit is supplied with side-entry spigot. Furthermore, the unit is equipped with a TA flange suitable for T-profile ceiling systems, but is also available with alternative flange designs, type: DC, DG, DS and E K (see fig. 6 or 7 and under order code). DIMENSIONS AND WEIGHT Orion-ATV-S Orion-ATV-S Weight valve [kg] Dim. D 160 159 9,3 200 199 10,0 250 249 10,8 315 314 12,4 400 399 13,0 Table 6 The front panel, ceiling plate and valve body are in a steel design, and the connection collar is fitted with an EPDM rubber gasket. Corner connection points are in plastic, and are fitted with holding magnets. All internal and external valve elements are in a RAL 9003 - gloss 30 finish. Other colours are available on request. QUICK SELECTION ATV-S [m³/h] Orion-ATV-S 25 db(a) 30 db(a) 35 db(a) Dim. 160 281 337 405 200 406 494 602 250 598 725 879 315 943 1148 1398 400* 1245 1543 1911 Table 5, The table provides the air flow rates with damper open. (*400 without damper) Fig. 4, Orion-ATV with side entry spigot (Ø160-315) w/damper ORDER CODE, Orion-ATV-S Orion-ATV - K - TA - S - 160 / 0 SL = Special finish Front-panel pattern: K = Square, standard S = Circular, custom For ceiling types: Dimension: Ø160 - Ø400 TA = A-flange DC = Dampa Clip-In DG = Dg-flange Spigot: : DS = Ds-flange S = Side, Ø400 without damper EK24 = E-flange-T24 EK15 = E-flange-T15 Orion-ATV-K-TA-S-160/0 Orion-ATV-S extract air terminal device with square front pattern, TA flange for inst. in T-profile ceiling. Standard top-entry spigot, dim. Ø160. Fig. 5, Orion-ATV with side entry spigot (S) Ø400 without damper. A-kant Dampa Clip-In Dg-kant Ds-kant E-kant T24/T15 18 Fig. 6, Ceiling types

RIA-SA RIA-SA is an extract-air louvre ideal for high air flow rates. RIA-SA is made from extruded aluminium profiles. DIMENSIONS AND WEIGHT, RIA-SA Weight: approx. 15 kg/m². Minimum dimension: 200 x 200 Maximum dimension, not split: 2000 x 2000 80 6 RIA-SA is made from extruded, seawater resistant aluminium profiles (EN- AW-6060-T66 / EN-AW-6063-T6), and comes in an RAL 9003 - gloss 30 finish as standard. The unit can also be delivered in anodized brown, black or natural. Alternative materials or enamel finish are available on request. H-4 ORDER CODE, RIA-SA Product B = Width H = Height RIA-SA - 600-800 / 0 RIA-SA-600-800 / 0 RIA-SA extract-air louvre. Width 600 and height 800. E = Anodized SL = Special finish Fig.1 B-4 INSTALLATION RIA-SA is designed for wall mounting. Upside down installation of the louvre is recommended to avoid see-through issues. 35 CALCULATION DIAGRAMS MAINTENANCE Unit can be cleaned with a damp cloth. 60 55 50 45 40 Free area = gross area x factor ENVIRONMENT Enquiries regarding product declaration can be directed to our sales team, or information can be found at our website: www.trox.no 35 200 600 1000 1400 1800 Height [mm] Diagram 1- RIA-SA 19

RIA RIA is an intake and exhaust louvre for external installation. B-4 85 RIA-1 is made from extruded aluminium profiles, and is equipped with animal-proof netting. The RIA-2 design is identical to RIA-1, but without a flange. RIA-3 is made of aluminium, and has insulated blades and animal-proof netting. Wall-mounting frame with anchor is available for RIA-1. H-4 RIA-1 and RIA-2 are made from extruded profiles in seawater resistant aluminium (EN-AW-6060-T66 / EN-AW-6063-T6). Delivered untreated as standard. Can also be delivered in anodized brown, black or natural. The louvres can also be supplied in painted finish. Other materials available on request. RIA-3 is made of seawater resistant aluminium (EN-AW-5052-H34), and is insulated with mineral wool with a glass fibre layer. Painted finish or alternative material available on request. Separate wall-mounting frame comes in an aluminium or galvanized steel design, and is equipped with anchor. Fig. 2, RIA-2 300 7 Product ORDER CODE, RIA 1 = Standard frame profile 2 = For embedded installation 3 = Sound absorbing design B = Witdh RIA - 1-500 - 800 / 0-0 - 0 / 0 E = Anodized L = Painted finish G = Equipped with KSA guide slip M = Wall-mounting frame VK = Heating cable H = Height H-4 RIA-1-500-800 / 0-0-0/ 0 RIA-1 standard frame profile, 500 width, 800 height. B-4 35 DIMENSIONS AND WEIGHT, RIA Specified size = order dimensions (B x H). Products are supplied undersized for installation at duct end and/or in groove as illustrated in figures: B and H. Weight: RIA-1 and 2, approx. 15kg/m² without wall-mounting frame and 20 kg/m² with wall-mounting frame. RIA-3 approx. 45 kg/m2. Max dim. RIA-1, RIA-2 and RIA-3, not split: 2000 x 2000 mm. Fig. 3, RIA-3 Min. hight RIA3: 380mm 84 H+50 B/H-4 B+50 105 Fig. 1, RIA-1 Fig. 4: Wall-mounting frame for RIA-1 20 2

OVA OVA is designed for use as a transfer and extract air unit. The grille is non see-through, and does not require an accurately dimensioned groove. OVA consist of a frame and fixed blades. Pre-drilled mounting holes are provided in the frame. The grille is made in extruded aluminium, and comes in a RAL 9003 - gloss 30 finish. Alternative colours are available on request. QUICK SELECTION OVA [m³/h] Dim. 10 Pa 15 Pa 20 Pa 200-100 58 72 83 300-100 112 137 155 300-150 184 223 263 300-200 252 306 360 400-100 144 176 205 400-150 223 270 317 400-200 288 353 403 500-150 245 299 349 500-200 360 443 504 500-250 461 547 648 500-300 540 666 792 600-200 414 511 594 600-300 666 810 954 600-400 882 1062 1224 DIMENSIONS AND WEIGHT, OVA Description BxH Weight [Nom. dim.] [mm] [kg] 200x100 202x100 0,3 300x100 304x100 0,4 300x150 304x144 0,5 300x200 304x202 0,6 400x100 400x100 0,5 400x150 400x144 0,6 400x200 400x202 0,8 500x150 500x144 0,8 500x200 500x202 1,0 500x250 500x246 1,1 500x300 500x304 1,3 600x200 600x202 1,1 600x300 600x304 1,6 600x400 600x392 1,9 600x500 600x500 2,3 600x600 600x600 2,7 Table 2 Table 1: The table shows flow rates at given pressure loss. ORDER CODE, OVA OVA - 300-200 / 0 Product B = Width from and incl. 100, max. 600 H = Height from and incl. 100, max. 600 OVA-300-200 / 0 OVA - Width: 300, Height: 200 SL = Special finish Figur 1 21

LOV LOV is a sound attenuated transfer unit with telescopic feed through for wall mounting LOV is made up of front panels in painted finish and a telescopic feed-through with sound mufflers for wall mounting. The system offers infinitely variable adjustment for wall thickness adaptation. DIMENSIONS AND WEIGHT, LOV Type A B T Groove Weight [kg] 612 25 582 85-135 550 x 110 4,8 613 35 582 85-135 550 x 110 5,1 812 25 782 85-135 750 x 110 6,1 813 35 782 85-135 750 x 110 6,3 Table 2 LOV s front panels are made in steel, and come in a RAL 9003 - gloss 30 finish. Other colours are available on request. The telescopic frame is in galvanised steel and the sound mufflers are isolated with sound absorber in polyester. QUICK SELECTION Sound level LOV [m³/h] difference Type 10Pa 15Pa 20Pa Dn,e,w 612 79 97 108 36 613 97 119 137 36 812 100 122 141 35 813 119 148 169 34 Table 1: The table shows air flow rates at L WA <30dB(A). Fig. 1 ORDER CODE, LOV LOV - 613 / LT / 0-0 Product SL = Special finish Type : SM = Special material 612, 613, 812 or 813 LT = Light-proof design LOV-613 / LT / 0-0 LOV type 613, light-proof design 22

VSR VSR is designed for use as an air inlet unit in areas exposed to adverse weather conditions. Can be installed in external wall or roof unit. DIMENSIONS AND WEIGHT, VSR Recommended dimensions: from 600 x 600 to 2000 x 2000. Module 50 mm. Millimetre adjustment on request. Weight: approx. 30 kg/m 2. VSR is equipped with vertical blades. The drainage chamber features external drainage, but is available with internal drainage if required. VSR is delivered with the flange unattached. B+87 47 195 17 VSR is made of seawater-resistant aluminium. (EN-AW-5052-H34) H+95 H-7 ORDER CODE, VSR 83 55 H/3 49 VSR - 1200-1600 / 0-0 47 B-7 47 Product L = Enamel finish B = Width SM = Special material H = Height Drainage chamber VSR-1200-1600 / 0-0 VSR Width: 1200, Height: 1600 All dimensions in mm. Groove dimensions: B x H + 5 mm Fig. 1 23

TOG-R TOG-R is a circular transfer unit for wall mounting, and is used for inter-room air transfer, such as from living room to corridor, using a central outlet. TOG-R comprises two mounting rings and two sound attenuating diffuser fronts which are installed on each side of the wall. The mounting rings feature a clip-on system for easy fitting of the front units. DIMENSIONS AND WEIGHT, TOG-R Type A C Weight [kg] 125 240 13-17-24 0,6 160 280 13-17-24 0,8 200 333 13-17-24 1,2 Table 2 Both the diffuser front and the mounting ring are made in steel, with a RAL 9003 - gloss 30 finish. Other colours available on request. QUICK SELECTION Sound level TOG-R [m³/h] difference Type 10Pa 15Pa 20Pa Dn,e,w 125 100 130 151 34 160 151 184 209 33 200 190 230 266 32 Table 1: The table shows air flow rates at max slot height, L WA < 30 db(a). Fig. 1 ORDER CODE, TOG-R TOG-R - 160 / 0 Product Type: 125-200 SL = Special finish TOG-R-160 / 0 TOG-R transfer unit, type 160. 24

0 1 2 3 4 5 6 Pegasus Comfort Pegasus Comfort is a wall diffusor with VAV functionality and a heating coil. It is used as a volume regulator and air inlet unit in demand controlled ventilation systems. Pegasus Comfort has very good induction, which makes it well-suited for variable airflows. FUNCTION Pegasus Comfort has a built-in VAV regulator for demand control of the airflow. The damper solution will choke the pressure at high flow rates and will maintain a low sound level. This may reduce the need for additional dampers and sound attenuators in a duct system.the unit is equipped with a heating coil for waterborne heating of inlet air. Pegasus Comfort is delivered with Belimo MP Bus, LON, Modbus or Belimo KNX for direct bus communications with building automation systems. Pegasus Comfort is built as a complete measurement and regulating unit for demand control of the airflows in the ventilation system. The measurement station measures pressure difference via measurement rods integrated into the unit. The unit is equipped with an LHV-D3 VAV regulator from Belimo. The regulator's specifications are found in the table below. Complete technical documentation can be downloaded from www.belimo.eu. The unit has a simple connection and service point on the outside of the box s side. See figure 10. Pegasus Comfort has a detachable front plate with selectable LØV- or Opus execution. LØV has 2 different patterns, long (L) or short (K) air throw. If Opus pattern is selected with turnable plastic nozzles, the designation (V) is for variable air throw. Pipe connection water side is delivered as standard with Ø15 smooth pipe. They can also be ordered with 1/2 internal or external threads. Actuator LHV-D3-MP/MOD/LON Operating voltage AC 24 V 50/60 Hz, DC 24 V Power consumption 2.5W Dim power 4.5VA (max.8 A @5 ms) Table 1, Technical specification, Belimo VAV controller MATERIALS AND FINISH Pegasus Comfort is made of galvanised steel. The measurement cross is in aluminium, hoses and nipples are in plastic. The damper has an affixed polyester cloth. The spigot has a rubber EPDM seal. Battery made of copper and aluminium. The K and L type front panels are made of steel with a RAL 9003 - gloss 30 finish. Other colours are available on request. The V type diffuser front features Opus nozzles in ABS plastic, is made of steel and comes in a RAL 9003 - gloss 30 finish. Other colours are also available, but without theadjustable nozzle option. 0 1 2 3 4 5 6 7 8 9 10 Short throw length (LØV) REGULATION RANGE, PEGASUS-COMFORT Pegasus-Comfort (m³/h) Dim. Minimum Maximum 125 26 265 160 43 434 200 70 700 250 106 1060 Table 3, Regulation range for VAV, airflow in m³/h. See dimensioning diagram for sound power and pressure loss. ORDER CODE Connection: B = Rear edge S = Side Dim. Ø125 - Ø250 Normal operating range for Pegasus Comfort Distance to opposite wall (m) Long throw length (LØV) Pegasus Comfort - B - 125 / L / 0 / IG / 0 Front, type: K = LØV perforation, short air throw L = LØV perforation, long air throw V = Opus nozzles, variable distribution pattern Variable throw length (OPUS) SL = Special lacquer Pipe connection Water side: 0 = Smooth pipes IG = Internal ½" threads UG = External ½" threads Connection: 0 = MP-Bus 2 = LON-Bus 3 = MOD-Bus 4 = MP-Bus with EasyLink plug 7 = Belimo KNX 8 = MOD-Bus for X-AIRCONTROL Pegasus-B-125/L/0/IG/0 Pegasus Comfort for rear connection, dim Ø125. LØV front plate with long air throw and MP-Bus actuator. Pipe connection on the water side is fitted with an internal ½" thread. 25

QUICK SELECTION PEGASUS-COMFORT LØV-B-K/L Pegasus-Comfort LØV-B-K/L m³/h (open) Dim. 25 db(a) 30 db(a) 35 db(a) 125 158 194 241 160 277 335 403 200 331 396 475 250 594 706 832 QUICK SELECTION PEGASUS-COMFORT OPUS-B Pegasus-Comfort Opus-B m³/h (open) Dim. 25 db(a) 30 db(a) 35 db(a) 125 140 173 212 160 234 284 342 200 266 335 425 250 497 605 731 QUICK SELECTION PEGASUS-COMFORT LØV-S-K/L Pegasus-Comfort LØV-B-K/L m³/h (open) Dim. 25 db(a) 30 db(a) 35 db(a) 125 169 205 252 160 274 335 407 200 342 410 490 250 518 630 763 Table 2, Quick selection Pegasus Comfort QUICK SELECTION PEGASUS-COMFORT OPUS-S Pegasus-Comfort Opus-S m³/h (open) Dim. 25 db(a) 30 db(a) 35 db(a) 125 137 173 216 160 230 281 342 200 281 349 432 250 536 626 727 DIMENSIONS AND WEIGHT, PEGASUS COMFORT Dim. D BF HF BK BK2 HK DS A B E F G H I J Weight [Kg] 125 124 510 205 470 700 173 570 82 145 197 175 18 138 235 257 15 160 159 560 255 520 700 223 605 100 163 197 175 18 188 235 257 17 200 199 580 295 540 700 263 645 120 183 197 175 25 213 235 257 19 250 249 840 367 800 800 337 695 145 208 186 186 37 275 246 246 25 Table 4 Figure 2, Dimensional sketch Pegasus Comfort-B 26

Pegasus Comfort Figure 3, Dimensional sketch Pegasus Comfort-S LØV-K LØV-L OPUS Figure 4, Pegasus Comfort fronts 27

Opus-4 and Opus-5 Opus-4 and Opus-5 are rectangular supply diffusers fitted to the side of circular and rectangular air ducts. The diffusers offer an adjustable flow pattern and are ideal for both under- and overheated air. Duct velocity ahead of the first diffuser should not exceed 5 m/s. Opus-4D and 4DD are made for installation in circular ducts, whereas Opus-5D and 5DD are designed for installation in rectangular ducts. The diffusers are equipped with adjustable Opus nozzles. Each unit is fitted with a diffuser plate to the rear which ensures even distribution at the front. The system is available with one (D) or two (DD) nozzle rows. In addition to the standard dimensions, made-to-measure diffusers with different numbers of nozzles are also available. Please contact your local dealer for more information. The standard nozzle settings are shown in fig. 1. DIMENSIONS AND WEIGHT, Opus-4 and Opus-5 Opus-4D with single nozzle row is suitable from and incl. dim. Ø200 to and incl. dim. Ø1000. Opus-4DD with double nozzle row is suitable from and incl. dim. Ø315 to and incl. dim. Ø1250. Product Weight [kg] Groove dimensions [mm] Opus-4D 1,3 950 x 70 Opus-5D 1,3 950 x 70 Opus-4DD 1,7 950 x 125 Opus-5DD 1,7 950 x 125 Table 2 The diffusers are steel plated, with a RAL 9003 - gloss 30 finish. Opus nozzles are in ABS plastic. Black RAL 9005, aluminium RAL 9006 and galvanised design can be provided on request. Other colours are also available, but without adjustable nozzles. QUICK SELECTION Opus 4 and Opus-5 Product [m³/h] Type 25 db(a) 30 db(a) 35 db(a) Opus 4/5D 138 163 193 Opus 4/5DD 251 308 377 Table 1: The table shows airflow rates at given sound power levels. (Duct velocity ahead of first diffuser 5 m/s). ORDER CODE Opus - 4 / DD / 315 / 0 SL = Special finish Type: G = Galvanized 4 = For circular duct 0 = RAL 9003 - gloss 30 5 = For rectangular duct Dim: Ø200 - Ø1250 D = Single row of nozzles. DD = Double row of nozzles MA = Special dimensions and number of nozzles Fig. 1 Exsemple: Opus-4 / DD / 315 / 0 Opus-4 for circular duct, double row of nozzles, dimension Ø315 finished in RAL 9003 - gloss 30. 28

Pegasus Pegasus is a wall diffuser unit with VAV function. It is used as a volume flow controller unit in demand controlled ventilation systems. Pegasus has very good induction, making it ideal for variable air flow rates. FUNCTION Pegasus has a built-in VAV controller for the demand controlled adjustment of air flow rates. The damper solution will choke the pressure at high flow rates and maintain a low sound level. This may reduce the need for additional dampers and sound attenuators in a duct system. Pegasus is supplied with Belimo MP-Bus, LON, Modbus or Belimo KNX for direct BUS communication with SD systems. Pegasus is a complete measuring and control unit for the demand control of air flow rates in ventilation systems. The measuring station measures the differential pressure using measuring rods integrated into the unit. The unit is equipped with an LHV-D3 VAV controller from Belimo. The controller's specifications are provided in the table below. Full technical documentation can be downloaded from www.belimo. eu. Pegasus has a removable front panel with a choice of LØV or Opus design. LØV has two different designs, long (L) or short (K) throw length. If the Opus design with turnable plastic nozzles is selected, (V) is the designation for the variable throw length. MATERIALS AND FINISH Pegasus is made of galvanised steel. The measuring cross is made of aluminium, hoses and nipples are made of plastic. The damper is fitted with a polyester cloth. The connection collar has an EPDM rubber gasket. Actuator Operating voltage Power consumption Dim. power LHV-D3-MP/MOD/LON AC 24 V 50/60 Hz, DC 24 V 2.5 W 4.5 VA (max. 8 A @5 ms) Table 1, Technical specification, Belimo VAV controller Figure 1 ORDER CODE Pegasus - B - 125 / L / 0 / 0 Connection: B = Rear edge S = Side Dim. 125-250 Front, type: K = LØV perforation, short throw length L = LØV perforation, long throw length V = Opus nozzles variable distribution pattern SL = Special lacquer 0 = MP-Bus 1 = MP-Bus with VIP-X plug 2 = LON-Bus 3 = MOD-Bus 4 = MP-Bus with EasyLink plug 5 = Stand alone with trafo for CO2 and temperature 6 = Stand alone with trafo for PIR 7 = Belimo KNX 8 = X-AIRCONTROL Pegasus-B-125/L/0/0 Pegasus for rear connection, dim. Ø125 LØV front panel with long throw length with MP Bus actuator without lead plug. 29

QUICK SELECTION PEGASUS LØV-B-K/L Pegasus LØV-B-K/L m³/h (open) Dim. 25 db(a) 30 db(a) 35 db(a) 125 158 194 241 160 277 335 403 200 331 396 475 250 594 706 832 QUICK SELECTION PEGASUS LØV-B-K/L Pegasus LØV-B-K/L m³/h (75 Pa) Dim. 25 db(a) 30 db(a) 35 db(a) 125 169 202 245 160 248 324 378 200 331 403 475 250 497 648 792 QUICK SELECTION PEGASUS LØV-S-K/L Pegasus LØV-S-K/L m³/h (open) Dim. 25 db(a) 30 db(a) 35 db(a) 125 169 205 252 160 274 335 407 200 342 410 490 250 518 630 763 QUICK SELECTION PEGASUS LØV-S-K/L Pegasus LØV-S-K/L m³/h (75 Pa) Dim. 25 db(a) 30 db(a) 35 db(a) 125 166 209 234 160 238 320 396 200 288 385 486 250 439 630 738 QUICK SELECTION PEGASUS OPUS-B Pegasus Opus-B m³/h (open) Dim. 25 db(a) 30 db(a) 35 db(a) 125 140 173 212 160 234 284 342 200 266 335 425 250 497 605 731 QUICK SELECTION PEGASUS OPUS-S Pegasus Opus-S m³/h (open) Dim. 25 db(a) 30 db(a) 35 db(a) 125 137 173 216 160 230 281 342 200 281 349 432 250 536 626 727 QUICK SELECTION PEGASUS OPUS-B Pegasus Opus-B m³/h (75 Pa) Dim. 25 db(a) 30 db(a) 35 db(a) 125 140 169 212 160 212 270 338 200 292 349 428 250 371 580 724 QUICK SELECTION PEGASUS OPUS-S Pegasus Opus-S m³/h (75 Pa) Dim. 25 db(a) 30 db(a) 35 db(a) 125 133 173 212 160 202 270 335 200 277 353 432 250 396 565 716 Table 2, Quick selection table Pegasus REGULATION RANGE, PEGASUS Pegasus (m³/h) Dim. Minimum Maximum 125 26 265 160 43 434 200 70 700 250 106 1060 Table 3, Adjustment range for VAV, air flow rate in m³/h. See calculation diagram for sound power level and pressure drop 30

Pegasus DIMENSIONS AND WEIGHT, PEGASUS Dim. D BF HF BK BK2 HK DB DS A B Weight [kg] 125 124 510 205 470 700 173 700 407 82 145 11 160 159 560 255 520 700 223 700 442 100 163 13 200 199 580 295 540 700 263 700 482 120 183 14.5 250 249 840 367 800 800 337 725 532 145 208 19 Table 4 Figure 2, Dimensioned sketch Pegasus-B Figure 3, Dimensioned sketch Pegasus-S Figure 4, Pegasus fronts 31

