Power Consumption Reduction: Hot Spare

Similar documents
Expansion Modules for Dell PowerConnect Switches

On Control Strategies for Wind Turbine Systems

Optimizing Battery Accuracy for EVs and HEVs

SHOULDER TO SHOULDER. The case for paralleling generator sets

VI Chip BCM Bus Converter Thermal Management

Battery Aging Analysis

White Paper: Pervasive Power: Integrated Energy Storage for POL Delivery

Getting Started With Your System

GUIDE TO BACK UP POWER

Thermal Considerations: Assuring Performance of Vicors Maxi, Mini, Micro Series High-Density DC-DC Converter Modules

400/230 Volt 60Hz UPS Power

HIGH EFFICIENCY MODES OF OPERATION. Path toward highest energy efficiency without load availability trade-off

Funding Scenario Descriptions & Performance

POWERFUL LINEUP. Paralleling Generator Sets

SOLAR TRACKER SITE DESIGN: HOW TO MAXIMIZE ENERGY PRODUCTION WHILE MAINTAINING THE LOWEST COST OF OWNERSHIP

Jeff Fehr, Senior Application Engineer. ACH550 Flux Optimization White Paper

Green Power Feasibility Study Econet Lesotho

Active ECO Mode in Single-Phase UPS. By Miguel Rascon AC Power Senior Product Manager

UAV Fuel Cell Module. Fly. Longer. Fly. Further. Achieve More

Nanopower IoT Power Supply Accurately Monitors Battery Discharge. by Samuel Nork Director, Boston Design Center Linear Technology Corporation

High Efficiency Battery Charger using Power Components [1]

UPS5000-E (25-75 kva) Series

Intelligent Transportation Systems. Secure solutions for smart roads and connected highways. Brochure Intelligent Transportation Systems

Investor Relations News

National Grid New Energy Solutions (NES)

REFINERY OPERATIONS ASIA April 2007, Singapore

Type 947D Polypropylene, High Energy Density, DC Link Capacitors

FINAL. Sound Transit Long-Range Plan Update. Issue Paper S.1: Tacoma Link Integration with Central Link. Prepared for: Sound Transit

HONOLULU AUTHORITY FOR RAPID TRANSPORTATION CITY AND COUNTY OF HONOLULU ADDENDUM NO. 1 TO THE REQUEST FOR INFORMATION FOR THE

Highlights of EU efforts for Smart Grids deployment and the way forward

Introducing the OMAX Generation 4 cutting model

LEGAL STATEMENT 1 / 2018 NAVIGANT CONSULTING, INC. ALL RIGHTS RESERVED

kVA. Liebert NX. Enterprise-Scale UPS Protection For Medium And Large Data Centers

RI Power Sector Transformation Con Edison Experiences. May 31 st, 2017

YASKAWA AC Drives. Compressor Applications Application Overview

Executive Summary. Draft Environmental Impact Statement/Environmental Impact Report ES-1

APPLICATION NOTE TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION. Abstract.

All in ONE Outdoor Skid Type. - PCS : 75, 100kW - PCS : 75, 100kW. - LiB : 200, 300, 400kWh - LiB : 200, 300, 400kWh.

High Power, High Current EDG Mica Grid Resistors, Grid Mill Bank Design

TEST REPORT. Test Report for Mating Cycle Validation of Mini Circuits QBL Series Quick-Lock Test Cables.

Implications of Digital Control and Management for a High Performance Isolated DC/DC Converter

When Grids Get Smart - ABB s Vision for the Power System of the Future

HIGH VOLTAGE vs. LOW VOLTAGE: POTENTIAL IN MILITARY SYSTEMS

Implications of. Digital Control. a High Performance. and Management for. Isolated DC/DC Converter. Technical Paper 003.

Transportation Demand Management Element

STEVAL-ISV012V1. Up to 5 W solar battery charger for single-cell Li-ion and Li-Pol batteries based on the SPV1040 and L6924D.

Implications of. Digital Control. a High Performance. and Management for. Isolated DC/DC Converter. Technical Paper 003.

Models DP10 & DP20 Series Low Voltage Disconnects User s Manual Rev. 1.1 October 31, 2007

UAV Fuel Cell Power Module. Fly. Longer. Fly. Further. Achieve More

ACTIVE ECO MODE IN SINGLE-PHASE UPS. Miguel Rascon AC Power Senior Product Manager

Application Note 103 January LTM4600 DC/DC µmodule Regulator Thermal Performance Eddie Beville, Jian Yin AN103-1

BLUECAT ENTERPRISE DNS

NetSure. 211 Series DC Power System

Three-phase UPS system DPA UPScale ST kw The modular UPS designed for lowand medium-power applications

Replacement Part has been judged by Mini Circuits Engineering as a suitable replacement to Original Part a. Case Style DQ849 (No Change) Marking MN5A

BZX84C2V4ET1 Series. Zener Voltage Regulators. 225 mw SOT 23 Surface Mount

24 hours BATTERY COOLING WITH DC COMPRESSORS WHITEPAPER NIDEC GLOBAL APPLIANCE.

