Diesel generator set QSB7 series engine

Similar documents
Diesel generator set 6BT5.9 series engine

Diesel generator set 4BT3.3 series engine

Diesel generator set. 50 kw - 60 kw EPA emissions stationary Standby. Specification sheet. Description. Features

Diesel generator set QSX15 series engine

Diesel generator set. 20 kw EPA emissions stationary Standby. Specification sheet. Description. Features

Diesel generator set QSL9-G7 series engine

Diesel generator set QSK23 series engine

Spark-ignited generator set

Diesel generator set. QSB5 series engine Hz EPA Tier 3 emissions. Specification sheet. Description. Features

Diesel generator set QSK50 series engine

Diesel generator set QSX15 series engine

Diesel generator set QSK23 series engine

Spark-ignited generator set

Spark-ignited generator set

Diesel generator set QST30 series engine

Diesel generator set QSK78 series engine

Diesel generator set QSK78 series engine

Diesel generator set QSK60 series engine

Diesel generator set QSK60 series engine

Diesel Generator set QSK95 series engine

Diesel Generator set QSK50 series engine 1135 kw-1500 kw 60 Hz EPA emissions

Rental Power QSB7 series engine

Diesel generator set QSK95 series engine

Diesel Generator set QSK95 series engine

Diesel generator set QSK60 series engine

Diesel generator set QSK78 series engine 2750kVA kVA 50 Hz

Rental Power QSL9 series engine

Diesel generator set QSK60 series engine

Diesel generator set QSK78 series engine 2750kVA kVA 50 Hz Data Center Continuous

Diesel generator set QSL9 series engine

Tier4 certified diesel generator set QSK50 series engine

Tier4 certified diesel generator set QSK78 series engine

Rental Power KTA50 G3 series engine

Diesel generator set B3.3 series engine 44 kva - 66 kva 50 Hz 40 kw - 60 kw 60 Hz

Diesel Generator Set S3.8 Series Engine

Rental Power 800 kw. Specification sheet. Description. Features. Options

Diesel Generator Set Model DGDB 60 Hz

Rental Power 1500 kw. Specification sheet. Description. Features. Options

Model DFEH 60 Hz EPA Emissions

Model DKAC 60 Hz EPA Emissions

Diesel Generator Set Model DFBF 60 Hz

Model DSHAE 60 Hz EPA Emissions

Diesel Generator Set Model DFCE 60 Hz

Diesel Generator Set Model DSHAD 60 Hz EPA Emissions

Rental Power 4BTAA3.3 series engine

Gaseous Fuel Generator Set Model GFDA

Rental Power Kubota V2403 series engine

Spark-Ignited Generator Set Model GGLA 60 Hz

Spark-Ignited Generator Set Model GGFD 60 Hz

Gaseous Fuel Generator Set QSK19G Engine Series

2000kW Rental Package

Diesel generator set QSL9 series engine

Diesel generator set C17D5T series

Diesel Generator Set Model DFJD 60 Hz

Diesel Generator Set Model DFHB 60 Hz

Gaseous Fuel Generator Set GTA19 Engine Series

Gaseous Fuel Generator Set GTA28 Engine Series

Spark-Ignited Generator Set Model GGKD 60 Hz

Gaseous Fuel Generator Set GTA50 Engine Series

Spark-Ignited Generator Set Model GGKC 60 Hz

Model DFHD 60 Hz EPA Emissions

Power Connect RX50. Series. Specification sheet. Features and benefits. Weight, size and sound level

KTA50 Land Based Drilling Power Modules

Power Connect TM Series RX60

100 KW(NG) / 100 KW(LP) LIQUID COOLED POWERED by

Gaseous Fuel Generator Set KTA19G Engine Series

20 KW / 25 KVA LIQUID COOLED POWERED by

2500 Prime 2100 Continuous Emissions level: EPA NSPS Stationary Emergency Tier 2

55 KW / 70 KVA POWERED by

SUBMITTAL COVER SHEET

130 KW / 165 KVA POWERED by

Generator set data sheet Prime. Fuel consumption. Engine Standby rating Prime rating Continuous rating. Fuel flow