Orion-LØV with Sirius Comfort Sirius Comfort is a diffusor unit with VAV and heating functions. It is used as a volume regulator and diffusor unit in demand cotrolled ventilation systems. Sirius Comfort has unique characteristics, that is well-suited for variable airflows and contributes to the valve's very good induction. FUNCTION Sirius Comfort has a built-in VAV regulator for demand control of airflows. The damper solution will choke the pressure at high flow rates and will maintain a low sound level. This may reduce the need for additional dampers and sound attenuators in a duct system. The unit is equipped with a heating coil for waterborne heating of inlet air. Sirius Comfort is delivered with Belimo MP Bus, LON, Modbus or Belimo KNX for direct bus communications with building automation systems. Measurement deviation for the area: 10-20% of nominal: ±25% 20-40% of nominal: <±10% 40-100% of nominal: <±4% At T-pipe situation, a distance of at least 5 x ØD is recommended in order to maintain same measurement precision. ORDER CODE Orion-LØV-Sirius-Comfort TA B 200 0 SL=Special lacquer False ceiling: TA=A-Edge DC=Dampa Clip-In DG=Dg-edge DS=Ds-edge Dim: Ø200 Ø250 Ø315 Ø400 EK 24=E-edge-T24 EK 15=E-edge-T15 B=Motion sensor (Connection 4 and 6) Orion-LØV-Sirius-Comfort-TA-B-200/0 Orion-LØV-Sirius-Comfort air inlet valve with buckling edge A for T profile ceiling Motion sensor in valve front, connection valve Ø200 Sirius Comfort is built as a complete measurement and regulating unit for demand control of airflows in the ventilation system. The measurement station measures pressure difference via measurement rods integrated into the unit. The unit is equipped with an LHV-D3 VAV regulator from Belimo. The controller s specifications are found in the table below. Complete technical documentation can be downloaded from www.belimo.eu. Orion-LØV has a detachable front plate with LØV perforation, and can be delivered adapted to different types of ceiling systems. Pipe connection water side is delivered as standard with Ø15 smooth pipe. They can also be ordered with 1/2 internal or external threads. Actuator LHV-D3-MP/MOD/LON Operating voltage AC 24 V 50/60 Hz, DC 24 V Power consumption 2.5W Dim power 4.5VA (max.8 A @5 ms) Table 1, Technical specification, Belimo VAV controller. MATERIALS AND FINISH Sirius Comfort is made of galvanised steel. The measurement cross is in aluminium, hoses and nipples are in plastic. The damper has an affixed polyester cloth. The spigot has a rubber EPDM seal. Heating coil is copper and aluminium. QUICK SELECTION ORION-LØV WITH SIRIUS COMFORT Orion-Løv with Sirius Comfort m³/h (open) ØD 25 db(a) 30 db(a) 35 db(a) 125 140 180 223 160 238 288 338 200 320 385 446 250 446 540 655 Table 2, Quick selection Orion LØV with Sirius Comfort Sirius Comfort - 125-200 - 0-0 Pipe connection water side: 0 = Smooth pipe IG = Internal ½" threads Dim: UG = External ½" threads 125-200 160-250 Connection: 200-315 0 = MP-Bus 250-400 1 = MP-Bus with VIP-X plug 2 = LON-Bus 3 = MOD-Bus 4 = MP-Bus with EasyLink plug 5 = Stand alone with transformator for CO2 and temperature 6 = Stand alone with transformator for PIR/potential-free switch 7 = Belimo KNX 8 = MOD-Bus for X-AIRCONTROL Sirius Comfort -125-200 - 0-0 Sirius Comfort with intake Ø125 and outlet Ø200, with MP-Bus regulator, smooth pipe connection on water side. QUICK SELECTION ORION-LØV WITH SIRIUS COMFORT Orion-Løv with Sirius Comfort m³/h (75Pa) Dim. 25 db(a) 30 db(a) 35 db(a) 125 137 176 216 160 194 281 230 200 281 371 446 250 270 511 655 32

ORDER CODE REGULATION RANGE Sirius (m³/h) ØD Minimum Maximum 125 26 265 160 43 434 200 70 700 250 106 1060 Table 3. Regulation range for vav regulator, airflow in m3/h. See dimensioning diagram for sound power and pressure loss. Orion-PTV-Sirius-Comfort TA B 200 SCK SL = Special lacquer False ceiling: TA=A-edge SCK - 125-200 - 0-0 DC=Dampa Clip-In DG=Dg-edge DS=Ds-edge EK 24=E-edge-T24 SCK=Sirius Comfort Intake-outlet Pipe connection water side: 0 = Smooth pipe IG = Internal ½" threads EK 15=E-edge-T15 125-200 UG = External ½" threads B=Motion sensor (Connection 4 and 6) 160-250 200-315 Connection: 0 = MP-Bus Dim: Ø200,Ø250,Ø315,Ø400 250-400 1 = MP-Bus with VIP-X plug 2 = LON-Bus 3 = MOD-Bus 4 = MP-Bus with EasyLink plug 5 = Stand alone with transformator for CO2 and temperature 6 = Stand alone with transformator for PIR/potential-free switch 7 = Belimo KNX 8 = MOD-Bus for X-AIRCONTROL Orion-PTV-Sirius-Comfort-TA-B-200-SCK-125-200-0-0/0 Orion-PTV-Sirius air intake valve with buckling edge A for T-profile, motion sensor in valve front, connection valve Ø200, Sirius chamber intake Ø125 og outlet Ø200, with MP-Bus regulator, smooth pipe connection on water side. 0 DIMENSIONS AND WEIGHT Dim. D DA B H L E F Weight [Kg] 125 124 202 325 175* 666 18 138 11.5 160 159 252 360 210** 682 23 163 13.5 200 199 317 400 240 715 26 188 15.5 250 249 402 450 290 672 26 238 18 Table 4. Sirius Comfort dimensions and weight table. *) 185 with the coil pipe parts are mounted on the left **) 220 with the coil pipe parts are mounted on the left Figur 1, Orion LØV with Sirius Comfort Dimensional sketch 33

Orion Opus with Sirius Comfort Orion-Opus with Sirius Comfort is a diffusor unit with VAV functionality and a heating function. It is used as a volume regulator and diffusor unit in demand controlled ventilation systems. Sirius Comfort has unique characteristics and Orion-Opus has a large capacity, good induction and is well-suited to large airflows. FUNCTION Sirius Comfort has a built-in VAV regulator for demand control of airflows. The damper solution will choke the pressure at high flow rates and will maintain a low sound level. This may reduce the need for additional dampers and sound attenuators in a duct system.the unit is equipped with a heating coil for waterborne heating of inlet air. Sirius Comfort is delivered with Belimo MP Bus, LON, Modbus or Belimo KNX for direct bus communications with building automation systems. Measurement deviation for the area: 10-20% of nominal: ±25% 20-40% of nominal: <±10% 40-100% of nominal: <±4% At T-pipe situation, a distance of at least 5 x ØD is recommended in order to maintain same measurement precision. ORDER CODE Orion-OPUS-Sirius-Comfort TA B 200 0 SL=Special lacquer False ceiling: TA=A-Edge DC=Dampa Clip-In DG=Dg-edge DS=Ds-edge Dim: Ø200 Ø250 Ø315 Ø400 EK 24=E-edge-T24 EK 15=E-edge-T15 B=Motion sensor (Connection 4 and 6) Orion-OPUS-Sirius-Comfort-TA-B-200/0 Orion-OPUS-Sirius-Comfort air inlet valve with buckling edge A for T profile ceiling, Motion sensor in valve front, connection valve Ø200 Sirius Comfort is built as a complete measurement and regulating unit for demand control of airflows in the ventilation system. The measurement station measures pressure difference via measurement rods integrated into the unit. The unit is equipped with an LHV-D3 VAV regulator from Belimo. The controller s specifications are found in the table below. Complete technical documentation can be downloaded from www.belimo.eu. Orion-Opus has a detachable front plate with nozzles of ABS plastic, and can be delivered adapted for different types of ceiling systems. Pipe connection water side is delivered as standard with Ø15 smooth pipe. They can also be ordered with 1/2 internal or external threads. Actuator LHV-D3-MP/MOD/LON Operating voltage AC 24 V 50/60 Hz, DC 24 V Power consumption 2.5W Dim power 4.5VA (max.8 A @5 ms) Table 1, Technical specification, Belimo VAV Controller. Sirius Comfort - 125-200 - 0-0 Pipe connection water side: 0 = Smooth pipe IG = Internal ½" threads Dim: UG = External ½" threads 125-200 160-250 Connection: 200-315 0 = MP-Bus 250-400 1 = MP-Bus with VIP-X plug 2 = LON-Bus 3 = MOD-Bus 4 = MP-Bus with EasyLink plug 5 = Stand alone with transformator for CO2 and temperature 6 = Stand alone with transformator for PIR/potential-free switch 7 = Belimo KNX 8 = MOD-Bus for X-AIRCONTROL Sirius Comfort -125-200 - 0-0 Sirius Comfort with intake Ø125 and outlet Ø200, with MP-Bus regulator, smooth pipe connection on water side. MATERIALS AND FINISH Sirius Comfort is made of galvanised steel. The measurement cross is in aluminium, hoses and nipples are in plastic. The damper has an affixed polyester cloth. The spigot has a rubber EPDM seal. Heating coil is copper and aluminium. QUICK SELECTION ORION-OPUS WITH SIRIUS COMFORT Orion-Løv with Sirius Comfort m³/h (open) Dim. 25 db(a) 30 db(a) 35 db(a) 125 151 187 234 160 252 302 374 200 310 378 468 250 468 565 666 Table 2, Quick selection Orion-Opus with Sirius Comfort. QUICK SELECTION ORION-OPUS WITH SIRIUS COMFORT Orion-Løv with Sirius Comfort m³/h (75Pa) Dim. 25 db(a) 30 db(a) 35 db(a) 125 137 184 230 160 230 302 360 200 180 338 468 250 306 511 666 34

ORDER CODE Orion-Opus-Sirius-Comfort TA B 200 SCK 0 REGULATION RANGE Sirius (m³/h) Dim. Minimum Maximum 125 26 265 160 43 434 200 70 700 250 106 1060 Table 3. Regulation range for vav regulator, airflow in m3/h. See dimensioning diagram for sound power and pressure loss. SL = Special lacquer False ceiling: TA=A-edge SCK - 125-200 - 0-0 DC=Dampa Clip-In DG=Dg-edge DS=Ds-edge EK 24=E-edge-T24 SCK=Sirius Comfort Intake-outlet Pipe connection water side: 0 = Smooth pipe IG = Internal ½" threads EK 15=E-edge-T15 UG = External ½" threads 125-200 B=Motion sensor 160-250 Connection: (Connection 4 and 6) 200-315 0 = MP-Bus Dim: Ø200,Ø250,Ø315,Ø400 250-400 1 = MP-Bus with VIP-X plug 2 = LON-Bus 3 = MOD-Bus 4 = MP-Bus with EasyLink plug 5 = Stand alone with transformator For CO2 og temperature 6 = Stand alone with transformator for PIR/potential-free switch 7 = Belimo KNX Orion-Opus-Sirius-Comfort-TA-B-200-SCK-125-200-0-0/0 8 = MOD-Bus for X-AIRCONTROL Orion-Opus-Sirius air intake valve with buckling edge A for T-profil, motion sensor in valve front, connection valve Ø200, Sirius chamber intake Ø125 and outlet Ø200, with MP-Bus regulator, smooth pipe connection on water side. DIMENSIONS AND WEIGHT Dim. D DA B H L E F Weight [Kg] 125 124 202 325 175* 666 18 138 11.5 160 159 252 360 210** 682 23 163 13.5 200 199 317 400 240 715 26 188 15.5 250 249 402 450 290 672 26 238 18 Table 4. Sirius Comfort dimensions and weight table. *) 185 with the coil pipe parts are mounted on the left **) 220 with the coil pipe parts are mounted on the left Figure 1, Orion Opus with Sirius Comfort - Dimensioned sketch 35

Orion-PTV with Sirius Comfort Orion-PTV with Sirius Comfort is a diffusor unit with VAV and heating functions. It is used as a volume regulator and diffusor unit in demand controlled ventilation systems. Sirius Comfort has unique characteristics and Orion-PTV has a large capacity, good induction and is wellsuited for the inlet of large airflows. FUNCTION Sirius Comfort has a built-in VAV regulator for demand control of airflows. The damper solution will choke the pressure at high flow rates and will maintain a low sound level. This may reduce the need for additional dampers and sound attenuators in a duct system.the unit is equipped with a heating coil for waterborne heating of inlet air. Sirius Comfort is delivered with Belimo MP Bus, LON, Modbus or Belimo KNX for direct bus communications with building automation systems. Measurement deviation for the area: 10-20% of nominal: ±25% 20-40% of nominal: <±10% 40-100% of nominal: <±4% At T-pipe situation, a distance of at least 5 x ØD is recommended in order to maintain same measurement precision. ORDER CODE Orion-PTV-Sirius-Comfort TA B 200 0 SL=Special lacquer False ceiling: TA=A-Edge DC=Dampa Clip-In DG=Dg-edge DS=Ds-edge Dim: Ø200 Ø250 Ø315 Ø400 EK 24=E-edge-T24 EK 15=E-edge-T15 B=Motion sensor (Connection 4 and 6) Orion-PTV-Sirius-Comfort-TA-B-200/0 Orion-PTV-Sirius-Comfort air inlet valve with buckling edge A for T profile ceiling. Motion sensor in valve front, connection valve Ø200 Sirius Comfort is built as a complete measurement and regulating unit for demand control of airflows in the ventilation system. The measurement station measures pressure difference via measurement rods integrated into the unit. The unit is equipped with an LHV-D3 VAV regulator from Belimo. The controller s specifications are found in the table below. Complete technical documentation can be downloaded from www.belimo.eu Orion-PTV has a detachable front plate with a perforated front and side edges on the valve, and can be delivered adapted for different types of ceiling systems. Pipe connection water side is delivered as standard with Ø15 smooth pipe. They can also be ordered with 1/2 internal or external threads. Actuator LHV-D3-MP/MOD/LON Operating voltage AC 24 V 50/60 Hz, DC 24 V Power consumption 2.5W Dim power 4.5VA (max.8 A @5 ms) Table 1, Technical specification, Belimo VAV Controller. Sirius Comfort - 125-200 - 0-0 Pipe connection water side: 0 = Smooth pipe IG = Internal ½" threads Dim: UG = External ½" threads 125-200 160-250 Connection: 200-315 0 = MP-Bus 250-400 1 = MP-Bus with VIP-X plug 2 = LON-Bus 3 = MOD-Bus 4 = MP-Bus with EasyLink plug 5 = Stand alone with transformator for CO2 and temperature 6 = Stand alone with transformator for PIR/potential-free switch 7 = Belimo KNX 8 = MOD-Bus for X-AIRCONTROL Sirius Comfort -125-200 - 0-0 Sirius Comfort with intake Ø125 and outlet Ø200, with MP-Bus regulator, smooth pipe connection on water side. MATERIALS AND FINISH Sirius Comfort is made of galvanised steel. The measurement cross is in aluminium, hoses and nipples are in plastic. The damper has an affixed polyester cloth. The spigot has a rubber EPDM seal. Heating coil is copper and aluminium. QUICK SELECTION ORION PTV WITH SIRIUS COMFORT Orion-PTV with Sirius Comfort m³/h (open) Dim. 25 db(a) 30 db(a) 35 db(a) 125 133 169 220 160 259 302 364 200 313 378 454 250 497 583 702 QUICK SELECTION ORION PTV WITH SIRIUS COMFORT Orion-PTV with Sirius Comfort m³/h (75Pa) Dim. 25 db(a) 30 db(a) 35 db(a) 125 133 180 220 160 227 292 364 200 288 374 454 250 288 533 702 Table 2, Quick selection Orion PTV with Sirius Comfort. 36

ORDER CODE Orion-PTV-Sirius-Comfort TA B 200 SCK 0 REGULATION RANGE Sirius (m³/h) Dim. Minimum Maximum 125 26 265 160 43 434 200 70 700 250 106 1060 Table 3. Regulation range for vav regulator, airflow in m3/h. See dimensioning diagram for sound power and pressure loss. SL = Special lacquer False ceiling: TA=A-edge SCK - 125-200 - 0-0 DC=Dampa Clip-In DG=Dg-edge DS=Ds-edge EK 24=E-edge-T24 SCK=Sirius Comfort Intake-outlet Pipe connection water side: 0 = Smooth pipe IG = Internal ½" threads EK 15=E-edge-T15 125-200 UG = External ½" threads B=Motion sensor (Connection 4 and 6) 160-250 200-315 Connection: 0 = MP-Bus Dim: Ø200,Ø250,Ø315,Ø400 250-400 1 = MP-Bus with VIP-X plug 2 = LON-Bus 3 = MOD-Bus 4 = MP-Bus with EasyLink plug 5 = Stand alone with transformator for CO2 and temperature 6 = Stand alone with transformator for PIR/potential-free switch 7 = Belimo KNX 8 = MOD-Bus for X-AIRCONTROL Orion-PTV-Sirius-Comfort-TA-B-200-SCK-125-200-0-0/0 Orion-PTV-Sirius air intake valve with buckling edge A for T-profile, motion sensor in valve front, connection valve Ø200, Sirius chamber intake Ø125 og outlet Ø200, with MP-Bus regulator, smooth pipe connection on water side. DIMENSIONS AND WEIGHT Dim. D DA B H L E F Weight [Kg] 125 124 202 325 175* 666 18 138 11.5 160 159 252 360 210** 682 23 163 13.5 200 199 317 400 240 715 26 188 15.5 250 249 402 450 290 672 26 238 18 Table 4. Sirius Comfort dimensions and weight table *) 185 with the coil pipe parts are mounted on the left **) 220 with the coil pipe parts are mounted on the left Figure 1, Orion PTV with Sirius Comfort - Dimensioned sketch 37

TLH TLH is a basic supply diffuser for wall, ceiling or riser installation. TLH features a perforated front and a connection collar fitted with a wide rubber gasket for installation directly in duct or groove without additional fastening devices. DIMENSIONS AND WEIGHT, TLH Dim. D DA A B Weight [kg] 100 99 175 16 48 0.6 125 124 175 20 53 0.6 160 159 215 22 56 0.8 Table 2 TLH is made of steel, and comes in a RAL 9003 - gloss 30 finish with EPDM rubber gasket fitted as standard. ODA QUICK SELECTION TLH [m³/h] Dim. 25 db(a) 30 db(a) 35 db(a) 100 58 72 86 125 108 130 155 160 194 230 274 Table 1: The table shows the air volume at 3 sound levels. The sound level is Lw(A). ORDER CODE, TLH TLH - 125 / 0 Product Dimension: Ø100 - Ø160 TLH-125 / 0 TLH supply diffuser dim. Ø125. SL = Special finish OD A B Fig.1 38

LØV-R LØV-R is a circular supply diffuser for ceiling mounting. LØV offers excellent induction and is suitable for both constant and variable volume flow. LØV-R features a removable front panel with LØV perforation. The diffuser front plate are made in steel. The diffuser body is in aluminium and is fitted with an EPDM rubber gasket at the connection collar. All internal and external diffuser elements are finished in RAL 9003 - gloss 30. Other colours are available on request. DIMENSIONS AND WEIGHT, LØV-R Dim. A B C G E F I Weight diffuserl [kg] 100 283 99 200 243 65 115 75 0,7 125 322 124 230 282 65 115 75 0,9 160 420 159 320 380 70 120 80 1,5 200 460 199 350 420 70 120 80 1,9 250 570 249 470 530 70 120 80 2,7 315 570 314 470 530 70 120 80 2,7 Table 2 QUICK SELECTION LØV-R [m³/h] Dim. 25 db(a) 30 db(a) 35 db(a) 100 68 83 97 125 104 122 140 160 180 205 238 200 230 270 313 250 349 400 461 315 472 558 662 Table 1. The table shows air flow rates at given sound power levels. ORDER CODE, LØV (LOEV-R) LØV-R-160-0 LOEV-R-160-0 Explantation: LOEV-R, standard dimension Ø160 SL = Special finish. Dimension: Ø160-315. Fig. 1 ORDER CODE, Luna UI = Outlet installed, low profile design I = Insulated Luna-0-0-125-160 Dimension outlet: Ø100 Ø315 Dimension inlet: Ø100 Ø315 Luna-0-0-125-160 Explantation: Luna plenum box with inlet Ø125 and outlet Ø160 39

LØV-R with Luna plenum box The Luna plenum box is recommended for improved sound attenuation, and provides an adjustment and measurement option. Luna is a rectangular box with a removable damper providing access to the connecting duct. The damper can be locked in the position required. The Luna plenum box features a damper and measurement device for adjustment. It is insulated with a sound absorber in polyester and is available with one or two dimensional changes between inlet and outlet. Furthermore, the box can be supplied with external condensation insulation. A low-profile design [UI] is also available, and for this design a reduction in capacity of approx. 20% will apply. The distance between diffuser and box can be increased by up to 35 cm without extending the wire and measuring tube. Luna is supplied in a galvanised finish, and with four internal walls lined with a sound absorber in polyester. The connection collar is fitted with an EPDM rubber gasket. QUICK SELECTION DIMENSIONS S AND WEIGHT, Luna Dim. D DA B H H1 H2 L L1 L2 Weight Luna [kg] 100-100 99 102 220 122 260 138 325 295 133 2,3 100-125 99 127 220 122 260 138 325 295 133 2,3 100-160 99 162 220 122 265 143 360 310 150 2,4 125-125 124 127 250 147 285 138 360 335 150 2,4 125-160 124 162 250 147 290 143 360 335 150 2,9 125-200 124 202 250 147 290 143 400 355 170 3,1 160-160 159 162 340 182 325 143 400 390 170 4,1 160-200 159 202 340 182 325 143 400 390 170 4,2 160-250 159 252 340 182 325 143 452 415 198 4,6 200-200 199 202 380 222 365 143 452 460 198 5,7 200-250 199 252 380 222 365 143 452 460 198 5,7 200-315 199 317 380 222 365 143 515 485 228 6,1 250-250 249 252 390 272 415 143 515 535 228 7,4 250-315 249 317 390 272 415 143 515 535 228 7,4 315-315 314 317 500 337 480 143 600 645 265 11 Table 4 LØV-R Luna [m³/h] Dim. Dim. 25 db(a) 30 db(a) 35 db(a) 100 100-100 58 72 88 125 100-125 76 91 120 125-125 86 101 119 160 125-160 97 126 158 160-160 144 166 191 200 160-200 162 191 227 200-200 191 216 245 250 200-250 248 288 338 250-250 274 317 367 315 250-315 313 374 439 315-315 367 425 497 Table 3. The table shows air flow rates at given sound power levels and 50 Pa total pressure loss. ORDER CODE, LØV-R (LOEV-R) with Luna LØV-R-L-0 SL = Special finish Fig. 2 L-0-0-125-160 L = Luna UI = Outlet installed, low profile design RH = Plenum box for fixed ceiling plate I = Insulated Dimension outlet: Ø100 Ø315 Dimension inlet: Ø100 Ø315 LOEV-R-L-0-0-125-160 Explantation: LOEV-R diffuser and Luna plenum box inlet Ø125 and outlet/diffuser dim. Ø160. 40