This technical bulletin applies to Spectralink 8020 and 8030 handsets and OEM derivatives. Battery Pack Technical Specifications

KNOWLEDGE

Smart Cities Transformed Using Semtech s LoRa Technology

Powering the most advanced energy storage systems

Chapter 13: Application of Proportional Flow Control

Evaluating Batteries: Deployment, Integration and Market Drivers

DC Power Grid System Lighting for a Typical Conference Room Evaluation

Guidelines for Modernizing Existing Electrical Switchgear in LV and MV Networks

Liebert NX TM. 250kVA kVA Transformer-free. High Efficiency, Scalable On-line UPS

2.2 Deep-dive E-Mobility

Discussion Paper. Effect of Anti-Squat Adjustment in Solid Axle 4 Link Rear Suspension Systems

SMA Utility Power System

Multi-megawatt power protection at medium voltage

Washington Metropolitan Area Transit Authority

Reducing Energy Consumption and Emissions Through Congestion Management

Three-phase UPS system. DPA UPScale ST kw Best-in-class modular UPS for maximum availability

Reliability Considerations of Inverter/DC Link Capacitor using PP Film and 105 C Engine Coolant

NterpriseIP Solution Adaptive, high-availability power system for IP Telephony. Business-Critical Continuity for Communications

Network Powering Strategies and Alternatives

Based on the findings, a preventive maintenance strategy can be prepared for the equipment in order to increase reliability and reduce costs.

Variable Speed Limit Pilot Project in BC

ELEN E9501: Seminar in Electrical Power Networks. Javad Lavaei

Retrofitting unlocks potential

Data Analytics in the Connected Vehicle Future to Revolutionize Safety, Emissions, and Funding

UAV Fuel Cell Module. Fly. Longer. Fly. Further. Achieve More

FIVE WAYS TO OPTIMIZE YOUR FLEET WITH GPS TRACKING

Overview of Proposed/Approved Peak Demand Reduction Demonstration Projections Memorandum to EEAC Peak Demand Reduction Subcommittee December 2, 2016

MSD Zero-Cross Distributor Chevrolet - PN 83971

INSERO QUARTERLY, Q4 2014

How to Create Exponential Decline in Car Use in Australian Cities. By Peter Newman, Jeff Kenworthy and Gary Glazebrook.

The DDFT is the time period from the moment the doors start to close till the moment the doors are fully open on the next target floor.

Est FlexiPower Mini UPS FPX Mini kVA

NaS (sodium sulfura) battery modelling

Power generation. for remote accommodation camps

Passenger Rail Solar Electrification: A Primer. Oregon Department of Transportation Rail Division. June 2009

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

PEANUT ROASTER Instruction Manual Model #5081

REDUCING CARBON DIOXIDE EMISSIONS AND ENERGY BILLS WITH 98% EFFICIENT RECTIFIERS. A White Paper on DC Power Efficiency

BMW GROUP DIALOGUE. HANGZHOU 2017 TAKE AWAYS.

SMART DIGITAL GRIDS: AT THE HEART OF THE ENERGY TRANSITION

Rhode Island Division of Public Utilities and Carriers & Office of Energy Resources. Power Sector Transformation

Solar Power Energy Harvesting Electrical Integration

Type BPDS Polypropylene Board Mount DC Link Capacitors PCB Mount Power Film Capacitors

Transcription:

Power Consumption Reduction: Hot Spare A Dell technical white paper Mark Muccini Wayne Cook

Contents Executive summary... 3 Introduction... 3 Traditional power solutions... 3 Hot spare... 5 Hot spare solution... 6 Emphasis on power reduction... 8 This document is for informational purposes only and may contain typographical errors and technical inaccuracies. The content is provided as is, without express or implied warranties of any kind. 2012 Dell Inc. All rights reserved. Dell and its affiliates cannot be responsible for errors or omissions in typography or photography. Dell, the Dell logo, and PowerEdge are trademarks of Dell Inc. Other trademarks and trade names may be used in this document to refer to either the entities claiming the marks and names or their products. Dell disclaims proprietary interest in the marks and names of others. February 2012 Rev 1.0 ii