Ultra-low sulphur diesel (15 ppm sulphur)

300 KW / 375 KVA POWERED by

400 KW / 500 KVA. POWERED by TP-JD400-T3-60-UL. kva 500 Standby 3 Phase kw /208, 110/220, 120/240, 277/480

19 KW / 24 KVA POWERED by

130 KW / 165 KVA POWERED by

2500 Prime 2200 Continuous

500 KW / 625 KVA POWERED by

60 KW / 75 KVA POWERED by

DIESEL GENERATOR SET. 60 Hz FEATURES

105 KW / 130 KVA. POWERED by TP-I100-T2-60. kva 130 Standby 3 Phase kw /208, 110/220, 120/240, 277/480. kva 125 Prime Power Factor 0.

DIESEL GENERATOR SETS

30 KW / 40 KVA POWERED by

STANDBY 720 ekw 900 kva 50 Hz 1500 rpm 400 Volts

55 KW / 69 KVA POWERED by

16 KW / 20 KVA POWERED by

60 Hz FEATURES. Exclusively from your Caterpillar dealer

640 KW / 800 KVA POWERED by

70 KW / 90 KVA POWERED by

204 KW / 254 KVA POWERED by

STANDBY 400 ekw 500 kva 50 Hz 1500 rpm 400 Volts

64 KW / 80 KVA POWERED by

STANDBY 3000 ekw 3750 kva 60 Hz 1800 rpm 4160 Volts

28 KW / 28 KVA POWERED by

CONTINUOUS 1600 ekw 2000 kva 50 Hz 1500 rpm 400 Volts

80 KW / 100 KVA POWERED by

1135 Prime 1000 Continuous Emissions level: EPA NSPS Stationary Emergency Tier 2

1000 KW / 1250 KVA POWERED by

700 KVA / 550 KW POWERED by

Transcription:

Specification sheet Diesel generator set QSB7 series engine 100 200 kw 60Hz Description Cummins commercial generator sets are fully integrated power generation systems providing optimum performance, reliability and versatility for stationary Standby and Prime Power applications. Features Cummins heavy-duty engine - Rugged 4- cycle, industrial diesel delivers reliable power, low emissions and fast response to load changes. Alternator - Several alternator sizes offer selectable motor starting capability with low reactance 2/3 pitch windings, low waveform distortion with non-linear loads and fault clearing short-circuit capability. Control system The PowerCommand 1.1 electronic control is standard equipment and provides total genset system integration including automatic remote starting/stopping, precise frequency and voltage regulation, alarm and status message display, output metering, auto-shutdown at fault detection and NFPA 110 Level 1 compliance. The optional PowerCommand 2.2 control is UL 508 Listed and provides AmpSentry protection. Cooling system - Standard integral set-mounted radiator system, designed and tested for rated ambient temperatures, simplifies facility design requirements for rejected heat. Enclosures - Optional weather protective and sound attenuated enclosures are available. NFPA - The genset accepts full rated load in a single step in accordance with NFPA 110 for Level 1 systems. Warranty and service - Backed by a comprehensive warranty and worldwide distributor network. Model Standby rating Prime rating Continuous rating Data sheets DSGAA 100 (125) 90 (113) D-3349 DSGAB 125 (156) 113 (141) D-3350 DSGAC 150 (188) 135 (169) D-3351 DSGAD 175 (219) 160 (200) D-3516 DSGAE 200 (250) 180 (225) D-3517