TLG-LØV TLG-LØV is a circular supply diffuser for ceiling mounting. TLG-LØV offers excellent induction, and is suitable for both constant and variable air flow rates. TLG-LØV features a front panel with LØV perforation and adjustable slot height. The diffuser and ceiling plate are in a steel design, and the connection collar is equipped with an EPDM rubber gasket. All internal and external diffuser elements come in a RAL 9003 - gloss 30 finish. Other colours are available on request. DIMENSIONS AND WEIGHT, LØV-R Dim. A B J T Groove Weight dim. diffuser [kg] 100 209 99 25 34-45 105 0,7 125 238 124 33 34-45 130 0,9 160 279 159 35 36-50 165 1,1 200 334 199 35 38-52 205 1,4 250 419 249 83 52-72 375 2,1 315 525 314 93 53-73 470 3,0 Table 2 QUICK SELECTION TLG-LØV [m³/h] Dim. 25 db(a) 30 db(a) 35 db(a) 100 87 104 123 125 144 167 194 160 238 273 312 200 328 378 436 250 609 707 820 315 897 1046 1220 Table 1: The table shows air flow rates at given sound power levels. Maximum slot height and valve fitted directly in straight duct. TLG-LØV 100-200 OB OA TLG-LØV 250 og 315 OB T J J ORDER CODE, TLG-LØV (TLG-LOEV) TLG-LØV-0-125-0 S = Vertical throw pattern E = One-way throw pattern Dimension: Ø100 Ø315 TLG-LOEV-0-125-0 Explantation: TLG-LOEV dim. Ø125 SL = Special finish Fig.1 OA T ORDER CODE, Luna Luna-0-0-125-125 UI = Outlet installed, low profile design, I = Insulated Dimension outlet: Ø100 Ø315 Dimension inlet: Ø100 Ø315 Luna-0-0-125-125 Explantation: Luna plenum box with inlet Ø125 and outlet Ø125. 41

TLG-LØV with Luna plenum box The Luna plenum box is recommended for improved sound attenuation, and works as an adjustment and measurement unit. Luna is a rectangular box equipped with a removable damper which provides access to the connecting duct. The damper can be secured in any position required. Luna plenum box features a damper and measuring outlet for commissioning. It is insulated with sound absorber in polyester and is available with one or two dimensional changes between inlet and outlet. Furthermore, the box can be delivered with external condensation insulation [I]. A lowprofile design [UI] is also available, and for this design a reduction in capacity of approx. 20% will apply. The distance between diffuser and box can be increased by up to 35 cm without extending the wire and measuring tube. Luna is supplied a galvanised finish, and with all four internal walls lined with sound absorber in polyester. The connection collar is fitted with an EPDM rubber gasket. DIMENSIONS AND WEIGHT, Luna Dim. D DA B H H1 H2 L L1 L2 Wight Luna [kg] 100-100 99 102 220 122 180 58 325 295 133 2,3 100-125 99 127 220 122 180 58 325 295 133 2,3 100-160 99 162 220 122 180 58 360 310 150 2,4 125-125 124 127 250 147 205 58 360 335 150 2,4 125-160 124 162 250 147 205 58 360 335 150 2,9 125-200 124 202 250 147 205 58 400 355 170 3,1 160-160 159 162 340 182 240 58 400 390 170 4,1 160-200 159 202 340 182 240 58 400 390 170 4,2 160-250 159 252 340 182 285 103 452 415 198 4,6 200-200 199 202 380 222 280 58 452 460 198 5,7 200-250 199 252 380 222 325 103 452 460 198 5,7 200-315 199 317 380 222 325 103 515 485 228 6,1 250-250 249 252 390 272 375 103 515 535 228 7,4 250-315 249 317 390 272 375 103 515 535 228 7,4 315-315 314 317 500 337 440 103 600 655 260 11 Table 4 QUICK SELECTION TLG-LØV Luna [m³/h] Dim. Dim. 25 db(a) 30 db(a) 35 db(a) 100 100-100 67 81 97 125 100-125 77 103 133 125-125 94 112 133 160 125-160 94 130 169 160-160 148 176 216 200 160-200 162 198 245 200-200 216 252 295 250 200-250 245 295 389 250-250 349 403 493 315 250-315 331 421 533 315-315 547 626 720 Table 3: The table provides air flow rates at given sound power levels and 50 Pa total pressure loss. ORDER CODE, TLG-LØV (TLG-LOEV) with Luna TLG-LØV-0-L-SL S = Vertical throw pattern E = One-way throw pattern SL = Special finish Fig. 2 L-0-0-125-160 L = Luna UI = Outlet installed, low profile design I = Insulated Dimension outlet: Ø100 Ø315 Dimension inlet: Ø100 Ø315 TLG-LOEV-0-L-0-0-125-160-SL Explantation: TLG-LOEV diffuser and Luna plenum box inlet Ø125 and outlet/diffuser dim. Ø160, special finish RAL 9006. *Colourcode must be remarked. 42

Tellus-LØV Tellus-LØV is a circular supply diffuser for exposed installation. It offers excellent induction and is suitable for both constant and variable air flow rates. The diffuser is also available with pass-through function. Tellus-LØV features a removable front panel with LØV perforation and adjustable slot height. Rotational pattern is supplied as standard. Other flow patterns are available on request. The box is insulated with a sound absorber in polyester and is equipped with measuring outlet and removable airflow adjustment damper. Available in high-profile or low-profile design. The high-profile version is also available in pass-through design as shown in fig. 3. DIMENSIONS AND WEIGHT, Tellus-LØV Dim. D DA H L S Weight [kg] 100 99 243 172 131 13/24 2,5 125 124 243 210 152 13/24 2,6 160 159 282 262 170 13/29 3,3 200 199 380 322 196 15/29 4 250 249 416 397 238 13/28/38 5,5 315 314 525 494 282 13/28/38 7 Table 3 The diffuser is made of steel with a RAL 9003 - gloss 30 finish. Other colours are available on request. It is internally lined with a sound absorber in polyester, and the connection collar is fitted with an EPDM rubber gasket. QUICK SELECTION, Tellus-LØV-H/L Tellus-LØV [m³/h] Dim. 25 db(a) 30 db(a) 35 db(a) 100 61 101 151 125 108 144 194 160 169 227 292 200 259 331 428 250 378 468 594 315 590 763 954 Table 1: The table shows air flow rates at given sound power levels and 30 Pa total pressure loss. Fig. 1, Tellus-LØV-L QUICK SELECTION, Tellus-LØV-H/D Quick selection for maximum slot height of Tellus-LØV type D together with Tellus-LØV-H, as a unit Tellus-LØV HD [m³/h] Dim. 25 db(a) 30 db(a) 35 db(a) 200 270 382 547 250 360 468 788 315 594 871 1260 Table 2, The table shows air flow rates at given sound power levels and 30 Pa total pressure loss Fig. 2, Tellus-LØV-H ORDER CODE, Tellus-LØV (LOEV) SL = Special finish D = Pass-through connection Dim: Ø200 - Ø315, type H only Dimension: Ø100 - Ø315 Fig. 3, Tellus-LØV-H-D 43

Tellus-Opus Tellus-Opus is a circular supply diffuser with adjustable nozzles for open installation. The diffuser is also available with pass-through function. With its adjustable Opus-nozzle solution, the flow pattern can be regulated and set as required. Tellus-Opus features a removable front panel with Opus nozzles and adjustable slot height. Rotational pattern is supplied as standard. Other flow patterns are available on request. The box is insulated with a sound absorber in polyester and is equipped with a measuring outlet and removable airflow adjustment damper. Also available as a passtrough unit as shown in fig.2. DIMENSIONS AND WEIGHT, Tellus-Opus Dim. D DA H L S Weight [kg] 125 124 282 210 152 13/29 3,1 160 159 380 262 170 13/29 4,3 200 199 416 322 196 15/28 6,7 250 249 525 397 238 13/28 10,2 Table 3 The diffuser is made of steel and comes in a RAL 9003 - gloss 30 finish. Black RAL 9005 and aluminium RAL 9006 are available on request. Other colours can be supplied, but without the nozzle-adjustment option. Opus-nozzles are in ABS plastic. The box is internally lined with a sound absorber in polyester, and the connection collar is fitted with an EPDM rubber gasket. QUICK SELECTION Tellus-Opus Tellus-Opus [m³/h] Dim. Damper 25 db(a) 30 db(a) 35 db(a) 125 max. 90 133 198 160 max. 155 234 338 200 max. 252 335 446 250 max. 335 475 659 Table 1: The table shows air flow rates at given sound power levels and 30 Pa total pressure loss with maximum open damper. QUICK SELECTION Tellus-Opus-D Quick selection for maximum slot height of Tellus-Opus type D and Tellus-Opus, together as one unit Tellus-Opus-D [m³/h] Dim. 25 db(a) 30 db(a) 35 db(a) 200 245 342 490 250 320 450 684 Table 2: The table shows air flow rates at given sound power levels and 30 Pa total pressure loss. Fig. 1 ORDER CODE, Tellus-Opus Tellus-Opus -125 / 0 / 0 Product SL =Special finish Dimension: Ø125 - Ø250 D = Pass-through connection, dim. 200 and 250 only. Tellus-Opus -125 / 0 / 0 Fig. 2 Tellus-Opus supply diffuser, dimension Ø125. 44

Tellus-LØV VAV Tellus-LØV VAV is a circular supply diffuser for open installation with VAV function. It has excellent induction and is suitable for both constant and variable air flow rate. FUNCTION Tellus-LØV VAV has a built-in VAV regulator for demand control of air flow. The damper solution will choke the pressure at high flow rates and maintain a low sound level. This may reduce the need for additional dampers and sound attenuators in a duct system. Tellus-LØV VAV is supplied with Belimo MP-Bus. For communication with Modbus, LON, KNX and BACnet, a Belimo UK 24-Gateway can be utilised. Measurement deviation for the area: 10-20% of nominal: ±25% 20-40% of nominal: <±10% 40-100% of nominal: <±4 % In order to sustain the product's measurement accuracy, straight ducting of min. 5 x ØD is recommended. Tellus-LØV VAV is designed as a complete measurement and regulating unit for demand control of air flow in the ventilation system. The measuring station measures the differential pressure via a sensor integrated into the unit. The unit is equipped with a CHV-VAV-MP regulator from Belimo. The regulator specifications are provided in the table below. Tellus-LØV VAV has a removable front plate with LØV perforation. Tellus-LØV VAV is available in both high-profile and low-profile design. Actuator CHV-VAV-MP Operating voltage AC 24 V 50/60 Hz, DC 24 V Power consumption 1.5W Dim. power 2.5 VA QUICK SELECTION, TELLUS-LØV VAV (Open) m 3/ h Dim. 25 db(a) 30 db(a) 35 db(a) 125 163 197 239 160 306 375 461 200 388 465 557 250 441 541 663 (75 Pa) m 3/ h Dim. 25 db(a) 30 db(a) 35 db(a) 125 115 170 234 160 252 332 440 200 260 396 550 250 370 475 641 Table 2 REGULATION RANGE, TELLUS-LØV VAV Tellus-LØV VAV (m 3/ h) ØD. Minimum Maximum 125 26 265 160 43 434 200 70 700 250 106 1060 Table 3, Regulation range for VAV, air flow rate in m³/h. See calculation diagram for sound power and pressure loss. Table 1, Technical specification, Belimo CHV-VAV-MP regulator MATERIALS AND FINISH Tellus-LØV VAV has a galvanised steel finish. The damper is fitted with a polyester cloth. The spigot has an EPDM rubber gasket. Tellus-LØV VAV are delivered in RAL 9003 - gloss 30. ORDER CODE, Tellus-LØV VAV 45

Tellus-LØV VAV DIMENSIONS AND WEIGHT, TELLUS-LØV VAV Dim. D DA H S Weight [kg] 125 124 380 210 15/29 7.5 160 159 380 262 15/29 8 200 199 380 322 15/29 9 250 249 416 397 13/28/38 11 Table 4 Figure 1. Dimensioned sketch, Tellus-LØV-H VAV Figure 2. Dimensioned sketch, Tellus-LØV-L VAV 46

Tellus-Opus VAV VAV Tellus-Opus VAV is a circular supply diffuser with VAV function for open installation. It has excellent induction and is suitable for both constant and variable air flow rate. The diffuser is also available with a passthrough function. FUNCTION Tellus-Opus VAV has a built-in VAV regulator for demand control of air flow. The damper solution will choke the pressure at high flow rates and maintain a low sound level. This may reduce the need for additional dampers and sound attenuators in a duct system. Tellus-Opus VAV is supplied with Belimo MP-Bus. For communication with Modbus, LON, KNX and BACnet, a Belimo UK 24-Gateway can be utilised. Measurement deviation for the area: 10-20% of nominal: ±25% 20-40% of nominal: <±10% 40-100% of nominal: <±4 % In order to sustain the product's measurement accuracy, straight ducting of min. 5 x ØD is recommended. Tellus-Opus VAV is designed as a complete measurement and regulating unit for demand control of air flow in the ventilation system. The measuring station measures the differential pressure via a sensor integrated into the unit. The unit is equipped with a CHV-VAV-MP regulator from Belimo. The regulator specifications are provided in the table below. Tellus-Opus VAV has a removable front plate with Opus nozzles. Actuator CHV-VAV-MP Operating voltage AC 24 V 50/60 Hz, DC 24 V Power consumption 1.5W Dim. power 2.5VA Table 1, Technical specification, Belimo VAV regulator QUICK SELECTION, Tellus-Opus VAV (Open) m 3/ h Dim. 25 db(a) 30 db(a) 35 db(a) 125 163 197 239 160 306 375 461 200 388 465 557 250 441 541 663 (75 Pa) m 3/ h Dim. 25 db(a) 30 db(a) 35 db(a) 125 115 170 234 160 252 332 440 200 260 396 550 250 370 475 641 Table 2 REGULATION RANGE, Tellus-Opus VAV Tellus-Opus VAV (m 3/ h) ØD. Minimum Maximum 125 26 265 160 43 434 200 70 700 250 106 1060 Table 3, Regulation range for VAV, air flow rate in m³/h. See calculation diagram for sound power and pressure loss. MATERIALS AND FINISH Tellus-Opus VAV has a galvanised steel finish. The damper is fitted with a polyester cloth. The spigot has an EPDM rubber gasket. Tellus-Opus VAV are delivered in RAL 9003 - gloss 30. ORDER CODE, TELLUS-OPUS VAV 47

Tellus-Opus VAV DIMENSIONS AND WEIGHT, Tellus-Opus VAV Dim. D DA H S Weight [kg] 125 124 380 210 15/29 7.5 160 159 380 262 15/29 8 200 199 380 322 15/29 9 250 249 416 397 15/29 11 Table 4 Figure 1. Dimensioned sketch, Tellus-Opus VAV 48

0 1 2 3 4 5 6 TLK-B TLK is a rectangular supply diffuser for wall mounting, and is ideal for office premises requiring rear-spigot air connection. With a choice of front panels, most room types can be supplied with a flow pattern adapted to size, width, interior, lighting etc. The TLK comes with a choice of three removable front panels - two with LØV perforation for short and long throw length (K and L), and one with Opus nozzles for variable flow pattern (V). With an adjustable mounting frame between the box and the front, the system can be adapted to the thickness of the wall. The box is equipped with removable damper, measuring outlet and a sound absorber in polyester. Available with rear spigot. The K and L type front panels are made of steel with a RAL 9003 - gloss 30 finish. Other colours are available on request. The V type diffuser front features Opus nozzles in ABS plastic, is made of steel and comes in a RAL 9003 - gloss 30 finish. Other colours are also available, but without the adjustable nozzle option. The box is supplied in a galvanised finish, and is internally lined with sound absorber in polyester. EPDM rubber gasket on connection collar. ORDER CODE, TLK box and front Product Connection collar: B = Rear S = Side Dim. 100-250 TLK -B-160 / L / 0 SL = Special finish Front, type: K = LØV perforation, short throw length L = LØV perforation, long throw length V = Opus nozzles, variable flow pattern TLK-B-160 / L / 0 TLK box with rear connection dim. Ø160. Front with LØV perforation, long throw length. Standard scope of use for TLK Distance to opposite wall [m] 0 1 2 3 4 5 6 7 8 9 10 Short throw length (LØV) Long throw length (LØV) QUICK SELECTION TLK-B-K/L TLK-B-K/L m³/h (30Pa) Dim. 25 db(a) 30 db(a) 35 db(a) 100 58 130-125 79 169-160 173 277-200 220 295 410 250 270 482 691 QUICK SELECTION TLK-B-V TLK-B-V m³/h (30Pa) Dim. 25 db(a) 30 db(a) 35 db(a) 100 61 97-125 108 151 187 160 184 292 378 200 252 328 432 250 284 403 569 Table 1, show air flow rates at 30 Pa total pressure loss. Sound level is L WA. QUICK SELECTION TLK-S-K/L TLK-S-K/L m³/h (30Pa) Dim. 25 db(a) 30 db(a) 35 db(a) 100 54 126-125 115 184-160 223 281-200 277 353-250 504 648 756 QUICK SELECTION TLK-S-V TLK-S-V m³/h (30Pa) Dim. 25 db(a) 30 db(a) 35 db(a) 100 61 101 137 125 108 148 187 160 220 302 385 200 252 317 389 250 374 486 605 Table 2, show air flow rates at 30 Pa total pressure loss. Sound level is L WA. Variable throw length (OPUS) Fig. 1: Scope of use TLK 49

TLK-S DIMENSIONS AND WEIGHT, TLK TLK Dim. 100 125 160 200 250 D 99 124 159 199 249 BF 460 510 560 580 840 HF 180 205 255 295 367 BK 418 470 520 540 800 HK 148 173 223 263 337 DB 300 300 300 300 300 Table 3 BF HF HK 10 45 DB D+40 BK ØD Fig. 2, TLK-B 10 BF HK HF 45 A BK Ds ØD D+40 Fig. 3, TLK-S Fig. 4, Front panels 50 3 DS 275 300 335 375 425 A 20 20 22 22 28 Weight [kg] Box 5,0 5,9 7,1 8,7 10 Weight [kg] Front 1,0 1,3 1,7 2,1 3,7

TUB TUB is a supply diffuser for open installation, and is developed to suit premises with high requirements for comfort and design. The diffuser can either be mounted to the ceiling away from the wall or be installed in the corner between wall and ceiling. TUB features a removable front panel with LØV perforation. The unit is available with two different flow patterns, and in 2, 4 and 6-metre lengths. A ½ curved design is used for open ceiling mounting, and a ¼ curved design is used for installation in corner between wall and ceiling. TUB is equipped with an integrated damper, measuring outlet and sound attenuator. Back panel to accommodate wall mounting can be supplied. DIMENSIONS AND WEIGHT, TUB Dim. Design H B Bs Weight[kg] 160 1/2-curved 200 350 175 18 200 1/2-curved 245 456 228 23 250 1/2-curved 295 578 289 30 160 1/4-curved 200 310 115 18 200 1/4-curved 245 408 160 23 250 1/4-curved 295 523 215 30 Table 3 The diffuser front is in a steel design with a RAL 9003 - gloss 30 finish. Other colours are available on request. All other elements are made in galvanised steel. The sound attenuator is lined with a sound absorber in polyester, and the connection collar is fitted with an EPDM rubber gasket. QUICK SELECTION 2000 2000 TUB [m³/h] Dim. 25 db(a) 30 db(a) 35 db(a) 160 256 315 380 200 340 420 490 250 739 828 936 Table 1. Air flow rates TUB-6m at given sound power levels and open damper. Table applies to both 1/2R and 1/4R execution. TUB [m³/h] Dim. 25 db(a) 30 db(a) 35 db(a) 160 250 310 380 200 340 420 490 250 450 660 930 Table 2. Air flow rates TUB-6m at given sound power levels 30Pa pressure loss. Table applies to both 1/2R and 1/4R execution. H 20 Bs B H 20 Bs B ORDER CODE, TUB TUB -160-1/4R -4 / DV / 0 Product SL = Special finish Fig. 1. The figure shows a 1/4R right unit. Dimension: Ø160 - Ø250 Types: 1/2R = ½ curved for ceiling installation 1/4R = ¼ curved for wall/ceiling installation L = Length: 2, 4 or 6 m Flow pattern 1/2R S = Right-angled D = ~ 45 out Flow pattern 1/4R SV = Right-angled out, left SH = Right-angled out, right DV= ~ 45 out, left D = ~ 45 out, right TUB-160-1/4R-4 / DV-0 / 0 TUB dim. Ø160 ¼ curved for ceiling installation, length: 4 m. Flow pattern: ~ 45 out, left. 51

TIH The TIH diffuser is ideal for industrial premises as well as department stores, garage facilities and similar. Available in 3 different designs and sizes, and comes with internal diffuser plate as standard. TIH-1 for circular-duct connection (see fig. 1), TIH-2 for flat-duct connection and TIH-3 with circular connection collar. Annular design is available on request. NB! Remember to specify connection diameter ( D2, fig. 2) when ordering TIH-1. DIMENSIONS AND WEIGHT, TIH TIH Weight Dim. A B H D [kg] 315 465 772 192 314 11 400 587 980 252 399 15 500 730 1225 315 499 20 Table 2: TIH Comes in a galvanised, steel-plated finish. Other materials and colours are available on request. QUICK SELECTION TIH [m³/h] Dim. 30 db(a) 35 db(a) 40 db(a) 315 830 1060 1300 400 1200 1500 2000 500 1700 2200 2700 Table 1: The table provides air flow rates at given sound power levels Fig. 1: TIH ORDER CODE, TIH TIH - 400-2 / 0-0 Product Dimension: Ø315 - Ø500 Type: 1, 2 or 3. As per fig. 1 L = Painted finish SM = Special material Fig. 2: TIH TIH-400-2 / 0-0 TIH, dim. Ø400, type 2. 52

TIR TIR is the ideal solution when high air flow rates are required, and is primarily intended as a freely suspended unit. It can, as an example, be used to supply hot or cold air to the occupied zone in rooms with high ceilings. TIR comes with a perforated face-plate and with fixed slot-height to the diffuser cover which is also the absorption mat. Fitted underneath the face-plate is a string-operated sector shutter where the air flow rate, and thus also the supporting air jet and throw length, are regulated. With a deflector, the slot can be adjusted to provide a vertical air flow (see fig. 4, last page). DIMENSIONS AND WEIGHT, TIR TIR Weight Dim. A B H [kg] 315 480 314 235 7 400 630 399 295 10 500 780 499 360 14 630 880 629 500 18 800 960 798 650 22 Table 4, TIR Supplied in a galvanised, steel-plated finish. Other materials and colours are available on request. QUICK SELECTION, TIR TIR [m³/h] Dim. 30 db(a) 35 db(a) 40 db(a) 315 1370 1620 1870 400 1800 2090 2500 500 2500 2900 3300 630 3300 4100 4700 800 4900 5800 6700 Table 3: The table provides air flow rates at given sound power levels Fig. 3, TIR ORDER CODE, TIR TIR - 500 / LR - 0 / 0-0 Product L = Painted finish Dimension Ø315 SM = Special material LR = Deflector SB = Sector shutter TIR-500/ LR-0 / 0-0 TIR, dim. Ø500, equipped with deflector. 53