Executive summary As the cost of energy continues to rise, there is an increased need to employ energy efficient solutions in the data center. This paper presents the traditional approach of power management for a 1+1 redundant power supply system and an energy efficient approach we call Hot Spare. Hot Spare is an energy efficient solution which operates the power supplies at a more efficient operating condition thus reducing the energy cost of operating the system. Introduction The IT industry continues to grow, and with it is an increased emphasis on methods to reduce energy consumption of server deployments. With data processing, communication and applications continuing to expand, many data centers are forced to grow and deploy higher density solutions to keep up with the demands of the market. The amount of existing power available to support larger scale deployments can become a limiting factor. By decreasing the amount of power consumption for given applications, more servers can be applied to the existing infrastructure. One way of reducing power consumption is by reducing the amount of power dissipation in the front end power conversion block, which is often configured with redundant AC-DC power supplies. Dell has implemented a number of methods in reducing the power dissipation associated with the front-end conversion blocks. Methods include, but are not limited to, improving PSU efficiency, rightsized power solutions and enhanced power management techniques. The intent of this paper is to discuss Dell s Hot Spare technology, which is one of the many power management techniques targeted at reducing the power consumption of Dell PowerEdge 12 th generation servers. We will start off with addressing the challenges associated with traditional redundant PSU deployments, followed by a review of Hot Spare and how it addresses some of those concerns. Traditional power solutions Many server configurations are deployed with redundant power supplies to assist with maintaining server operation in the event of input power loss or PSU servicing. As illustrated in the Dell white paper, High Efficiency Power Supplies (found on Dell.com), redundant power supplies usually share the output load of the server, which places each power supply at less than 50% load. It should be noted that many agency standards, such as 80 PLUS, require peak PSU efficiency when the power supply is operating at 50% of its rating. These types of requirements have design related impacts, such as: 1) Reducing the fixed PSU losses that are made up of control and supervisory functions. 2) Reducing switching losses associated with many switch mode power supply designs. 3) Maintaining sufficient conduction losses, without jeopardizing the switching losses mentioned above. 3

However, even with light load PSU efficiency improvements, there are loading conditions which would be more efficient if a single power supply were operating as opposed to dual PSUs operating. Figure 1 illustrates PSU power dissipation vs. load based on operating one PSU vs. dual redundant PSUs across the load spectrum. The Platinum efficiency levels, which are specified by 80 PLUS, are listed in Table 1. Table 1. Platinum efficiency levels % Load % Efficiency 20 90.0 50 94.0 100 91.0 Throughout the paper, we will be referring to these efficiency specifications as a baseline for our discussion. We have derived the efficiency vs. load curves used in this paper by means of applying a curve fitting function to these efficiency points. These points are taken under specific test conditions, such as 230VAC input and at a specific ambient temperature. For more information on these requirements, please refer to the 80 PLUS website: http://www.plugloadsolutions.com/ 80PlusPowerSupplies.aspx. Figure 1. PSU power dissipation vs. load (single vs. dual PSU), 750 Platinum level efficiency 80.0 70.0 60.0 Pdis (W) 50.0 40.0 30.0 20.0 Dual Pdis (W) Single Pdis (W) 10.0 0.0 37.5 75.0 150.0 225.0 300.0 375.0 450.0 525.0 600.0 675.0 750.0 In Figure 1, it can be observed that at load levels less than 525W (~70% of this PSUs rating), there is less power being dissipated by operating a single PSU vs. dual PSUs. At a system load of greater than 525W, it can be observed that operating dual PSUs is more efficient compared to operating in a single 4

PSU configuration. It would seem apparent, that if the system were to allow a single power supply to operate up to 525W and then transition to dual PSUs above 525W, power could be saved compared to operating dual supplies under all conditions. This is where Hot Spare steps in. Hot spare To address the situation discussed above, Dell has derived a power management feature which reduces power consumption while maintaining redundancy and availability. To keep things simple, we will refer to the 1x1 PSU configuration using 750W Platinum level efficiency PSUs. The basic premise of the feature is to have one power supply active and one PSU in a suspended state, during light load conditions. As a result, the active supply is forced to deliver the entire system load thus pushing it to operate at a higher part of the efficiency curve. As the system load increases beyond the threshold of power consumption benefit from operating one power supply, dual PSUs become active. For example, the graph below illustrates the efficiency of the AC-DC power conversion block. If we assume the system load is ~150W (20% of a single PSUs output capability), the efficiency for a single supply operating is ~90% (~16.7 Watts dissipated). With dual power supplies operating, each power supply would share ½ of the 150W load at 75W/PSU (10% of a single PSUs output capability). The power supply efficiency at 75W is ~82% (~16.5 Watts dissipated). With dual power supplies delivering the load, the total loss would be 33W compared to 16.7W when operating a single PSU. It is observed that the calculated overall savings is ~16.3W when operating a single PSU vs. dual in this load range. The best case condition would be for only one power supply to be operating during this time; however, that would void PSU redundancy. The problem is how to operate the system as if it were operating from a single PSU, but both PSU present and operational. Dell s Hot Spare solution addresses this concern. Figure 2. Efficiency vs. load, 750W Platinum level spec values 96.0 94.0 92.0 90.0 Efficiency % 88.0 86.0 84.0 Single PSU operating %Eff 82.0 80.0 78.0 Dual PSUs operating 76.0 75.0 150.0 375.0 750.0 5