Generator set specifications Governor regulation class Voltage regulation, no load to full load ± 1.0% Random voltage variation ± 0.5% Frequency regulation ISO8528 Part 1 Class G3 Isochronous Random frequency variation ± 0.25% Radio frequency emissions compliance Engine specifications Bore Stroke Meets requirements of most industrial and commercial applications. 107 mm (4.21 in) 124.0 mm (4.88 in) Displacement 6.69 L (408 in 3 ) Configuration Cast iron, in-line, 6 cylinder Battery capacity 1100 amps minimum at ambient temperature of -18 C to 0 C (0 F to 32 F) Battery charging alternator Starting voltage Fuel system Fuel filter Air cleaner type Lube oil filter type(s) Standard cooling system Alternator specifications Design Stator Rotor Insulation system Standard temperature rise Exciter type Phase rotation Alternator cooling AC waveform Total Harmonic Distortion (THDV) Telephone Influence Factor (TIF) 100 amps 12 volt, negative ground Direct injection: number 2 diesel fuel, fuel filter, automatic electric fuel shutoff Single element, 10 micron filtration, spin-on fuel filter with water separator Dry replaceable element Spin-on, full flow High ambient radiator Alternator specifications Brushless, 4 pole, drip proof, revolving field 2/3 pitch Single bearing, flexible discs Class H Telephone Harmonic Factor (THF) < 3% 150 ºC Standby at 40 C ambient Torque match (shunt) standard, PMG optional A (U), B (V), C (W) Direct drive centrifugal blower fan < 5% no load to full linear load, < 3% for any single harmonic < 50 per NEMA MG1-22.43 Available voltages Three phase Line-Neutral/Line-Line Single phase Line-Neutral/Line-Line 110/190 110/220 115/200 115/230 Delta 120/208 120/240 Delta 127/220 139/240 220/380 230/400 Note: Consult factory for other voltages. 240/416 255/440 277/480 347/600 110/220 115/230 120/240 (not available with DSGAD or DSGAE) Generator set options and accessories Engine 120 V 150 W lube oil heater 120/240 V 1500 W coolant heater Fuel System 24 hour sub-base tank (dual wall) Alternator 105 C rise 125 C rise 120 V 100 W anti-condensation heater PMG excitation Single phase Exhaust system Heavy duty exhaust elbow Slip on exhaust connection

Generator set options and accessories (continued) Generator set Battery Battery charger Enclosure: aluminium, steel, weather protective or sound attenuated Main line circuit breaker Remote annunciator panel Spring isolators 2 year Prime power warranty 2 year Standby power warranty 5 year Basic power warranty Note: Some options may not be available on all models - consult factory for availability.

Control system PowerCommand 1.1 Engine data DC voltage Lube oil pressure Coolant temperature Engine speed PowerCommand is an integrated generator set control system providing voltage regulation, engine protection, operator interface and isochronous governing (optional). Major features include: Battery monitoring and testing features and smart starting control system. Standard PCCNet interface to devices such as remote annunciator for NFPA 110 applications. Control boards potted for environmental protection. Control suitable for operation in ambient temperatures from -40 C to +70 C (-40 F to +158 F) and altitudes to 5000 meters (13,000 feet). Prototype tested; UL, CSA, and CE compliant. InPower PC-based service tool available for detailed diagnostics. Operator/display panel Manual off switch Alpha-numeric display with pushbutton access for viewing engine and alternator data and providing setup, controls and adjustments (English or international symbols). LED lamps indicating genset running, not in auto, common warning, common shutdown, manual run mode and remote start Suitable for operation in ambient temperatures from -20 C to +70 C Bargraph display (optional) AC protection Over current warning and shutdown Over and under voltage shutdown Over and under frequency shutdown Over excitation (loss of sensing) fault Field overload Engine protection Overspeed shut down Low oil pressure warning and shut down High coolant temperature warning and shut down Low coolant level warning or shut down Low coolant temperature warning High low and weak battery voltage warning Fail to start (overcrank) shut down Fail to crank shut down Redundant start disconnect Cranking lockout Sensor failure indication Low fuel level warning or shutdown Fuel-in-rupture-basin warning or shutdown Alternator data Line-to-Line and Line-to-Neutral AC volts 3-phase AC current Frequency Total kva Other data Genset model data Start attempts, starts, running hours Fault history RS485 Modbus interface Data logging and fault simulation (requires InPower service tool) Digital governing (optional) Integrated digital electronic isochronous governor Temperature dynamic governing Digital voltage regulation Integrated digital electronic voltage regulator 2-phase Line-to-Line sensing Configurable torque matching Control functions Time delay start and cooldown Cycle cranking PCCNet interface (2) Configurable inputs (2) Configurable outputs Remote emergency stop Glow plug control (some models) Options Auxiliary output relays (2) 120/240 V, 100 W anti-condensation heater Remote annunciator with (3) configurable inputs and (4) configurable outputs PMG alternator excitation PowerCommand iwatch web server for remote monitoring and alarm notification (loose) Auxiliary, configurable signal inputs (8) and configurable relay outputs (8) Digital governing AC output analog meters (bargraph) Color-coded graphical display of: 3-phase AC voltage 3-phase current Frequency kva Remote operator panel PowerCommand 2.2 control with AmpSentry protection For further detail see document S-1531.