DKW DKW is a perforated duct diffuser for freely suspended or embedded installation. The system can be adjusted to the length required by combining active parts and blanked-off ducts. With its choice of flow patterns, the DKW can be used for both under- and overheated air and is a high installation-friendly solution. FLOW PATTERNS To accommodate for room geometry and positioning, the following flow patterns are available. Type and dispersion angle must be included in the order code. * = only as 4m diffuser for Ø315-500 ** = only as 4m diffuser for Ø500 DKW has a diameter equivalent to standard ductwork dimensions. The unit is delivered with an active length of 2 m or 4 m. Total length required is achieved by using blanked-off ducts. Both the blanked-off ducts and active parts are available in 1m or 2m modules. Parts are joined together by means of connection nipples and a sealed end-cover. The DKW is fitted with a suspension bar at the top. DKW comes in a galvanised steel-plate design with a RAL 9003 - gloss 30 finish. Other colours and galvanised versions are available on request. DIMENSIONS AND WEIGHT, DKW DKW has a diameter equivalent to standard ductwork dimensions. The modules are available in 1m or 2m lengths. Fig. 1: Flow patterns and types POSITIONING IN ROOM Air velocities in the occupied zone will, in addition to air flow rate and temperature, depend on solid geometry, heat sources and the positioning of these. In order to limit the risk of draft in the occupied zone, the diffuser should have 3 x ØD from the wall, see figur 2. For undercooled air, mounting height to the diffuser s lower part should be at least 2.5 m at Dt=3, and at least 3.5 at Dt=10. Dim. Weight per meter [kg] 160 2,8 200 3,5 250 4,4 315 5,5 400 6,9 500 8,7 Table 1 QUICK SELECTION DKW [m³/h] Dim. 25 db(a) 30 db(a) 35 db(a) Ø160, 2m 212 246 285 Ø160, 4m 237 276 320 Ø200, 2m 331 384 446 Ø200, 4m 371 431 500 Ø250, 2m 517 601 697 Ø250, 4m 579 673 781 Ø315, 2m 820 954 1106 Ø315, 4m 919 1069 1240 Ø400, 2m 1322 1538 1784 Ø400, 4m 1483 1724 2000 Ø500, 2m 2066 2403 2787 Ø500, 4m 2317 2694 3125 Fig. 2: Spacing for positioning in room ORDER CODE DKW - 160-4 - 2-4 - 2x90 / B - 1500 - S - T - 0 / 0 Product SL = Special finish Dimension: J = Adjustable attachment Ø160 - Ø500 T = Sealed end-cover Active length: 2 or 4 m. S = Connection nipple Active length, split: Length, blanked-off duct: 200-2000 1 or 2 m B = Blanked-off duct Type as per fig. 1 Pattern as per fig. 1 DKW-160-4-2-4-2x90 / B-1500-S-T-0 / 0 DKW, dim. Ø160, 4m length, two 2m units, type 4, pattern: 2x90º. Blanked-off duct, length: 1500, connection nipple and sealed end-cover. Number of connection nipples and sealed end-covers is determined by the total length required. For suspension purposes, each length is delivered with one M6 nut as standard. Table 2: The table shows air flow rate at given sound power levels. 54

RFD RFD is a circular swirl diffuser for ceiling mounting. Swirl diffuser with fixed deflection blades. RFD is made of steel and comes in a RAL 9003 - gloss 30 finish. DIMENSIONS AND WEIGHT, RFD-R-D-K Dim. A B H Weight [kg] 125 123 200 75 0,4 160 158 250 78 0,8 200 198 300 78 1,0 250 248 350 75 1,3 315 313 450 88 2,1 400 398 580 88 3,0 Table 2: QUICK SELECTION, RFD-R-D-K RFD [m³/h] Dim. 25 db(a) 30 db(a) 35 db(a) 125 76 90 107 160 120 144 172 200 158 193 235 250 260 308 366 315 366 440 530 400 471 559 662 ØB ØA 50 H Table 1: The table shows air flow rates at given sound power levels. ORDER CODE, RFD-R-D-K RFD-R-D-K - 160 Product Dimension : Ø125 - Ø400 Fig. 1 RFD-R-D-K - 160 RFD-R-D-K, dimension Ø160 ORDER CODE, Luna Luna-0-0-125-160 UI = Outlet installed, low profile design RH = Plenum box for fixed ceiling plate I = Insulated Dimension outlet: Ø125 Ø400 Dimension inlet: Ø100 Ø315 Luna-0-0-125-160 Luna plenum box with inlet Ø125 and outlet Ø160 55

RFD with Luna plenum box The Luna plenum box is recommended for improved sound attenuation, and works as an adjustment and measurement option. Luna is a rectangular box fitted with a removable damper which provides access to the connecting duct. The damper can be secured in any position required. The Luna plenum box features a damper and measurement device for adjustment. It is insulated with a sound absorber in polyester and is available with one or two dimensional changes between inlet and outlet. Furthermore, the box can be supplied with external condensation insulation. A low-profile design [UI] is also available, and for this design a reduction in capacity of approx. 20% will apply. The distance between diffuser and box can be increased by up to 35 cm without extending the wire and measuring tube. Luna is supplied in a galvanised finish, and with all four internal walls lined with sound absorber in polyester. The connection collar is fitted with an EPDM rubber gasket. DIMENSIONS IONS AND WEIGHT, Luna Dim. D DA B H H1 H2 L L1 L2 Weight Luna [kg] 100-125 99 127 220 122 210 88 325 295 133 2,3 100-160 99 162 220 122 213 91 360 310 150 2,4 125-160 124 162 250 147 238 91 360 335 150 2,9 125-200 124 202 250 147 238 91 400 355 170 3,1 160-200 159 202 340 182 273 91 400 390 170 4,2 160-250 159 252 340 182 270 88 452 415 198 4,6 200-250 199 252 380 222 310 88 452 460 198 5,7 200-315 199 317 380 222 323 101 515 485 228 6,1 250-315 249 317 390 272 373 101 515 535 228 7,4 250-400 249 402 500 272 373 101 600 580 265 9,1 315-400 314 402 500 337 438 101 600 645 265 11 Table 4 QUICK SELECTION RFD-R-D-K Luna [m³/h] Dim. Dim. 25 db(a) 30 db(a) 35 db(a) 125 100-125 58 76 94 160 125-160 90 112 135 200 160-200 154 183 216 250 200-250 209 256 317 315 250-315 266 338 421 400 315-400 360 439 540 Table 3: The table shows air flow rates at given sound power levels and 50 Pa total pressure loss. ORDER CODE, RFD-R-D-K with Luna RFD-R-D-K-L Fig. 2 L-0-0-125-160 L = Luna UI = Outlet installed, low profile design RH = Plenum box for fixed ceiling plate I = Insulated Dimension outlet: Ø125 Ø400 Dimension inlet: Ø100 Ø315 RFD-R-D-K-L-0-0-125-160 RFD-R-D-K swirl diffuser and Luna plenum box with inlet Ø125 and outlet/diffuser dim. Ø160. 56

Orion-LØV Orion-LØV is a square supply diffuser for installation in modular ceiling systems. The unit offers excellent induction, and is suitable for both constant and variable air flow rates. Orion-LØV features a removable front panel with LØV perforation. Rotational pattern is supplied as standard. The unit is equipped with a TA flange suitable for T-profile ceiling systems, but is also available with alternative flange designs, type: DC, DG, DS and EK (see fig. 2 and under order code). DIMENSIONS AND WEIGHT, Orion-LØV Orion-LØV D Weight walve [kg] 125 124 3,9 160 159 3,9 200 199 3,9 250 249 3,9 315 314 3,9 400 399 3,9 Table 2 The front panel, ceiling plate and valve body are in a steel design, and the valve body is equipped with EPDM rubber gasket. Corner connection points are in plastic, and are fitted with holding magnets. All internal and external valve elements are in a RAL 9003 - gloss 30 finish. Other colours are available on request. QUICK SELECTION Orion-LØV [m³/h] Dim. 25 db(a) 30 db(a) 35 db(a) 125 106 125 147 160 181 211 246 200 237 278 326 250 347 403 468 315 472 551 644 400 620 757 925 Table 1: The table provides air flow rates at given sound power levels. Fig. 1 ORDER CODE, Orion-LØV (Orion-LOEV) A-flange Dampa Clip-In Dg-flange Orion-LØV - TA - 160 / 0 Ceiling systems: : TA = A-flange DC = Dampa Clip-In DG = Dg-flange DS = Ds-flange EK 24 = E-flange -T24 EK 15 = E-flange -T15 SL = Special finish Dimension: Ø125 - Ø400 Orion-LOEV-TA-160/0 Orion-LOEV supply diffuser with A flange for T-profile ceiling system, spigot Ø160. DS-flange E-flange BESTILLINGSKODE, ORDER CODE, Luna Luna (Side 2) T24/T15 Luna-0-0-125-160 Fig. 2 UI = Outlet installed, low profile design I = Insulated Dim. outlet: Ø125 - Ø400 Dim. inlet: Ø100 - Ø315 Luna-0-0125-160 Luna with inlet Ø125 and outlet Ø160 57

Orion-LØV with Luna plenum box The Luna plenum box is recommended for improved sound attenuation, and works as an adjustment and measurement unit. Luna is a rectangular box fitted with a removable damper which provides access to the connecting duct. The damper can be secured in any position required. The Luna plenum box features a damper and measuring outlet for commissioning. It is insulated with a sound absorber in polyester and is available with one or two dimensional changes between inlet and outlet. Furthermore, the box can be delivered with external condensation insulation. A low-profile design [UI] is also available, and for this type a reduction in capacity of approx. 20% will apply. The distance between valve and box can be increased by up to 35 cm without extending the wire and measuring tube. Luna is supplied a galvanised finish and with all four internal walls lined with sound absorber in polyester. The spigot is fitted with an EPDM rubber gasket.. QUICK SELECTION Orion-LØV Luna [m³/h] Dim. Dim. 25 db(a) 30 db(a) 35 db(a) 125 100-125 83 97 115 125-125 76 90 108 160 100-160 86 130 162 125-160 97 126 158 160-160 130 155 184 200 125-200 104 151 198 160-200 166 198 234 200-200 166 202 241 250 160-250 162 216 270 200-250 216 270 328 250-250 274 317 367 315 200-315 212 295 396 250-315 335 407 500 315-315 396 446 518 400 250-400 353 472 594 315-400 468 544 648 Table 3: The table provides air flow rates at given sound power levels and 30 Pa total pressure loss.. ORDER CODE, Orion-LØV (Orion-LOEV) with Luna DIMENSIONS AND WEIGHT, Luna Dim. D DA B H H1 L L1 L2 Weight Luna [kg] 100-125 99 127 220 122 228 325 295 133 2,3 100-160 99 162 220 122 228 360 310 150 2,4 125-125 124 127 250 147 253 360 335 150 2,4 125-160 124 162 250 147 253 360 335 150 2,9 125-200 124 202 250 147 253 400 355 170 3,1 160-160 159 162 340 182 288 400 390 170 4,1 160-200 159 202 340 182 288 400 390 170 4,2 160-250 159 252 340 182 288 452 415 198 4,6 200-200 199 202 380 222 328 452 460 198 5,7 200-250 199 252 380 222 328 452 460 198 5,7 200-315 199 317 380 222 328 515 485 228 6,1 250-250 249 252 390 272 378 515 535 228 7,4 250-315 249 317 390 272 378 515 535 228 7,4 250-400 249 402 500 272 378 600 580 265 9,1 315-315 314 317 500 337 443 600 655 255 10,7 315-400 314 402 500 337 443 600 645 265 10,7 Table 4 Fig. 3 Luna-0-0-125-160 UI = Outlet installed, low profile design I = Insulated Dim. outlet: Ø125 - Ø400 Dim. inlet: Ø100 - Ø315 Luna-0-0125-160 Luna with inlet Ø125 and outlet Ø160 58

Orion-Opus Orion-Opus is a square supply diffuser for installation in modular ceiling systems. The unit offers excellent induction, and is suitable for both constant and variable air flow rates. Orion-Opus features a removable front panel with Opus nozzles, and is available with 4 different nozzle settings: rotational, 1-way, 2-way 180º or 2-way 90º. Please see order code and fig.3. Furthermore, the unit is equipped with a TA flange suitable for T-profile ceiling systems, but is also available with alternative flange designs, type: DC, DG, DS and EK (see fig. 2 and order code). DIMENSIONS AND WEIGHT, Orion-Opus Orion-Opus D Valve weight [kg] 125 124 3,9 160 159 3,9 200 199 3,9 250 249 3,9 315 314 3,9 400 399 3,9 Table 2 The front panel, ceiling plate and valve body are in a steel design, and the connection collar is fitted with an EPDM rubber gasket. Opus nozzles at the front and corner connection points are in plastic. Connection points are fitted with holding magnets. All internal and external valve elements are in a RAL 9003 - gloss 30 finish. Other colours are available on request. QUICK SELECTION Orion-Opus [m³/h] Dim. 25 db(a) 30 db(a) 35 db(a) 125 119 148 180 160 166 202 245 200 223 270 328 250 313 378 457 315 425 504 601 400 544 644 763 Table 1: The table provides air flow rates at given sound power levels. Fig. 1 A-flange A-kant Dampa Clip Clip-In Dg Dg-kant flange Ds Ds-kant flange E flange E-kant T24/T15 ORDER CODE, Orion-Opus Orion-Opus - R - TA - 160 / 0 Fig. 2 Nozzle settings, front: R = Rotational 1 = 1-way 2A = 2-way 180º 2B = 2-way 90º See fig. 3 SL = Special finish Dimension: Ø125 - Ø400 For ceiling system: TA = A flange DC = Dampa Clip In DG = Dg flange DS = Ds flange EK24 = E-flange - T24 EK15 = E-flange - T15 Orion-Opus-R-TA-160/0 Orion-Opus supply diffuser with rotational nozzle setting at front. A flange for T-profile ceiling system, spigot Ø160. Rotation pattern 1-way pattern BESTILLINGSKODE, Luna ORDER CODE, Luna (Side 2) Luna-0-0-125-160 Dim. outlet: Ø125 - Ø400 UI = Outlet installed, Dim. inlet: Ø100 - Ø315 low profile design I = Insulated Luna-0-0125-160 Luna with inlet Ø125 and outlet Ø160. 2-way pattern 180 dgr. Fig. 3 Nozzle settings, Orion-Opus 2-way pattern 90 dgr. 59

Orion-Opus with Luna plenum box 60 The Luna plenum box is recommended for improved sound attenuation, and works as an adjustment and measurement unit. Luna is a rectangular box fitted with a removable damper which provides access to the connecting duct. The damper can be secured in any position required. Luna plenum box features a damper and measuring outlet for commissioning. It is insulated with a sound absorber in polyester and is available with one or two dimensional changes between inlet and outlet. Furthermore, the box can be delivered with external condensation insulation. A low-profile design [UI] is also available, and for this type a reduction in capacity of approx. 20% will apply. The distance between valve and box can be increased by up to 35 cm without extending the wire and measuring tube. Luna is supplied in a galvanised finish, and with all four internal walls lined with sound absorber in polyester. Equipped with EPDM rubber gasket on connection collar. QUICK SELECTION Orion-Opus Luna [m³/h] Dim. Dim. 25 db(a) 30 db(a) 35 db(a) 125 100-125 61 90 119 125-125 79 104 133 160 100-160 61 97 130 125-160 83 126 184 160-160 122 148 180 200 125-200 76 137 216 160-200 151 198 266 200-200 184 223 270 250 160-250 137 216 320 200-250 216 277 353 250-250 266 324 396 315 200-315 227 320 439 250-315 324 396 500 315-315 382 443 526 400 250-400 338 432 576 315-400 450 536 641 Table 3: The table provides air flow rates at given sound power levels and 30 Pa total pressure loss. ORDER CODE, Orion-Opus with Luna Orion-Opus - R - TA - L / 0 SL = Special finish Nozzle settings, front: R = Rotational 1 = 1-way 2 = 2-way 2A = 2-way 180º 2B = 2-way 90º See fig. 3 For ceiling system: TA = A flange DC = Dampa Clip In DG = Dg flange DS = Ds flange EK 24 = E-flange - T24 EK 15 = E-flange - T15 L - 0-0 - 125-160 L = Luna Dim. outlet: Ø125 - Ø400 UI = Outlet installed, low profile design Dim. inlet: Ø100 - Ø315 I = Insulated Orion-Opus-R-TA-L-0-0-125-160/0 Orion-Opus supply diffuser with rotational nozzle setting at front, A flange for T-profile ceiling system. Luna plenum box, inlet dim. Ø125 and outlet/valve dim. Ø160. DIMENSIONS AND WEIGHT, Luna Dim. D DA B H H1 L L1 L2 Weight Luna [kg] 100-125 99 127 220 122 228 325 295 133 2,3 100-160 99 162 220 122 228 360 310 150 2,4 125-125 124 127 250 147 253 360 335 150 2,4 125-160 124 162 250 147 253 360 335 150 2,9 125-200 124 202 250 147 253 400 355 170 3,1 160-160 159 162 340 182 288 400 390 170 4,1 160-200 159 202 340 182 288 400 390 170 4,2 160-250 159 252 340 182 288 452 415 198 4,6 200-200 199 202 380 222 328 452 460 198 5,7 200-250 199 252 380 222 328 452 460 198 5,7 200-315 199 317 380 222 328 515 485 228 6,1 250-250 249 252 390 272 378 515 535 228 7,4 250-315 249 317 390 272 378 515 535 228 7,4 250-400 249 402 500 272 378 600 535 260 9,1 315-315 314 317 500 337 443 600 655 260 10,7 315-400 314 402 500 337 443 600 655 260 10,7 Table 4 Fig. 4

Orion-PTV Orion-PTV is a square supply diffuser for installation in modular ceiling systems. Orion-PTV is a high-capacity system with excellent induction, and is ideal for high air flow rates. Orion-PTV features a removable front panel with perforated front and sides. The unit is equipped with a TA flange suitable for T-profile ceiling systems, but is also available with alternative flange designs, type: DC, DG, DS and EK (see fig. 2 and order code). DIMENSIONS AND WEIGHT, Orion-PTV Orion-PTV D Vekt ventil [kg] 125 124 3,9 160 159 3,9 200 199 3,9 250 249 3,9 315 314 3,9 400 399 3,9 Tabell 2 The front panel, ceiling plate and valve body are in a steel design, and the connection collar is fitted with an EPDM rubber gasket. Corner connection points are in plastic, and are fitted with holding magnets. All internal and external valve elements are in a RAL 9003 - gloss 30 finish. Other colours are available on request. QUICK SELECTION Orion-PTV [m³/h] Dim. 25 db(a) 30 db(a) 35 db(a) 125 140 162 191 160 184 212 248 200 234 270 310 250 299 346 403 315 410 479 558 400 648 756 878 Table 1: Air flow rate at given sound power levels Fig. 1 ORDER CODE, ORION-PTV A-flange A-kant Dampa Clip-In Dg-flange Dg-kant Orion-PTV - TA - 160 / 0 For ceiling system: TA = A-flange DC = Dampa clip in DG = Dg flanget DS = Ds flange EK24 = E-flange-T24 EK15 = E-flange-T15 SL = Special finish Dimension: Ø125 - Ø400 Ds-flange Ds-kant E-flange E-kant Orion-PTV-TA-160/0 Orion-PTV supply diffuser with A flange for T-profile ceiling system, spigot Ø160. ORDER CODE, Luna Luna-0-0-125-160 Fig. 2 T24/T15 UI = Outlet installed, low profile design I = Insulated Dim. outlet: Ø125 - Ø400 Dim. inlet: Ø100 - Ø315 Luna-0-0125-160 Luna with inlet Ø125 and outlet Ø160. 61

Orion-PTV with Luna plenum box The Luna plenum box is recommended for improved sound attenuation, and works as an adjustment and measurement unit. Luna is a rectangular box fitted with a removable damper which provides access to the connecting duct. The damper can be secured in any position required. Luna plenum box features a damper and measuring outlet for commissioning, is lined with a sound absorber in polyester and is available with one or two dimensional changes between inlet and outlet. Furthermore, the box can be delivered with external condensation insulation. A lowprofile design [UI] is also available, and for this type a reduction in capacity of approx. 20% will apply. The distance between valve and box can be increased by up to 35 cm without extending the wire and measuring tube. The front panel, ceiling plate and valve body are in a steel design, and the connection collar is fitted with an EPDM rubber gasket. Corner connection points are in plastic, and are fitted with holding magnets. All internal and external valve elements are in a RAL 9003 - gloss 30 finish. Other colours are available on request. QUICK SELECTION Orion-PTV Luna [m³/h] Dim. Dim. 25 db(a) 30 db(a) 35 db(a) 125 100-125 61 90 126 125-125 83 112 151 160 100-160 58 112 162 125-160 90 137 187 160-160 144 180 220 200 125-200 90 140 216 160-200 166 223 274 200-200 187 230 277 250 160-250 144 216 324 200-250 176 209 248 250-250 263 306 360 315 200-315 198 281 374 250-315 317 371 457 315-315 371 428 497 400 250-400 364 457 547 315-400 432 504 605 Table 3: Air flow rates at given sound power levels and 30 Pa total pressure loss. DIMENSIONS AND WEIGHT, Luna Dim. D DA B H H1 L L1 L2 Weight Luna [kg] 100-125 99 127 220 122 228 325 295 133 2,3 100-160 99 162 220 122 228 360 310 150 2,4 125-125 124 127 250 147 253 360 335 150 2,4 125-160 124 162 250 147 253 360 335 150 2,9 125-200 124 202 250 147 253 400 355 170 3,1 160-160 159 162 340 182 288 400 390 170 4,1 160-200 159 202 340 182 288 400 390 170 4,2 160-250 159 252 340 182 288 452 415 198 4,6 200-200 199 202 380 222 328 452 460 198 5,7 200-250 199 252 380 222 328 452 460 198 5,7 200-315 199 317 380 222 328 515 485 228 6,1 250-250 249 252 390 272 378 515 535 228 7,4 250-315 249 317 390 272 378 515 535 228 7,4 250-400 249 402 500 272 378 600 580 265 9,1 315-315 314 317 500 337 443 600 655 255 10,7 315-400 314 402 500 337 443 600 645 265 10,7 Table 4 Fig. 3 ORDER CODE, Orion-PTV with Luna Orion-PTV - TA - L / 0 Product For ceiling system: TA = A-flange DC = Dampa clip-in DG = Dg-flange DS = Ds-flange EK24 = E-flange-T24 EK15 = E-flange-T15 L = Luna UI = Outlet installed, low profile design I = Insulated SL = Special finish L - 0-0 - 125-160 Dim. outlet: Ø125 - Ø400 Dim. inlet: Ø100 - Ø315 62 Orion-PTV-TA-L-0-0-125-160/0 Orion-PTV supply diffuser with A flange for T- profile ceiling system, Luna plenum box inlet dim. Ø125 and outlet/valve dim. Ø160. 3