Hot spare solution The ability to reduce power consumption, for this type of solution, relies on the ability for a PSU to suspend power delivery at light load conditions and thus force the load to be provided by the remaining active PSU. Dell s solution utilizes a sleep mode state of operation to force the load shift. Loading conditions that warrant a single PSU to operate force one power supply to actively supply the load, while the remaining PSU suspends power delivery. A suspended PSU remains prepared to support the redundant bus in case the active PSU becomes void of operation. The suspended PSU remains ready to respond, while minimizing power consumption. Since the suspended PSU voids load delivery, the amount of suspended PSU power dissipation becomes a fixed loss. The following equation summarizes the total Hot Spare dissipation of both power supplies: Front End Power Block Power Dissipation = Operating PSU Power Dissipation + Suspended PSU Power Dissipation. By means of advanced power management techniques, the suspended PSU power consumption is kept to a minimum to maximize power savings. It will be the loading conditions of the system and efficiency of the PSUs that will dictate when it is appropriate to enter and exit suspended modes of operation. Since the power supplies have the ability to monitor their output loading condition, action can be taken to enter and exit sleep states accordingly. To illustrate this, we will continue to refer to a 1+1 application using the 750W Platinum compliant PSUs. Figure 3. Power dissipation vs. system load, single PSU compared to dual power dissipation, 750W Platinum PSU Power dissipation (W) 90.00 85.00 80.00 Power 75.00 dissipation 70.00 1Sleep/1Active 65.00 60.00 55.00 50.00 45.00 40.00 35.00 30.00 25.00 20.00 Power dissipation 15.00 dual PSUs operating 10.00 5.00 0.00 75 275 475 675 Total Pdis 1 Sleep/1 Active Pdis Dual Supply Total 6

Figure 3 illustrates total calculated power block power dissipation vs. system load when operating a server type application with a single PSU versus dual PSU operation. It is observed that below ~450W of system power draw, less power is dissipated by operating a single PSU compared with running dual PSUs. Conversely, at power levels above ~450W, it is more efficient to have both PSUs active. With these power dissipation regions understood, the power system can make decisions on when to enter and exit sleep states. Figure 4 illustrates what the calculated power dissipation vs. system load would look like with Hot Spare enabled. Figure 4. Power dissipation vs. system load, 750W PSU with hot spare algorithm, 1+1 PSU configuration Power dissipation (W) 90.00 85.00 80.00 75.00 70.00 65.00 60.00 55.00 Power 50.00 dissipation 45.00 1Sleep/1Active 40.00 35.00 30.00 25.00 20.00 Power dissipation dual 15.00 PSUs operating 10.00 5.00 0.00 75 175 275 375 475 575 675 Total Pdis 1 Sleep/1 Active Pdis Dual Supply Total Figure 5 illustrates the calculated total power dissipation with the Hot Spare algorithm implemented. We observed that the savings are most pronounced in the region that is deemed typical operation. In end systems, power savings will vary based on a wide variety of conditions. As an example, PSU efficiency variations will vary based on design differences. Other factors such as input voltage conditions and environmental differences may also change results. 7

Figure 5. Power savings vs. system load, 750W PSU with hot spare 1+1 PSU configuration 14.00 12.00 Power dissipation (W) 10.00 8.00 6.00 4.00 Hot Spare power savings Hot Spare Savings 2.00 Typical server loading 0.00 75 175 275 375 475 575 675 775 Emphasis on power reduction With the data center environment continuing to emphasize the need for lower power consumption, the drive to reduce power consumption at the server and PSU level is very apparent. Dell has responded with a power strategy that includes higher efficiency PSUs, right-sized solutions and features such as Hot Spare. By utilizing this new intelligent power management feature, you can now further reduce power consumption without sacrificing availability or redundancy. By employing the monitoring and management capabilities of the PSU, the Hot Spare feature can dynamically shift the load between redundant power supplies, and therefore manipulate the front end power block efficiency vs. load characteristics. Benefits include reducing PSU and server operational expenditures by means of lowering utility consumption and cooling. Learn more For more information on Dell power and cooling, visit Dell.com/PowerandCooling. 8