Ratings definitions Emergency Standby Power (ESP): Applicable for supplying power to varying electrical loads for the duration of power interruption of a reliable utility source. Emergency Standby Power (ESP) is in accordance with ISO 8528. Fuel Stop power in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514. Limited-Time Running Power (LTP): Applicable for supplying power to a constant electrical load for limited hours. Limited-Time Running Power (LTP) is in accordance with ISO 8528. Prime Power (PRP): Applicable for supplying power to varying electrical loads for unlimited hours. Prime Power (PRP) is in accordance with ISO 8528. Ten percent overload capability is available in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514. Base Load (Continuous) Power (COP): Applicable for supplying power continuously to a constant electrical load for unlimited hours. Continuous Power (COP) in accordance with ISO 8528, ISO 3046, AS 2789, DIN 6271 and BS 5514. This outline drawing is for reference only. See respective model data sheet for specific model outline drawing number. Do not use for installation design Model Dim A Dim B Dim C Set weight* dry kg (lbs) Set weight* wet kg (lbs) DGDB 2656 (104.6) 1100 (43.3) 1549 (61) 1180 (2602) DSGAB 2656 (104.6) 1100 (43.3) 1549 (61) 1225 (2700) DSGAC 2656 (104.6) 1100 (43.3) 1549 (61) 1263 (2784) DSGAD 2656 (104.6) 1100 (43.3) 1549 (61) 1361 (3000) DSGAE 2656 (104.6) 1100 (43.3) 1549 (61) 1361 (3000) *Note: Weights represent a set with standard features. See outline drawings for weights of other configurations. Codes and standards Codes or standards compliance may not be available with all model configurations consult factory for availability. CSA This generator set is designed in facilities certified to ISO 9001 and manufactured in facilities certified to ISO 9001 or ISO 9002. The Prototype Test Support (PTS) program verifies the performance integrity of the generator set design. Cummins products bearing the PTS symbol meet the prototype test requirements of NFPA 110 for Level 1 systems. All low voltage models are certified to CSA C22.2 No.100 and CSA C22.2 No.14. UL2200 U.S. EPA International Building Code The generator set is available listed to UL 2200. Engine certified to Stationary Emergency U.S. EPA New Source Performance Standards, 40 CFR 60 subpart IIII Tier 3 exhaust emission levels. U.S. applications must be applied per this EPA regulation The generator set package is available certified for seismic application in accordance with the following International Building Code: IBC2000, IBC2003 IBC2006, IBC2009 and IBC2012. Warning: Back feed to a utility system can cause electrocution and/or property damage. Do not connect to any building s electrical system except through an approved device or after building main switch is open. For more information contact your local Cummins distributor or visit 2017 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and Our energy working for you. are trademarks of Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice. S-1544 (10/17)