JBV These air diffusers are designed for comfort ventilation in all types of homes where balanced ventilation is installed, e.g. new builds or rehabilitated blocks of flats. They are designed for standard wall thicknesses with steel joists and a single sheet of plasterboard on both sides. The rectangular JBV air diffuser consists of two parts: the mounting frame, with a spigot for the supply air duct, and a removable front face. No tools are required to install the diffuser face, and it can be easily removed for cleaning, etc. The diffuser face has separate grooves for control wires and measuring tubes. DIMENSIONS AND WEIGHT, JBV Dim D H Weight [kg] 100 99 147 0,7 125 124 147 0,8 160 159 202 0,9 Table 1 MATERIALS AND FINISH The diffuser's parts are made of galvanised sheet steel. The surface is painted standard white RAL 9003 - gloss 30. ORDER CODE, JBV JBV- 100 / 0 Product Dimension: 100,125 or 160 SL = Special paint Figure 1, JBV JBV-100/0 JBV diffuser dimension Ø100, standard paint RAL 9003 - gloss 30. ORDER CODE, BVK BVK - R - 100 Produkt: R = Straight design V= Angle design Dimension Dimensjon intake innløp - utløp: outflow: 100-100, 125-125 eller or 160-160 BVK-R-100 BVK box with Ø100 intake and Ø100 outflow. 63

JBV with BVK box A BVK plenum box is recommended because it provides better sound attenuation and control and measuring options. The BVK is a rectangular box with detachable sound insulation and a damper which provides access to the connecting duct. The damper can be locked in any position required. The BVK comes in two designs, straight and angled. The sound insulation effectively dampens sound and releases no material fibres to the surroundings. The insulation can be removed for cleaning. The plenum box features a wire operated damper and measuring outlet for adjustment. DIMENSIONS AND WEIGHT, BVK Dim. D DA B H C Weight [kg] 100-100 99 102 154 154 116 2,9 125-125 124 127 154 154 116 3,1 160-160 159 162 189 189 132 3,3 Table 4 MATERIALS AND FINISH The BVK is supplied with a galvanised finish and polyester sound insulation. The spigot has a rubber EPDM seal. QUICK PICK, JBV with BVK-R box JBV BVK-R [m³/h] Dim Dim 25dB 30dB 35dB 100 100-100 65 79 90 125 125-125 94 108 122 160 160-160 130 151 162 Table 2: the table shows the air flow rate at the stated sound power level and 30Pa total pressure. Figure 2, BVK-R QUICK PICK, JBV with BVK-V box JBV BVK-V [m³/h] Dim Dim 25dB 30dB 35dB 100 100-100 61 76 86 125 125-125 83 94 108 160 160-160 115 133 155 Table 3: the table shows the air flow rate at the stated sound power level and 30Pa total pressure. Figure 3, BVK-V ORDER CODE, JBV with BVK JBV - K / 0 SL= Special paint K - R - 100 Produkt: K = BVK kammer R = Straight design V = Angle design Dimensjon Dimension innløp intake - utløp: outflow 100-100, 125-125 or eller 160-160 JBV-K-R-100/0 JBV diffuser with accompanying BVK box, box with intake dimension Ø100 and outflow/diffuser dimension Ø100. Diffuser painted with standard RAL 9003 - gloss 30. 64

Orion-LØV with Sirius Orion-LØV with Sirius is a diffuser unit with VAV function, and is used as volume flow controller and diffuser in ventilation systems to enable air flow rates to be set as per requirements. Orion-LØV offers excellent induction, and is ideal for variable air flow rates. FUNCTION Orion-LØV with Sirius has a built-in VAV controller for adjustment of air flow rates according to requirements. The damper solution will choke the pressure at high flow rates and will maintain a low sound level. This may reduce the need for additional dampers and sound attenuators in a duct system. Orion-LØV with Sirius is delivered with Belimo MP-bus, LON, Modbus or Belimo KNX for direct BUS communication to SD systems. Deviation for working range 10-20% of V nom :±25% 20-40%: of V nom <±10% 40-100%: of V nom <±4% If T-pipes are used, a spacing of at least 5 x ØD is recommended in order to maintain the measurement accuracy. ORDER CODE, diffuser - Orion-LØV Sirius (Connection 4 and 6) Orion-LØV-Sirius supply diffuser with A flange for T-profile ceiling system, Orion-LØV with Sirius is a complete measuring and control unit where the air flow rates in ventilation systems can be set as required. At the measuring station, the differential pressure is measured by using measuring rods integrated in the unit. Sirius is equipped with LHV.D3 VAV controller from Belimo. Controller specifications are provided in the table below. Full technical documentation can be downloaded from www.belimo.eu. Orion-LØV features a removable front panel with LØV perforation, and is suitable for a range of ceiling systems. Actuator LHV-D3-MP/MOD/LON Operating voltage AC 24 V 50/60 Hz, DC 24 V Power drain 2,5W Dim. effect 4.5VA (max.8 A @5 ms) Table 1: Technical specifications, Belimo VAV controller Sirius comes in a galvanised steel design. The measurement unit is in aluminium, and hoses and nipples are in plastic. The damper is equipped with polyester material, and the connection collar is fitted with EPDM rubber gasket. ORDER CODE, Sirius Dim: 125-200 160-250 200-315 250-400 Sirius - 125-200 - 4 Connection: 0 = MP-Bus 1 = MP-Bus with VIP-X plug 2 = LON-Bus 3 = MOD-Bus 4 = MP-Bus with EasyLink plug 5 = Stand alone with trafo for CO2 and temperature 6 = Stand alone with trafo for PIR/potential free switch 7 = Belimo KNX 8 = MOD-Bus for X-AIRCONTROL Sirius-125-200-4 Sirius with Ø125 inlet and Ø200 outlet, ready for EasyLink with MP-Bus controller. 65

Orion-LØV with Sirius QUICK SELECTION, Orion-LØV with Sirius [open] m³/h Sirius dim. 25dB(A) 30dB(A) 35dB(A) 125 155 184 220 160 256 310 374 200 374 446 529 250 526 626 749 (75Pa) m³/h Sirius dim. 25dB(A) 30dB(A) 35dB(A) 125 144 184 220 160 234 295 374 200 367 443 529 250 342 569 734 DIMENSIONS AND WEIGHT, Orion-LØV with Sirius Dim. D DA B H L L1 Weight Weight Sirius Sirius with valvel [kg] [kg] 125-200 124 202 325 175 645 386 8 12 160-250 159 252 360 210 645 402 9 13 200-315 199 317 400 240 645 435 10,5 14,5 250-400 249 402 450 290 645 392 12 16 Table 4 Table 2: Quick selection, Orion-LØV with Sirius Sirius (m³/h) ØD. Minimum Maximum 125 26 265 160 43 434 200 70 700 250 106 1060 Table 3: Adjustment range for VAV controller, air flow rate in m 3 /h. See calculation diagram for sound power level and pressure drop. ORDER CODE, Orion-LØV with Sirius Fig. 1: Dimensions, Orion-LØV with Sirius Orion-LØV-Sirius TA B 200 S 0 SL = Special finish Modular ceiling system: TA=A-flange DC=Dampa Clip-In SK - 125-200 - 4 DG=Dg-flange Connection: DS=Ds-flange SK=Sirius 0 = MP-Bus EK 24=E-flange-T24 1 = MP-Bus with 4 pole plug EK 15=E-flange-T15 Inlet-outlet 2 = LON-Bus 125-200 3 = MOD-Bus B=Motion sensor 160-250 4 = MP-Bus with EasyLink plug (Connection 4 and 6) 5 = Stand alone with trafo for 200-315 CO2 and temperature Dim: Ø200,Ø250,Ø315,Ø400 250-400 6 = Stand alone with trafo for PIR/potential free switch 7 = Belimo KNX 8 = MOD-Bus for X-AIRCONTROL Orion-LØV-Sirius-TA-B-200-SK-125-200-4/0 Orion-LØV-Sirius supply diffuser with A flange for T-profile, motion-sensor at diffuser front, spigot Ø200, Sirius box Ø125 inlet and Ø200 outlet, ready for EasyLink with MP-Bus controller. 66

Orion-Opus with Sirius Orion-Opus with Sirius is a diffuser unit with VAV function, and is used as volume flow controller and diffuser in ventilation systems to enable air flow rates to be set as per requirements. Orion-Opus offers excellent induction, and is ideal for variable air flow rates. FUNCTION Orion-Opus with Sirius has a built-in VAV controller for adjustment of air flow rate. The damper solution will choke the pressure at high flow rates and will maintain a low sound level. This may reduce the need for additional dampers and sound attenuators in a duct system. Orion-Opus with Sirius is delivered with Belimo MP-Bus, LON, Modbus or belimo KNX for direct BUS communication to SD systems. Deviation for working range 10-20% of V nom :±25% 20-40%: of V nom <±10% 40-100%: of V nom <±4% If T-pipes are used, a spacing of at least 5 x ØD is recommended in order to maintain the measurement accuracy. Orion-Opus with Sirius is a complete measuring and control unit where the air flow rates in ventilation systems can be set as required. At the measuring station, the differential pressure is measured by using measuring rods integrated in the unit. Sirius is equipped with LHV-D3 VAV controller from Belimo. Controller specifications are provided in the table below. Full technical documentation can be downloaded from www.belimo.eu. Orion-Opus with Sirius features a removable front panel, and is available with 4 different nozzle settings: rotational, 1-way, 2-way 180 or 2-way 90. It is suitable for a range of ceiling systems. Actuator LHV-D3-MP/MOD/LON Operating voltage AC 24 V 50/60 Hz, DC 24 V Power drain 2,5W Dim. effect 4.5VA (max.8 A @5 ms) Table 1: Technical specifications, Belimo VAV controller Sirius comes in a galvanised steel design. The measurement unit is in aluminium, and hoses and nipples are in plastic. The damper is equipped with polyester material, and the connection collar is fitted with EPDM rubber gasket ORDER CODE, diffuser - Orion-Opus Sirius (Connection 4 and 6) ORDER CODE, Sirius Dim: 125-200 160-250 200-315 250-400 Sirius - 125-200 - 4 Connection: 0 = MP-Bus 1 = MP-Bus with VIP-X plug 2 = LON-Bus 3 = MOD-Bus 4 = MP-Bus with EasyLink plug 5 = Stand alone with trafo for CO2 and temperature 6 = Stand alone with trafo for PIR/potential free switch 7 = Belimo KNX 8 = Mod-Bus for X-AIRCONTROL Sirius-125-200-4 Sirius with Ø125 inlet and Ø200 outlet, ready for EasyLink with MP-Bus controller. 67

Orion-Opus with Sirius QUICK SELECTION, Orion-OPUS with Sirius [Open] m³/h Sirius dim. 25dB(A) 30dB(A) 35dB(A) 125 175 221 280 160 306 367 440 200 374 446 529 250 478 575 692 (75Pa) m³/h Sirius dim. 25dB(A) 30dB(A) 35dB(A) 125 158 223-160 252 353 432 200 360 450 558 250 360 526 677 Table 2: Quick selection, Orion-Opus with Sirius DIMENSIONS AND WEIGHT, Orion-Opus with Sirius Dim. D DA B H L L1 Weight Weight Sirius Sirius with valve [kg] [kg] 125-200 124 202 325 175 645 386 8 12 160-250 159 252 360 210 645 402 9 13 200-315 199 317 400 240 645 435 10,5 14,5 250-400 249 402 450 290 645 392 12 16 Table 4 Sirius (m³/h) ØD. Minimum Maximum 125 26 265 160 43 434 200 70 700 250 106 1060 Table 3: Adjustment range for VAV controller, air flow rate in m3/h. See calculation diagram for sound power level and pressure drop. ORDER CODE, Orion-Opus with Sirius Fig. 1: Dimensions, Orion-Opus with Sirius Orion-Opus-Sirius R TA B 200 SK 0 SL=Special finish 68 Nozzle settings front: R = Rotational 1 = 1-way 2A = 2-way 180 2B = 2-way 90 Dim: Ø200 Ø250 Ø315 Ø400 Modular ceiling system: SK - 125-200 - 4 TA=A-flange DC=Dampa Clip-In Connection: DG=Dg-flange 0 = MP-Bus SK=Sirius DS=Ds-flange 1 = MP-Bus with VIP-X plug EK 24=E-flange-T24 Inlet - outlet 2 = LON-Bus EK 15=E-flange-T15 125-200 3 = MOD-Bus B=Motion-sensor (Connection 4 and 6) 160-250 4 = MP-Bus with EasyLink plug 200-315 5 = Stand alone with trafo for 250-400 CO2 and temperature 6 = Stand alone with trafo for PIR/ potential free switch 7 = Belimo KNX Orion-Opus-Sirius-R-TA-B-200-SK-125-200-4/0 8 = MOD-Bus for X-AIRCONTROL Orion-Opus-Sirius supply diffuser with rotational nozzle setting at front, A flange for T-profile ceiling system, motion-sensor at front, spigot Ø200, Sirius box inlet Ø125 and outlet Ø200, Ready for EasyLink with MP-Bus controller. 3

Orion-PTV with Sirius Orion-PTV with Sirius is a diffuser unit with VAV function, and is used as volume flow controller and diffuser in ventilation systems to enable air flow rates to be set as per requirements. Orion-PTV is a highcapacity system with excellent induction, and is ideal for high air flow rates. FUNCTION Orion-PTV with Sirius has a built-in VAV controller for adjustment of air flow rates according to requirements. The damper solution will choke the pressure at high flow rates and will maintain a low sound level. This may reduce the need for additional dampers and sound attenuators in a duct system. Orion-PTV with Sirius is delivered with Belimo MP-Bus, LON, Modbus or Belimo KNX for direct BUS communocation to SD systems. Deviation for working range 10-20% of V nom :±25% 20-40%: of V nom <±10% 40-100%: of V nom <±4% If T-pipes are used, a spacing of at least 5 x ØD is recommended in order to maintain the measurement accuracy. Orion-PTV with Sirius is a complete measuring and control unit where the air flow rates in ventilation systems can be set as required. At the measuring station, the differential pressure is measured by using measuring rods integrated in the unit. Sirius is equipped with LHV-D3 VAV controller from Belimo. Controller specifications are provided in the table below. Full technical documentation can be downloaded from www.belimo.eu. Orion-PTV features a removable front panel with perforation at the front and sides, and is suitable for a range of ceiling systems. Actuator Operating voltage Power drain 2,5W Dim. effect LHV-D3-MP/MOD/LON AC 24 V 50/60 Hz, DC 24 V 4.5VA (max.8 A @5 ms) Table 1: Technical specifications, Belimo VAV controller Sirius comes in a galvanised steel design. The measurement unit is in aluminium, and hoses and nipples are in plastic. The damper is equipped with polyester material, and the connection collar is fitted with EPDM rubber gasket. ORDER CODE, diffuser - Orion-PTV Sirius ORDER CODE, Sirius Dim: 125-200 160-250 200-315 250-400 (Connection 4 and 6) Sirius - 125-200 - 4 Connection: 0 = MP-Bus 1 = MP-Bus with VIP-X plug 2 = LON-Bus 3 = MOD-Bus 4 = MP-Bus with EasyLink plug 5 = Stand alone with trafo for room controller 6 = Stand alone with trafo for PIR/potential free switch 7 = Belimo KNX 8 = MOD-Bus for X-AIRCONTROL Sirius-125-200-4 Sirius with inlet Ø125 and outlet Ø200, ready for EasyLink with MP-Bus controller. 69

Orion-PTV with Sirius QUICK SELECTION, Orion-PTV with Sirius [Open] m³/h Sirius dim. 25dB(A) 30dB(A) 35dB(A) 125 198 238 284 160 299 352 414 200 374 440 516 250 498 597 715 (75Pa) m³/h Sirius dim. 25dB(A) 30dB(A) 35dB(A) 125 166 234 288 160 234 334 414 200 378 438 510 250 382 547 697 DIMENSIONS AND WEIGHT, Orion-PTV with Sirius Dim. D DA B H L L1 Weight Weight Sirius Sirius with valve [kg] [kg] 125-200 124 202 325 175 645 386 8 12 160-250 159 252 360 210 645 402 9 13 200-315 199 317 400 240 645 435 10,5 14,5 250-400 249 402 450 290 645 392 12 16 Table 4 Table 2: Quick selection, Orion-PTV with Sirius Sirius (m³/h) ØD. Minimum Maksimum 125 26 265 160 43 434 200 70 700 250 106 1060 Table 3: Adjustment range for VAV controller, air flow rate in m 3 /h. See calculation diagram for sound power level and pressure drop. ORDER CODE, Orion-PTV with Sirius Fig. 1:Dimensions, Orion-PTV with Sirius Orion-PTV-Sirius TA B 200 S 0 Modular ceiling system: TA=A-flange DC=Dampa Clip-In DG=Dg-flange DS=Ds-flange EK 24=E-flange-T24 EK 15=E-flange-T15 B=Motion-sensor (Connection 4 and 6) Dim: Ø200,Ø250,Ø315,Ø400 SL = Special finish SK - 125-200 - 4 Connection: 0 = MP-Bus SK=Sirius 1 = MP-Bus with VIP-X plug Inlet-outlet 2 = LON-Bus 125-200 3 = MOD-Bus 160-250 4 = MP-Bus with EasyLink plug 200-315 5 = Stand alone with trafo for room controller 250-400 6 = Stand alone with trafo for PIR/potential free switch 7 = Belimo KNX 8 = MOD-Bus for X-AIRCONTROL Orion-PTV-Sirius-TA-B-200-SK-125-200-4/0 Orion-PTV-Sirius supply diffuser with A flange for T-profile, motion sensor at diffuser front, spigot Ø200, Sirius box inlet Ø125 and outlet Ø200, ready for EasyLink with MP-Bus controller. 70 3

Siv-inn 1 The Siv-inn 1 diffuser units are designed for wall mounting, and are intended solely for displacement ventilation. For floor mounting, the unit is turned over and a decorative cover fitted to the top. Siv-inn 1 comprises a base, diffuser unit, main cover with splice connector and telescopic cover on top. The front is perforated with a design-protected clover pattern. The standard design covers ceiling heights of between 2.3 and 2.9 m (incl. 75 mm base unit). All parts are in a steel design. The unit comes in a RAL 9003 - gloss 30 finish. DIMENSIONS AND WEIGHT, Siv-inn 1 Dim. A B C1 C2 D E H1 Weight [kg] 100 275 177 78,5 70 99 145 600 5 125 326 227 97,5 85 124 175 600 6 160 375 262 115 106 159 215 600 7 200 454 317 135 126 199 255 900 11 250 546 382 161 151 249 305 900 13 315 681 480 193 188 314 380 1200 19 400 808 570 235 255 398 460 1500 28 Table 2, Siv-inn 1 QUICK SELECTION Siv-inn 1 [m³/h] Dim. 25 db(a) 30 db(a) 35 db(a) 100 120 150 170 125 170 220 280 160 220 290 320 200 360 540 720 250 540 720 900 315 1080 1260 1620 400 1440 1800 2160 Table 1: The table shows air flow rates at given sound power levels. Siv-inn 1 1/4R ORDER CODE, Siv-inn 1 Siv-inn 1-1/2R -200 / 0 -S-0-0-0 / 0 Produc t SL = Special finish 1/4R =1/4curved SM=Special material or 1/2R = 1/2 curved reinforced front: 1.25 mm Dimension: Ø100 -Ø400 SN = SSP connection nipple T = Telescopic cover L = LSM for commissioning* S=Base P = Decorative cover for floor mounting Siv-inn 1-1/2R-200 / 0-S-0-0-0 / 0 Siv-inn 1-½ curved, dimension Ø200 and suitable base * = not applicable to dim. Ø400 Siv-inn 1 1/2R Fig. 1, Siv-inn 1 71

Siv-inn 2000 In principle, Siv-inn 2000 is a complete Siv-inn 1 unit, i.e. with damper, measuring outlet and sound attenuator. Siv-inn 2000 comprises a complete diffuser unit with a telescopic cover on top. Base is supplied as accessory. Front perforation is a design-protected clover pattern. The standard design covers ceiling heights of between 2.3 and 2.9 m (incl. 75 mm base unit). DIMENSIONS AND WEIGHT, Siv-inn 2000 Dim. A B C1 C2 D E Weight [kg] 125 326 227 97.5 85 124 175 9.5 160 375 262 115 106 159 215 11,5 200 454 317 135 126 199 255 16, 250 546 382 161 151 249 305 20,0 Table 4, Siv-inn 2000 All parts are in a steel design. The unit comes in a RAL 9003 - gloss 30 finish. QUICK SELECTION Siv-inn 2000 [m³/h] Dim. 25 db (A) 30 db (A) 35 db (A) 125 150 200 250 160 180 260 340 200 350 470 620 250 500 650 800 Table 3: The table shows air flow rates at given sound power levels. Siv-inn 2000 1/4R ORDER CODE, Siv-inn 2000 Siv-inn 2000-1/4R - 160 / S / 0-0 Product 1/4R = 1/4 curved 1/2R = 1/2 curved Dimensjon: Ø125 - Ø250 SL = Special finish SM = Special material or reinforced front: 1.25 mm S = Base Siv-inn 2000-1/4R-160 / S / 0-0 Siv-inn 2000 - ¼ curved, dimension Ø160 and suitable base Siv-inn 2000 1/2R Fig. 2, Siv-inn 2000 72

Siv-inn Inlaid The 300x600, 600x300, 400x400, 600x600 and 600x900 product range comprises air supply units for displacement ventilation, and is designed for embedded installation in wall. Siv-inn Inlaid features a duct, box and front grille. Duct height can be adjusted as stated in table 2. The front grill is available in 5 dimension options, and is easily assembled with the screws supplied. DIMENSIONS AND WEIGHT, Siv-inn Inlaid Dim. B H C D BK HK E F L weight* [kg] 300-600 300 600 72 125 243 543 210 49 1355-2620 11 600-300 600 300 72 125 543 243 210 49 1625-2620 11 400-400 400 400 72 125 343 343 210 49 1625-2620 12 600-600 600 600 72 160 543 543 500 49 1390-2350 21 600-900 600 900 92 200 543 843 500 64 1420-2350 25 Table 2: Siv-inn Inlaid (*weight with duct) Siv-inn Inlaid is made of solid steel plate. The front panel is fitted with a gasket and comes in a RAL 9003 - gloss 30 finish as standard, while the box and duct are in a galvanised steel-plate finish. Reinforced front panel is available on request. QUICK SELECTION Siv-inn Inlaid [m³/h] Type 25 db(a) 30 db(a) 35 db(a) 1 140 160 180 2 200 250 300 3 290 400 470 Table 1: The table shows air flow rates at given sound power levels. Type 1 = Dim. 300x600, 400x400 og 600x300 Type 2 = Dim. 600x600 Type 3 = Dim. 600x900 Fig. 1: Siv-inn Inlaid ORDER CODE, Siv-inn Inlaid Siv-innInlaid - 300-600 / AL - Ø125-0 - 0 / 0-0 Product SL = Special finish, Front Box and front grille, dim.: SM = Spesial material or Width: 300, 400 or 600 reinforced front Height: 300, 400, 600 or 900 (standard dimensions, see table 2) S = SSP L = LSM AL = Moulding Connecting duct, dim.: Ø125 for: 300-600, 400-400 and 600-300 Ø160 for: 600-600 Ø200 for: 600-900 Siv-Inn Inlaid-300-600 / AL-Ø125-0-0 / 0-0 Siv-inn Inlaid, box and front dimensions: 300 x 600. Supplied with moulding and connecting duct Ø125. 73

Siv-inn School Siv-inn School is designed for classrooms and lecture halls, but can also be used in other areas. What makes this solution unique is its compliance with the requirements for efficient air replacement, low velocity in the occupied zone and easy-clean design. The unit is particularly well-suited for renovation work as it provides a certain clearance between diffuser and wall. Conflict with cornices, cables, etc. is thus avoided. The unit features a sound attenuator, measuring station and damper. Its front, perforated with our design protected-clover pattern, provides excellent induction and even air distribution to the room. The unit comes in a galvanized steel-plate design, with a RAL 9003 - gloss 30 finish as standard. Other materials/colours are available on request. DIMENSIONS AND WEIGHT, Siv-inn School Dim. d D H tot Weight [kg] 125 124 165 2075 7,5 160 159 205 2080 9,0 200 199 255 2090 17,0 250 249 320 2110 19,5 315 314 405 2340 22,5 Table 2 Adjustable: 70-90 mm. QUICK SELECTION Siv-inn School [m³/h] Dim. 25 db(a) 30 db(a) 35 db(a) 125 140 200 250 160 230 270 340 200 340 530 520 250 610 750 900 315 720 1080 1440 Table 1. The table shows air flow rates at given sound power levels. Fig.1 ORDER CODE, Siv-inn School 74

Siv-inn 2 Siv-inn 2 is designed for displacement ventilation in industrial buildings. Comes with a top-entry spigot, and is available in a rectangular as well as a 1/4, 1/2 and 1/1 curved design. All parts are in a steel design. The unit is delivered in a galvanized steel finish as standard, but is also available in special material and/or in an painted finish. QUICK SELECTION, Siv-inn 2. 1/4R, 1/2R og 1/1R H = 1500 and H = 2000 Siv-inn 2 [m³/h] Dim. 35 db(a) 40 db(a) 45 db(a) 315 1370 1550 2000 400 2000 2450 3000 500 3100 4000 4700 630 4700 5700 6500 800 5800 6800 8300 Table 1: The table shows air flow rates at given sound power levels. DIMENSIONS AND WEIGHT, Siv-inn 2 Dim. A B C D E Weight [kg] Weight [kg] *1/2R *1/1R 315 485 500 235 314 400 28 / 37 21 / 27 400 605 630 290 399 500 35 / 45 27 / 35 500 760 800 360 499 630 44 / 56 33 / 42 630 970 1000 470 629 800 59 / 75 43 / 55 800 1220 1200 620 799 1000 83 / 103 55 / 70 Table 3: Siv-inn 2. 1/2R and 1/1R (*for H=1500 and H=2000 respectively). Dim. A B D *Weight [kg] 315 713 321 314 38 / 48 400 840 371 399 44 / 57 500 1120 502 499 61 / 77 630 1377 656 629 77 / 97 800 1782 835 799 107 / 132 Table 4: Siv-inn 2. 1/4R (*for H=1500 and H=2000 respectively). Type B C E H D Weight [kg] 128 600 270 145 1200 199 21 206 600 330 180 1980 249 42 2010 995 380 192 1980 314 48 2012 1190 460 232 1980 399 56 Table 5: Siv-inn 2. Rectangular QUICK SELECTION, Siv-inn 2. Rectangular Siv-inn 2 [m³/h] Type 35 db(a) 40 db(a) 45 db(a) 128 540 630 810 206 828 954 1152 2010 1278 1584 1980 2012 1602 1980 2340 Table 2: The table shows air flow rates at given sound power levels. ORDER CODE, Siv-inn 2. 1/4R, 1/2R and 1/1R Siv-inn 2-1/2R - 500-2000 / 0-0 Product 1/4R = 1/4 curved 1/2R = 1/2 curved 1/1R = 1/1 curved SL = Special finish SM = Special material Height: 1500 or 2000 Dimension: Ø315 - Ø800 Siv-inn 2-1/2R-500-2000 / 0-0 Siv-inn 2-1/2 curved, dimension Ø500 and height 2000 ORDER CODE, Siv-inn 2. Rectangular Siv-inn 2-206 / 0-0 Product Type: 128, 206, 2010 or 2012 SL = Special finish SM = Special material Siv-inn 2-206 / 0-0 Siv-Inn 2 type 206 75

A Siv-inn 2 B OD A C H=høyde=1500mm H = height = mm eller or 2000mm mm Fig. 1, Siv-inn 2. 1/2R OE OD H = height = 1500 mm or 2000 mm H=høyde=1500mm eller 2000mm Fig. 2, Siv-inn 2. 1/1R B OD H H=høyde=1500mm = height = mm eller or 2000mm mm Fig. 3, Siv-inn 2. 1/4R OD C E B H = height H=høyde Fig. 4, Siv-inn 2. Rectangular. 76

Siv-inn T/V Siv-inn T/V is a supply diffuser for areas requiring high air flow rates such as commercial kitchens or laboratories. Suitable for open as well as embedded installation (se fig. 2). The product is available in 6 different sizes, with circular end-spigot as standard. External dimensions are designed to fit T-profile ceiling systems with module 600. Alternative connection solutions and positioning are available on request. Siv-inn T/V can also be supplied with perforated sides. The front panel is reinforced and can be removed by unfastening the screws. WEIGHT AND DIMENSIONS, Siv-inn T/V Type A B C D [kg] 0312 1190 290 270 199 10,0 0612 1190 590 320 249 18,5 0618 1790 590 320 249 27,0 1212 1190 1190 380 314 37,0 1218 1790 1190 380 314 55,5 1224 2390 1190 480 399 74,0 Table 2 Siv-inn T/V comes in a galvanised steel-plate design. Sides and front are in a white RAL 9003 - gloss 30 finish. QUICK SELECTION Siv-inn T/V [m³/h] Type 25 db(a) 30 db(a) 35 db(a) 0312 230 300 430 0612 340 470 580 0618 540 680 860 1212 700 900 1200 1218 1000 1200 1600 1224 1200 1600 2000 Table 1: The table shows air flow rates at given sound power levels. Fig. 1 ORDER CODE, Siv-inn T/V Siv-inn T/V - 0612 / 0-0 - 0-0 Product Type: 0312, 0612, 0618, 1212, 1218 or 1224 SL = Special finish SM = Special material P = Perforation long side(s) A = Alternative spigot positioning Siv-inn T/V-0612 / 0-0-0-0 Siv-inn T/V, type: 0612 with spigot Ø250. Fig. 2 77

Siv-inn PP and PK The Siv-inn panel is a customised product offering every solution imaginable in terms of tailored displacement units, and is available as a made-to measure solution as well as with prefabricated plenum boxes suitable for both wall and ceiling mounting. Grilles measuring over 2 m 2 are split. DIMENSIONS AND WEIGHT, SIV-INN PP/PK Weight: approx. 15 kg/m 2. Recomended groove: B+5 and H+5. B+50 Siv-inn PP and PK are available in two standard designs with width/ height measurements to the nearest millimetre. Featuring a flush flange, type PP is an ideal slot-in solution. Type PK is equipped with a bracket flange and is installed as a protruding unit. Siv-inn PK comes with screw holes fitted with gaskets and spacers, and the screws are in a white enamel finish. The front is perforated (15 %) with our clover pattern. H+50 MAX 400 mm H-2 Both types are equipped with a permanent galvanized diffuser plate. The front comes in a RAL 9003 - gloss 30 finish as standard. QUICK SELECTION O 6 B-2 [m³/h] Siv-inn PP/PK 25 db(a) 30 db(a) 35 db(a) 750 900 1100 Table 1: The table shows air flow rates at given sound power levels (per m2 of active area). ORDER CODE, SIV-INN PP/PK 30 30 10 PK B-2 B-2 Product Type: PP = Flush flange PK = Bracet flange Width: (mm.) Siv-inn - PP - 500-800 / 0-0 SL = Special finish SM = Special material Hight: (mm.) PP 2 Fig. 1: Siv-inn PP and PK Siv-Inn-PP-500-800 / 0-0 Siv-inn front with flush flange, width: 500 mm and height: 800 mm. ORDER CODE, Siv-inn PP/PK Box Fig. 2: Spigot entry pos. 2 or pos. 3 requires a minimum C-dimension of: ød + 30. Option 4, loose spigot: optional mounting location. Installer creates mounting hole for spigot 78

Siv-inn Aula Siv-inn Aula 100 and 125 are primarily intended to meet seating area requirements as shown in fig. 1A. Siv-inn Aula 400, 500 and 600 are intended for low risers as shown in fig. 1B. Siv-inn Aula 2000 is also intended for low risers, but offers continuous-length mounting as shown in fig. 1C. ORDER CODE, Siv-inn-Aula 100 og 125, 0-0 Fig. 1 ORDER CODE, Siv-inn-Aula 400, 500 og 600 SM = Aula 100 and 125 are available in a circular design with Ø100 and Ø125 connection collar. Sealing gasket is fitted as standard. Aula 400, 500 and 600 come in a rectangular design and feature a separate distribution box. The front grille is equipped with a gasket underneath and at both ends, and is perforated with a clover pattern. In addition, the upper edge has been perforated to limit the near-field. Aula 2000 has a rectangular design and is equipped with a rear distribution box dim. 400, 500 or 600. Screws in an enamel finish are standard. Aula 2000 is available as standard lengths of 2000 mm, with splice connectors and end pieces supplied loose. Adjustment lengths are available on request. ORDER CODE, Siv-inn-Aula 2000 The products are made of galvanised steel plates, and come in a RAL 9003 - gloss 30 finish as standard. Other colours and materials are available on request. QUICK SELECTION Siv-inn Aula [m³/h] Dim. 25 db(a) 30 db(a) 35 db(a) 100/125 35 50 60 400 40 50 60 500 50 60 80 600 70 90 110 Table 1: The table shows air flow rates at given sound power levels. 79

Siv-inn Aula DIMENSIONS AND WEIGHT, Siv-inn Aula Siv-inn Aula 2000, weight 1.6 kg per metre. Dim. A B Weight [kg] 400 400 350 0,6 500 500 450 0,8 600 600 550 1,0 Table 2 Fig. 2 80

DRS/DRS-T DRS Ø100 Ø630 is a manual commissioning damper, at dim. 100 315 actuator type CM can be mounted. DRS-M Ø400 Ø 630 is an actuator-controlled commissioning damper. DRS and DRS-M satisfy the EN 1751 requirements for air permeability class 0 and C. DRS-T Ø100 Ø 630 is a manual commissioning and shut-off damper. DRS-T-M DRS-T-M Ø100 Ø 630 is an actuator-controlled commissioning and shut-off damper. DRS-T and DRS-T-M satisfy the EN 1751 requirements for air permeability class 4 and C. The damper s operating temperature is max. 100 C. DIMENSIONS AND WEIGHT Dim. D L B1 Weight [kg] 100 99 230 70 0,5 125 124 230 70 0,6 160 159 230 70 0,9 200 199 230 70 1,1 250 249 285 70 1,3 315 314 285 70 2,0 Table1: DRS dim 100-315 DRS and DRS-T are supplied with graduated scale and lockable commissioning solution. DRS-M and DRS-T-M are equipped with actuator bracket, and the dampers are available with actuator mounted. On the DRS Ø100 Ø315 (fig. 1), provisions have been made for subsequent installation of Belimo CM actuators. DRS Ø100 Ø315 has galvanised steel casing, bracket and scale, whereas the damper, support and commissioning solution come in a plastic design. DRS Ø400 Ø630 features a casing, damper, shaft, bracket and scale in galvanised steel. Support and spacer are in a plastic design. DRS-M Ø400 Ø630 has galvanised steel casing, damper, shaft and actuator bracket, whereas the support come in a plastic design. DRS-T has galvanised steel casing, damper, bracket and scale. The damper blade is fitted with rubber gasket, and the supports are in a plastic design. DRS-T-M has galvanised steel casing, damper, bracket and shaft. The damper blade is fitted with rubber gasket, and the supports are in a plastic design. All damper types are equipped with EPDM rubber gasket. Fig. 1, DRS dim 100-315 Dim. D L B2 C Weight excl. actuator [kg] 100 99 230 100 47 0,9 125 124 230 100 47 1,1 160 159 230 100 47 1,3 200 199 230 100 47 1,5 250 249 285 100 50 2,3 315 314 285 100 50 2,9 400 399 285 100 50 3,9 500 498 285 100 50 5,2 630 628 285 100 50 7,2 Table 2, DRS / DRS-M 400-630 and DRS-T / DRS-T-M 100-630. ORDER CODE, DRS DRS - 160 / T - M - P / 0 Product L = Enamel finish Dimension Ø100 Ø630 T = Sealed design M = Actuator bracket fitted P = Equipped with actuator DRS-160 / T-M-P/ 0-0 DRS dim. Ø160 sealed design, equipped with actuator bracket and actuator. (Actuator can be ordered separately: see table 3). P.S. If you choose another type of actuator than CM, be aware of that actuator brackets have different constructions depending on actuator type, we recommend: damper and actuator mounted together at factory. Alternatively, specify type of actuator which will be used afterwards. Fig. 2, DRS / DRS-M 400-630 and DRS-T / DRS-T-M 100-630. (DRS-M and DRS-T-M are equipped with 8x 8 shaft) (H-dimensions, see table 3) 81

DRS/DRS-T ACCESSORIES DAMPER ACTUATOR AND FUNCTION The dampers in table 3 are ready for mounting of Belimo brands. Damper Dim. Actuator Function Torque H-diml weight type [Nm] [mm] [kg] DRS 100-315 CM24-F-R On/Off 2 40 0,2 DRS 100-315 CM230-F-R On/Off 2 40 0,2 DRS 100-315 CM24-SR-FR.2 Modulating 2 40 0,2 DRS-M 400-630 NM24A/NM230A On/Off 10 62 0,8 DRS-M 400-630 NM24A-SR/NM230A-SR Modulating 10 62 0,8 DRS-M 400-630 NM24A-MP MP-Bus 10 62 0,7 DRS-M 400-630 NM24A-LON LON 10 62 0,8 DRS-M 400-630 SF24A/SF230A On/Off spring return 20 85 1,7 DRS-M 400-630 SF24A-SR Modulating spring return 20 98 2,7 DRS-M 400-630 SF24A-MP MP-Bus spring return 20 98 2,7 DRS-M 400-630 SF24A-LON LON spring return 20 98 2,7 DRS-T-M 100-315 LM24A-F/LM230A-F On/Off 5 64 0,5 DRS-T-M 100-315 LM24A-SR-F/LM230A-SR-F Modulating 5 64 0,5 / 0,7 DRS-T-M 100-315 LM24A-MP-F MP-Bus 5 64 0,5 DRS-T-M 100-315 LM24A-LON-F LON 5 64 0,6 DRS-T-M 100-315 LF24/LF230 On/Off spring return 4 82 1,4 / 1,6 DRS-T-M 100-315 LF24-SR Modulating spring return 4 82 1,4 DRS-T-M 100-315 LF24-MFT2 MP-Bus spring return 4 82 1,4 DRS-T-M 400-630 SM24A/SM230A On/Off 20 64 1,0 / 1,1 DRS-T-M 400-630 SM24A-SR/SM230A-SR Modulating 20 64 1,1 / 1,2 DRS-T-M 400-630 SM24A-MP MP-Bus 20 64 0,9 DRS-T-M 400-630 SM24A-LON LON 20 64 1 DRS-T-M 400-630 SF24A/SF230A On/Off spring return 20 85 1,7 DRS-T-M 400-630 SF24A-SR Modulating spring return 20 98 2,7 DRS-T-M 400-630 SF 24A-MP MP-Bus spring return 20 98 2,7 DRS-T-M 400-630 SF24A-LON LON spring return 20 98 2,7 Table 3. (Alternative type damper and actuator for DRS 100-315, is DRS-T-M 100-315) 82

EPS EPS is used for commissioning and completion of ventilation systems without damper EPS is supplied with graduated scale and lockable commissioning solution. The EPS casing, damper and graduated scale are in a galvanised steel design. Supports are in plastic DIMENSIONS AND WEIGHT, EPS EPS Dim. D B L H Weight [kg] 100 91 93 140 107 0,6 125 115 104 165 107 0,7 160 147 114 200 107 0,8 200 184 122 230 107 1,0 250 225 129 280 107 1,2 315 290 136 340 107 1,6 Table1 ORDER CODE, EPS EPS - 250 Product Dimension: Ø100 - Ø315 H EPS-250 EPS dimension Ø250. ØD B L Fig. 1 83

Rego-T Rego-T is a user-friendly commissioning damper with an extremely low noise level. The unit is intended for manual operation only, and correct installation according to air flow is crucial. NB! Actuatorcontrolled operation is not possible. Max operating temperature for the damper is 100 C. DIMENSIONS AND WEIGHT, Rego-T Min. width: 200mm. Max width: 1400mm. Module: 50mm Min. height: 50mm. Max height: 1400mm. Module: 50mm Weight in kg = damper area in m² x factor 20. Rego-T is available in 3 different designs. 1. Height (H) = 50, 75, 100 and 150mm with one damper-blade only. NB! For installation in duct with internal insulation, dimensions must be taken into consideration for the 150mm unit as the damper blade protrudes from the damper frame. 2. Standard design with damper blades moving in opposite directions as shown in fig. 1. 50mm module. 3. Standard design with circular spigot available in dim. from and incl. Ø400 to and incl. Ø1250, shown as D in fig. 2. Shut-off level is max 90%. The damper lever is equipped with a graduated scale, and can be locked in position with 2 thumbscrews. Damper blades are pinion operated. Rego-T is available in other materials and/or dimensions on request. Frame profiles and damper blades are supplied in a galvanised steel finish, pinion in PBT plastic. Rego-T in dimensions Ø400, Ø500 and Ø630, featuring circular connection collars, are fitted with EPDM rubber gaskets. ORDER CODE, Rego-T Rego-T - 1200-800 / 0-0 Product B = Width H = Height SM = Special material SA = Circular connection, Ø400 - Ø1250 Rego-T 1200-800 / 0-0 Rego-T, rectangular damper, 1200 width and 800 height Fig. 1, Rego-T. Fig. 2, Rego-T, with circular spigot 84

Iris Iris is an air-flow regulation and measuring damper compliant with the air tightness requirements of EN 1751, Class C. Iris comprises an adjustable diaphragm which can be controlled with an adjusting nut or the enclosed handle, adjustment scale and air flow rate measuring nipples. Iris is made of hot-dip galvanised steel. Measuring nipples and adjustment devices are in plastic. The damper is fitted with a rubber gasket. ORDER CODE, Iris DIMENSIONS AND WEIGHT, Iris Dim. d D L A Weight [kg] 80 79 125 115 35 0,5 100 99 165 115 30 0,6 125 124 188 115 30 0,7 150 149 230 115 30 1,0 160 159 230 115 30 1,0 200 199 285 120 30 1,4 250 249 335 135 40 2,0 300 299 405 140 40 2,6 315 314 405 140 40 2,6 400 399 525 150 55 6,5 500 499 655 150 52 9,0 630 629 815 160 60 16,0 800 799 1015 290 120 25,0 Table 1 Iris - 250 Product Dimension Ø80 - Ø800 Iris-250 Iris, dimension Ø250. Fig 1: Iris, dimension 80 Fig 2: Iris, dimension 100-800 85

Leo Leo is a volume flow controller which works independently of the duct pressure. It is the desired air flow rate at choked damper that determines the duct pressure required for the applicable unit/string. The VAV unit is based on dynamic measurement of volume flows, and controls the damper position to maintain the air flow rate required. When a change in duct pressure occurs, such as when other volume flow controllers on the branch open or close, the unit will compensate by adjusting the damper until the correct volume flow has been restored. The required air flow rate can, for example, be provided as a 0-10V signal from room thermostat / CO² sensor in the occupied zone covered by the unit. Minimum and maximum air flow rates can be set at the factory or during installation by using a service tool from Belimo. The VAV unit is designed to provide comfort ventilation at temperature conditions of between 0 C and 50 C and a relative humidity between 5% and 95% without condensation. A 4-conductor cable connects the controller to various control equipment in the room. Consistent use of a common reference system for all equipment is important. For the VAV controller, cable no. 1 is system-0. All control and measurement signals are linked up in accordance with this. Wiring diagram for Leo in combination with various room control equipment is available at our website. For energy-efficient operation, VAV systems are equipped with pressure sensors in the ductwork, which transmit control signals to branch dampers or to the fan frequency control. Please see schematic diagram in fig.1. Explanation to fig. 1 1) Pressure sensor for fan control 2) VAV unit 3) Motorised damper with pressure control system 4) Pressure sensor 5) Fan FUNCTION Leo will always adjust to the air flow rate consistent with the signal transmitted from the room control equipment. The VAV unit comprises an adjustable damper and measuring station for air flow rate, and the measurement principle is dynamic measurement of the air flow. In the damper motor s control unit, should the admission for the damper is regulated according to the desired should-value. Leo has an adjustment range shown in table 2. Deviation for working range 10-20% of Vnom:±25% 20-40%: <±10% 40-100%: <±4% If T-pipes are used, a spacing of at least 5 x ØD is recommended in order to maintain the measurement accuracy. ORDER CODE, LEO Type: 0 = Not Encased D = Encased Controller Option: 0 = MP-Bus MOD = MOD LON = LON KNX-B = Belimo KNX XAC = X-AIRCONTROL ELP = EasyLink plug ELC = EasyLink Connect Leo - 0-0 - 160 / L1-0 A = ASN, extraction unit with mesh grille Sound attenuator: 0 = Without sound attenuator K = LEV-K (Length 500mm) L = LEV-L (Length 1000mm) Type: 1,2,3 or 4 see fig 2 Dimension: Ø100 - Ø630 1 3 2 4 Leo-0-0-160 / L1-0 Leo not encased, MP-bus, dim Ø160. Delivered with sound attenuator LEV-L, lenght 1000mm, type 1, Ø160. 4 3 2 4 3 2 5 Fig. 1: Pressure conditions in VAV system 86

Leo Leo VAV is a complete measuring and control unit where the air flow rates in ventilation systems can be set as required. At the measuring station, the differential pressure is measured via measuring rod integrated in the unit. The unit is installation-friendly in terms of straight ducting, and can thus be mounted in most ductwork sections. It is fully compliant with air permeability class 4 for damper in closed position, and class C for leakage to the surroundings. Leo is equipped with VAV controller from Belimo or Siemens. Controller specifications are provided in the table below. Full technical documentation can be downloaded from our website www.trox.no Belimo LMV/NMV-D3 is used as analog control or for MP-bus. Belimo LON or MOD-bus controller is also available. For KNX, Belimo LMV-D3-KNX and NMV-D3-KNX is available. If additional protection against structure-borne noise is required, e.g. for open installation, the unit can be delivered with external insulation and casing. This will reduce the level of noise emitted from the actual unit at high choke pressure and high velocity past the damper. However, this should be followed up with additional protection against structure-borne noise from the duct at both sides of the unit. Please see acoustic datasection. The LEV sound attenuator is designed for VAV systems, and is available in 500mm and 1000mm lengths. LEV has a full attenuator cross-section, and this ensures a low-level pressure loss. It is insulated with mineral wool featuring a reinforced top layer to prevent fibres breaking away with the supply air. An extraction unit with mesh grille, ASN, in the same design as LEV is also available. Leo-D, LEV and ASN can be delivered pre-assembled with ducting clips and are equipped with adjustable brackets from factory. Leo Leo comes in a galvanized steel design. The measurement unit is in aluminium. Tubing, nipples and motor casing are in plastic. Leo s connection collars are fitted with EPDM rubber gaskets. LEV is made of galvanised steel, and comes with mineral wool and a glass fibre layer as attenuation material. Connection collars are fitted with EPDM rubber gaskets. ASN is made of galvanised steel and is equipped with an EPDM rubber gasket on the connection collar. LMV-D3-MP/MOD/LON NMV-D3-MP/MOD/LON Operating voltage AC 24 V 50/60 Hz, DC 24 V AC 24 V 50/60 Hz, DC 24 V Power drain consumption 36 2W 3W Dim effect 4 VA (max. 8 A @ 5 ms) 5 VA (max. 8 A@ 5 ms) Table 1: Technical specifications, Belimo VAV controller QUICK SELECTION [m³/h] Dim. Max [V nom] Min 100 170 17 125 265 26 160 434 43 200 700 70 250 1060 106 315 1750 175 400 3619 361 500 5655 565 630 8973 897 Table 2: The table shows max. and min. air volumes. Dimensions available: Dimensions available: Dimensions available: Leo-D and LEV type 3 and 4 are delivered with ducting clips Dimensions available: *Only available in length 1000 mm. Fig. 2 87

Leo DIMENSIONS AND WEIGHT Dim. D DA B L 100 99 102 220 400 125 124 127 245 400 160 159 162 280 400 200 199 202 320 400 250 249 252 370 600 315 314 317 435 600 400 399 402 520 600 500 499 502 620 705 630 629 632 750 835 Table 3 Weight [kg] Dim. Leo Leo-D LEV-500 LEV-1000 ASN 100 1,6 3,2 3,3 5,8 1,5 125 1,8 3,5 3,8 6,6 1,8 160 2,1 4,1 4,5 7,8 2,1 200 2,5 4,9 5,3 9,0 2,5 250 3,8 8,0 6,4 11,0 3,1 315 4,8 9,8 7,2 12,4 3,9 400 6,0 12,0 9,6 15,6 5,0 500 9,7 23,0 18,8 6,5 630 12,5 28,0 23,1 8,7 Table 4 OD 52 60 45 L Fig. 3, Leo Fig. 4, Leo-D 500/1000 OB ODA OD OD OB 60 45 L 300 ODA OB 45 45 Fig. 5, LEV Fig. 6, ASN (extraction unit) 88

TSK TSK is mainly used in rectangular ventilation ducts for shut-off, volume flow and pressure control. The damper meets the requirements for air permeability class 3. DIMENSIONS AND WEIGHT, TSK Weight approx. 25kg/m² TSK is delivered as a 50mm width and height module as standard, and is equipped with guide spigot. Actuator is available as accessory. On request, the damper can be supplied with a flange spigot or adapted to fit circular ducts. The damper is also available in air permeability class 4. Max. dimensions, complete damper unit: W=2600 x H=2000 The damper s operating temperature is 100 C max. Frame profiles are made in galvanised steel, whereas the damper profiles are in an aluminium design and equipped with silicone moulding for air tightness. The damper shaft is made in Zytel Super Tough nylon and the bushings in Delrin. Fig. 1: Dimensions, damper class 3 with guide spigot ORDER CODE, TSK TSK - 600-400 / 0 / 0-0 - 0 Product B = Width H = Height M = Equipped with actuator (Actuator type must be specified) 4 = Damper class S = Circular spigot (Ød must be stated). F = Flange TSK 600-400/0/0-0-0 TSK airtight damper class 3. Width: 600 Height: 400. Fig. 2: Dimensions, damper class 3 with flange spigot Actuator Function Torque Height Weight Max. area [Nm] [mm] [kg] TSK [m²] SF24 / SF230 On/Off spring return 15 98 3,0 / 3,3 2,6 SF24-SR Modulating spring return 15 98 2,7 2,6 NM24A / NM230A On/Off 10 62 0,8 / 0,8 2,0 NM24A-SR / NM230A-SR Modulating 10 62 0,8 / 0,9 2,0 SM24A / SM230A On/Off 20 64 1,0 / 1,1 2,6 SM24A-SR / SM230A-SR Modulating 20 64 1,1 / 1,2 2,6 Table 1 (Damper height from 1400 up to 2000 requiers 2 actuators) 89

LEV LEV is a circular sound attenuator for use in ductwork. LEV is a circular steel unit lined with attenuation material inside. Available in both 500 mm and 1000 mm lengths. LEV complies air tightness class C. LEV is made of galvanised steel with mineral wool and a glass fibre layer as attenuation material. Connection collars are fitted with EPDM rubber gaskets. DIMENSIONS AND WEIGHT, LEV LEV Weight [kg] Dim. D A L LEV 500 LEV 1000 100 99 220 500/1000 3,3 5,8 125 124 245 500/1000 3,8 6,6 160 159 280 500/1000 4,5 7,8 200 199 320 500/1000 5,3 9,0 250 249 370 500/1000 6,4 11,0 315 314 435 500/1000 7,2 12,4 400 399 520 500/1000 9,6 15,6 500 498 620 1000-22,5 630 629 750 1000-23,1 Table 1 LEV Type 0 Available dimensions: 100-100 125-125 160-160 200-200 250-250 315-315 400-400 500-500* 630-630* ORDER CODE, LEV LEV - 160-1000 / 0-0 Dimension: Ø100 Ø630 Length: 500 or 1000 A = ASN, extraction unit with mesh grille Type 0,1,2,3 or 4. See fig. 2 LEV Type 1 Available dimensions: 100-100 125-125 160-160 200-200 250-250 315-315 400-400 500-500* 630-630* LEV-160-1000/0-0 LEV, dimension Ø160, length 1000mm, type 0 LEV Type 2 Available dimensions: 100-125 125-160 160-200 250-315 250-400 LEV Type 3 Available dimensions: 100-100 125-125 160-160 200-200 250-250 315-315 400-400 500-500* 630-630* Fig. 2. Dimensional sketch LEV, Type 0 LEV Type 4 Available dimensions: 100-125 125-160 160-200 200-250 250-315 315-400 * Available in 1000mm lengths only Fig. 1 90

LKR LKR is a square sound attenuator with circular end spigots. LKR-V is a square sound attenuator with a circular end and side spigot in order to accommodate a right-angled bend. LKR and LKR-V comprise a square steel unit where all 4 internal walls are lined with mineral wool with a glass fibre layer. From dimension Ø315 and up, all sound attenuators are equipped with a centre baffle. LKR and LKR-V complies air tightness class C. LKR and L KR-V are supplied in a galvanised steel finish. The units from dimension Ø100 up to Ø630 are fitted with EPDM rubber gasket on the connection collars, remaining dimensions without rubber gasket. Internally, the units are lined with mineral wool with a glass fibre layer. DIMENSIONS AND WEIGHT, LKR LKR Weight [kg] Dim. L = 300 L = 600 L = 900 L = 1200 L = 1500 100 1,8 3 3,9 5,1-125 2,2 3,5 4,6 6,1-160 2,7 4,5 5,8 7,6-200 3,3 5,4 7,3 9,1-250 4,3 6,8 9,2 12-315 5,6 9,2 11,7 15-400 - 12,7 15,4 19,5-500 - 16,8 22 26,5-630 - - 29,5 35-800 - - 38 44-1000 - - - - 100 1250 - - - - 120 Table 1: LKR and LKR-V QUICK SELECTION In order to ensure the optimum choice of LKR, please use the Attenuator Selection computer program available for download from our website: www.trox.no ORDER CODE, LKR Fig.1, LKR 91

LKK LKK is a rectangular sound attenuator for installation in rectangular ducting. DIMENSIONS AND WEIGHT, LKK AND LKK-V LKK is a rectangular steel unit featuring internal vertical splitters with mineral wool with a glass fibre layer inside. The unit is equipped with a flanged connection at each end. LKK is available in heights from 400 mm to 3000 mm (100 mm increments), and in widths from 600 mm to 3000 mm (100 mm increments), and in lengths of 640, 1240, 1500, 1800 and 2480 mm. 1880 and 2480 mm systems are delivered as two-piece units. An LKK-V version is also available, and is a sound attenuator with connection collars forming a right angle in order to accommodate a right-angled bend. LKK and LKK-V complies air tightness class C. LKK comes in a galvanised steel design. The flanged joint is equipped with a polyethylene gasket. Splitters with mineral wool with a glass fibre layer have been fitted inside. QUICK SELECTION In order to ensure optimum splitter combination, an Attenuator Selection computer program has been developed and is available for download from our website: www.trox.no Fig. 1, LKK ORDER CODE, LKK LKK - 1200-500 - 1500 / 3125D / 0-0 Product B = Width H = Height L = Length: 640, 1240, 1500, 1880 or 2480 L = Enamel finish SM = Special material K = Code (available in table 1-8: or from www.trox.no LKK-1200-500-1500 / 3125D / 0-0 LKK, width 1200, height 500, length 1500, code: 3125D. ORDER CODE, LKK-V LKK-V - 1200-600 - 300-300 / 0-0 Product B = Width H = Height I = IN dimension L = Enamel finish SM = Special material U = OUT-dimension LKK-V-1200-600-300-300 / 0-0 LKK-V, width 1200, hight 600, IN dimension 300 and OUT dimension 300. Fig. 2, LKK-V 92

LKL LKL is a rectangular sound attenuator for installation in rectangular ducting. LKL is a rectangular steel unit with internal splitter. The unit is equipped with a flanged connection at each end. LKL is available in heights from 150 mm to 400 mm (50 mm increments), and in lengths of 640, 1000, 1240 and 1500 mm. Widths in 50 mm increments. LKL complies air tightness class C. LKL comes in a galvanised steel design. The flanged joint is equipped with a polyethylene gasket. A splitter with mineral wool with a glass fibre layer has been fitted inside. DIMENSIONS AND WEIGHT, LKL *Weight is calculated by using the formula: factor x B X L, with B and L specified in metres. Height Width Length [mm] Weight* [kg] 150 150 1000 640, 1000 18,5 x B x L 1240, 1500 200 200 1000 640, 1000 19,0 x B x L 1240, 1500 250 250 1000 640, 1000 21,8 x B x L 1240, 1500 300 300 1000 640, 1000 23,2 x B x L 1240, 1500 350 350 1000 640, 1000 25,0 x B x L 1240, 1500 400 400 1000 640, 1000 27,0 x B x L 1240, 1500 Table 1 QUICK SELECTION In order to ensure correct/optimum splitter combination, an Attenuator Selection computer program has been developed and is available for download from our website: www.trox.no. Length ORDER CODE, LKL LKL - 500-350 - 1240 / 0-0 Product L = Painted finish B = Width SM = Special material H = Height L = Length; 640, 1000, 1240 or 1500 LKL-500-350-1240 / 0-0 LKL, width 500, height 350 and length 1240 Width Heigt Figur 1 93

ILP and ILS ILP and ILS are access door systems for cleaning and inspection of rectangular and circular ducts. The access doors are also available as insulated units. Insulated version inspection hatchet with quick-release clamps: The access door system comprises: Door panel, frame and neoprene gasket Quick-release clamps are used to attach the panel, and the unit is lined with Rockwool for thermal and acoustic insulation. The frame is designed to provide the correct compression at clamp ends, and this ensures that the panel is held in place. A tooth-grip profile is used to secure the frame to the duct, and allows for easy installation in duct wall. In order to ensure adequate sealing between panel, frame and duct wall, the frame has been fitted with a neoprene gasket on both the inside and the outside. MATERIAL AND SURFACE COATING The access doors come in a galvanised steel finish, and are compression moulded for improved strength/density. ORDER CODE, ILP ILP = Uninsulated ILP-I = Insulated ILP - 30-20 ILP-30-20 ILP uninsulated, dimension 300x200. Dimensjon: 20-15 = 250x150 30-20 = 300x200 45-35 = 450x350 60-45 = 600x450 Ø20 = Ø200, (uninsulated only) DIMENSIONS AND WEIGHT, ILP ILP Access door dimension ILP ILP-I Dim. [mm] Weight [kg] Weight [kg] 25-15 250 x 150 0,7 0,7 30-20 300 x 200 1,1 1,1 45-35 450 x 350 2,8 2,5 60-45 600 x 450 4,9 3,9 Ø 200 Ø200 0,5 - Table 1 DIMENSIONS AND WEIGHT, ILS ILS Access door dimension Weight Dim. [mm] [kg] 100/125 180 x 80 0,3 160 180 x 80 0,3 200 250 x 150 0,5 250 250 x 150 0,5 315 250 x 150 0,5 400 250 x 150 0,5 500 400 x 300 1,4 630 400 x 300 1,4 800 400 x 300 1,4 1000 400 x 300 1,4 Table 2 INSTALLATION Grooves in ducting are cut by using the template provided. MAINTENANCE No specific maintenance requirements. ORDER CODE, ILS ILS - 315 ENVIRONMENT Enquiries regarding product declaration can be directed to our sales team, or information can be found at our website: www.trox.no Product ILS-315 ILS for duct dimension Ø315. For duct dimension: Ø100/Ø125, same. Ø160 to and incl. Ø1250 94

KSA KSA is a duct connection system for rectangular ductwork. Sealant has been applied to the KSA duct connector base. ORDER CODE, KSA KSA - SSA / 0-0 - KPA KSA = Duct connector SSA = C-clip track profile KPA = Gasket KIA = Inner bend YH1 = Outer bend The duct connection system comes in a galvanised steel design. KSA-SSA / 0-0-KPA KSA duct connector, SSA c-clip track profile and KPA gasket. DIMENSIONS AND WEIGHT, KSA As specified in fig. 1 1 Outer bend, type YH-1 2 C-clip track profile, type SSA [0.21 kg/m] 3 Duct connector, type KSA [0,42 kg/m] 4 Inner bend, type KIA 5 Gasket, type KPA KSA connectors are delivered in 3m lengths, 50m per bundle. KPA gaskets are delivered in 1.5 m lengths, 100m per bundle. SSA profiles are delivered in 3m lengths, 100m per bundle. KIA bends are delivered in packs of 500. YH-1 bends are delivered in packs of 500. INSTALLATION KSA and SSA profiles are delivered in 3m lengths, 50m and 100m per bundle respectively, and are cut to size using saw, cut-off wheel or similar. A manual (KPH) or pneumatic (KPL) hand-press can also be used to cut the KSA connector in lengths = B/H 10mm. Please see fig. 1. The KSA connector is pressed onto the duct end until it is fully attached, and can be secured as follows: fig. bolted, screwed or spot welded as shown in fig. 2 (A), or secured with compressing pliers as shown in fig. 2 (B). When all four sides of the KSA connector have been attached, the KIA inner bend is fitted and can be fixed in place by using compressing pliers. The KPA gasket is attached to the profile as shown in fig. 1, and the duct units can then be connected using the SSA track profile. When the sections have been joined, the YH-1 outer bend is fitted. Figure 1 MAINTENANCE No specific maintenance requirements. ENVIRONMENT Enquiries regarding product declaration can be directed to our sales team, or information can be found at our website: www.trox.no Figure 2 Assembly 95

Svalbard-H Svalbard-H is a hydronic cooling, heating and ventilation system for use in offices, shops, schools etc. The system is designed to provide excellent cooling effect, and a high induction level ensures a draft-free environment in the occupied zone. Svalbard-H is made for corner installation, i.e. between wall and ceiling. FUNCTION Air is supplied via nozzles, and indoor air is extracted and fed through the coil. Effective mixing of indoor air and supply air, i.e. induction, minimises the risk of draft in the occupied zone. When Svalbard is utilised for heating, the same technique is used for dispersion of heat along the ceiling. The indoor air is extracted through the perforated area on the unit s front-panel in order to avoid dirt accumulation on the ceiling. Nozzle configuration for the chilled beam, i.e. desired air supply and pressure, is specified at time of order. Svalbard-H comes with integrated air flow rate measuring point. The front panel can be folded down for inspection and cleaning. Svalbard-H is available in installation lengths of 1200, 1800, 2400 and 3000 mm. Coil types: SKB = standard cooling coil or VKB heating and cooling coil. Dispersion type: unidirectional Connection to air: Ø125 mm (spigot dimension). Connection to air and water on same side Connection to water, cooling and heating: Cu Ø15x1.0 mm Changeable flowpattern via Jet Split lamellaes in the beams outlet, standard pattern is fan style. Blind cover can be provided for adaptation to the wall. See Figure 9. MATERIAL ANDSURFACE TREATMENT Frame and casing in galvanised steel. Delivered in a powdered painted finish (white RAL 9003 - gloss 30) as standard. Copper tube coils with aluminium lamellae. Adjustable lamellae are in a plastic design. DIMENSIONS AND WEIGHT, Svalbard-H ORDER CODE, Svalbard-H Svalbard-H - 1800-55 - SKB - A - 1 / 0-0 - S - 0 Product SL = Special finish L = Length: 1200, 1800, 2400 S = Damper, DRS-K Ø125 A1 = Actuator 24V, off/on or 3000 A2 = Actuator 230V, off/on Pre-set value, W = TROX TRV 2-way valve from Auracool. Coil type: *Connection to water, see fig. 2 1 or 2 SKB = Standard cooling coi VKB = Heating and cooling coil *Connection to air, see fig. 2 A or B Svalbard-H-1800-55-SKB-A-1/0-0-S-0 Svalbard-H, corner beam, length 1800 w/ pre-set value 55 and standard cooling coil Connection to air A and water 1. Commissioning damper DRS-K Ø125 supplied separately. Connection to air and water on same side as standard, A-1or B-2. ACCESSORIES See order code, pre-installed in chilled beam. W = TROX TRV 2-way valve, Broen (see separate data sheet). A1 = Actuator 24V on/off, Broen (see separate data sheet). A2 = Actuator 230V on/off, Broen (see separate data sheet). ACCESSORIES Ordered and supplied separately. Ballorex Dynamic valve (see separate data sheet). Actuator: 24V, 230V or 24V modulating 0-10V signal. Transformer, EasyTrafo 75 VA (see separate data sheet). Transformer, EasyTrafo 105 VA (see separate data sheet). Room controller, EasyReg (see separate data sheet). Length L Weight* Weight: water in cooling coil [kg] [mm] [mm] [kg] SKB VKB 1200 1200 17,0 1,0 0,8 1800 1800 24,5 1,5 1,2 2400 2400 33,5 2,1 1,5 3000 3000 40,0 2,6 2,0 Table 1 (* No water in cooling coil) Fig. 2 Brackets Cooling Brackets Cooling/heating Cooling Heating Cooling/heating Brackets Brackets Heating 96 Fig. 1, Svalbard-H

Svalbard-H QUICK SELECTION, Svalbard-H The tables state the cooling effect from the chilled beam s water circuit and the emitted sound power level from the beam. In order to calculate total cooling effect, the cooling effect of the supply air must be added as shown in the example below. Examplel Svalbard-H1800 Battery type: Standard Water-side cooling effect at 40 Pa as per table 3 = 310 W Air flow rate: 80 m³/h Supply-air cooling effect: q/3600 x 1,2 x c p x t room-supply air:: = t room-water: 10 0 C 80/3600 x 1,2 x 1010 x 6 = 160 W t room-supply air: 6 0 C Total cooling effect = 470 W Svabard-H-1200 mm t k [ C] 6 8 10 L w db(a) Total pressure in duct [Pa] 40 80 40 80 40 80 40Pa 80 Pa Air flow rate [m³/h] 40 110 130 150 170 180 210 23 32 50 120 140 160 190 200 230 27 33 60 120 150 170 200 210 240 30 35 70 130 150 180 200 220 250 32 36 80 140 160 190 210 230 260 34 38 Table 2: Cooling effects at 0.06 litres of water per sec Svabard-H-1800 mm t k [ C] 6 8 10 L w db(a) Total pressure in duct [Pa] 40 80 40 80 40 80 40Pa 80 Pa Air flow rate [m³/h] 40 150 160 200 220 240 270 21 29 60 170 190 220 250 270 310 26 32 80 180 210 250 290 310 360 29 34 100 200 230 270 310 330 380 32 37 120 210 240 280 320 350 400 34 40 Table 3: Cooling effects at 0.06 litres of water per sec Svabard-H-2400 mm t k [ C] 6 8 10 L w db(a) Total pressure in duct [Pa] 40 80 40 80 40 80 40Pa 80 Pa Air flow rate [m³/h] 60 200 230 270 300 340 370 22 29 80 220 250 295 330 370 410 26 32 100 240 270 320 360 400 450 29 35 120 250 290 335 385 420 480 31 37 140 260 300 350 400 440 500 33 39 Table 4: Cooling effects at 0.06 litres of water per sec Svabard-H-3000 mm t k [ C] 6 8 10 L w db(a) Total pressure in duct [Pa] 40 80 40 80 40 80 40Pa 80 Pa Air flow rate [m³/h] 60 230 240 310 330 390 420 21 29 80 250 270 340 380 430 480 23 31 100 270 310 370 420 460 520 26 34 130 300 340 400 450 500 560 30 37 160 320 360 430 480 530 600 33 39 Table 5: Cooling effects at 0.06 litres of water per sec 97

Svalbard-I Svalbard-I is a hydronic cooling, heating and ventilation system for use in offices, shops, schools etc. The system is designed to provide a draft-free cooling effect in the occupied zone. Svalbard-I is suitable for integration in a ceiling grid with 600mm modules. FUNCTION Air is supplied via nozzles, and indoor air is extracted and fed through the coil. Effective mixing of indoor air and supply air, i.e. induction, minimises the risk of draft in the occupied zone. When Svalbard-I is used for heating, the same technique is used for dispersion of heat along the ceiling. The indoor air is extracted through the perforated area on the unit s front panel in order to avoid dirt accumulation on the ceiling. Nozzle configuration for the chilled beam, i.e. desired air supply and pressure, is specified at time of order. Svalbard-I is delivered with integrated pressure outlet for air flow rate measurements. The front panel can be folded down for inspection and cleaning. Dispersion options: symmetrical 50/50 or asymmetrical 75/25 (25/75) can be adjusted on site. Connection to air: Svalbard-I, 175mm height, is equipped with a Ø125 spiro connection at gable end (spigot dimension). Fig. 1 and 2. Svalbard-I, 235mm height, is available with Ø125 side spigot. For alternative positioning options, see fig. 1 & 3 and under order code. Svalbard-I can be supplied in a low profile design, 150 mm, with Ø100 spiro connection at gable end. Connection to water: copper pipe, Ø15x1.0 mm. Delivered with vertical pipe-ends as standard (see fig. 1, 2 & 3 and under order code). changeable flowpattern via Jet Split lamellaes in the beams outlet, standard pattern is fan style. Frame and casing in a galvanised, steel-plated finish. Delivered in white enamel finish ((RAL 9003 - glans 30) as standard. Copper tube coils with aluminium lamellae. Adjustable lamellae are in a plastic design. ORDER CODE, Svalbard-I-L Low overhall heigth, 175 mm. Svalbard-I-L - 1800-118 - SKB - A - 3-50/50 / W - A1 - S - 0 Product SL = Special finish Length: S = Damper, DRS-K Ø125 1200, 1800, 2400 A1 = Actuator 24V, on/off or 3000 A2 = Actuator 230V, on/off Preset value W = TROX TRV 2-way valve from Auracool Flow pattern, X/Y: Coil type: Symmetrical: standard 50/50 SKB = Standard cooling coil Asymmetrical: 75/25 or 25/75 HKB = High-capacity coil */**Connection to water: VKB = Heating and cooling coil 3 or 4 Vertical (standard) *Connection to air: 1 or 2 Horizontal (additional) A or B Svalbard-I-L-1800-118-SKB-A-3-50/50 / W-A1-S-0 Explantation: Svalbard-I for integration in modular ceiling sy stems, low overall heighth 175 mm and length 1800, preset value 118. Standard coil, connection to air at gable end Ø125, standard flow pattern 50/50. TROX TRV 2-way valve and 24V actuator fitted, Damper DRS-K Ø125 supplied separately. *Standard air and water connection is A3 or B4 (see fig. 1). **Water connection is supplided as standard vertic al (3 or 4), alternative horizonatal water connection (1 or 4) will be delivered with push-fit coupling with smooth end installed. ORDER CODE, Svalbard-I-H Height 235 mm. Svalbard-I-H - 1800-105 - SKB - A - 3-50/50 / W - A1 - S - 0 Product SL = Special finish Length: S = Damper, DRS-K Ø125 1200, 1800, 2400 A1 = Actuator 24V, on/off or 3000 A2 = Actuator 230V, on/off Preset value W = TROX TRV 2-way valve from Auracool Flow pattern, X/Y: Coil type: Symmetrical: standard 50/50 SKB = Standard cooling coil Asymmetrical: 75/25 or 25/75 HKB = High-capacity coil */**Connection to water: VKB = Heating and cooling coil 3 or 4 Vertical (standard) *Connection to air: 1 or 2 Horizontal (additional) Gable: A or B (L=1200-3000) Side connection: C,D,E or F (L=1200-2400) CD or EF. (***L= 3000) Svalbard-I-H-1800-105-SKB-A-3-50/50 / W-A1-S-0 Explantation: Svalbard-I for integration in modular ceiling systems, height: 235 mm. and length 1800, preset value 105. Standard coil, connection to air at gable end Ø125, standard flow pattern 50/50. TROX TRV 2-way valve and 24V actuator fitted. Damper DRS-K Ø125 supplied separately. *Standard air and water connection is A3 or B4 (see fig.1). is supplied as standard vertical (3 ACCESSORIES See order code, supplied mounted in beam. W = TROX TRV 2-way valve, Broen. See separate data sheet. A1 = Actuator 24V on/off, Broen. See separate data sheet. A2 = Actuator 230V on/off, Broen. See separate data sheet. Fig. 1 (spigot C to F only available for 235 mm height) ACCESSORIES Ordered separately and supplied loose. Ballorex Dynamisk valve. See separate data sheet. Actuator: 24V, 230V or 24V modulating 0-10V signal. Transformator EasyTrafo 75 V A. See separate data sheet. Transformator EasyTrafo 105 V A. See separate data sheet. Room controller EasyReg. See separate data sheet. 98

Svalbard-I QUICK SELECTION Svalbard-I The tables state the cooling effect from the chilled beam s water circuit and the emitted sound power level from the beam. In order to calculate total cooling effect, the cooling effect of the supply air must be added as shown in the example below. Example Svalbard-I 1800 Battery type: Standard Water-side cooling effect at 40 Pa as per table 2 = 580 W Air flow rate: 75 m³/h Supply-air cooling effect: q/3600 x 1,2 x c p x t room-supply air: = t room-water(mid.): 10 K 75/3600 x 1,2 x 1010 x 6 = 152 W t room-supply air: 6 0 K Total cooling effect = 732 W Svabard-I-1200 mm t k [ C] 6 8 10 L w db(a) Total pressure in duct [Pa] 40 80 40 80 40 80 Low, gable High, gable High, side Coll type SKB HKB SKB HKB SKB HKB SKB HKB SKB HKB SKB HKB 40 Pa 80 Pa 40 Pa 80 Pa 40 Pa 80 Pa 40 210 250 240 280 280 330 320 370 350 410 410 470 <20 27 <20 29 <20 29 60 240 280 270 330 330 380 390 440 410 470 470 550 <20 28 22 30 22 30 80 260 300 300 340 340 390 400 460 420 510 510 600 24 30 23 31 23 31 100 270 320 320 360 360 420 430 490 450 550 550 650 27 32 26 32 26 32 120 280 340 330 380 380 440 450 520 470 570 570 680 31 35 29 34 29 34 Table 1: Cooling effects at 0.06 litres of water per sec. Air flow rate Svabard-I-1800 mm t k [ C] 6 8 10 L w db(a) Total pressure in duct [Pa] 40 80 40 80 40 80 Low, gable High, gable High, side Coll type SKB HKB SKB HKB SKB HKB SKB HKB SKB HKB SKB HKB 40 Pa 80 Pa 40 Pa 80 Pa 40 Pa 80 Pa 50 300 350 340 400 400 460 440 520 500 580 560 640 <20 24 <20 23 <20 26 75 340 400 380 460 460 520 500 600 580 660 640 740 <20 26 <20 26 23 30 100 380 450 420 500 500 580 560 680 620 700 680 820 22 30 21 28 27 32 125 400 480 460 550 550 640 620 740 700 780 760 880 26 32 24 31 30 34 150 420 500 480 580 580 680 660 780 740 840 820 940 29 34 27 33 31 36 Table 2: Cooling effects at 0.06 litres of water per sec. Air flow rate Svabard-I-2400 mm t k [ C] 6 8 10 L w db(a) Total pressure in duct [Pa] 40 80 40 80 40 80 Low, gable High, gable High, side Coll type SKB HKB SKB HKB SKB HKB SKB HKB SKB HKB SKB HKB 40 Pa 80 Pa 40 Pa 80 Pa 40 Pa 80 Pa 60 400 440 440 500 500 580 540 640 620 720 680 800 <20 24 <20 23 <20 22 90 440 500 480 600 600 680 640 740 700 800 760 900 <20 26 <20 26 <20 25 120 480 560 540 640 640 740 720 840 800 920 900 1060 23 29 22 28 24 29 150 520 620 580 680 680 780 760 880 840 980 980 1040 26 32 25 31 29 32 180 550 660 620 740 720 840 820 960 900 1040 1040 1200 30 35 27 33 33 35 Table 3: Cooling effects at 0.06 litres of water per sec. Air flow rate [m³/h] [m³/h] Svabard-I-3000 mm t k [ C] 6 8 10 L w db(a) Total pressure in duct [Pa] 40 80 40 80 40 80 Low, gable High, gable High, side Coll type SKB HKB SKB HKB SKB HKB SKB HKB SKB HKB SKB HKB 40 Pa 80 Pa 40 Pa 80 Pa 40 Pa 80 Pa 80 486 556 538 620 658 763 714 818 815 947 898 1038 <20 26 <20 28 <20 24 110 538 623 718 819 724 822 813 937 907 1044 1001 1175 <20 29 <20 29 <20 27 140 574 677 657 782 784 923 902 1035 987 1141 1098 1304 25 31 22 30 22 28 170 616 723 698 835 824 955 959 1096 1039 1224 1173 1421 28 34 25 31 26 30 200 638 749 740 860 864 1000 975 1135 1089 1263 1259 1514 32 37 28 33 28 32 Table 4: Cooling effects at 0.06 litres of water per sec. Air flow rate [m³/h] [m³/h] 99

Svalbard-I DIMENSIONS AND WEIGHT, Svalbard-I H=175 Length L L2 Weight* Weight: water in cooling coil [ [kg] [mm] [mm] [mm] [kg] SKB HKB VKB 1200 1194 1248±10 17 0,5 1,0 0,8 1800 1794 1848±10 25 0,8 1,5 1,2 2400 2394 2448±10 33 1,0 2,1 1,5 3000 2994 3048±10 43 1,3 2,6 2,0 Table 36005 (* No 3594 water 3634±10 in cooling coil) 48 1,6 3,1 2,4 DIMENSIONS AND WEIGHT, Svalbard-I H=235 Length L L2 Weight* Weight: water in cooling coil [ [kg] [mm] [mm] [mm] [kg] SKB HKB VKB 1200 1194 1248±10 18 0,5 1,0 0,8 1800 1794 1848±10 26 0,8 1,5 1,2 2400 2394 2448±10 35 1,0 2,1 1,5 3000 2994 3048±10 44 1,3 2,6 2,0 Table 36006 (* No 3594 water in 3634±9 cooling coil) 52 1,6 3,1 2,4 Fig. 2: Svalbard-I H=175 Fig. 3: Svalbard-I H=235 100

Svalbard-F Svalbard-F is a hydronic cooling, heating and ventilation system for use in offices, shops, schools etc. The system is designed to provide excellent cooling effect, and a high induction level ensures a draft-free environment in the occupied zone. Svalbard-F is designed for open installation in ceiling or covering. FUNCTION Air is supplied via adjustable nozzles which ensure that the air is dispersed along the ceiling in a fan-shaped flow pattern. This technique optimises the dispersion effect by providing a larger area for the supply air and indoor air to mix. Such effective mixing of indoor air and supply air, i.e. induction, minimises the risk of draft in the occupied zone. Svalbard systems which are used for heating only utilises the same technique for effective dispersion of heat along the ceiling. The secondary air is extracted through the perforated area on the unit s frontpanel in order to avoid dirt accumulation on the ceiling. ORDER CODE, Svalbard-F Svalbard-F - 1800-104 - SKB - A - 1-50/50 / W - A1- S - 0 Product L = Length: 1200, 1800, 2400 or 3000 Pre-set value from Auracool Coil type: SKB = Standard cooling coil Flow pattern, X/Y: HKB = High-capacity coil Symmetrical: standard 50/50 VKB = Heating and cooling coil Asymmetrical: 75/25 or 25/75 *Connection to air, see fig. 2: *Connection to water, see fig. 2: A = Standard B = Special 1 = Standard 2 = Special SL = Special finish S = Damper, DRS-K Ø125 A1 = Actuator 24V off/on A2 = Actuator 230V off/on W = TROX TRV 2-way valve Svalbard-F-1800-104-SKB-A-1-50/50 / W-A1-S-O Svalbard-F for open installation, 1800mm length, pre-set value 104. Standard coil and connection to air Ø125 (A1), symmetrical flow pattern 50/50. Water valve TROX TRV and 24V actuator fitted, commissioning damper DRS-K Ø125 supplied separately. *Connection to air and water will be on gable A1 or B2 as standard (see fig.2). Nozzle configuration for the chilled beam, i.e. desired air supply and pressure, is specified at time of order. Svalbard-F is delivered with integrated pressure outlet for air flow rate measurements. The front panel can be folded down for inspection and cleaning. Svalbard-F is available in installation lengths of 1200, 1800, 2400 and 3000 mm. Dispersion options: symmetrical 50/50 or asymmetrical 75/25 (25/75) can be adjusted on site. Connection to air: gable end Ø125 mm (spigot dimension). Connection to water: Cu Ø15 x 1, 0 mm. Changeable flowpattern via Jet Split lamellaes in the beams outlet, standard pattern is fan style. Blind cover can be provided for adaptation to the wall. See Figure 9. ACCESSORIES- See order code, delivered fitted in chilled beam. W = TROX TRV 2-way valve, Broen (see separate data sheet). A1 = Actuator 24V on/off, Broen (see separate data sheet). A2 = Actuator 230V on/off, Broen (see separate data sheet). ACCESSORIES - Ordered and supplied separately. Ballorex Dynamic valve (see separate data sheet). Actuator: 24V, 230V or 24V modulating 0-10V signal. Transformer, EasyTrafo 75 VA (see separate data sheet). Transformer, EasyTrafo 105 VA (see separate data sheet). Room controller, EasyReg (see separate data sheet). Frame and casing in a galvanised, steel-plated finish. Delivered in a powdered painted finish (white RAL 9003 - gloss 30) as standard. Copper tube coils with aluminium lamellae. Adjustable lamellae are in a plastic design. DIMENSIONS AND WEIGHT, Svalbard-F Length L Weight * Weight: water in cooling coil [kg] [mm] [mm] [kg] SKB HKB VKB 1200 1200 19 0,5 1,0 0,8 1800 1800 27 0,8 1,5 1,2 2400 2400 35 1,0 2,1 1,5 3000 2994 45 1,3 2,6 2,0 Table 1 (* No water in cooling coil) Fig. 2 Fig. 1 101

Svalbard-F QUICK SELECTION, Svalbard-F The tables state the cooling effect from the chilled beam s water circuit, and the emitted sound power level from the beam. In order to calculate total cooling effect, the cooling effect of the supply air must be added as shown in the example below. Example Svalbard-F 1800 Battery type: Standard Water-side cooling effect at 40 Pa as per table 3 = 580 W Air flow rate: 75 m³/h Supply-air cooling effect: q/3600 x 1,2 x c p x t room-supply air: = t room-water: 10 0 K 75/3600 x 1,2 x 1010 x 6 = 152 W t room-supply air: 6 0 K Total cooling effect = 732 W Svabard-F-1200 mm t k [ C] 6 8 10 L w Total pressure in duct [Pa] 40 80 40 80 40 80 db(a) Coil type SKB HKB SKB HKB SKB HKB SKB HKB SKB HKB SKB HKB 40 Pa 80 Pa 40 210 250 240 280 280 330 320 370 350 410 410 470 <20 27 60 240 280 270 330 330 380 390 440 410 470 470 550 <20 28 80 260 300 300 340 340 390 400 460 420 510 510 600 24 30 100 270 320 320 360 360 420 430 490 450 550 550 650 27 32 120 280 340 330 380 380 440 450 520 470 570 570 680 31 35 Table 2: Cooling effects at 0.06 litres of water per sec. Air flow rate [m³/h] Svabard-F-1800 mm t k [ C] 6 8 10 L w Total pressure in duct [Pa] 40 80 40 80 40 80 db(a) Coil type SKB HKB SKB HKB SKB HKB SKB HKB SKB HKB SKB HKB 40 Pa 80 Pa 50 300 350 340 400 400 460 440 520 500 580 560 640 <20 24 75 340 400 380 460 460 520 500 600 580 660 640 740 <20 26 100 380 450 420 500 500 580 560 680 620 700 680 820 22 30 125 400 480 460 550 550 640 620 740 700 780 760 880 26 32 150 420 500 480 580 580 680 660 780 740 840 820 940 29 34 Table 3: Cooling effects at 0.06 litres of water per sec Air flow rate [m³/h] Svabard-F-2400 mm t k [ C] 6 8 10 L w Total pressure in duct [Pa] 40 80 40 80 40 80 db(a) Coil type SKB HKB SKB HKB SKB HKB SKB HKB SKB HKB SKB HKB 40 Pa 80 Pa 60 400 440 440 500 500 580 540 640 620 720 680 800 <20 24 90 440 500 480 600 600 680 640 740 700 800 760 900 <20 26 120 480 560 540 640 640 740 720 840 800 920 900 1060 23 29 150 520 620 580 680 680 780 760 880 840 980 980 1040 26 32 180 550 660 620 740 720 840 820 960 900 1040 1040 1200 30 35 Table 4: Cooling effects at 0.06 litres of water per sec. Air flow rate [m³/h] Svabard-F-3000 mm t k [ C] 6 8 10 L w Total pressure in duct [Pa] 40 80 40 80 40 80 db(a) Coil type SKB HKB SKB HKB SKB HKB SKB HKB SKB HKB SKB HKB 40 Pa 80 Pa 80 486 556 538 620 658 763 714 818 815 947 898 1038 <20 26 110 538 623 718 819 724 822 813 937 907 1044 1001 1175 <20 29 140 574 677 657 782 784 923 902 1035 987 1141 1098 1304 25 31 170 616 723 698 835 824 955 959 1096 1039 1224 1173 1421 28 34 200 638 749 740 860 864 1000 975 1135 1089 1263 1259 1514 32 37 Table 5: Cooling effects at 0.06 litres of water per sec. Air flow rate [m³/h] 102

DID-614 Active chilled beams of type DID614 for the integration into various ceiling systems, preferably for room hights up to 4.20 m. Particularly suitable for grid ceilings with grid size 600 or 625. 2-pipe or 4-pipe heat exchangers enable good comfort levels with a low conditioned primary air volume flow rate. Energy-efficient solution since water is used as a medium for heating and cooling. JetSplit adjustable air control blades allow for the manual adjustment. Large volum flow rate range due to the adjustable twin nozzles (optional). Four-way air discharge. Horizontal heat exchanger as 2-pipe or 4-pipe system. Water connection, Ø12 mm Cu pipe or coupling with 1/2" external thread or 1/2" internal thread. Adjustable nozzle configuration for a large volume flow range. Spigot is suitable for circular ducts to EN 1506 or EN 13180. Removable front fixed with magnets with safety cables. 4 suspension points for on-site installation. Five nozzle variants to optimise induction MATERIALS AND FINISH Casing, spigot, nozzle plate, and front made of galvanised sheet steel. Heat exchanger with copper tubes and aluminium fins. Exposed surfaces are powder-coated with RAL 9010. JetSplit-air control blades made of polypropylene, UL 94, flame retardant (V0). Order code, DID-614 Order code DID614 D1 4 HE R A1 / 593 x 593 160 SL RAL 9006 / KV24 / HV24 1 2 3 4 5 6 7 8 9 10 11 1 Type DID614 2 Design variante D1 3 Varme og kjølebatteri 2 4 4 Dyse varianter HE S1 S2 HP DA DA-F 5 Plassering av vanntilkobling R L 8 Primærluft anslutning 125 160 RAL 9003 - gloss 30 9 SL 10 Kjøleventil - aktuator KV KV 24 KV 230 11 Varmeventil - aktuator HV HV 24 HV 230 6 Vanntilkoblinger A1 A2 7 Standard dimensjoner [mm] 593 593 598 598 618 618 623 623 1193 593 1198 598 1243 618 1248 623 103

DID-614 DIMENSIONS AND WEIGHT DID614 Nominal L B L1 L2 G 59 59 50 52 47 59 59 50 52 47 600 x 600 61 61 50 52 47 62 62 50 52 47 119 59 110 112 47 1200 x 600 119 59 110 112 47 124 61 112 114 3 124 62 112 114 3 Dimensions (mm) D H A 123 230 125 158 245 143 Weight (kg) Nominal size kg/piece Contained water (max) 600 x 600 16 2 1200 x 600 30 3 L2 42,5 42,5 G A 557 47 A H 12 8 D B L A B L1 595 502 B 82 104

VIP-X is a complete system for managing and monitoring of VAV systems. It contains a web server with ready web images for configuration of the system. VIP-X can control up to 32 dampers and acquire signals from up to 32 sensors. Up to five VIP-X units may be connected via a switch, so that the total number of dampers and sensors reaches 160. Using damper angle monitoring to set up function for optimum fan operation. VIP-X can communicate via Modbus/TCP, BACnet/IP or KNXnet/IP and can be provided for 16 or 32 dampers. Modbus/TCP will always be implemented, regardless of whether one chooses VIP-X for BACnet/IP or KNXnet/IP. VIP-X consists of a prefabricated unit that contains both a controller with web server, transformers to supply power to all dampers and sensors and connectors for connection via Winsta pluggable cabling system. VIP-X has a robust casing that is manufactured in galvanized sheet steel. It is Winsta terminals for dampers and 230V operating voltage and RJ45 connector for TCP / IP in bottom plate. The unit has four binding lugs for mounting. 105

EasyLink EasyLink EasyLink is a complete control system for energy proper management and control of indoor climate in a building. The system can regulate both VAV, heating, cooling, CO2, motion and light at room level. FUNCTION EasyLink system can control up to 240 room controllers with their corresponding temperature sensors in the same system. If higher plant, an EasyLink system expanded by multiple systems connected in series. The system has damperblade control connectable mode for optimal fan operation. EasyLink provides internal communication via EXOline-bus (RS485) and communicate further on EXOline, Modbus and BACnet on TCP / IP. EasyLink system have prefabricated units consisting of an overall system controller (Master), Router, room controller, room sensors, connection cards for connection of cables and cable packages. Connection card has input for 24 V operating voltage or 230 V with built-in transformer. All connectors and cables have interface with RJ-standard and Phoenix plugs for easy connection. MATERIALS AND FINISH Master, Router, CO2 sensor and room controller has robust housing made of polycarbonate. Connection card has sturdy casing made of galvanized steel. DIMENSIONS AND WEIGHT, EasyLink Master/Router: WxHxD = 149x121x60mm, weight = 250 grams Romregulator: WxHxD = 95x95x28mm, weight = 110 grams Koblingskort: WXHXD = 125/225x165x75mm, weight = 560 grams ORDER CODE, EasyLink EasyLink system buildup EasyLink Connect, connection card election 9 in the order code 106

NO0103 03.16 Head Office/factory PO Box 100 NO-2712 Brandbu Telephone:+47 61 31 35 00 Telefax:+47 61 31 35 10 www.trox.no Sales office Sweden Konsumentvägen 17 SE-125 30 Älvsjö Sales office Sorgenfriveien 9 NO-7037 Trondheim Sales office Fabrikkveien 14 NO-4033 Stavanger Sales office Tvetenveien 152 NO-0671 Oslo Sales office Damsgårdsveien 169 NO-5160 Laksevåg TINT Kommunikasjon www.tintkom.no 107